CONVENTIONAL FIRE ALARM CONTROL PANEL 2PD1-5L

CONVENTIONAL FIRE ALARM CONTROL PANEL 2PD1-5L
CONVENTIONAL FIRE ALARM CONTROL PANEL
2PD1-5L
■ Features
•
Alarm delay function
- Heat Detector : 20 sec.
- Smoke Detector : 60 sec.
•
Alarm delay ON/OFF switch function
•
Supervision of detector lines and fault conditions
•
Energy saving technorogy for its running cost
•
Extra slim design
•
Light body using flame retardant ACS resin
•
High reliablility minimmizes maintenance cost
•
Equipped with surge absorbers
•
Re-sounding system
•
1 output for zone alarm bells
•
1 output for signal transfer to external facility
•
Easy wiring by Push-in terminals’ one-touch
connection
2PD1-5L
■ Description
■ Remote Test Function
The 2PD1-5L is a conventional fire alarm panel with
a stylish wall-mount design supplied in 5 zone format.
All detector circuits will be indicated with lighting red
LEDs in alarm conditions and flushing in open circuit
fault conditions. Slide-in paper labels are included
for clear zone identification. The alarm panel has an
alarm delay function on detector circuits to reduce
false alarms, including a delay ON/OFF function.
2PD1-5L utilizes the latest modern technology to
achieve a compact, sophisticated and highly reliable
product. This panel is suitable for a wide range of
environmental risks in industrial and commercial
applications. E.g. Shops, offices, warehouses, guest
houses, post-offices, mobile phone stations, etc.
2PD1-5L is provided with surge absorbers on the
primary and secondary sides of the transformer to
protect its circuit from the lightning and electricalsurge.
Remote test function is available on 2KW-P and
2KAD2-P detectors etc. with a dedicated testing
device.
2KW-P
- Distinguishes steam
and smoke
- Automatic sensitivity
compensation
- Suited for Shower
rooms and Kitchens
* Operating Image
2KAD2-P
- Remote-test available
- Automatic sensitivity
compensation
- Suited for Condominiums
NOT TO BE USED FOR INSTALLATION PURPOSES.
Nittan reserves the right to make changes at any time without notice in prices, colours, materials,
components, equipment, specifications and models and also to discontinue models.
2PD1-5L-DAT-00
Rev.0
■ Indicators on Operation Panel
AC Power Source Indicator
Zone Alarm Indicators
Normal: Turn off
Fire : Turn on (Red)
Open Circuit : Flush (Red)
Circuit Voltage Indicator
Switch Operation Indicator
Alarm Delay Indicator
Panel Buzzer Silence Switch
Activation of this switch when a
panel buzzer is sounding, turns
off the buzzer sounding
Zone Alarm Silence Switch
Activation of this switch makes
zone alarms silence
System Reset Switch
Activation of this switch resets
the panel condition
Alarm Transfer Stop Switch
Battery Test Switch
Fire Test Switch
Test Reset Switch
■ Functions
Alarm Delay ON/OFF switch
This switch can make the alarm delay function ineffective
for installation and mainenance work.
Surge absobers
Lightning surge protection devices are provided as
standard to the primary and secondary sides of a
transformer to protect semiconductor parts.
Push-in type terminals
Push-in type terminals are employed to improve
efficiency at installation.
Test Reset Switch
To aid commissioning and assist routine maintenance
works, an auto-resetting “one man walk test” is available
with the activation of Test Reset switch.
NOT TO BE USED FOR INSTALLATION PURPOSES.
Page 2 of 4
2PD1-5L-DAT-00
Rev.0
■ Dimensions
1. Mounting Hole φ6, φ10
2. Wiring Hole 28.5 x 117
3. Mounting Hole 2-6 x 10
4. Wiring Hole φ11 for AC
Mounting Layout (Front view)
■ Typical Wiring Diagram
2PD1-5L Fire Alarm Control Panel
Input from Manual Alarm Stations
A
L1
For Detectors
Fire Alarm Zones (24 VDC+)
and
Manual Alarm Stations
Fire Alarm Common (-)
For Zone Alarm Bells
Zone Alarm Output (125mA@24VDC)
For Indication Lamps
Indication Lamp Power Source (300mA@25VAC)
Annunciator Power Source (41.5mA@24VDC)
For Annunciator
Fixed Temp.
Heat
L
ROR
Heat
C
Alarm Transfer, Non-Voltage Contact
(Works compulsorily, less than 1A@24VDC)
Alarm Transfer, Non-Voltage Contact
(Stopping switch effective,
less than 1A@24VDC)
F
GA
F’
GC
GB
Smoke
C
For Earth Connection
S
*1
L
C
P
*2
C
P
Bell
B
LED
Bell
B
CRE *3
L *4
*5
*6
LED
*7
I+
I+
I1
I5
I5
IC
IC
F
F'
GA
GB
GC
IB
P1
P2
E
For AC Power Source Input (220 VAC)
A
L
Fire Alarm Zone Indication (-)
Annunciator Buzzer Silence (-)
For Fire Alarm Signal
Transfer
L5
C
B
BC
PL
PL'
I+
I1
L
PSH-5L
Annunciator
F
F'
Security System, etc.
220 VAC
Exclusive
Power supply
*1: Max. number of smoke detectors is 20 pcs. per zone.
*2: P = Manual Alarm Station
*3: The CRE is a dedicated end-of-line device which comes with the 2PD1-5L fire alarm control panel.
*4: Make sure to be used F-F’ terminals when using Remote indication lamps.
*5: Max. number of bells is 12 pcs. when using the motor bells rated at 10 mA, 24 VDC.
*6: Max. number of indication lamps is 30 pcs. when using the indication lamps rated at 9 mA, 24 VDC/AC.
*7: When using Annunciator, any Remote indication lamp with this wiring is not available.
NOT TO BE USED FOR INSTALLATION PURPOSES.
Page 3 of 4
2PD1-5L-DAT-00
Rev.0
■ Specifications
Specifications
AC Power
Standby Battery
Nominal Delay Time
Dimensions
LED Indicators
Functions
External Line Resistance
End of Line Device
Panel Alarm Sounder
Fire Alarm Transfer
Output Current for Zone Alarm Bells
Output Current for Indication Lamps
Number of Connectable Detectors
Connectable Manual Alarm Station
Connectable Annunciator Panel
Operating Temperature
Primary Materials
Body Color
2PD1-5L
220 VAC ±10% 50/60 Hz
24VDC / 0.225 Ah, Sealed Type Ni-Cd battery
60 sec. (For smoke detector: 60 sec. For heat detector: 20 sec.)
W 240 x H330 x D 70 mm
Zone alarm, AC power, Circuit voltage, Switch operation, Alarm
delay
Circuit voltage monitoring, Cable break monitoring
50 Ω and less
CRE
Piezoelectric buzzer, automatic re-sounding type
Contact Capacity
Common Fire Alarm : F-F’ (Normally-Open)
1 A 24 VDC
Fire Alarm
: GA-GB-GC (Form-C)
1 A 24 VDC
125 mA @ 24 VDC (B-BC)
25 VAC 300 mA (PL-PL’)
Standard type Smoke detector: Max. 20 /zone
Heat detector: As required
Thermistor type Heat detector: Max. 24 /zone, Total 12 x zones
2ME1A 2MH1A
Model PSH x 1 unit
0°C to +40°C
Flame retardant resin
JPMA Color Code A22-90B Semi-gloss (off-white)