Series GA-170 Gas Alarm

Series GA-170 Gas Alarm
Series GA-170
Gas Alarm
The Series GA-170 Gas Alarm system provides a reliable
and simple solution for gas detection applications. The
GA-170 Gas Alarm incorporates a simple modular design
that can integrate a variety of gas sensor types with up to
four sensors per alarm module. The digital alarm module
is controlled through a user-friendly interface consisting
of push-buttons and a two line, sixteen character, alphanumeric, backlit LCD Display. The digital alarm module is
housed in a NEMA-4X enclosure, and includes visual and
audible alarms. The electrochemical gas sensor(s) can be
located up to 1000 feet (300 m) away from the alarm module. The alarm module includes common contact relays
and adjustable alarm contact relays for each sensor. All
sensor contact relays are user adjustable and High Alarms
can be set as latching or non-latching and failsafe or nonfailsafe. Battery Back-Up is available as an option.
Configuration
Sensor configuration mode is entered using a password and then adjusted using push buttons. Latching and
Failsafe alarm options are also password adjustable.
Operation
Simple menu driven, push-button controlled programming is
performed on the alarm module. Alarm outputs are provided
to activate external devices. A front panel push button function
is used to acknowledge/deactivate latching alarms. A contact
input is provided for remote acknowledge of latching alarms.
Front Panel display and LED’s provide continuous and clear
operation status.
Maintenance
Gas sensors can be replaced and/or recalibrated through the
push-button menu. Sensor types can be easily changed.
Calibration
Contact Hydro Instruments for calibration gas and sensor
testing devices.
Highlights:
• Up to 4 Sensors
• User-friendly key pad interface for
easy calibration and operation
• Available for Cl2, SO2, NH3, H2S, O3,
ClO2, H2, O2, NO, NO2, HCl
• Includes six alarm relays
• Backlit Liquid Crystal Display (LCD)
for easy reading. 2 line, 16 spaces
• Built-In 90 dB audible Alarm and
Danger/Alarm LEDs
• Optional Battery Back-Up
• RS232 Output Option
• 4-20 mA Output Option
• Remote Acknowledge
• Password Protection
PROUDLY
INSTRUMENTS
BULLETIN GA-170 Rev. 3/13
MADE IN USA
600 Emlen Way, Telford, PA 18969 • Telephone: (215) 799-0980 • Fax: (215) 799-0984
Toll Free in the U.S.: 1 (888) 38-HYDRO • www.hydroinstruments.com • sales@hydroinstruments.com
Digital Alarm Module:
Standard Gas Sensors:
NEMA 4X Enclosure
8" x 6" x 4"
Temperature Range
0°-55°C / 32°-131°F
Total Weight
7 lbs
Weight with Battery
9 lbs
Relays:
Common AC Power Loss
5A SPDT
Common Sensor Failure
5A SPDT
Each Channel
Low Alarm (Danger)
5A SPDT
High Alarm (Alarm)
5A DPDT
Audible Alarm90dB
Power Requirement
120 V/240 V, 50-60 Hz
Power Consumption
20 W max.
Battery Back-Up (optional)
12 hours, 2.9 A•Hr, 12 VDC gel cell
External Acknowledge
Input Contact
Signal Output (optional)
RS232, 4-20 mA
Remote Acknowledge
Input Contact
Warranty
1 year limited
Ammonia (NH3):
0-100 PPM
Chlorine (Cl2):
0-10 PPM
Chlorine Dioxide (ClO2):
0-10 PPM*
Ozone (O3):
0-10 PPM*
Sulfur Dioxide (SO2):
0-30 PPM
Hydrogen (H2):
0-200 PPM
Hydrogen Sulfide (H2S):
0-100 PPM
Nitric Oxide (NO):
0-100 PPM*
Nitrogen Dioxide (NO2):
0-100 PPM
Oxygen (O2):0-25%
Hydrogen Chloride (HCl):
0-10 PPM
Note: Other ranges are available.
Consult the factory.
Sensor:
Cable Type:
22 AWG shielded
Cable Length: 25 ft. std. (longer available)
Sensor Type:Electrochemical
Includes shipping cap and calibration ports.
Note: Single and Dual sensor units will have both Low Alarm and High Alarm relays for each sensor. Three and Four
sensor units will only have one High Alarm relay per sensor.
Series GA-170 Gas Alarm Ordering Information
Model GA-170 - A - B - C - D - E - F - G - H
A.
B.
C.
D.
E.
F.
G.
H.
Sensor 1 Gas Type:
1 - Chlorine (0-10 PPM)
2 - Sulfur Dioxide (0-30 PPM)
3 - Ammonia (0-100 PPM)
4 - Other (consult factory)
Sensor 2 Gas Type:
1 - Chlorine (0-10 PPM)
2 - Sulfur Dioxide (0-30 PPM)
3 - Ammonia (0-100 PPM)
4 - Other (consult factory)
5 - None
Sensor 3 Gas Type:
1 - Chlorine (0-10 PPM)
2 - Sulfur Dioxide (0-30 PPM)
3 - Ammonia (0-100 PPM)
4 - Other (consult factory)
5 - None
Sensor 4 Gas Type:
1 - Chlorine (0-10 PPM)
2 - Sulfur Dioxide (0-30 PPM)
3 - Ammonia (0-100 PPM)
4 - Other (consult factory)
5 - None
Power Requirements:
1 - 120 VAC, 50-60 Hz
2 - 240 VAC, 50-60 Hz
Battery Back-Up:
1 - Not Included
2 - Included
Sensor Cable Length:
1 - 25 ft. (8 m) standard per sensor
2 - Additional length
Output:
1 - None
2 - 4-20 mA
Examples:
GA-170-2-5-5-5-1-1-1-1
Danger Relay
Alarm Relay
Note: Add an “A” after the
number for each gas type
to indicate a side mounted
sensor enclosure.
SO2
GA-170-1-2-3-5-1-1-1-2
4-20mA Output
Danger Relays
Alarm Relays
Cl2
NH3
SO2
INSTRUMENTS
PROUDLY
MADE IN USA
600 Emlen Way, Telford, PA 18969
Telephone: (215) 799-0980 • Fax: (215) 799-0984
Toll Free in the U.S.: 1 (888) 38-HYDRO
www.hydroinstruments.com • sales@hydroinstruments.com
BULLETIN GA-170 Rev. 3/13