Fire Detectors
AIG Programs
Loss Control Bulletin
Fire Detectors
Fire detectors are available for residential, commercial, and industrial use. Models are
available for both single and multiple stations, as well as system applications. There are a
number of different types of detectors available, including smoke, flame, heat, and gas
detectors. This handout provides basic information on the operation and application of fire
detectors.
Smoke Detectors
Smoke detectors are designed to provide early warning for a fire, involving ordinary combustible materials,
that is expected to progress through distinct incipient and/or smoldering stages. The type, volume, and
density of smoke produced during the fire development process will vary greatly depending on the fuels
involved and the amount of oxygen available. Typically, the greatest volume of visible smoke is produced
during the ignition (incipient) stage and the smoldering stage.
While there are a number of different types of smoke detectors available, the two most commonly used
smoke detectors are the ionization and photoelectric types.
Ionization Detectors
The ionization smoke detector reacts to both visible and invisible products of combustion. This spot-type
detector contains a small radiation source that produces electrically charged air molecules called ions. The
use of a long, half-life radioactive source, coupled with low energy consumption, gives the ionization detector
long life expectancy with minimal maintenance. Ionization-type detectors respond better to a flaming fire.
Ionization detectors are not suitable for use in applications where high ambient radioactivity levels are to be
expected. High ambient radiation reduces the detector's sensitivity. Ionization detectors have been known to
react to non-fire-generated particles of combustion and the presence of ozone, ammonia, or insects. Single
chamber ionization detectors installed in higher altitudes usually require a modification in sensitivity during
installation.
Photoelectric Detectors
There are two types of photoelectric detectors: beam and light scattering, both of which consist of a light
source, a collimating lens system, and a photosensitive cell. In a beam-type photoelectric detector, a light
beam is directed at a photocell; when smoke interferes with the beam, the infrared light reaching the receiver
drops, initiating a signal. The light scattering photoelectric detector detects smoke by sensing the light
reflected by smoke particles. When the smoke particles are dense enough to reflect a predetermined amount
of light, the detector's circuit actuates the alarm. Photoelectric detectors respond better to a smoldering fire.
Air Sampling Detectors
Air sampling detectors draw a small amount of air from a target area into a detection device. Typically, these
samplers use a light scattering detection method to analyze the particles found in the sampled air. These
detectors can be calibrated to produce a high degree of sensitivity based on the area protected.
Linear Beam Smoke Detectors
The linear beam smoke detector operates on the same principle as the photoelectric smoke detector in that a
light source is directed on a photosensitive receiver. The difference is that this type of detector consists of two
separate units: a light source, or transmitter, that emits an invisible infrared beam, over open-area distances
of 35 to 300 ft (10.7 to 91.4 m), and a light receiver. This type of smoke detector has many applications, such
as atriums, airport terminals with very high ceilings, aircraft hangars, churches, and large open facilities.
Smoke Detector Use
Smoke detectors are designed to provide early warning for a fire, involving ordinary combustible materials,
that is expected to progress through distinct incipient and/or smoldering stages. The type, volume, and
density of smoke produced during the fire development process will vary greatly depending on the fuels
involved and the amount of oxygen available. Typically, the greatest volume of visible smoke is produced
during the ignition (incipient) stage and the smoldering stage.
Smoke Detector Effectiveness
Even with ready access to low cost and, at times, free smoke detectors, exposure to fire and smoke is
responsible for thousands of deaths and billions of dollars in property damage each year. One challenge for
many property owners is determining what type (i.e., design) of smoke detector to purchase and where to
install the units. Some detectors are more effective (respond quicker) to flaming combustion, while others
respond better to smoldering combustion. Likewise, some detectors are more prone to false activation from
environmental factors than others.
The 2011 National Fire Protection Association (NFPA) Report, “Smoke Alarms in US Home Fires,” indicates
that 385 of the home fire deaths occurred where there were no detectors. Further, the report reveals that 50%
of the detectors that failed to operate were missing batteries, 23% had dead batteries, and 7% had the power
disconnected. In short, the single greatest cause of detector failure does not have to do with the type of
detector, but with a lack of power to the detector.
The NFPA smoke detector webpage offers the following advice: “For each type of smoke alarm, the
advantage it provides may be critical to life safety in some fire situations. Home fatal fires, day or night,
include a large number of smoldering fires and a large number of flaming fires. You cannot predict the type of
fire you may have in your home or when it will occur. Any smoke alarm technology, to be acceptable, must
perform acceptably for both types of fires in order to provide early warning of fire at all times of the day or
night and whether you are asleep or awake.”
In general, photoelectric detectors respond better to a smoldering fire and ionization-type detectors to a
flaming fire. To address the differences in detector types, nearly all of the major manufacturers offer dual (ion
and photo) sensor detectors. Additionally, most risk control specialists recommend that carbon monoxide
detectors also be installed to ensure that all possible combustion products are detected.
Flame Detectors
Flame detectors are primarily intended to protect areas where anticipated fires will develop quickly, with little
or no incipient or smoldering stages, or where ignition is almost instantaneous (i.e., flammable liquids and
combustible gas fires, explosions, and flash fires). A flame detector optically senses radiation given off by
flames or glowing embers. Types of flame detectors include:
Infrared (IR) Flame Detectors
The infrared flame detector senses light at the extreme, high end of the light spectrum. Flicker-flame detectors
are infrared detectors capable of sensing the typical flicker of a flame. With the flicker-flame unit, if the initial
flames are directly hidden from the unit, the flickering light (or radiation) being reflected, such as off a ceiling
or wall, is adequate for initiating an alarm.
Ultraviolet (UV) Light Detectors
The ultraviolet flame detector’s sensing element usually consists of either a solid-state device, such as silicon
carbide or aluminum nitride, or a gas-filled tube in which the gas is ionized by ultraviolet radiation. This
causes the materials to become conductive, resulting in the initiating of an alarm.
Combination Flame Detectors
Combination UV/IR flame detectors are designed to see portions of both light spectrums and use the resulting
composite signal to initiate an alarm. These detectors generally require both UV and IR light sources fitting a
particular frequency to cause an alarm. This process results in fewer false alarms due to the finite
combinations of frequencies accepted.
Spark Detectors
While not a true flame detector, spark detectors identify radiant energy produced by sparks and embers in
closed environments, such as air ducts. Sparks produce both IR and visual light, and as such, these detectors
detect those light spectrums and, through processing circuits, initiate a signal based on the concentrations of
these two sources.
Heat Detectors
Heat detectors respond to the thermal energy of a fire. They are generally located at or near the ceiling of a
building and are best suited for fire detection in small confined spaces where rapidly growing, high-heat
output fires may be expected. Heat detectors are designed to sense a pre-described change in the physical or
electrical property of a material exposed to heat. They may respond either at a fixed temperature, a specified
rate of temperature change, or both.
Fixed Temperature Detectors
Fixed temperature detectors (spot or continuous line type) are designed to activate an alarm when the
temperature of the operating element reaches a specified value. Spot detectors are located in a protected
area and each provides an independent initiation source. Continuous line types consist of a pair of wires in a
twin wire or a coaxial type of conductor that stretches across the protected area. When the wire’s insulation
melts, under fire conditions, the wires short, causing an alarm.
Rate-of-Rise Detectors
One effect that a fire has on the surrounding environment is to generate a rapid increase in the air
temperature in the area above the fire. The rate-of-rise detector is designed to activate when the rate of
temperature change exceeds a predetermined value, typically around 15°F (8.3°C) per minute.
Combination Rate-of-Rise/Fixed Temperature Detectors
Combination detectors are designed to incorporate both rate-of-rise and fixed temperature detectors into one
unit. Rate-of-rise detectors will not activate if the rate of temperature rise is less than the specified value, and
thus, extreme temperatures might be permitted to develop slowly with no alarm. For this reason, heat
detection devices that operate on both the rate-of-rise and fixed temperature principles are available.
Gas Detectors
Gas detectors operate by sensing gases produced by a fire. The presence of certain gases, or aerosols,
causes a reduction in the surface resistance of the sensor, resulting in an increased current flow that is used
to trigger an alarm. This device will only detect fires that burn with incomplete combustion, which produce
significant quantities of gases, as opposed to fires that burn with complete combustion and produce relatively
little or no gases.
Contact
AIG Programs Loss Control
T 800 611 3994
F 888 659 9047
programslc@aig.com
COPYRIGHT ©2013, ISO Services, Inc.
CH-25-51 4/17/13
The information contained in this publication was obtained from sources believed to be reliable. ISO Services, Inc., its companies and employees make no guarantee of results and assume
no liability in connection with either the information herein contained or the safety suggestions herein made. Moreover, it cannot be assumed that every acceptable safety procedure is
contained herein or that abnormal or unusual circumstances may not warrant or require further or additional procedure.
American International Group, Inc. (AIG) is a leading international insurance organization serving customers in more than 130 countries. AIG companies serve commercial,
institutional, and individual customers through one of the most extensive worldwide property- casualty networks of any insurer. In addition, AIG companies are leading
providers of life insurance and retirement services in the United States. AIG common stock is listed on the New York Stock Exchange and the Tokyo Stock Exchange.
Additional information about AIG can be found at www.aig.com | YouTube: www.youtube.com/aig | Twitter: @AIG_LatestNews | LinkedIn: www.linkedin.com/company/aig
AIG is the marketing name for the worldwide property-casualty, life and retirement, and general insurance operations of American International Group, Inc. For additional
information, please visit our website at www.aig.com. All products and services are written or provided by subsidiaries or affiliates of American International Group, Inc.
Products or services may not be available in all countries, and coverage is subject to actual policy language. Non-insurance products and services may be provided by
independent third parties. Certain property-casualty coverages may be provided by a surplus lines insurer. Surplus lines insurers do not generally participate in state guaranty
funds, and insureds are therefore not protected by such funds.