D7024‑EXP Fire Alarm Control Panels
Fire Alarm Systems | D7024‑EXP Fire Alarm Control Panels
D7024‑EXP Fire Alarm Control Panels
▶ Four detector zones (expandable to eight); up to 20
two‑wire smoke detectors per zone
▶ Built-in DACT
▶ Two notification appliance circuits (NACs) on board
with an internal 24 VFWR, 4 A NAC power supply
▶ Easily converts to addressable with the addition of a
D7039 Multiplex Expansion Module
▶ Programmable through front panel interface, remote
D7033 Liquid‑crystal Display (LCD) Keypads, or remote
programming software (RPS)
The D7024‑EXP Fire Alarm Control Panels (FACPs) can be
used in commercial and public building applications such
as schools, universities, manufacturing plants, and health
care facilities.
The D7024‑EXP FACPs support four on-board initiating
zones that can be expanded to eight using the D7034. Each
initiating loop supports two-wire and four-wire detectors
configurable as Class A, Style D (with D7014) or Class B,
Style B loops. Each zone can support up to 20 two-wire
detectors, or any number of four-wire detectors depending
on available power. Each FACP has a built-in digital fire
alarm communicator transmitter (DACT).
Enhance the D7024‑EXP conventional system features
when running version 2.02 or higher firmware by adding a
D7039 Multiplex Expansion Module. Adding a D7039
Multiplex Expansion Module to the D7024‑EXP turns the
conventional FACP into an addressable FACP. The D7039
adds up to 247 addressable points to the base system and
adds an additional 400 events to the history buffer for a
total of 499 events. The D7039 also increases the number
of programmable relay outputs from 18 to 58 and allows up
to 100 system users (an addition of 84 PINs to the base
system).
Functions
Notification Appliance Circuits (NACs)
Two on-board Class B, Style Y or Class A, Style Z (with
D7015) NACs provide up to 4 A of 24 VFWR power to
operate horns, strobes, bells, and other notification
appliances. Each NAC can be programmed to provide
Temporal Code 3, steady, pulsed, and synchronized output
for Wheelock™ and Gentex™ notification appliances.
User Interface
A viewing port in the keyed control panel enclosure door
shows the system status light‑emitting diodes (LEDs) and
LCD display while maintaining system keypad security.
Unlocking the enclosure door provides access to the system
controls for silencing off‑normal conditions, zone
bypassing, detector resetting, testing, other fire functions,
and programming. These functions are also available on all
D7033 LCD Keypads connected to the system. All D7036
LCD Annunciators provide custom text annunciation on a
32-character, backlit, two‑line LCD display. All system
keypads and annunciators have built‑in sounders. Back‑light
intensity and sounder volume are programmable.
www.boschsecurity.com
2 | D7024‑EXP Fire Alarm Control Panels
Personal Identification Numbers (PINs)
There are 16 PINs available for accessing system control.
Assign each number an authority level to limit access to the
system control functions.
Note
The number of PINs increases to 100 with the
addition of a D7039 Multiplex Expansion
Module.
Category
Modules
History Buffer
The system stores events in a 99‑event history buffer.
Note
The number of events that can be stored in the
history buffer increases to 499 with the
addition of a D7039 Multiplex Expansion
Module.
Central Station Reporting
The D7024‑EXP FACPs send reports to two telephone
numbers with full single, double, and backup reporting.
They communicate in BFSK, SIA, Contact ID, Modem IIIa2,
and 4/2 and 3/1 Tone Bursts.
Dirty Smoke Detector Monitoring
All on‑board zones and D7034 zones are continuously
monitored for smoke detectors signaling a dirty condition
using the Bosch Chamber Check® feature and CleanMe®
protocol. If a detector's smoke chamber is dirty, the
detector sends a CleanMe signal on the two-wire loop or a
dirty detector signal on the addressable loop. The control
panel annunciates that there is a dirty detector on the loop
or the address. The Chamber Check feature signals a dirty
smoke chamber using the LED on the detector head.
NAC Devices
Category
Product ID
Product Description
Batteries and
D126
12 V, 7 Ah battery
Power Supplies
D1218
12 V, 18 Ah battery
D7038
Remote NAC power supply
Detectors
For two-wire detectors, refer to D7022-D7024 Compatibility List Technogram (P/N: 34445)
Keypads and
Annunciators
D7030X
Eight‑point LED annunciator
(eight red)
D7030X‑S2
Eight‑point LED annunciator
(two yellow, six red)
D7030X‑S8
Eight‑point LED annunciator
(eight yellow)
Eight‑zone LED annunciator expander
(eight red)
D7033
LCD fire system keypad
D7036
LCD annunciator
D132B
Smoke detector reversing relay module
D184A
Auxiliary local energy interface kit
D185
Reversing polarity module
D275
EOL power supervision module
D7014
Zone converter module
D7015
Class B to Class A NAC converter
D7031
Silence reset module
D7034
Four-point expander
D7035
Octal relay module
D7035B
Octal relay module in box
D7039
Multiplex expansion module
D7039R
Multiplex expansion module retrofit kit
Refer to D7024 NAC Compatibility List Technogram (P/
N: 34950)
Product ID
Product Description
Modules
D7042
Multiplex eight‑input remote module
D7042B
Multiplex eight‑input remote module
in box
D7044
Multiplex single‑input module
D7044M
Mini multiplex single‑input module
D7048
Multiplex octal driver
D7048B
Multiplex octal driver in box
D7052
Multiplex dual‑input module
D7053
Multiplex input-output module
FMM‑7045
Single‑action manual station
FMM‑7045‑D
Double‑action manual station
Pull Stations
The following products are compatible with the D7024-EXP
FACPs:
D7032
Category
The D7024‑EXP enclosure has space for additional
accessory modules and two D1218 (18 Ah) batteries or two
D126 (7 Ah) batteries.
Compatible Products
Product Description
The following additional product is compatible with the
D7024‑EXP Addressable FACPs:
Accessories
Installation/Configuration Notes
Product ID
D7024‑EXP Fire Alarm Control Panels | 3
Parts Included
Trademarks
Quant.
Component
1
D7024-EXP board in a static-resistant bag
Chamber Check® is a registered trademark of Bosch Security Systems, Inc.
in the United States.
1
Enclosure (P/N: 30897)
1
Lock set with 2 keys (P/N: 24065)
1
Transformer (P/N: 38602)
6
2.21 kΩ end-of-line (EOL) resistors (P/N: 25899 or
4998113202)
1
Hardware pack
1
Literature pack
Note
Wheelock™ is a trademark of Wheelock, Inc.
Gentex™ is a trademark of Gentex Corporation.
Ordering Information
For the D7024-EXP to be addressable, a D7039
Multiplex Expansion Module must be installed.
The D7039 is purchased separately.
Technical Specifications
Environmental Considerations
Temperature (operating):
CleanMe® is a registered trademark of GE Interlogix in the United States and/
or other countries.
0°C to +49°C
D7024-EXP FACP for Export
Four detector zones (expandable to eight); up
to 20 two wire smoke detectors per zone
D7024-EXP
D7024-EXPLT FACP for Export without
Enclosure and Transformer
Four detector zones (expandable to eight); up
to 20 two wire smoke detectors per zone
D7024-EXPLT
Accessories
KEY‑625 Replacement Key
Replacement key
KEY-625
Mechanical Properties
Color:
Red
Dimensions (H x W x D):
52.8 cm x 38.1 cm x 10.9 cm
Material:
Cold-rolled steel
Base: 1.2 mm
Cover: 1.1 mm
Outputs
NAC:
24 VFWR nominal, 4 A maximum
On-board Relays:
Two Form C contacts rated at 5 A, 28 VDC
Off-board Relays:
Up to two D7035 Octal Relay Modules each providing eight Form C relay outputs; contacts rated at 5 A,
28 VDC
In an addressable system, up to 20 D7053 Multiplex
Input‑Output Modules per bus for a total of 40
Power Requirements
Current (alarm):
380 mA
Current (standby):
200 mA
Power (primary)
220 VAC, 1.5 A maximum, 50 Hz
Sensor Circuits
Current:
44 mA maximum per loop
Line resistance:
150 Ω
Voltage:
24 VDC nominal
www.boschsecurity.com
4 | D7024‑EXP Fire Alarm Control Panels
Americas:
Bosch Security Systems, Inc.
130 Perinton Parkway
Fairport, New York, 14450, USA
Phone: +1 800 289 0096
Fax: +1 585 223 9180
security.sales@us.bosch.com
www.boschsecurity.us
Europe, Middle East, Africa:
Bosch Security Systems B.V.
P.O. Box 80002
5600 JB Eindhoven, The Netherlands
Phone: + 31 40 2577 284
Fax: +31 40 2577 330
emea.securitysystems@bosch.com
www.boschsecurity.com
© Bosch Security Systems Inc. 2010 | Data subject to change without notice
T3642949899 | Cur: en-US, V6, 4 Jul 2010
Asia-Pacific:
Represented by
Robert Bosch (SEA) Pte Ltd, Security Systems
11 Bishan Street 21
Singapore 573943
Phone: +65 6258 5511
Fax: +65 6571 2698
apr.securitysystems@bosch.com
www.boschsecurity.com
Was this manual useful for you? yes no
Thank you for your participation!

* Your assessment is very important for improving the work of artificial intelligence, which forms the content of this project

Download PDF

advertising