ADDENDUM
CONTROL CONNECTION WIRING
MODEL S3 OPERATORS
Models: SL/540/570/580/590 & SW420/470/490
WARNING:
All controls that are to be used to operate the gate system, MUST be installed where the user cannot touch the gate while
operating the controls. Also, always install the controls where the user has full view of gate operation.
All inputs are normally open and momentary, except the stop (NC), and emergency close & emergency open (constant pressure). The following instructions are
based upon UL 325, dated March of 1999 and include recommendations for significant increase in safety. We strongly recommend that you follow the UL
guidelines presented throughout the manual. Installation device instructions - always follow the instructions provided by the manufacturer when installing and
adjusting any control device. If these instructions are contrary to the advise given here, call for assistance.
This addendum is to be used in conjunction with the owner’s manual included with this operator. Refer to this addendum for all programming and wiring instructions.
FOR ALL OTHER INSTALLATION INSTRUCTIONS REFER TO OWNERS MANUAL
SHIPPED WITH OPERATOR.
5
5
7
UNSUPERVISED
(WIRELESS) OPEN BUTTON
SUPERVISED OPEN BUTTON
Caution - Only wired devices in sight of the gate
may be used with this input.
For wireless device see fig 2.
OPEN
5
9
External Entrapment open
Will reverse (close) the gate if active. If struck
again during a reversal the gate will stop.
5
Any device can be used here and the radio (R2)
is wired here internally by the factory. Note, on
a second obstruction, this input will not function
(disabled). See page 8 for details.
Secondary safety
It is recommended that secondary
safeties always be used for both
the open and close directions.
Use photo eyes, safety edges or both. In any case, the
device must sense people. Loops cannot be used.
8
2
3
Interrupt loop
1
This input is for vehicles only and does not
provide UL secondary safety for persons. This
functions as an wireless open unless on the
close limit where it is defeated - thus preventing
vehicles from entering.
5
6
Close/single button
This input allows for either a close operation, or
single button. In the single button mode, the
feature opens the operator except when on the
open limit where it will act as a close.
CLOSE
5
10
External Entrapment close
Will reverse (open) the gate if active.If struck
again during a reversal the gate will stop.
May defeat the timer to close.
E- CLOSE
E- OPEN
These are constant pressure inputs that
bypasses the processor and may be used in an
emergency even if the processor fails.
4
TABLE OF CONTENTS
5
3
S3 BOARD LAYOUT
STOP BUTTON
- REQUIRED -
BOARD GROUND POINTS
This is a normally closed input and the operator
will not run unless this is installed!
R3
2 3
RADIO
RECEIVER
1
24 VAC
R2
TERMINAL STRIP
ON SIDE OF
CONTROL PANEL
JUMPER (SEE FIGURE 1)
LED (RED)
(J1) TERMINAL STRIP
SWITCH #2
1
R1
OPERATOR WIRING
Single Phase (SL540/570) . . . . . . . . . . . . . . . . . .4
Three Phase (SL540/570) . . . . . . . . . . . . . . . . . .5
Single Phase (SL580) . . . . . . . . . . . . . . . . . . . . . .6
Three Phase (SL580) . . . . . . . . . . . . . . . . . . . . . .7
Single Phase (SL590) . . . . . . . . . . . . . . . . . . . . . .8
Three Phase (SL590) . . . . . . . . . . . . . . . . . . . . . .9
Single Phase (SW420) . . . . . . . . . . . . . . . . . . . . .10
Single Phase (SW470) . . . . . . . . . . . . . . . . . . . . .11
Single Phase (SW490) . . . . . . . . . . . . . . . . . . . . .12
Three Phase (SW490) . . . . . . . . . . . . . . . . . . . . .13
Control Wiring . . . . . . . . . . . . . . . . . . . . . . . . . . . .16
OPERATOR PROGRAMMING
S3 Board Layout . . . . . . . . . . . . . . . . . . . . . . . . . .1
Close Button . . . . . . . . . . . . . . . . . . . . . . . . . . . . .2
Open/ Close Button . . . . . . . . . . . . . . . . . . . . . . .2
Open/ Close/ Stop Button . . . . . . . . . . . . . . . . . . .2
Left & Right Hand . . . . . . . . . . . . . . . . . . . . . . . . .2
Audible Warning Device . . . . . . . . . . . . . . . . . . . .2
Master Slave (Primary/ Secondary) . . . . . . . . . . .2
Activity LED . . . . . . . . . . . . . . . . . . . . . . . . . . . . .2
Timer To Close . . . . . . . . . . . . . . . . . . . . . . . . . . .3
Emergency Inputs . . . . . . . . . . . . . . . . . . . . . . . . .3
Inherent Obstruction Protection . . . . . . . . . . . . . .3
11
12
13
14
2
3
4
5
6
7
8
9
10
11 12
13 14
15 16
4
3
2
1
J1
STD1
1
CHASSIS
QC2
2
3
MOV1
4
5
6
7
8
9
J2
1
8
10
11 12 13 14
SENSOR
12
MASTER/SLAVE
Use shielded twisted pair.
do not run with power wiring.
D19
POWER
D1
U1
GATE LOCK
USE POWER TO MATCH GATE LOCK
REQUIREMENTS, NOT TO EXCEED 115V 10A.
D18
R37
Z2
D3
C1
D4
1
GND
+
O/P
QC1
D5
W1
+
LED1
SW1
R40
R6
R41
R30
R23
R24
W4 W3
K1
R9
C6
R34
Q7
Z1
R33
K3
+
R32
R7
R10
U3
R8
K4
+
C11
C9
C10
R26
R27
W2
R28
R29
D7
K2
R13
1
R25
R14
I/P
C2
FOR WARNING DEVICES, CALL THE FACTORY
RN1
JP1
4 MASTER/SLAVE
3 WARNING DEVICE
2 LEFT / RIGHT
1 CLOSE/SINGLE BUTTON
+
R42
R43
R20
W8
R22
W6
W7
D2
11
3
2
1
SW2
15 16
R21 R15
SWITCH #1
K5 U2
R12
R16
R36
+
Numbers shown inside a box are on the J1 terminal strip on the circuit board.
D16
R17
D17
D15
Connections shown here are field connections. The radio receiver may be ordered factory installed.
Q2
D8
D6
R35
D10
Q1
c 2001, The Chamberlain Group, Inc.
01-18298A
All rights Reserved
R2
+
C4
D9
R1
C3
Q4
C8
R4
R19
D13
R3
Q3
C7
P/N 34-G2000 REV A
Q6
R18
OPERATOR NOTES
PROGRAM SETTINGS (DIP SWITCH #1)
NOTE: For Printed Circuit Board component locations refer to S3 board layout on page 1.
CLOSE SINGLE BUTTON SELECT
The single button (programmable) control can be used to program terminal #4 either
for single button control or to function as a close button only.
Close Button
ON
ON
1
SINGLE BUTTON CONTROL (OPEN/CLOSE)
This input functions as an open command until on the open limit, then it will work as
a close command. Once the gate leaves the open limit, it becomes an open command again. If power has been interrupted, it will always open with first activation.
For single button control, set SW1 pin 1 to off.
2
3
4
OFF
Open/Close Button
ON
ON
1
2
3
4
OFF
THREE BUTTON CONTROL (OPEN/CLOSE/STOP)
(Close is programmable). Stop will override all other functions. If closing, open will
cause the operator to stop and reverse to full open. Close command will close the
gate from open limit or midstop only.
Three Button
ON
ON
1
2
3
4
OFF
LEFT & RIGHT HAND
This input will make the gate open to the left or to the
right. When opening to the right, this is determined
inside of fence looking out.
Left Hand
ON
ON
ON
1
AUDIBLE WARNING DEVICE
If the operator should sense a second obstruction in
sequence with the first: i.e. back to back, or in the same
cycle, the sounder will activate. Also the sounder can
be programmed to warn 2 seconds prior to gate movement and continue during gate movement.
Right Hand
ON
2
3
4
4
Warning Disabled
ON
1
ON
2
3
4
ON
1
2
3
4
Master Slave Unit
ON
ON
OFF
1
OFF
Single Unit
2
3
Warning Enabled
ON
OFF
ACTIVITY LED
LED is solid when gate is at either open or close
limit.
LED flashes once per second when gate is off a
limit in normal operation.
LED flashes twice per second when an entrapment has been sensed.
2
OFF
ON
MASTER SLAVE & SINGLE UNIT
In Master/Slave gate configurations, it is imperative that
the operator is programmed correctly. For maximum
performance the slave should be programmed as
shown.
1
OFF
ON
2
3
4
1
OFF
2
3
4
ON = Left
OFF = Right
15
OPERATOR NOTES
PROGRAM SETTINGS (DIP SWITCH #2)
NOTE: For Printed Circuit Board component locations refer to S3 board layout on page 1.
FIGURE 1
Timer To Close:
Timer to close is disabled at the factory. To activate the timer to close, follow
steps below:
1. Move safety jumper from bottom two pins to top two pins. (Refer to figure 1)
JUMPER DETAIL
{
2. Set Switch SW2 to desired time. (Refer to switch settings below)
DEFAULT
3. To disable the timer to close program and disable, simply return the jumper
to the bottom two pins, or turn ON all pins of SWITCH #2.
TTC
{
ENABLE
TTC
OPERATOR
TIMER TO CLOSE
Important Note: When using master/slave, only set the time for the master operator. The slave operator must be set to disabled position (all poles on).
ON
ON
ON
ON
ON
ON
ON
ON
ON
ON
1
2
3
4
1
2
3
4
OFF
OFF
1
2
3
4
Disabled
1
2
3
4
OFF
OFF
1 Second*
13 Seconds*
1
26 Seconds
ON
ON
ON
ON
ON
ON
ON
ON
ON
1
2
3
4
1
2
3
4
1
2
65 Seconds*
52 Seconds*
3
4
OFF
OFF
1
ON
ON
ON
ON
ON
ON
ON
1
2
3
4
155 Seconds*
1
2
3
4
OFF
1
2
3
4
1
4
4
1
2
3
4
OFF
2
3
117 Seconds*
4
OFF
OFF
167 Seconds*
3
104 Seconds*
ON
OFF
2
OFF
78 Seconds*
3
40 Seconds*
ON
OFF
2
OFF
180 Seconds*
194 Seconds*
OPERATOR FEATURES
EMERGENCY INPUTS
There is an emergency back-up system that works even if the processor is missing.
INHERENT OBSTRUCTION PROTECTION
The limit shaft is equipped with an R.P.M. sensor that measures gate speed. When the gate meets an obstruction, the loss of gate speed will cause the gate to reverse. A second obstruction will cause the gate to stop and
the alarm to go off. A renewed wired input will restart the gate.
14
3
SINGLE PHASE WIRING DIAGRAM (SL540/570)
G1018
GATE OPERATOR WIRING DIAGRAM
THREE PHASE WIRING DIAGRAM (SW490)
G1024
O
’
’
’
208/230V MOTOR
460V MOTOR
J2 PLUG
’
ALARM ASSY
76-G0597
24V Sec.
Note 1
24V
Sec.
575V MOTOR
J1 PLUG
OPTIONAL WIRE
HARNESS
P/N 90-G0601
LEGEND
NOTES:
1. TRANSFORMER PRIMARY VOLTAGE SAME AS OPERATOR
LINE VOLTAGE 24V SECONDARY 50VA.
2. COIL VOLTAGE SAME AS LINE VOLTAGE.
3. WIRE COLOR 120V-BLACK, 208V-RED, 230V-ORANGE,
460V-VIOLET, 575V-GRAY.
4. (B+) AND (B-) ARE 100db SAFETY ALARMS.
5. HARD JUMPER ON TERMINAL BLOCK.
4
ALARM ASSY
76-G0597
13
NOTES:
1. TRANSFORMER PRIMARY VOLTAGE SAME AS OPERATOR
LINE VOLTAGE 24V SECONDARY 50VA.
2. WIRE COLOR 120V-BLACK, 208V-RED, 230V-ORANGE,
460V-VIOLET, 575V-GRAY.
3. (B+) AND (B-) ARE 100db SAFETY ALARMS.
4. OVERLOAD PROTECTION EITHER IN THE MOTOR OR
EXTERNAL OVERLOAD.
SINGLE PHASE WIRING DIAGRAM (SW490)
G1020
THREE PHASE WIRING DIAGRAM (SL540/570)
G1023
R WIRING DIAG R A M
24V
Sec.
Note 1
24V
Sec.
LEGEND
LEGEND
NOTES:
1. TRANSFORMER PRIMARY VOLTAGE SAME AS OPERATOR
LINE VOLTAGE 24V SECONDARY 50VA.
2. WIRE COLOR 120V-BLACK, 208V-RED, 230V-ORANGE,
460V-VIOLET, 575V-GRAY.
3. (B+) AND (B-) ARE 100db SAFETY ALARMS.
4. HARD JUMPER ON TERMINAL BLOCK.
NOTES:
1. TRANSFORMER PRIMARY VOLTAGE SAME AS OPERATOR
LINE VOLTAGE 24V SECONDARY 50VA.
2. COIL VOLTAGE SAME AS LINE VOLTAGE. TERMINAL DESIGNATIONS SHOWN FOR 115V ONLY
3. WIRE COLOR 120V-BLACK, 208V-RED, 230V-ORANGE, 460VVIOLET, 575V-GRAY.
4. (B+) AND (B-) ARE 100db SAFETY ALARMS.
12
5
SINGLE PHASE WIRING DIAGRAM (SL580)
G1016
SINGLE PHASE WIRING DIAGRAM (SW470)
G1019
SEE NOTE 2
24V
SEC.
ALARM ASSY
76-G0597
PRIMARY
J2 PLUG
24V Sec.
OPTIONAL WIRE
HARNESS
90-G0601
J1 PLUG
NOTES:
1. TRANSFORMER PRIMARY VOLTAGE SAME AS OPERATOR
LINE VOLTAGE 24V SECONDARY 50VA.
2. WIRE COLOR 120V-BLACK, 208V-RED, 230V-ORANGE,
460V-VIOLET, 575V-GRAY.
3. COIL VOLTAGE SAME AS LINE VOLTAGE. TERMINAL DESIGNATIONS SHOWN FOR 115V ONLY.
4. (B+) AND (B-) ARE 100db SAFETY ALARMS.
5. HARD JUMPER ON TERMINAL BLOCK.
6
ALARM ASSY
76-G0597
NOTES:
1. TRANSFORMER PRIMARY VOLTAGE SAME AS OPERATOR
LINE VOLTAGE 24V SECONDARY 50VA.
2. WIRE COLOR 120V-BLACK, 208V-RED, 230V-ORANGE,
460V-VIOLET, 575V-GRAY.
3. (B+) AND (B-) ARE 100db SAFETY ALARMS.
11
SINGLE PHASE WIRING DIAGRAM (SW420)
G1017
THREE PHASE WIRING DIAGRAM (SL580)
G1022
24V Sec.
LEGEND
NOTES:
1. TRANSFORMER PRIMARY VOLTAGE SAME AS OPERATOR
LINE VOLTAGE 24V SECONDARY 50VA.
2. WIRE COLOR 120V-BLACK, 208V-RED, 230V-ORANGE,
460V-VIOLET, 575V-GRAY.
3. (B+) AND (B-) ARE 100db SAFETY ALARMS.
4. FOR SINGLE BUTTON RADIO, SET SW1, PIN 1 TO OFF AND
USE TERMINALS #4 & #5.
5. CONNECTED INTERNALLY ON S3 PC BOARD.
10
NOTES:
1. TRANSFORMER PRIMARY VOLTAGE SAME AS OPERATOR
LINE VOLTAGE 24V SECONDARY 50VA.
2. WIRE COLOR 120V-BLACK, 208V-RED, 230V-ORANGE, 460VVIOLET, 575V-GRAY.
3. (B+) AND (B-) ARE 100db SAFETY ALARMS.
4. EXTERNAL OVERLOAD USED WHEN MOTOR IS NOT SUPPLIED WITH INTERNAL THERMAL OVERLOAD WIRES (J WIRES IN
MOTOR).
5. HARD JUMPER ON TERMINAL BLOCK.
7
SINGLE PHASE WIRING DIAGRAM (SL590)
G1021
THREE PHASE WIRING DIAGRAM (SL590)
SEE NOTE 1
PRIMARY
G1025
ALARM ASSY
76-G0537
24V SEC.
24V Sec.
OPTIONAL WIRE
HARNESS
P/N 90-G0601
ALARM ASSY
76-G0537
NOTES:
1. TRANSFORMER PRIMARY VOLTAGE SAME AS OPERATOR
LINE VOLTAGE 24V SECONDARY 50VA.
2. COIL VOLTAGE SAME AS LINE VOLTAGE. TERMINAL DESIGNATIONS SHOWN FOR 115V ONLY
3. WIRE COLOR 120V-BLACK, 208V-RED, 230V-ORANGE,
460V-VIOLET, 575V-GRAY.
4. (B+) AND (B-) ARE 100db SAFETY ALARMS.
5. HARD JUMPER ON TERMINAL BLOCK.
8
NOTES:
1. TRANSFORMER PRIMARY VOLTAGE SAME AS OPERATOR LINE VOLTAGE 24V SECONDARY 50VA.
2. WIRE COLOR 120V-BLACK, 208V-RED, 230V-ORANGE, 460V-VIOLET,
575V-GRAY.
3. (B+) AND (B-) ARE 100db SAFETY ALARMS.
4. EXTERNAL OVERLOAD USED WHEN MOTOR IS NOT SUPPLIED WITH
INTERNAL THERMAL OVERLOAD WIRES (J WIRES IN MOTOR).
5. HARD JUMPER ON TERMINAL BLOCK.
9
SINGLE PHASE WIRING DIAGRAM (SL590)
G1021
THREE PHASE WIRING DIAGRAM (SL590)
SEE NOTE 1
PRIMARY
G1025
ALARM ASSY
76-G0537
24V SEC.
24V Sec.
OPTIONAL WIRE
HARNESS
P/N 90-G0601
ALARM ASSY
76-G0537
NOTES:
1. TRANSFORMER PRIMARY VOLTAGE SAME AS OPERATOR
LINE VOLTAGE 24V SECONDARY 50VA.
2. COIL VOLTAGE SAME AS LINE VOLTAGE. TERMINAL DESIGNATIONS SHOWN FOR 115V ONLY
3. WIRE COLOR 120V-BLACK, 208V-RED, 230V-ORANGE,
460V-VIOLET, 575V-GRAY.
4. (B+) AND (B-) ARE 100db SAFETY ALARMS.
5. HARD JUMPER ON TERMINAL BLOCK.
8
NOTES:
1. TRANSFORMER PRIMARY VOLTAGE SAME AS OPERATOR LINE VOLTAGE 24V SECONDARY 50VA.
2. WIRE COLOR 120V-BLACK, 208V-RED, 230V-ORANGE, 460V-VIOLET,
575V-GRAY.
3. (B+) AND (B-) ARE 100db SAFETY ALARMS.
4. EXTERNAL OVERLOAD USED WHEN MOTOR IS NOT SUPPLIED WITH
INTERNAL THERMAL OVERLOAD WIRES (J WIRES IN MOTOR).
5. HARD JUMPER ON TERMINAL BLOCK.
9
SINGLE PHASE WIRING DIAGRAM (SW420)
G1017
THREE PHASE WIRING DIAGRAM (SL580)
G1022
24V Sec.
LEGEND
NOTES:
1. TRANSFORMER PRIMARY VOLTAGE SAME AS OPERATOR
LINE VOLTAGE 24V SECONDARY 50VA.
2. WIRE COLOR 120V-BLACK, 208V-RED, 230V-ORANGE,
460V-VIOLET, 575V-GRAY.
3. (B+) AND (B-) ARE 100db SAFETY ALARMS.
4. FOR SINGLE BUTTON RADIO, SET SW1, PIN 1 TO OFF AND
USE TERMINALS #4 & #5.
5. CONNECTED INTERNALLY ON S3 PC BOARD.
10
NOTES:
1. TRANSFORMER PRIMARY VOLTAGE SAME AS OPERATOR
LINE VOLTAGE 24V SECONDARY 50VA.
2. WIRE COLOR 120V-BLACK, 208V-RED, 230V-ORANGE, 460VVIOLET, 575V-GRAY.
3. (B+) AND (B-) ARE 100db SAFETY ALARMS.
4. EXTERNAL OVERLOAD USED WHEN MOTOR IS NOT SUPPLIED WITH INTERNAL THERMAL OVERLOAD WIRES (J WIRES IN
MOTOR).
5. HARD JUMPER ON TERMINAL BLOCK.
7
SINGLE PHASE WIRING DIAGRAM (SL580)
G1016
SINGLE PHASE WIRING DIAGRAM (SW470)
G1019
SEE NOTE 2
24V
SEC.
ALARM ASSY
76-G0597
PRIMARY
J2 PLUG
24V Sec.
OPTIONAL WIRE
HARNESS
90-G0601
J1 PLUG
NOTES:
1. TRANSFORMER PRIMARY VOLTAGE SAME AS OPERATOR
LINE VOLTAGE 24V SECONDARY 50VA.
2. WIRE COLOR 120V-BLACK, 208V-RED, 230V-ORANGE,
460V-VIOLET, 575V-GRAY.
3. COIL VOLTAGE SAME AS LINE VOLTAGE. TERMINAL DESIGNATIONS SHOWN FOR 115V ONLY.
4. (B+) AND (B-) ARE 100db SAFETY ALARMS.
5. HARD JUMPER ON TERMINAL BLOCK.
6
ALARM ASSY
76-G0597
NOTES:
1. TRANSFORMER PRIMARY VOLTAGE SAME AS OPERATOR
LINE VOLTAGE 24V SECONDARY 50VA.
2. WIRE COLOR 120V-BLACK, 208V-RED, 230V-ORANGE,
460V-VIOLET, 575V-GRAY.
3. (B+) AND (B-) ARE 100db SAFETY ALARMS.
11
SINGLE PHASE WIRING DIAGRAM (SW490)
G1020
THREE PHASE WIRING DIAGRAM (SL540/570)
G1023
R WIRING DIAG R A M
24V
Sec.
Note 1
24V
Sec.
LEGEND
LEGEND
NOTES:
1. TRANSFORMER PRIMARY VOLTAGE SAME AS OPERATOR
LINE VOLTAGE 24V SECONDARY 50VA.
2. WIRE COLOR 120V-BLACK, 208V-RED, 230V-ORANGE,
460V-VIOLET, 575V-GRAY.
3. (B+) AND (B-) ARE 100db SAFETY ALARMS.
4. HARD JUMPER ON TERMINAL BLOCK.
NOTES:
1. TRANSFORMER PRIMARY VOLTAGE SAME AS OPERATOR
LINE VOLTAGE 24V SECONDARY 50VA.
2. COIL VOLTAGE SAME AS LINE VOLTAGE. TERMINAL DESIGNATIONS SHOWN FOR 115V ONLY
3. WIRE COLOR 120V-BLACK, 208V-RED, 230V-ORANGE, 460VVIOLET, 575V-GRAY.
4. (B+) AND (B-) ARE 100db SAFETY ALARMS.
12
5
SINGLE PHASE WIRING DIAGRAM (SL540/570)
G1018
GATE OPERATOR WIRING DIAGRAM
THREE PHASE WIRING DIAGRAM (SW490)
G1024
O
’
’
’
208/230V MOTOR
460V MOTOR
J2 PLUG
’
ALARM ASSY
76-G0597
24V Sec.
Note 1
24V
Sec.
575V MOTOR
J1 PLUG
OPTIONAL WIRE
HARNESS
P/N 90-G0601
LEGEND
NOTES:
1. TRANSFORMER PRIMARY VOLTAGE SAME AS OPERATOR
LINE VOLTAGE 24V SECONDARY 50VA.
2. COIL VOLTAGE SAME AS LINE VOLTAGE.
3. WIRE COLOR 120V-BLACK, 208V-RED, 230V-ORANGE,
460V-VIOLET, 575V-GRAY.
4. (B+) AND (B-) ARE 100db SAFETY ALARMS.
5. HARD JUMPER ON TERMINAL BLOCK.
4
ALARM ASSY
76-G0597
13
NOTES:
1. TRANSFORMER PRIMARY VOLTAGE SAME AS OPERATOR
LINE VOLTAGE 24V SECONDARY 50VA.
2. WIRE COLOR 120V-BLACK, 208V-RED, 230V-ORANGE,
460V-VIOLET, 575V-GRAY.
3. (B+) AND (B-) ARE 100db SAFETY ALARMS.
4. OVERLOAD PROTECTION EITHER IN THE MOTOR OR
EXTERNAL OVERLOAD.
OPERATOR NOTES
PROGRAM SETTINGS (DIP SWITCH #2)
NOTE: For Printed Circuit Board component locations refer to S3 board layout on page 1.
FIGURE 1
Timer To Close:
Timer to close is disabled at the factory. To activate the timer to close, follow
steps below:
1. Move safety jumper from bottom two pins to top two pins. (Refer to figure 1)
JUMPER DETAIL
{
2. Set Switch SW2 to desired time. (Refer to switch settings below)
DEFAULT
3. To disable the timer to close program and disable, simply return the jumper
to the bottom two pins, or turn ON all pins of SWITCH #2.
TTC
{
ENABLE
TTC
OPERATOR
TIMER TO CLOSE
Important Note: When using master/slave, only set the time for the master operator. The slave operator must be set to disabled position (all poles on).
ON
ON
ON
ON
ON
ON
ON
ON
ON
ON
1
2
3
4
1
2
3
4
OFF
OFF
1
2
3
4
Disabled
1
2
3
4
OFF
OFF
1 Second*
13 Seconds*
1
26 Seconds
ON
ON
ON
ON
ON
ON
ON
ON
ON
1
2
3
4
1
2
3
4
1
2
65 Seconds*
52 Seconds*
3
4
OFF
OFF
1
ON
ON
ON
ON
ON
ON
ON
1
2
3
4
155 Seconds*
1
2
3
4
OFF
1
2
3
4
1
4
4
1
2
3
4
OFF
2
3
117 Seconds*
4
OFF
OFF
167 Seconds*
3
104 Seconds*
ON
OFF
2
OFF
78 Seconds*
3
40 Seconds*
ON
OFF
2
OFF
180 Seconds*
194 Seconds*
OPERATOR FEATURES
EMERGENCY INPUTS
There is an emergency back-up system that works even if the processor is missing.
INHERENT OBSTRUCTION PROTECTION
The limit shaft is equipped with an R.P.M. sensor that measures gate speed. When the gate meets an obstruction, the loss of gate speed will cause the gate to reverse. A second obstruction will cause the gate to stop and
the alarm to go off. A renewed wired input will restart the gate.
14
3
OPERATOR NOTES
PROGRAM SETTINGS (DIP SWITCH #1)
NOTE: For Printed Circuit Board component locations refer to S3 board layout on page 1.
CLOSE SINGLE BUTTON SELECT
The single button (programmable) control can be used to program terminal #4 either
for single button control or to function as a close button only.
Close Button
ON
ON
1
SINGLE BUTTON CONTROL (OPEN/CLOSE)
This input functions as an open command until on the open limit, then it will work as
a close command. Once the gate leaves the open limit, it becomes an open command again. If power has been interrupted, it will always open with first activation.
For single button control, set SW1 pin 1 to off.
2
3
4
OFF
Open/Close Button
ON
ON
1
2
3
4
OFF
THREE BUTTON CONTROL (OPEN/CLOSE/STOP)
(Close is programmable). Stop will override all other functions. If closing, open will
cause the operator to stop and reverse to full open. Close command will close the
gate from open limit or midstop only.
Three Button
ON
ON
1
2
3
4
OFF
LEFT & RIGHT HAND
This input will make the gate open to the left or to the
right. When opening to the right, this is determined
inside of fence looking out.
Left Hand
ON
ON
ON
1
AUDIBLE WARNING DEVICE
If the operator should sense a second obstruction in
sequence with the first: i.e. back to back, or in the same
cycle, the sounder will activate. Also the sounder can
be programmed to warn 2 seconds prior to gate movement and continue during gate movement.
Right Hand
ON
2
3
4
4
Warning Disabled
ON
1
ON
2
3
4
ON
1
2
3
4
Master Slave Unit
ON
ON
OFF
1
OFF
Single Unit
2
3
Warning Enabled
ON
OFF
ACTIVITY LED
LED is solid when gate is at either open or close
limit.
LED flashes once per second when gate is off a
limit in normal operation.
LED flashes twice per second when an entrapment has been sensed.
2
OFF
ON
MASTER SLAVE & SINGLE UNIT
In Master/Slave gate configurations, it is imperative that
the operator is programmed correctly. For maximum
performance the slave should be programmed as
shown.
1
OFF
ON
2
3
4
1
OFF
2
3
4
ON = Left
OFF = Right
15
ADDENDUM
CONTROL CONNECTION WIRING
MODEL S3 OPERATORS
Models: SL/540/570/580/590 & SW420/470/490
WARNING:
All controls that are to be used to operate the gate system, MUST be installed where the user cannot touch the gate while
operating the controls. Also, always install the controls where the user has full view of gate operation.
All inputs are normally open and momentary, except the stop (NC), and emergency close & emergency open (constant pressure). The following instructions are
based upon UL 325, dated March of 1999 and include recommendations for significant increase in safety. We strongly recommend that you follow the UL
guidelines presented throughout the manual. Installation device instructions - always follow the instructions provided by the manufacturer when installing and
adjusting any control device. If these instructions are contrary to the advise given here, call for assistance.
This addendum is to be used in conjunction with the owner’s manual included with this operator. Refer to this addendum for all programming and wiring instructions.
FOR ALL OTHER INSTALLATION INSTRUCTIONS REFER TO OWNERS MANUAL
SHIPPED WITH OPERATOR.
5
5
7
UNSUPERVISED
(WIRELESS) OPEN BUTTON
SUPERVISED OPEN BUTTON
Caution - Only wired devices in sight of the gate
may be used with this input.
For wireless device see fig 2.
OPEN
5
9
External Entrapment open
Will reverse (close) the gate if active. If struck
again during a reversal the gate will stop.
5
Any device can be used here and the radio (R2)
is wired here internally by the factory. Note, on
a second obstruction, this input will not function
(disabled). See page 8 for details.
Secondary safety
It is recommended that secondary
safeties always be used for both
the open and close directions.
Use photo eyes, safety edges or both. In any case, the
device must sense people. Loops cannot be used.
8
2
3
Interrupt loop
1
This input is for vehicles only and does not
provide UL secondary safety for persons. This
functions as an wireless open unless on the
close limit where it is defeated - thus preventing
vehicles from entering.
5
6
Close/single button
This input allows for either a close operation, or
single button. In the single button mode, the
feature opens the operator except when on the
open limit where it will act as a close.
CLOSE
5
10
External Entrapment close
Will reverse (open) the gate if active.If struck
again during a reversal the gate will stop.
May defeat the timer to close.
E- CLOSE
E- OPEN
These are constant pressure inputs that
bypasses the processor and may be used in an
emergency even if the processor fails.
4
TABLE OF CONTENTS
5
3
S3 BOARD LAYOUT
STOP BUTTON
- REQUIRED -
BOARD GROUND POINTS
This is a normally closed input and the operator
will not run unless this is installed!
R3
2 3
RADIO
RECEIVER
1
24 VAC
R2
TERMINAL STRIP
ON SIDE OF
CONTROL PANEL
JUMPER (SEE FIGURE 1)
LED (RED)
(J1) TERMINAL STRIP
SWITCH #2
1
R1
OPERATOR WIRING
Single Phase (SL540/570) . . . . . . . . . . . . . . . . . .4
Three Phase (SL540/570) . . . . . . . . . . . . . . . . . .5
Single Phase (SL580) . . . . . . . . . . . . . . . . . . . . . .6
Three Phase (SL580) . . . . . . . . . . . . . . . . . . . . . .7
Single Phase (SL590) . . . . . . . . . . . . . . . . . . . . . .8
Three Phase (SL590) . . . . . . . . . . . . . . . . . . . . . .9
Single Phase (SW420) . . . . . . . . . . . . . . . . . . . . .10
Single Phase (SW470) . . . . . . . . . . . . . . . . . . . . .11
Single Phase (SW490) . . . . . . . . . . . . . . . . . . . . .12
Three Phase (SW490) . . . . . . . . . . . . . . . . . . . . .13
Control Wiring . . . . . . . . . . . . . . . . . . . . . . . . . . . .16
OPERATOR PROGRAMMING
S3 Board Layout . . . . . . . . . . . . . . . . . . . . . . . . . .1
Close Button . . . . . . . . . . . . . . . . . . . . . . . . . . . . .2
Open/ Close Button . . . . . . . . . . . . . . . . . . . . . . .2
Open/ Close/ Stop Button . . . . . . . . . . . . . . . . . . .2
Left & Right Hand . . . . . . . . . . . . . . . . . . . . . . . . .2
Audible Warning Device . . . . . . . . . . . . . . . . . . . .2
Master Slave (Primary/ Secondary) . . . . . . . . . . .2
Activity LED . . . . . . . . . . . . . . . . . . . . . . . . . . . . .2
Timer To Close . . . . . . . . . . . . . . . . . . . . . . . . . . .3
Emergency Inputs . . . . . . . . . . . . . . . . . . . . . . . . .3
Inherent Obstruction Protection . . . . . . . . . . . . . .3
11
12
13
14
2
3
4
5
6
7
8
9
10
11 12
13 14
15 16
4
3
2
1
J1
STD1
1
CHASSIS
QC2
2
3
MOV1
4
5
6
7
8
9
J2
1
8
10
11 12 13 14
SENSOR
12
MASTER/SLAVE
Use shielded twisted pair.
do not run with power wiring.
D19
POWER
D1
U1
GATE LOCK
USE POWER TO MATCH GATE LOCK
REQUIREMENTS, NOT TO EXCEED 115V 10A.
D18
R37
Z2
D3
C1
D4
1
GND
+
O/P
QC1
D5
W1
+
LED1
SW1
R40
R6
R41
R30
R23
R24
W4 W3
K1
R9
C6
R34
Q7
Z1
R33
K3
+
R32
R7
R10
U3
R8
K4
+
C11
C9
C10
R26
R27
W2
R28
R29
D7
K2
R13
1
R25
R14
I/P
C2
FOR WARNING DEVICES, CALL THE FACTORY
RN1
JP1
4 MASTER/SLAVE
3 WARNING DEVICE
2 LEFT / RIGHT
1 CLOSE/SINGLE BUTTON
+
R42
R43
R20
W8
R22
W6
W7
D2
11
3
2
1
SW2
15 16
R21 R15
SWITCH #1
K5 U2
R12
R16
R36
+
Numbers shown inside a box are on the J1 terminal strip on the circuit board.
D16
R17
D17
D15
Connections shown here are field connections. The radio receiver may be ordered factory installed.
Q2
D8
D6
R35
D10
Q1
c 2001, The Chamberlain Group, Inc.
01-18298A
All rights Reserved
R2
+
C4
D9
R1
C3
Q4
C8
R4
R19
D13
R3
Q3
C7
P/N 34-G2000 REV A
Q6
R18