SmartOnline 208/240V 3kVA 2.7kW Double
SmartOnline 208/240V 3kVA 2.7kW
Double-Conversion UPS, 2U, Extended Run, SNMP
Card Option, LCD, USB, DB9
Highlights
Zero transfer time suitable for
advanced network applications
2% output voltage regulation in
online and battery modes
MODEL NUMBER: SU3000LCD2UHV
Selectable
200/208/220/230/240V output
voltage
6 NEMA 6-15/20R and 2 NEMA
L6-20R outlets
13.5 min. runtime at half load; 5
min. at full load
Package Includes
SU3000LCD2UHV SmartOnline
3000VA/2700W On-Line
Double-Conversion UPS
4-post rack-mount installation kit
USB cable
RS-232 cable
Description
Owner’s manual
The SU3000LCD2UHV SmartOnline® 3000VA/2700W On-Line Double-Conversion UPS converts AC input to
DC power, and then converts DC to fully regulated sine wave AC output with +/-2% voltage regulation in online and battery modes. An interactive front-panel
LCD interface provides detailed real-time UPS status and advanced setup and configuration options.
In case of AC power outage, the internal batteries support 13.5 minutes of runtime at half load and five minutes at full load. Extended runtime is possible with
optional external battery packs. “Smart” battery packs, such as Tripp Lite’s BP72V18-2US, are automatically sensed and configured during replacement. An
intelligent battery management system extends battery life.
Managing the UPS is simplified through the interactive front-panel LCD interface, which displays operating conditions and diagnostic data, such as load and
battery levels. You can set power strategies to reflect your protection priorities, whether it’s precise power quality for sensitive systems or the highest possible
electrical efficiency, all while ensuring 100% uptime for your systems.
This UPS offers eight receptacles—six NEMA 6-15/20R and two NEMA L6-20R—in two switched load banks. Power is filtered to protect connected equipment
against surges and EMI/RFI line noise that can damage equipment or destroy data. Adding an optional Tripp Lite SNMPWEBCARD accessory card permits
remote management of the UPS, including reboots, configuration, updates and activity logs.
Features
Protects Mission-Critical Rack-Mounted Equipment
Converts AC input to DC power, then DC to fully regulated sine wave AC output
+/-2% voltage regulation in online and battery modes
Selectable 200/208/220/230/240V output voltage
3000VA/2700W capacity
6 NEMA 6-15/20R and 2 NEMA L6-20R outlets
570-joule surge suppression rating
1/6
Interactive Front-Panel LCD
Reports detailed status information, including load and battery levels
Offers advanced configuration options, including output voltage and power strategies
5 Power Strategies
Auto Adaptive enables high efficiency and high-quality operation as necessary for ideal equipment protection
Max Efficiency favors economy operation with high 95% efficiency
Max Quality favors on-line, double-conversion mode, maintaining +/-2% output voltage regulation and zero transfer time
Frequency Regulation and Frequency Conversion enable +/-0.05 Hz output regulation for selected frequency(50/60 Hz)
Reliable, Expandable Battery Backup
Supports half load(1350W) for 13.5 min. and full load(2700W) for 5 min.
Add external battery packs for extra runtime
“Smart” battery packs, such as Tripp Lite’s BP72V18-2US, are automatically sensed and configured during replacement
Full 2700W capacity available with and without external battery packs
Electronic Bypass
Maintains utility output during UPS fault conditions
Adjustable bypass range and high-efficiency mode voltage settings
Highly Customizable
Customize communications and behavior to integrate with device makers' specific needs
Selectable auto-restart from 0 to 60 sec. after AC power is restored
Selectable minimum battery charge level before auto-restart
Schedule system reboot if USB signal from connected device is lost
Set overload thresholds and low battery levels for alert and shutdown
Remote on/off(toggle) support via DB9
SNMP/Web Capability
Optional Tripp Lite SNMPWEBCARD permits remote management of UPS, including reboots, configuration, updates and activity logs
Specifications
OUTPUT
Output Volt Amp Capacity (VA)
3000
Output kVA Capacity (kVA)
3
Output Watt Capacity (Watts)
2700
Output kW Capacity (kW)
2.7
2/6
Output Capacity Details
DE-RATING INFORMATION: Max output in Frequency Conversion mode is reduced to 1890 watts for
208/220/230/240V output voltages; Max output is reduced to 2160W at 200V output voltage in all operating modes
OVERLOAD CAPACITY: Supports inverter operation up to 105% load continuously, 125% for 3 minutes, 150% for
30 seconds and >150% for 0.5 seconds before switching to BYPASS (when bypass input voltage and frequency are
WITHIN bypass limits) or SHUTDOWN (when bypass input voltage or frequency are OUTSIDE bypass limits).
Power Factor
0.9
Crest Factor
3:1
Nominal Output Voltage(s)
Supported
200V; 208V; 220V; 230V; 240V
Nominal Voltage Details
Nominal output voltage is user configured on first power-on
Frequency Compatibility
50 / 60 Hz; Supports 50 to 60 Hz and 60 to 50 Hz conversion
Frequency Compatibility Details
Output frequency matches input nominal on startup; Output capacity de-rates by 30% during frequency conversion
operation
Output Voltage Regulation (Line
Mode)
+/- 2%
Output Voltage Regulation
(Economy Line Mode)
+/- 10%
Output Voltage Regulation (Battery
Mode)
+/- 2%
Output Receptacles
(6) 6-15/20R; (2) L6-20R
Included Output Power Cables
Includes 2 C13 to C14 and 1 C19 to C20 power cables
Load Management Receptacles
Two switchable 4 outlet load banks (3 C13 and 1 C19 per bank)
Output AC Waveform (AC Mode)
Pure Sine wave
Output AC Waveform (Battery Mode)
Pure Sine wave
INPUT
Rated input current (Maximum Load)
14.97A
Nominal Input Voltage(s) Supported
200V AC; 208V AC; 220V AC; 230V AC; 240V AC
UPS Input Connection Type
C20 inlet
Input Phase
Single-Phase
BATTERY
Full Load Runtime (min.)
5 min. (2700w)
Half Load Runtime (min.)
13.5 min. (1350w)
Expandable Battery Runtime
Supports extended runtime with optional external battery packs
External Battery Pack Compatibility
BP72V15-2U (limit 1); BP72V28RT-3U(multi-pack compatible); BP72V18-2US(multi-pack compatible)
DC System Voltage (VDC)
72
Battery Recharge Rate (Included
Batteries)
3.0 hours from 10% to 90% (typical, full load discharge)
Internal UPS Replacement Battery
Cartridge
RBC72S
3/6
Battery Access
Front panel battery access door
Battery Replacement Description
Hot-swappable, replaceable batteries
Expandable Runtime
Yes
VOLTAGE REGULATION
Voltage Regulation Description
Online, double-conversion power conditioning
Overvoltage Correction
2% output voltage regulation during overvoltages to 288
Undervoltage Correction
2% output voltage regulation during undervoltages to 160V (100% load), 130V (70% load), 100V (30% load)
USER INTERFACE, ALERTS & CONTROLS
Front Panel LCD Display
Interactive front-panel LCD interface reports UPS operating mode, detailed UPS status and site-power information;
LCD interface also enables a variety of advanced UPS setup and configuration options
Switches
5 front panel switches: On/Off, Up, Down and Escape
Alarm Cancel Operation
Power-fail alarm can be silenced by following on-screen prompts
Audible Alarm
Audible alarm indicates power failure, low battery, overload and fault
LED Indicators
4 front panel LEDs: AC input (green), AC output (green), Battery (yellow), Fault (red)
SURGE / NOISE SUPPRESSION
UPS Dataline Suppression Details
Single line dialup / network dataline protection included
EMI / RFI AC Noise Suppression
Yes
AC Suppression Joule Rating
570
AC Suppression Response Time
Instantaneous
PHYSICAL
Included Mounting Accessory
Description
4 post installation accessories included
Installation Form Factors Supported
with Included Accessories
4 post 19 inch rackmount
Installation Form Factors Supported
with Optional Accessories
2 post rackmount(2POSTRMKITWM)
Optional Mounting Accessory Notes
Upright tower configurations not recommended
Primary Form Factor
Rackmount
UPS Power Module Dimensions
(hwd, in.)
3.46 x 17.24 x 24.25
UPS Power Module Dimensions
(hwd, cm)
8.8 x 43.8 x 61.6
Rack Height (U Spaces)
2
UPS Power Module Weight (lbs.)
70.81
UPS Power Module Weight (kg)
32.1
4/6
UPS Shipping Dimensions (hwd / in.)
9.45 x 23.62 x 29.92
UPS Shipping Dimensions (hwd /
cm)
24 x 56.0 x 76.0
Shipping Weight (lbs.)
86.02
Shipping Weight (kg)
39.1
Cooling Method
Fan
UPS Housing Material
Metal
ENVIRONMENTAL
Operating Temperature Range
+32 to +104 degrees Fahrenheit / 0 to +40 degrees Celsius.
Storage Temperature Range
+5 to +122 degrees Fahrenheit / -15 to +50 degrees Celsius.
Relative Humidity
5 to 95%, non-condensing
AC Mode BTU / Hr. (Full Load)
933
AC Economy Mode BTU / Hr. (Full
Load)
484
Battery Mode BTU / Hr. (Full Load)
1399
AC Mode Efficiency Rating (100%
Load)
>90%
AC Economy Mode Efficiency Rating
(100% Load)
>95%
Audible Noise
<50dB at front side 1M
COMMUNICATIONS
Communications Interface
USB (HID enabled); DB9 Serial; Contact closure; EPO (emergency power off); Slot for SNMP/Web interface
Network Monitoring Port Description
This model works with optional SNMPWEBCARDXLCD SNMP/Web interface only; Supports detailed monitoring of
UPS and site power conditions; DB9 port supports RS232 plus assignable contact closure pin functions for
On-battery, On bypass, Output-on and Low-battery conditions and remote Shutdown, Output-off, Reboot and
Power-toggle operations
PowerAlert Software
Available for download at www.tripplite.com
Communications Cable
USB and DB9 cabling included
WatchDog Compatibility
Supports Watchdog application, OS and hard-reboot restart options for remote applications
LINE / BATTERY TRANSFER
Transfer Time
No transfer time (0 ms.) in online, double-conversion mode; 4 ms. transfer time during economy mode operation
Low Voltage Transfer to Battery
Power (Setpoint)
160V (100% load), 140V (66% load), 120V (33% load)
High Voltage Transfer to Battery
Power (Setpoint)
288V
SPECIAL FEATURES
Grounding Lug
Back panel grounding lug included
5/6
Cold Start (Startup in Battery Mode
During a Power Failure)
Cold-start operation supported
High Availability UPS Features
Automatic inverter bypass; Hot swappable batteries
Green Energy-Saving Features
High efficiency economy mode operation; Individually controllable load banks
CERTIFICATIONS
UPS Certifications
Meets FCC Part 15 Category A (EMI); Tested to CSA (Canada); Tested to NOM (Mexico); Tested to UL1778 (USA)
WARRANTY
Product Warranty Period (Worldwide)
2-year limited warranty
© 2015 Tripp Lite. All rights reserved. All product and company names are trademarks or registered trademarks of their respective holders. Use of them does
not imply any affiliation with or endorsement by them. Tripp Lite has a policy of continuous improvement. Specifications are subject to change without notice.
Tripp Lite uses primary and third-party agencies to test its products for compliance with standards. See a list of Tripp Lite's testing agencies:
http://www.tripplite.com/products/product-certification-agencies
6/6
Was this manual useful for you? yes no