VESDA Series
s
Data Sheet
Fire Safety & Security Products
VESDA Series
Display Modules
Models VRT[s]  100 / 200 / 300 / 400 / 500 / 600 / 700 / 800 and / 900
ARCHITECT AND ENGINEER SPECIFICATIONS
 Provides immediate status reporting for a
single VESDA zone
 Allows zone control of assigned VESDA
detector
 Vertical bar-graph display containing 20
segments
 Comprehensive fault reporting
 Alarm-threshold indicators
 High-intensity light-emitting diode (LED) for Alarm events
 Built-in sounder for audible warning
 Multi-mode numeric display
 Defaults to smoke obscuration
 Remote relay option
Model VRT-series
[SCANNER-display version]

Model VRT-series
[Standard-display version]
UL 864 9th Edition Listed, ULC Listed;
FM, CSFM and NYC Fire Department Approved
Product Overview
The VESDA display modules, which provide real-time
indication of device status, contain the following:





One (1) [20-segment] vertical bar graph display
One (1) [two-digit] numeric display
One (1) audible sounder
One (1) clear alarm
Multiple fault indicators
Each display module can be mounted into one (1)
detector unit; one (1) remote mounting box, or one
(1) 19-inch sub rack. Several displays can be
configured to display information from a single
detector in multiple locations.
Specifications
Each VESDA display module varies, due to relayconfiguration requirements and detector types. For
example, the LaserSCANNER display has a fourth
mode for the numerical display, which shows the
First Alarm Sector (FAS). The FAS indicates the
number of the sector (pipe) that has detected
smoke. For the LaserCOMPACT display, the Fire 2
LED is not present.
Smoke Indication Level
Smoke levels are continuously shown on a bar-graph
display in which each illuminated segment indicates
the current level of detected smoke. The top
segment of the bar graph indicates the maximum Fire
1 smoke-threshold level, and each segment below the
top segment represents 1/20TH of the Fire 1 smokethreshold level.
To the left of the bar graph are the Fire 1, Action and
Alert smoke-threshold indicators. These indicators,
which represent programmable alarm thresholds, will
illustrate smoke levels and the proximity for
triggering into the next alarm level.
Status Lights
High-intensity flashing LEDs, which provide a clear
indication of the fire condition, are accompanied by
an audible warning signal that corresponds to the
alarm condition. Similarly, any fault condition is
indicated by a series of LEDs and an audible tone that
provide a comprehensive range of status data.
VESDA Display Modules
s Industry, Inc.
Building Technologies Division
1172
Product Overview ─ (continued)
The audible warning is easily silenced by pressing the
Silence button at which point any flashing LEDs are
illuminated until the cause of the event is identified,
rectified and the system has been reset.
Technical Data ─ (continued)
Inactivity
Time Out:
S
Y
S
T
E
M
Numeric Display
A two-digit numerical readout has a number of
modes that are indicated by a maximum four (4)
LEDs:




The current smoke level in % obscuration / feet
(international: % obscuration / m)
Fire 1 threshold in % obscuration / feet
(international: % obscuration / m)
 This is the sensitivity of the detector
The VESDA zone number
First Alarm Sector on the LaserSCANNER display
 The numeric readout shows the sector (pipe)
number that has detected smoke
Four (4) large, sizable push-button keys enable users
to reset, isolate or silence the detector; as well as
control the mode of the display module. The buttons
can be disabled to prevent operation of its functions.
A lamp-test routine is initiated by pressing the Mode
key for two seconds. A manual scan can be initiated
on the LaserSCANNER by holding the Silence button
for two seconds.
Technical Data
VESDA Display Module Specifications 
Module
Handheld
Remote
Min. 0.6 Watts
1.3 Watts
1.3 Watts
3.0 Watts
Max. 2.3 Watts
3.0 Watts
Min.
20mA
50mA
50mA
Current:
Max.
80mA
110mA
110mA
(@ 24VDC)
Dimensions: In. 3.9” -x- 5.1” -x- 1.2” 4.1” -x- 5.3” -x- 2.4” 5.5” -x- 5.9” -x- 3.4”
(9.8 cm. -x- 13 cm. (11 cm. -x- 14 cm. (14 cm. -x- 15 cm.
{ W -x- H -x- D }
cm.
-x- 30 cm.)
-x- 6 cm.)
-x- 9 cm.)
Power:
(@ 24VDC)
Connections:
Supply Voltage:
Operating
Temperature:
Relative
Humidity:
Push-Button
Keys:
Terminal connector to
head processor card or to
expansion connector on
another VESDA device
Fifteen-pin, ‘D’-type
connector. VESDAnet
cable required in order to
connect to detector, or to
remove VESDAnet socket
[12 ─ 30 American Wire Gauge (AWG)]
[0.2 ─ 2.5 mm²]
32° ─ 103° F
(0° ─ 39° C)
10 ─ 99 %; non-condensing
0.75’’ -x- 0.50’’
(1.9 cm. -x- 1.2 cm.)
2.75” -x- 1.45”
(7.0 cm. -x- 3.7 cm.)
Screen Display
Characteristics: Large characters:
 eight (8) lines
 21 characters per line
s Industry, Inc.
Building Technologies Division
 Push-button lockout
 Display name:  Zone number and name:
 21 characters
 21 characters
Alarm thresholds:
 Alert
 Fire 1
 Action
 Fire 2
 Alarm delays:
 0  60 seconds
 Pipes in use:
 Pipe 1 to 4
 Event log:
 Up to 18,000 events
 Day / night / weekend / holiday options
 Aspirator speed & flow control
 Confirmation of filter change
 Relay configuration
-
D
E
V
I
C
E
S
-
RS485 VESDAnet field
wiring; used to screw
terminal blocks:
18 ─ 30VDC
(Two (2) Rows -xfour (4) keys, each)
A
D
D
R
E
S
S
E
D
Full-graphics display
 Adjustable backlit
screen with
contrast control
S
E
C
U
R
I
T
Y
 Beeps at 1 minute, 15 seconds before
automatic log-off, due to end-user inactivity
 Software and status versions
 Descriptive Alarm and Fault events
 Smoke and flow readings
F
U
N
C
T
I
O
N
S
Push-button keys
 10 minutes of end-user inactivity
 will default to log-on screen
-
A
C
C
E
S
S
-
 Referencing
 AutoLearn™
 250 VESDA devices max.
VESDA addressed devices:

Detectors & displays
 LaserPLUS
Detectors & displays
 LaserSCANNER 
Detectors & displays
 LaserCOMPACT 
 High-level interface:
 Model HLI
 Remote programmer:
 Model VRT-100
 Handheld programmer:
 Model VHH-1000
 Optional recessed mounting kit:
 Model VSP-012
 19-inch (48.3 cm.) sub-rack configuration
 Contact Siemens  Fire Safety
 Relay modules / remote relays
 Ordering information
 User ID characteristics:
 Three (3) characters minimum
 Four (4)-digit Personal Identification
Number (PIN)
Default IDs:
 ‘ USR ‘
 ‘ ADM ‘
 ‘ DST ‘
 User [Operator level]
 Administrator
[Accessibility to most system functions]
 VESDA Distributor
[Accessibility to ALL system functions]
Number of user levels:

[for ‘ USR’ ]
 10

[for ‘ ADM’ ]
 Three (3)

[for ‘ DST’ ]
 One (1)
Mounting Diagrams
Details for Ordering
Model
Number
s Industry, Inc.
Part
Number
VRT-100
500-699829
VRT-200
500-699830
VRT-300
500-699835
VRT-400
500-699832
VRT-500
500-699836
VRT-600
500-699831
VRT-700
500-699833
VRT-800
500-699834
VRT-900
500-699837
Building Technologies Division
Description
Remote Programmer with remote termination card
[zero (0) relays]
Standard Display with remote termination card
[seven (7) relays]
VESDAnet Socket
Scanner Display with remote termination card
[seven (7) relays]
Remote termination card for Models VLC and VLP
[seven (7) relays]
Scanner display with remote termination card
[zero (0) relays]
Scanner display with remote termination card
[zero (0) relays]
Scanner display with remote termination card
[12 relays]
Model VLS remote termination card
[12 relays]
Notice: This marketing data sheet is not intended to be used for system design or installation purposes.
For the most up-to-date information, refer to each product’s installation instructions.
s Industry, Inc.
Building Technologies Division
Fire Safety
8 Fernwood Road
Florham Park, NJ 07932
Tel: (973) 593-2600
FAX: (908) 547-6877
URL: www.SBT.Siemens.com/FIS
(SII-FS)
Printed in U.S.A.
Fire Safety
2 Kenview Boulevard
Brampton, Ontario
L6T 5E4 / Canada
Tel: (905) 799-9937
FAX: (905) 799-9858
April 2012
Supersedes sheet dated 1/03