Differential Pressure Transmitter Datasheet Application Types

Differential Pressure Transmitter Datasheet Application Types
DPA+
Differential Pressure Transmitter
Datasheet
Subject to technical alteration
Issue date: 29.05.2017
Application
Differential pressure and volume flow transducer for monitoring differential pressure and volume flow of air and other nonflammable and non-aggressive gases. Three types with eight different measuring ranges are available for different applications.
In addition to differential pressure all variants provide the calculated volume flow as second analog output signal. K-values for
flow calculation (default 1500) can be parameterized via Thermokon USEapp. With the option board relay two-point controllers or
a 2-stage 2-point controller for differential pressure or volume flow can be realized. The mounting base (included in delivery)
allows mounting on a level surface or mounting on DIN rail TS35 (35x7,5 mm) according to EN 60715.
Types Available
Differential pressure transducer with display – 2x 0..10 V
DPA250+ VV MultiRange <AZ>
DPA2500+ LCD VV MultiRange <AZ>
DPA7000+ VV MultiRange <AZ>
Differential pressure transducer with display – 2x 4..20 mA
DPA250+ AA MultiRange <AZ>
DPA2500+ AA MultiRange <AZ>
DPA7000+ AA MultiRange <AZ>
Differential pressure transducer with display – 2x 0..10 V + Relay
DPA250+ VV MultiRange Relay <AZ>
DPA2500+ VV MultiRange Relay <AZ>
DPA7000+ VV MultiRange Relay <AZ>
MultiRange: Measuring ranges adjustable at the transducer
<AZ>: automatic zero-point calibration (optional)
Thermokon Sensortechnik GmbH, Platanenweg 1, 35756 Mittenaar, Germany · tel: +49 2778 6960-0 fax: -400 www.thermokon.com· email@thermokon.com
DPA+_Datasheet_en.docx © 2017
Page 2 / 5
Issue date: 29.05.2017
Security Advice – Caution
The installation and assembly of electrical equipment should only be performed by authorized personnel.
The product should only be used for the intended application. Unauthorised modifications are prohibited! The
product must not be used in relation with any equipment that in case of a failure may threaten, directly or indirectly,
human health or life or result in danger to human beings, animals or assets. Ensure all power is disconnected
before installing. Do not connect to live/operating equipment.
Please comply with

Local laws, health & safety regulations, technical standards and regulations

Condition of the device at the time of installation, to ensure safe installation

This data sheet and installation manual
Notes on Disposal
As a component of a large-scale fixed installation, Thermokon products are intended to be used permanently as
part of a building or a structure at a pre-defined and dedicated location, hence the Waste Electrical and Electronic
Act (WEEE) is not applicable. However, most of the products may contain valuable materials that should be
recycled and not disposed of as domestic waste. Please note the relevant regulations for local disposal.
Technical Data
Measuring values
Medium
Output voltage
Output Amp
Output switch contact
Power supply
AA
Relay
VV | Relay
AA
Power consumption
Measuring range velocity
Measuring range pressure
type 250
type 2500
type 7000
Accuracy pressure
Max. working overpressure
Calibration
Sensor
Enclosure
Protection
Cable entry
Connection electrical
Connection mechanical
Ambient condition
Mounting
type 250
type 2500
type 7000
VV | AA
Relay
differential pressure, volume flow
air or other non-flammable/non-aggressive gases
0..10 V or 0..5 V, min. load 10 kΩ
(live-zero configuration via Thermokon USEapp)
2x 4..20 mA. max. load 500 Ω
2 floating contacts for 24 V ~ or 24 V = / 3 A
15..35 V = or 19..29 V ~,
15..35 V =
max. 2,3 W (24 V =) | max. 4,3 VA (24 V ~)
0… 750.000 m³/h (default), optionally configured via Thermokon USEapp
selectable at the device
0..+25 | 0..+50 | 0..+100 | 0..+250 | -25..+25 | -50..+50 | -100..+100 | -150..+150
Pa
-100..+100 | 0..+100 | 0..+250 | 0..+500 | 0..+1000 | 0..+1500 | 0..+2000 |
0..+2500 Pa
0..+1000 | 0..+1500 | 0..+2000 | 0..+2500 | 0..+3000 | 0..+4000 | 0..+5000 |
0..+7000 Pa
±1 Pa at range <250 Pa,
±5 Pa at range <500 Pa, ±10 Pa at range >500 Pa,
±10 Pa at range <2000 Pa, ±25 Pa at range >2000 Pa, deviation from
calibration reference device (calibrator)
40 kPa
manually, automatic zero-point calibration (optional)
piezo measuring element
enclosure USE-L, PC, pure white, with removeable cable entry
IP65 according to EN 60529
M16, for wire max. Ø=8 mm
M20, for wire max. Ø=10 mm, seal insert for double cable entry for wire max
Ø=6 mm
removeable plug-in terminal, max. 2,5 mm²
pressure connection male Ø=5,0 mm / Ø=6,3 mm, connection tube: PVC, soft
-10..+50 °C, max. 85% rH short term condensation
screw mounted onto flat surface, prepared for mounting on DIN rail TS35
(35x7,5 mm) according to EN 60715
Thermokon Sensortechnik GmbH, Platanenweg 1, 35756 Mittenaar, Germany · tel: +49 2778 6960-0 fax: -400 www.thermokon.com· email@thermokon.com
DPA+_Datasheet_en.docx © 2017
Issue date: 29.05.2017
Page 3 / 5
Mounting Advices
Before installing the device, please check the leak tightness of the pressure lines.
A prerequisite for the operation is a proper installation of all electrical supply, control and sensing leads as well as the
pressurized connection line.



In order to connect the device, the process lines must be unpressurized
Consider the suitability of the device for the medium to be measured
Consider maximum pressures
below
atmospheric
pressure
-
overpressure
+
filter
+
fan
-
-
+
Connection Plan
DPA+ VV MultiRange
(volume flow | 0..10 V)
(differential pressure | 0..10 V)
(15..35 V = or 19..29 V ~)
DPA+ AA MultiRange
(volume flow | 0..10 V)
(differential pressure | 0..10 V)
(15..35 V =)
(volume flow | 4..20 mA)
(differential pressure | 4..20 mA)
DPA+ VV MultiRange Relay
(volume flow | 0..10 V)
(differential pressure | 0..10 V)
(15..35 V = or 19..29 V ~)
(Relay 2 | NO)
(Relay 1 | NO)
Thermokon Sensortechnik GmbH, Platanenweg 1, 35756 Mittenaar, Germany · tel: +49 2778 6960-0 fax: -400 www.thermokon.com· email@thermokon.com
DPA+_Datasheet_en.docx © 2017
Page 4 / 5
Issue date: 29.05.2017
Measuring range adjustment – type 250 | 2500 | 7000
default
Response time
default
Output voltage
default
Unit
default
Flow calculation: (default parameters)
𝑞 = 𝑘 ∗ √2 ∗
∆𝑝
𝜌
with k=1500, fan manufacturer Rosenberg, Comefri, Nicotra Gebhardt, default measuring range 0..750.000 m³/h.
Further calculation formulas, fan manufacturers and k-values can be selected via the USEapp.
Automatic Zero-Point Calibration - (optional)
Transmitters equipped with the auto zero calibration are maintenance free.
The auto-zero calibration electronically adjusts the transmitter zero every 10 minutes. The function eliminates all
output signal drift due to thermal, electronic or mechanical effects. The auto-zero adjustment takes approx. 4
seconds after which the device returns to its normal measuring mode. During the 4 second adjustment period, the
output and display values will freeze to the latest measured value.
Manual zero-point calibration (for devices without auto-zero function)
In normal operation zero point calibration should be executed every 12 months.
Attention! For executing zero point calibration the power supply must be
connected one hour before.
• Release both connection tubes from the pressure terminals + and • Press the button until the LED lights permanently
• Wait until the LED flashes again and reinstall the connection tubes to the pressure
ports (note + and -)
Configuration
The Thermokon bluetooth dongle with micro-USB is required for communication between
USEapp and USE-M / USE L (Item No..: 668262). Commercial bluetooth dongles are not
compatible.
Application-specific reconfiguration of the devices can
The configuration is carried out in the voltage-supplied state.
be
carried
out
using
the
Thermokon
USEapp.
The configuration-app and the app description can be found in the download area of our webpage.
→ Download (APK-file for Android)
Thermokon Sensortechnik GmbH, Platanenweg 1, 35756 Mittenaar, Germany · tel: +49 2778 6960-0 fax: -400 www.thermokon.com· email@thermokon.com
DPA+_Datasheet_en.docx © 2017
Issue date: 29.05.2017
Page 5 / 5
Dimensions (mm)
Accessories (included in delivery)
Mounting base enclosure USE-L
2 m PVC connection tube
KKS40 kit

2 plastic duct flanges

4 mounting screws 4x20
Item No. 668361
Item No. 484268
Item No. 430135
Mounting kit 2 (only version VV & AA)

Cable entry M16

Cover screw

2 Screws (countersunk head)
Item No. 640503
Mounting kit 3 (only version Relay)

Cable entry M20

seal insert for double cable entry 2x 6 mm

Cover screw

2 Screws (countersunk head)
Item No. 674133
Accessories (optional)
Bluetooth dongle USE for USEapp
Cable entry M25 USE white, sealing insert 4x Ø=7 mm (4 pcs)
T-hose connector for pressure hoses Ø=4 mm (10 pcs)
Adapter 90° angle for pressure hoses Ø=4 mm
Metal duct connectors 40 mm
Metal duct connectors 100 mm
Item No. 668262
Item No. 641364
Item No. 668323
Item No. 668330
Item No. 265138
Item No. 302531
M16 Sealing inserts cable entry (packaging unit 10 pcs.)
for wire with Ø
Item No
3 mm
641036
5 mm
641012
7 mm
639248
8 mm
641340
2x7 mm
641333
6 mm
641074
8 mm
641081
M20 Sealing inserts cable entry (packaging unit 10 pcs.)
for wire with Ø
Item No
2x6 mm
641319
Thermokon Sensortechnik GmbH, Platanenweg 1, 35756 Mittenaar, Germany · tel: +49 2778 6960-0 fax: -400 www.thermokon.com· email@thermokon.com
DPA+_Datasheet_en.docx © 2017