PTS TYPE

PTS TYPE
VOLTAGE RELAY
PTS TYPE
High-performance under-voltage relay
that activates output when all 3-phase voltages
fall below a reference voltage by monitoring voltage
on each phase of 4 wires
FEATURES
Monitoring voltages of 3-phase 4 wires with a single unit
The PTS type for monitoring 3-phase 4 wires is newly available in addition to
the conventional FVS type that monitors only one phase. The PTS type
under-voltage relay monitors all 3-phase voltages to verify that voltages on all
phases are lower than a reference voltage. The PTS type incorporates 1a1b
output contacts.
Operation status LED
Digital switch
With the operation monitor LED, you can
easily check control power ON/OFF
status and monitor voltage.
(POWER, UV)
The digital switch simplifies the reference
voltage setting procedure.
G17
Labels that indicate reference voltage settings
are included in the product.
If you attach a label after setting a voltage, you
can easily confirm the reference voltage.
Since control voltage is input from the monitor power
supply, the relay unit does not need an additional
control power supply.
∗ The internal relay turns OFF when input voltage
falls below 38V regardless of the reference voltage
setting.
High-performance engineering
plastic is used for the storing case.
Specification
250V
Monitor/control input voltage
Each phase: 40 to 110V AC
Max. input value
130V (continuous), 250V (instantaneous)
Input impedance
4kΩ or more (when output relay is exited)
40, 50, 60, 70, 80V AC (5 settings)
Noise resistance
10MΩ or more (500V DC Megger tester) ∗2
L-A
2,000V AC for 1 min. ∗1
L-L
2,000V AC for 1 min. ∗2
L-A
±7kV / 3 times for each pole ∗1
L-L①
±4.5kV / 3 times for each pole ∗2
L-L②
±3kV / 3 times for each pole (between monitor / control input terminals)
Static noise
Vibration resistance
Shock resistance
Ambient temperature
TERMINAL
BLOCK
150MHz band (5W), 400MHz band (5W)
Electric wave noise
900MHz band (cellular phone)
Contact discharge: 8kV Air discharge: 15kV
Frequency: 16.7Hz Double amplitude: 0.4mm
Direction: Forward / backward, right / left, up / down
Shock value: 294m/s2
Vibration time: 10min
Number of shocks: 3 times each (forward, backward, right, left, up, down)
Performance warranty
0 to 40˚C
Operation warranty
–10 to 55˚C (Allowable for several hours per day)
–20 to 60˚C
Recovery warranty
30 to 90% (daily average)
Relative humidity
Altitude
2,000 m max.
Power consumption
Approx. 3.5 W (Control power supply: Maximum rating, When output relay is excited)
Approx. 220g
Weight
∗1 Between monitor/control input and output contact terminals and mounting rail
∗2 Between monitor/control input terminals and output contact terminals, and between individual output contact terminals
G18
ELECTRONIC
DEVICES
Impulse withstand voltage (Uimp)
10MΩ or more (500V DC Megger tester) ∗1
L-L
G
Power-frequency withstand voltage
L-A
F SWITCH
Reference voltage
Insulated resistance
PILOT LAMP &
INDICATOR
Item
Rated insulation voltage (Ui)
E
SPECIFICATIONS(RATINGS, PERFORMANCE)
D TEST TERMINAL
C
To enhance flame-retardance, high-performance
engineering plastic is used for the storing case.
(UL94, V-1)
A
Control voltage is input from monitor
power supply. No additional control
power supply is required.
B CONNECTOR
Voltage indication label
(standard accessory)
CONTROL
CENTER PARTS
ELECTRONIC DEVICES
VOLTAGE RELAY
PTS TYPE
HOW TO ORDER
No.
Item
Indication
①
②
Basic type
Shape code
PTS
S
③
Circuit code
P
④
Power supply voltage
AC 40 / 120
Description
Remarks
8-pin socket type
Applicable to the socket, 8PFA1 (OMRON)
3-phase 4-wire AC
under-voltage monitoring
Since control voltage is input from monitor power supply, no additional control power supply is required.
40 to 120V AC
CONFORMABLE STANDARDS
Standard
Name
Year
JEC-174D
JEC-2500
B-402
Auxiliary relay for power supply
Protection relay for power supply
Digital protection relay and protection relay equipment
1987
1979
1997.10
OTHER SPECIFICATIONS
Item
Description
Set / Reset time
Error range
Reset dead band
Temperature effect
Output contact rating
Number of output contacts
Operational indication color
Max. operational voltage
Rated current-carrying capacity (Ith)
UNDER
Power supply indicator
Output contact indicator
0.5 sec. max.
Within ±2V
Within +4V
Within ±1V / 10°C
380V AC max. 125V DC max.
5A
1a1b
Green (during operation)
Red (during operation)
MAXIMUM SWITCHING CAPACITY OF OUTPUT CONTACT
Contact current (V)
AC resistance load
DC resistance load
AC inductive load
DC inductive load
Contact voltage (V)
G19
Input indicator
(Green)
Operation indicator
(Red)
Reference voltage setting
(Digital switch)
Location of voltage indication label
(Attached after setting)
B CONNECTOR
A
STANDARD PRODUCTS
TERMINAL
BLOCK
ELECTRONIC DEVICES
■Connection diagram
(Example: Operating voltage: UNDER=DC50V)
Monitor / control input B
Monitor / control input C
Monitor / control input N
PILOT LAMP &
INDICATOR
Operation error
(Within ±2V)
Monitor / control input A
Output contact
operation
0.5 sec. max.
0.5 sec. max.
●Operation
By monitoring input voltage on each phase of AC 3-phase 4 wires, the output contact is switched when all
3-phase voltages fall below a reference voltage. The internal relay has no voltage when input voltage is
38V or lower regardless of the reference voltage setting.
The above operation chart is based on “a-contact” output.
In constant monitoring mode, the internal relay is ON.
⇒ (Terminals 3 - 4: Open, Terminals 5 - 6: Closed)
When all 3-phase voltages fall below a reference voltage or when the monitor input is lost, the internal
relay turns OFF.
⇒ (Terminals 3 - 4: Closed, Terminals 5 - 6: Open)
E
Input: AC
Monitor input
(constant)
: 100V
Reference voltage
(UNDER)
: 50V
Reset dead zone
(Within +4V)
UNDER contact
PTS main unit
SW setting
Phase A, B, C
F SWITCH
■Operation chart
D TEST TERMINAL
C
CONTROL
CENTER PARTS
Digital switch selection table NP
All 3-phase voltages are 38 V or lower
All 3-phase voltages are reference voltage or lower
At least one-phase voltage is higher than reference voltage
Internal relay Terminals 3 – 4 Terminals 5 – 6
Unlit
Unlit
No voltage
Lit
Lit
No voltage
Lit
Unlit
G20
Excited
G
Power supply indicator lamp (Green) Operation indicator lamp (Red)
ELECTRONIC
DEVICES
●Indicators
VOLTAGE RELAY
PTS TYPE
TECHNICAL DATA
REFERENCE VOLTAGE SETTING PROCEDURE
Reference voltage (operating voltage) setting
By referring to the “Digital switch selection table” on
the side of the relay unit, specify a reference voltage
with the digital switch.
(Example: To set “70 V AC”, turn ON the No. 4 bit.)
Digital switch selection table
∗ Attached on side of the product body
Attaching voltage indication label
To indicate the reference voltage specified in step ① ,
attach the voltage indication label (included in the
product).
Be sure to attach this label so that the voltage is not
y changed
g after setting.
g
accidentally
Before attaching the label, verify tha
Bef
that the digital switch
sett
ting conforms to the selection tab
setting
table on the side of
the product body.
Voltage indication
in
label
∗ Standard acc
accessory included in the product
Connecting the relay unit to a socket
Connect the relay unit to a specified applicable socket
to apply a monitor voltage.
G21
A
ACCESSORIES
TERMINAL
BLOCK
ELECTRONIC DEVICES
Voltage indication label (∗Included as standard accessory)
(Order unit: 10)
(Order unit: 10)
●PTS-SP-NP
Modified PPE
Brass / Tin-plated
Remarks
■Instructions for handling the product and other information
● When setting a voltage, be sure to disconnect the
relay unit from the socket, or do not apply a monitor
voltage or power supply voltage to the relay unit (to
prevent output error).
● After setting a voltage, be sure to attach the voltage
indication label suitable for each state (to prevent
erroneous operation and entry of a foreign
substance).
● When you set a reference voltage with the digital
switch, do not turn ON multiple bits simultaneously
(to prevent output error).
ELECTRONIC
DEVICES
● This product is applicable to a 3-phase 4-wire voltage
circuit and is not applicable to a 3-phase 3-wire
voltage circuit. In applications to other circuits, this
product enables monitoring of typical phase voltage
of 3-phase 4-wire circuit, and monitoring of
single-phase 2-wire voltage.
● For connection with a PT (transformer), check the
capacity of the transformer (including other load).
PILOT LAMP &
INDICATOR
Material
Case
Plug pin
E
Part name
G22
G
No.
F SWITCH
Typical parts list
D TEST TERMINAL
C
CONTROL
CENTER PARTS
●8PFA1 [OMRON]
B CONNECTOR
Applicable socket