AE/SA-PX2, AE/94-PX2, AE/PX2
Fire extinguishing control panel PX2 SERIES
AE/SA-PX2, AE/94-PX2, AE/PX2
Description
Extinguishing control panels designed and approved EN12094-1:2006.
Easy and intuitive operation.
D.P.C.
ÚN
CER
TI
CADOS S
EG
FI
· Two monitored areas with dual conventional detection
and three different operating modes:
· Crossed detection:
· Dual detection in one of the loops.
· Mixed detection through crossed detection or dual
detection in either of the two loops.
· Release pushbutton monitored loop.
· Release pushbutton on the panel front, with protective
cover and indicator lamp.
· Hold pushbutton monitored loop.
· Hold pushbutton on the panel front, with protective
cover and indicator lamp.
· Monitored circuit for flow detector.
· Monitored circuit for weight control or pressure switch.
· Monitored evacuation zone.
· Monitored extinguishing zone with programmable delay
time.
· Programmable flood control timer.
· Output for extinguishing released board, monitored.
· Control of reset hold time after release has taken place.
· Power supply unit and battery charger, with mains
voltage control, batteries, feed, battery charging and
auxiliary output.
· Possibility of connection in 2- and 3-wire algorithmic
systems of Aguilera Electrónica.
· Selection of automatic, manual and disabled operating
mode, and access level by means of safety key.
· Internal and external indicator lamps, as well as an
alphanumeric display for presentation of release time
and menu functions.
· Programmed values stored in EEPROM memory.
Technical Characteristics:
Energy Efficiency:
Classification: Class A
Temperature range: 0 º C to +40 º C
Size:
Width: 320 mm
Height: 273 mm
Depth: 123 mm
Colour: RAL9002
Material: AP 011 rolled sheet
Weight: 9 kg with batteries
Power supply:
Power supply voltage: 100~ 250Vac / 40~60Hz.
Recommended cable: H05 VV-F 3 X 1.5mm2
Switched supply adjustment voltage: 28.0 Vdc
Working voltage: 27.2 Vdc
Power supply voltage failure: < 21.5 Vdc > 29.5 Vdc
Automatic disconnection: < 17.0 Vdc
Maximum supply current: 2 A.
Batteries:
2 rechargeable sealed lead-acid 12V / 7Ah batteries.
Charge voltage: 2.275 V per cell, 27.3 V in total
Discharged battery alert voltage: < 21.0 Vdc
Deep discharge battery voltage: < 16.0 Vdc
Battery state test every 10 s
Edición 01/10
España: Madrid A Coruña Barcelona Valencia Sevilla Las Palmas
Fire extinguishing control panel PX2 SERIES
AE/SA-PX2, AE/94-PX2, AE/PX2
Fuses:
Mains: 2 A fuse.
Batteries: 3 A fuse.
Power supply: 2 A fuse.
Detection loops: PTC, current limit at 100mA.
Evacuation: PTC, current limit at 500mA
Extinguishing: PTC, current limit at 1.1A
Extinguishing board released: PTC, current limit 500mA
Auxiliary supply output: PTC, current limit 500mA
Access levels:
Level 1: Functions accessible from front keypad
Level 2: Functions accessible from front keypad, with operating
mode key in manual position.
Level 3: Functions accessible from CPU motherboard.
Operating controls:
Operating mode selection: 3-way key. Automatic, Manual
and Disabled.
Keys on front:
- Silence buzzer
- Reset
- Test
Internal keys: Accessible from access level 3
- Programming
- Reset
Release pushbutton:
Local release pushbutton: Located on front, with protective
cover and indicator lamp.
Remote release pushbutton: Loop monitored by current, with
E.O.L of 2K7 and load resistance of 1K
Hold pushbutton:
Local hold pushbutton: Located on front, with protective cover
and indicator lamp.
Remote hold pushbutton: Loop monitored by current, with
E.O.L of 2K7 and load resistance of 1K
Buzzer:
Type of buzzer: Piezoelectric.
Continuously activated in alarm, and intermittent in fault.
Automatic detection zones:
Number of detection zones: 2
Operating mode selection: Via programming menu.
Detectors max. current: 20 mA
End-of-line resistance: 2K7 1/2W
Flow detector:
Loop monitored by current, with E.O.L of 2K7 and load
resistance of 1K
State confirmation time: 1s
España: Madrid A Coruña Barcelona Valencia Sevilla Las Palmas
Edición 01/10
Light-emitting indicators:
General:
- Power supply
- ON
- Released
- General Fault
- Power supply fault
- System failure
Individual:
- Detection zone 1, alarm and fault
- Detection zone 2, alarm and fault
- Release Pushbutton
- Flow Detector
- Evacuation, alarm and fault
- Extinguishing, alarm and fault
- Hold pushbutton
For operating mode:
- Manual Mode.
- Disabled Mode
Display:
- 2-digit alphanumeric 7 segments display.
Internal individual visible from access level 3:
- Ground Fault
- Flow Detector Fault
- Weight Control or Pressure Switch
- Hold Pushbutton Fault
- Release Pushbutton Fault
- Fault in Extinguishing Release Board
- Auxiliary supply output fault
- Power supply voltage fault
- Battery fault
- Mains failure
Fire extinguishing control panel PX2 SERIES
AE/SA-PX2, AE/94-PX2, AE/PX2
Weight Control or Pressure Switch:
Loop monitored by current, with E.O.L of 2K7 and load resistance
of 1K
State confirmation time: 1s
Sounder:
Monitored 24V output, with E.O.L of 2K7 1/2W. / 500 mA
Extinguishing board released:
Monitored 24V output / 500 mA
Extinguishant:
24V output monitored by diode with solenoid valve 1A
Delay time: Configurable in programming menu from 1 to 60
seconds.
Auxiliary supply output:
Monitored 24V output / 500 mA
4 Relay outputs (optional) AE/PX2R motherboard :
Relay alert or pre-released: NO, C and NC contacts
Relay in released state: NO, C and NC contacts
Relay in fault state: NO, C and NC contacts Actuated in idle.
Manual state relay: NO, C and NC contacts
Incorporation in Algorithmic System:
AE/PX2
AE/SA-PX2: 2-Wire Algorithmic System
AE/94-PX2: 3-Wire Algorithmic System
Edición 01/10