Technical data sheet VAV-Compact LON

Technical data sheet VAV-Compact LON
Technical data sheet
A pressure sensor, digital VAV controller and
damper actuator all in one, providing a VAVCompact solution with a communications
capability for pressure-independent VAV
systems in the comfort zone
•Control function: VAV
•Control: LONWORKS®
•Integration into LONWORKS® systems
•Conversion of sensor signals
•Service button and LEDs for servicing and
commissioning
•Diagnostic socket for operating devices
VAV-Compact LON
LMV-D2LON
NMV-D2LON
Brief description
Application
The digital VAV-Compact has PI control characteristics and is used for pressure-independent
control of VAV units in the comfort zone.
Mode of operation
The actuator is equipped with an integrated interface for LONWORKS®. The actuator can be
directly connected and controlled with LONWORKS® via a FTT-10A transceiver.
Converter for sensors
Connection option for a sensor (active sensor or switching contact). In this way, the analog
sensor signal can be easily digitised and transferred to LONWORKS®.
Pressure measurement
Actuator
VAV – variable air volume
Test function / test display
Operating and service devices
Assembly and connection
OEM factory settings
Maintenance-free, dynamic, differential pressure sensor technology, proven in a wide range of
applications, suitable for use in offices, hospital wards, alpine hotels or cruise liners.
Three versions available, depending on the size of the VAV unit: 5 / 10 / 20 Nm.
– Rotary actuator, depending on size
– Linear actuator 150 N with 100, 200 or 300 mm linear motions
The VAV-Compact is supplied with its modulating setpoint by a room temperature controller via
LONWORKS®. This facilitates demand-related, power-saving ventilation in individual rooms or
zones of air conditioning systems. The operating range (min und max) can be set either locally
with PC-Tool or using the LNS plug-in available from Belimo.
The VAV-Compact features an LED with a ready display for commissioning and functional
checking as well as a service mode with air shortage, excess air and setpoint = actual value
display with LEDs.
Belimo PC-Tool, remote control or ZTH-VAV, plugged into the VAV-Compact.
The VAV-Compact, which is assembled on the unit by the OEM, is connected using the prefabricated connecting cable.
The VAV-Compact is mounted on the VAV unit by the unit manufacturer, who adjusts and tests it
according to the application. The VAV-Compact is sold exclusively via the OEM channel for this
reason.
..
..
..
Overview of types
Type
Torque
Power consumption
LMV-D2LON
NMV-D2LON
5 Nm
10 Nm
2.5 W
3W
For wire sizing
Weight
5 VA (max. 5 A @ 5 ms)
6 VA (max. 5 A @ 5 ms)
approx. 500 g
approx. 700 g
Safety notes
!
www.belimo.com
• The device is not allowed to be used outside the specified field of applica­tion, especially in
aircraft or any other form of air transport.
• Assembly must be carried out by trained personnel. Any legal regulations or regulations
issued by authorities must be observed during assembly.
• The device may only be opened at the manufacturer‘s site. It does not contain any parts that
can be replaced or repaired by the user.
• The cable must not be removed from the device.
• When calculating the required torque, the specifications supplied by the damper
manufacturers (cross section, design, installation site), and the air flow conditions must be
observed.
• The device contains electrical and electronic components and is not allowed to be disposed
of as household refuse. All locally valid regulations and requirements must be observed.
T4-VAV-Compact LON • en • v1.1 • 06.2008 • Subject to changes
/8
..
..
..
..
..
..
VAV-Compact LON
Air volume controller for LONWORKS®
Technical data
Supply
Nominal voltage
Power supply range
AC 24 V, 50/60 Hz
DC 24 V
AC 19.2 ... 28.8 V
DC 21.6 ... 28.8 V
Differential pressure sensor
Operating pressure
Characterising
Installation position
Operating medium (see «Materials»)
Materials
Measuring air conditions
2 ... ~300 Pa (OEM-specific)
max. 1000 Pa
OEM-specific differential pressure sensor, linearisation
Any, no reset necessary
Supply and exhaust air in the comfort zone and in applications with sensor-compatible media
PC + ABS to UL94-V0; stainless steel, DIN 1.4301 X10CrNiS1810; PP Santoprene
0 ... +50°C / 5 ... 95% r.h., non-condensing
Application
Supply/exhaust air units, integrated into LONWORKS® systems
Operating volumetric flow
nom
max
min
mid
OEM-specific nominal volumetric flow setting, matches VAV box
30 ... 100% of nom
0 ... 100% of nom (see VAV-Compact documentation, page 17 «Minimum setting limit»)
0 ... 100% of (min ... max)
Control
Measured value signal U5
(connection 5)
– Adjustable: 2 ... 10 V or 0 ... 10 V
– Adjustable: Air volume or damper position
Bus function LONWORKS®
Certified
Processor
Transceiver
Functional profile
LNS plug-in for actuator / sensor
Service button and status LED
Conductors, cables
max. 0.5 mA
According to LONMARK® 3.3
Neuron 3120
FTT-10A, compatible with LPT-10
According to LONMARK® / Damper actuator object #8110 / Open loop sensor object #1
Can be run with any LNS-based integration tool (min. for LNS 3.x)
According to LONMARK® guidelines
Conductor lengths, cable specifications and topology of the LONWORKS® network according to the
ECHELON® directives
Bedienung und Service
Communication
Button
LED indicator
Pluggable / PC-Tool (V3.1 or higher)
LONWORKS®
Adaptation / addressing / service function
– 24 V feed
– Status / service / bus function
Actuator
Anschluss
Brushless, non-blocking actuator with current reduction
see «Overview of typest» on page 1
left / right
95° , with adjustable mechanical or electronic limitin
Setting range recording and resolution to control range
Pushbutton, self-resetting without affecting functions
Mechanical with pointer
max. 35 dB (A)
–Clamp, for round spindles 10 ... 20 mm / square spindles 8 ... 16 mm
–Positive fit, wide range of versions, e.g. 8 x 8 mm
Cable, 6 x 0.75 mm2, terminals
Safety
Protection class
Degree of protection
EMC
Mode of operation
Rated impulse voltage
Control pollution degree
Ambient conditions
Non-operating temperature
Ambient humidity range
Maintenance
III Safety extra-low voltage
IP54
CE according to 89/336/EEC
Type 1 (to EN 60730-1)
0.5 kV (to EN 60730-1)
2 (to EN 60730-1)
0 ... +50°C
–20 ... +80°C
5 ... 95% rH, non-condensating (to EN 60730-1)
Maintenance-free
/8
T4-VAV-Compact LON • en • v1.1 • 06.2008 • Subject to changes
Torque (nominal torque)
Direction of rotation
Angle of rotation
Adaptation
Manual disengagement
Position indication
Sound power level
Spindle driver
www.belimo.com
VAV-Compact LON
Air volume controller for LONWORKS®
Functional profile according to LONMARK®
The LON-capable air volume controller is certified by LONMARK®. The controller functions are supplied with the LONWORKS® network as
standardised network variables according to LONMARK®. The node object #0, the damper actuator object #8110 and the open loop sensor object
#1 are implemented in the actuator.
Node object #0
Node Object #0
nviRequest
SNVT_obj_request
nvoStatus
SNVT_obj_status
nvoFileDirectory
SNVT_address
Configuration Properties
SCPTdevMajVer (165)
SCPTdevMinVer (166)
SCPTobjMajVer (167)
SCPTobjMinVer (168)
Damper actuator object #8110
Damper Actuator Object #8110
nviRelStpt
SNVT_lev_percent
nvoActualValue
SNVT_lev_percent
nviActuatState
SNVT_switch
nvoAbsAngle
SNVT_angle_deg
nviManOvrd
SNVT_hvac_overid
nvoAbsAirFlow
SNVT_flow
Configuration Properties
SCPTobjMajVer (167)
SCPTobjMinVer (168)
SCPTminSendTime (52)
SCPTmaxSendTime (49)
SCPTminRcvTime (48)
SCPTminDeltaAngl (43)
SCPTminDeltaFlow (47)
SCPTserialNumber (179)
SCPTactuatorType (41)
SCPToemType (61)
SCPTlocation (17)
SCPTnomAngle (58)
SCPTnomAirFlow (57)
SCPTminSetpoint (53)
SCPTmaxSetpoint (50)
SCPTdriveTime (45)
SCPTdirection (44)
Open Loop Sensor Object #1
nvoSensorValue
SNVT_xxx
The actuator object is used to transmit the functions of the actuator to
the LonWorks® network.
nviRelStpt
SNVT_lev_percent
Via this input variable, the set volume is specified for the VAV
controller in % Nom of the VAV unit.
This variable is normally linked to the output variable of an HVAC
controller.
nviActuateState
SNVT_switch
Via this input variable, a preset volume is specified for the VAV
controller (in % Nom of the VAV unit).
Note on priority: The last variable that was active, either
­nviActuatorState or nviRelStpt, has priority.
nviManOvrd
SNVT_hvac_overid
Via this input variable, the actuator can be manually overridden to set
a particular position or particular volume (in % Nom).
nvoActualValue
SNVT_lev_percent
This output variable shows the current volume (in % Nom of the VAV
box) and can be used for control circuit feedback or for displaying
positions.
nvoAbsAngle
SNVT_angle_deg
This output variable shows the current angle of rotation of the actuator
or the damper blade and can be used to display the position or for
service purposes.
nvoAbsAirFlow
SNVT_flow
This output variable shows the current volumetric flow through the
corresponding VAV unit and can be used for control and display
purposes.
Open loop sensor object #1
A sensor can be connected to the air volume controller. An active
sensor (output 0 ... 32 V) or a switch (on/off) can be connected.
In the case of the open loop sensor object, the measured sensor
values are transferred to the LONWORKS® network.
nvoSensorValue
SNVT_xxx
This output variable shows the current sensor value.
Depending on the connected sensor, the output variable can be
configured via the sensor plug-in and specifically adapted to the
system.
Configuration Properties
SCPTobjMajVer (167)
SCPTobjMinVer (168)
SCPTminSendTime (52)
SCPTmaxSendTime (49)
SCPTsndDelta (27)
SCPTmaxNVLength (255)
SCPTnvType (254)
UCPTadFunction (1)
UCPTadTransformation (2)
SCPTtrnsTblX (28)
SCPTtrnsTblY (29)
SCPTinvrtOut (16)
Note
Detailed information on the functional profiles can be found on the website
of LONMARK® (www.lonmark.org).
www.belimo.com
The node object contains the object status and object request
­functions.
nviRequest
SNVT_obj_request
Input variable for requesting the status of a particular object in the
node.
nvoStatus
SNVT_obj_status
Output variable that outputs the current status of a particular object in
the node.
nvoFileDirectory
SNVT_address
Output variable that shows information in the address range of the
Neuron chip.
The SNVT_.. can be configured as:
SNVT_temp_p
SNVT_lev_percent
SNVT_temp
SNVT_abs_humid
SNVT_switch
SNVT_enthalpy
SNVT_flow
SNVT_ppm
SNVT_flow_p
SNVT_rpm
T4-VAV-Compact LON • en • v1.1 • 06.2008 • Subject to changes
SNVT_lux
SNVT_press_p
SNVT_smo_obscur
SNVT_power
SNVT_elec_kwh
/8
VAV-Compact LON
Air volume controller for LONWORKS®
Override control with the SNVT nviManOvrd
Functions
Note
The basic setting is “HVO_OFF”. This value is
loaded when the power supply is switched on.
Example
state
variable used
air flow controller
HVO_OFF
HVO_POSITION
HVO_FLOW_VALUE
-percent
flow
HVO_FLOW_PERCENT
percent
no reaction
no reaction
0 ... nciNomAirFlow (liter/sec).
The value 0xFFFF represents invalid data.
0% ... +100.00% (o.005%).
The value 0x7FFF represents invalid data.
full open
full closed
configured flow
configured flow
not supported
HVO_OPEN
HVO_CLOSE
HVO_MINIMUM
HVO_MAXIMUM
all others
Function
Description
HVO_OFF
HVO_OPEN
Temperature controller setpoints are active
All VAV units are fully open
(e.g. flushing operation or night cooling)
All VAV units are fully closed
(system closed when the plant is switched off)
HVO_CLOSE
Setpoint from room temperature controller
------
Setpoint from room temperature controller
Damper Actuator Object #8110
Setpoint from room temperature controller
Damper Actuator Object #8110
Damper Actuator Object #8110
nviRelStpt
SNVT_lev_percent
nvoActualValue
SNVT_lev_percent
nviRelStpt
SNVT_lev_percent
nvoActualValue
SNVT_lev_percent
nviRelStpt
SNVT_lev_percent
nvoActualValue
SNVT_lev_percent
nviActuatState
SNVT_switch
nvoAbsAngle
SNVT_angle_deg
nviActuatState
SNVT_switch
nvoAbsAngle
SNVT_angle_deg
nviActuatState
SNVT_switch
nvoAbsAngle
SNVT_angle_deg
nviManOvrd
SNVT_hvac_overid
nvoAbsAirFlow
SNVT_flow
nviManOvrd
SNVT_hvac_overid
nvoAbsAirFlow
SNVT_flow
nviManOvrd
SNVT_hvac_overid
nvoAbsAirFlow
SNVT_flow
Setpoint from room temperature controller
Setpoint from room temperature controller
Setpoint from room temperature controller
Damper Actuator Object #8110
Damper Actuator Object #8110
Damper Actuator Object #8110
nviRelStpt
SNVT_lev_percent
nvoActualValue
SNVT_lev_percent
nviRelStpt
SNVT_lev_percent
nvoActualValue
SNVT_lev_percent
nviRelStpt
SNVT_lev_percent
nvoActualValue
SNVT_lev_percent
nviActuatState
SNVT_switch
nvoAbsAngle
SNVT_angle_deg
nviActuatState
SNVT_switch
nvoAbsAngle
SNVT_angle_deg
nviActuatState
SNVT_switch
nvoAbsAngle
SNVT_angle_deg
nviManOvrd
SNVT_hvac_overid
nvoAbsAirFlow
SNVT_flow
nviManOvrd
SNVT_hvac_overid
nvoAbsAirFlow
SNVT_flow
nviManOvrd
SNVT_hvac_overid
nvoAbsAirFlow
SNVT_flow
HVO_OFF
HVO_OPEN
HVO_CLOSE
/8
SNVT for override control
T4-VAV-Compact LON • en • v1.1 • 06.2008 • Subject to changes
www.belimo.com
VAV-Compact LON
Air volume controller for LONWORKS®
Electrical installation
Connection without sensor
T
AC 24 V
~
Wiring diagrams
LONWORKS®
OPEN
MAX
CLOSED
Bus operation
!
V
3
5
6
Possible connection
of a voltmeter for checking
the air volume or the position feedback U.
7
LON
2
LON
1
T
Note
If no sensor is connected, the analogue override
control function can be used.
Please note: This only works if the actuator is
supplied with AC 24 V.
MFT
V
~
Note
Connect via safety isolation transformer.
Connection with switching contact, e.g. ∆p-monitor
~
AC 24 V
DC 24 V –
+
LONWORKS®
T
∆p
Requirements for switching contact:
T
~
–
3
+
5
6
7
LON
2
LON
1
MFT
The switching contact must be able to accurately
switch a current of 16 mA @ 24 V.
Connection with active sensor, e.g. 0 ... 10 V @ 0 ... 50°C
T
–
~
AC 24 V
DC 24 V
+
LONWORKS®
Possible input voltage range:
0 ... 32 V (resolution 30 mV)
T
~
–
www.belimo.com
+
3
5
6
7
LON
2
LON
1
MFT
Sensor scaling:
The sensors can be scaled with the sensor plugin (sensor table)
T4-VAV-Compact LON • en • v1.1 • 06.2008 • Subject to changes
/8
VAV-Compact LON
Air volume controller for LONWORKS®
Parameterisation
Connection of the MFT parameterisation
­devices, e.g. Belimo PC-Tool MFT-P
Parameterisation of the actuator
The actuator can be parameterised as follows:
– min and max settings
– Torque reduction
– Direction of rotation
– Function test or adaption can be triggered
– Air volume or damper position
Parameterisation of the actuator when it has already been integrated in the complete system and
is supplied with AC 24 V
Belimo
PC-Tool
ZIP-232-KA
RJ11 (4/6)
Rx/Tx
Enable
Power
Notes
–The actuator can be triggered with the PC-Tool
under „PP“.
–The scope of delivery of ZIP-232-KA includes the
RS232 cable.
–The connection cable ZK1-GEN has to be
ordered separately.
RS-232 lead, 9-pol
female/female
ZK1-GEN
Parameterisation of the actuator before it is integrated in the complete system
Belimo
PC-Tool
OFF
1
2
+
U
PP
RS232
–
5
RS-232, 9-pin
female/female
1:1 interconnected
(included with ZIP-RS232)
Supply MP-Bus
T
2
– +
3
5
6
U EN
PP
7
MFT
LON
LON
1
+
~
–
T
~
T
/8
T
Notes
–The actuator can be triggered with the PC-Tool
under „PP“.
–The scope of delivery of ZIP-232-KA includes the
RS232 cable.
–The power supply unit ZN230-24 has to be
ordered separately.
Actuator
ON
~
AC 230 V
ZN230-24
ZIP-RS232
T4-VAV-Compact LON • en • v1.1 • 06.2008 • Subject to changes
www.belimo.com
VAV-Compact LON
Air volume controller for LONWORKS®
Dimensions [mm]
47
61
Dimensional drawings LMV-D2LON
66
116
116
22
41
49
62
Dimensional drawings NMV-D2LON
80
124
25
121
41
Operating controls and indicators
1
Pushbutton and green LED display
Off:
No voltage supply or fault
Green, on:
Operation
Press button:
Switches on angle of rotation adaption followed by standard operation
2
Service button for commissioning for LONWORKS® and yellow LED display for the LON status
Off:
The damper actuator is ready for operation in the LONWORKS® network.
Yellow, on:
No application software is loaded in the actuator.
Yellow, flashing:
The actuator is ready for operation but not integrated in the LONWORKS®
(flashing interval 2 s)
network (unconfigured).
Other flashing codes:
A fault is present in the actuator.
Press button:
Service pin message is sent to the LONWORKS® network.
3
Gear disengagement switch
Press button:
Gear disengaged, motor stops, manual override possible
Release button:
Gear engaged, synchronisation starts, followed by standard operation
4
Service plug
For connecting MFT parameterising and service tools (see page 5)
1
2
3
4
Detailed description see Product information S4-VAV-Compact.
www.belimo.com
T4-VAV-Compact LON • en • v1.1 • 06.2008 • Subject to changes
/8
VAV-Compact LON
/8
Air volume controller for LONWORKS®
T4-VAV-Compact LON • en • v1.1 • 06.2008 • Subject to changes
www.belimo.com