F413N Dimmer for Electronic Ballast 1-10V

F413N Dimmer for Electronic Ballast 1-10V
Dimmer for Electronic Ballast 1-10V
F413N
Description
Control device for electronic ballast or driver power supply units with dimmer function; it
can supply fluorescent lamps or LED lamps and adjust their brightness depending on the
voltage, with values between 1 and 10V (max. 6mA), with which they are driven. From
any specially configured control point and connected to the BUS system one can switch
the lights connected on and off or set their brightness. Briefly pressing the control button
is enough to switch the load on or off, while holding it down will adjust the brightness.
The minimum brightness level and the type of load connected (Ballast for fluorescents or
driver for LEDs) can be selected during the configuration.
1 2 NC 3 4
-+
0-10V
C1
4
Technical data
Power supply via SCS BUS: Operating power supply with SCS BUS: Current draw: Operating temperature: Linear fluorescent lamps:
Dissipated power with max. load: Protection index:
Impact resistance:
27 Vdc
18 – 27 Vdc
30 mA
(-5) – (+45) °C
2A
460W@230Vac
220W@110Vac
Max 10 ballast type T5, T8,
compact or driver for LEDs
1W
IK04
IP20
3
1
2
Legend
1. Configurator socket (note that this must only be used in My Home systems with the
physical configuration).
2. BUS connector
3. Load status LED
4. Load on/off button
Dimensions
Size: 2 DIN modules
Configuration
1. My Home system
If the device is installed in a My Home system it can be configured in two ways:
- PHYSICAL CONFIGURATION, inserting the configurators in position.
- Configuration via MYHOME_Suite software package, downloadable from
www.homesystems-legrandgroup.com; this mode has the advantage of offering many
more options than the physical configuration.
For a list of the procedures and their meanings, please refer to the instructions in this
sheet and to the "Function Descriptions" help section in the MYHOME_Suite software
package.
1.1 Addressing
Address type
Point-to-point
Group
Virtual configuration (MYHOME_Suite)
Physical configuration
Room
0-10
A=1-9
Lighting point
0-15
PL=1-9
Group 1 - Group 10 = 0-255
G = 0-9
MQ00277-e-EN
07/06/2014
1
Dimmer for Electronic Ballast 1-10V
F413N
1.2 Mode
Virtual configuration (MYHOME_Suite)
Function
Physical configuration
Parameter / setting
Master Actuator
Master
M=0
Actuator as Slave. Receives a control sent by a Master actuator
with the same address
Slave
M=SLA
Pushbutton (ON monostable) ignores Room and General controls
Master PUL
M=PUL
OFF delay: Master actuator with OFF control delayed on the
corresponding Slave actuator. 1)
0 - 255
M=1
1 minute
M=2
2 minutes
M=3
3 minutes
Selection of the minimum brightness level 2)
Selection of the type of load used
3)
M=4
4 minutes
L=0
1 Volt
L=1
1.5 Volt
L=2
2 Volt
L=3
0 Volt
L=4
0.5 Volt
Fluorescent lamps
TYPE=0
Fluorescent lamps
LED lamp
TYPE=1
LED lamp
1-100
Note 1): In the Master and Master PUL mode you can set an OFF delay of 0-255 seconds (via
MYHOME_Suite) and of 1-4 minutes using the physical configuration. Only for point-point control.
With the OFF control the Master actuator deactivates; the Slave actuator deactivates after the
time set with the configurators has elapsed. The ON control activates the Master actuator and the
Slave actuator at the same time. The next OFF control deactivates the Master actuator and keeps
the Slave actuator active for the period of time set with configurator 1 - 4 connected to M of the
Master actuator as indicated in the table.
Note 2): In the physical configuration, the configurator in the L position establishes the minimum
output voltage between clamps 1 and 2 when the load is on, thus allowing the minimum
brightness level to be selected. 5 different voltage levels can be selected, so that the standard
0-10V is possible as well as the standard 1-10V.
Note 3): In the physical configuration, the configurator in the TYPE position determines the
type of load used on the basis of the following table. If ballasts for fluorescent lamps with typical
switching ON delay of 1.5s are used, the device will send the soft/start switching ON command
taking account of the delay. If power supply units for LED lamps must be controlled instead, the
device will send an immediate soft/start switching ON command.
To use the “Actuator as a slave with PUL function”, for additional options of the “Type of
load” (Dali standard, DSI, Halogen lamp, Trailing edge LED / electronic transformers) and
for adjusting the voltage, use MYHOME_Suite virtual configuration.
2. Lighting Management System
When installed in a Lighting Management system, the device can be configured in the
following ways:
- Push & Learn: procedure for pairing different connected devices or changing the
assignments defined automatically in the Plug & Go procedure. For more details, please
refer to the specific document.
MQ00277-e-EN
2
- Software Configuration: using the Virtual Configurator software; for more details, please
refer to the specific manual.
07/06/2014
Dimmer for Electronic Ballast 1-10V
F413N
Wiring diagram
≥ 3m
N
L
L
1 2 NC 3 4
-+
0-10V
–
+ NC NO
N
+
–
Ballast
LED driver
L
Fluorescent lamp
LED lamp
C1
1
1
SCS BUS
2
2 NC 3
0 10 V
MAX 6mA
NC
3
4
4