Self-Contained 120/240 Vac Power Supply

Self-Contained 120/240 Vac Power Supply
Effective: June 2007
Self-Contained 120/240 Vac
Power Supply
For AnaLASER II® Detectors
TM
R
Protection Systems
A UTC Fire & Security Company
F-89-258
FEATURES
•
•
•
•
•
•
•
•
•
•
UL Listed
FM Approved
ULC Listed
CSFM Listed
NYC MEA Approved MEA 60-02-E
120 or 240 Vac Input
24 Vdc Output
4 Hours of Battery Backup
Integral Battery Charger
Fully Supervised
•
Easily Integrated with an AnaLASER® II Detector
DESCRIPTION
The Self-Contained 120/240 Vac Power Supply Assembly provides supervised 24 Vdc power with 4-hour
backup for a single AnaLASER® II Detector. The universal input accepts either 120 Vac or 240 Vac input voltage
and does not require manual voltage selection to operate
in either range.
The Self-Contained 120/240 Vac Power Supply Assembly is designed with a matching enclosure to attach to the
bottom of an AnaLASER II Detector to create a Self-Contained AnaLASER II Detector Assembly.
The enclosure holds the power supply/battery charger
and two sealed lead-acid batteries. This will provide
power with 4 hours battery back-up for an AnaLASER II
Detector, making it ideal for single zone detection applications in a facility with emergency power systems.
The power supply/battery charger supervises the input
AC power, the batteries and the battery charger. A trouble signal provides power supply supervision to the
AnaLASER II Detector. There are no controls on the
power supply.
The Self-Contained AnaLASER II Detector Assembly is
designed for surface mounting with a painted steel backbox and a light gray polycarbonate cover. All wiring from
the power supply to the Detector is routed through
matching knockouts on the top of the power supply and
on the bottom of the AnaLASER II Detector.
The power supply is listed and approved as a smoke
detector accessory.
POWER SUPPLY TECHNICAL SPECIFICATIONS
Input Voltage:
120 or 240 Vac 50/60 Hz.
Must be fed from an emergency power circuit.
Maximum Input Current:
33 mA @ 120 Vac
200 mA @ 240 Vac
Operating Temperature:
32º to 120ºF (0º to 49ºC)
Operating Humidity:
10 to 93% RH,
(non-condensing)
Output Voltage:
28.75 Vdc
Output Current:
1 A maximum
Battery Charger Voltage:
27.3 Vdc
Battery Charging Circuit:
500 mA
Trouble Output:
Normally closed TTL Logic
Electrical Connections:
18 to 14 AWG (0.75 to
2.08 mm2) wiring to terminal
block
Shipping Weight:
7.4 lb. (3.4 kg)
Dimensions:
12-19/32 in. W x 4-35/64 in.
H x 4-1/4 in. D (320 mm W x
115 mm H x 108 mm D)
SBATTERY TECHNICAL SPECIFICATIONS
MECHANICAL DRAWINGS
12 Vdc
Capacity:
2 Ah
Construction:
Sealed Lead-Acid
Termination:
0.187 quick disconnect terminals
Dimensions:
5-29/32 in. W x 3-1/2 in. H x
25/32 in. D (150 mm W x
89 mm H x 20 mm D)
Shipping Weight:
1.54 lb. (0.7 kg)
4-11/16 in.
(117 mm)
Nominal Voltage:
4-13/64 in.
(107 mm)
FRONT
12-19/32 in.
(320 mm)
BOTTOM
SIDE
ORDERING INFORMATION
Component
Part Number
Self-Contained 120/240 Vac Power
Supply Assembly. Consists of:
(1) 89-300008-000 and
(2) 89-300023-001
89-300008-001
Self-Contained 120/240 Vac Power
Supply with Enclosure Only
89-300008-000
12 Vdc, 2.0 Ah Battery
89-300023-001
AnaLASER is a registered trademark of Kidde-Fenwal, Inc.
TM
This literature is provided for informational purposes only. KIDDE-FENWAL, INC.
assumes no responsibility for the product’s suitability for a particular application. The
product must be properly applied to work correctly.
If you need more information on this product, or if you have a particular problem or question, contact KIDDE-FENWAL, INC., Ashland, MA 01721. Telephone: (508) 881-2000.
F-89-258 Rev AC
© 2007 Kidde-Fenwal Inc.
Printed in USA
R
Protection Systems