Data Sheet K85005-0135 -- VS Series Intelligent Fire Alarm Systems

Data Sheet K85005-0135 -- VS Series Intelligent Fire Alarm Systems
Kidde Catalog u Small Building Fire Alarm Solutions
Technology that saves lives
Intelligent Fire
Alarm Systems
VS1, VS4
COA 6229
7165-1657:
0244
S3000
Overview
Features
Kidde brand intelligent life safety systems offer the power of highend intelligent processing in configurations that deliver uncomplicated solutions for small to mid-sized applications. With intelligent
detection, electronic addressing, automatic device mapping,
optional Ethernet® connectivity, and a full line of easily-configured
option cards and modules, these flexible systems offer versatility
that benefits building owners and contractors alike.
• Auto-programming speeds installation time
The VS1 provides one Class B intelligent device loop that supports up to 64 device addresses, and two Class B Notification Appliance Circuits (NACs). Optional Class A device wiring is available
with the use of a module.
• Two programmable switches with LEDs and custom labeling
The VS4 provides one Class A or Class B intelligent device
loop that supports up to 250 device addresses. Loop controller
modules may be added in combination to expand total system
capacity in 250-point increments to up to 1,000 device addresses.
VS4 panels include four NACs that may be wired for either Class A
or Class B operation.
The RZI16-2 module adds even more capacity to VS installations
by adding up to 16 conventional device circuits and two additional
notification appliance circuits. This makes them ideal retrofit solutions that can accommodate new intelligent detectors, as well as
existing conventional devices.
VS Series supports a wide range of high-end features, including:
• Intelligent modules, detectors, and bases
• GSA-REL Releasing Modules
• Supports V-Series intelligent modules and detectors
• Form C contacts for alarm and trouble, Form A for supervisory
• Electronic addressing with automatic device mapping
• Optional Ethernet port for diagnostics, programming and a
variety of system reports
• Supports Genesis horn silence over two wires, and UL
1971-compliant strobe synchronization
• Supports GSA-REL releasing module for fire suppression
• Class B or Class A wiring
• Ground fault detection by module
• Supports up to eight serial annunciators, (LCD, LED-only, and
graphic interface)
• Can use existing wiring for most retrofit applications
• Upload/download remotely or locally
• Two-level maintenance alert reporting
• Pre-alarm and alarm verification by point
• Adjustable detector sensitivity
• 4 x 20 character backlit LCD display
• Optional earthquake hardening: seismic Importance Factor 1.5
• R-Series remote annunciators
• Standalone operation
• Integrated Carbon Monoxide gas sensing with V-PCOS detectors including distinct audible signaling
• Transmission test frequency by hour
Page 1 of 8
V85005-0135
D ATA S H E E T
Not to be used for installation purposes. Issue 1
Application
Kidde VS Series life safety systems are powerful intelligent solutions
for small to mid-sized buildings. Advanced intelligent technology
delivers the benefits of flexible system installation, while clean and
easy-to-operate user interfaces make panel operation and system
maintenance quick and intuitive.
Flexibility built right in
Two fully-programmable front panel switch/LED combinations provide an added measure of flexibility. Their slide-in labels take the
mystery out of custom applications, and present a clean finished
appearance.
The smart choice
Electronic addressing eliminates the tedium of setting dipswitches,
and automatic device mapping ensures that each device resides
on the system at its correct location. Meanwhile, innovative programming allows the designer to customize the system to precisely suit the needs of the building owner.
Perfect for retrofits
Kidde VS Series control panels are particularly well-suited to
retrofit applications. All connections are made over standard wiring
– no shielded cable required. This means that in most situations
existing wiring can be used to upgrade a legacy control panel
to VS technology without the expense or disruption of rewiring
the entire building. VS control panels also support the ingenious
RZI16-2 zone module, which adds up to 16 conventional circuits
and two NACs. This combination easily accommodates new intelligent detection alongside existing conventional circuits, making it
an superior solution in the retrofit market.
Reliability you can count on
The inherent fault-tolerant characteristics of Analog/Addressable Technology boosts the reliability of Kidde fire alarm systems.
When combined with VS Series smoke and heat detectors, these
systems deliver a level of dependability not previously available
for small to mid-sized applications. All Kidde systems are built to
exacting reliability benchmarks and meet international standards
for quality, in addition to agency listings for dependability.
Clear-cut remote annunciation
Remote annunciation is a strong suit of the VS Series fire alarm
systems. Up to eight annunciators can be installed on a single
system. Compatible annunciators include a range of LED and LCD
models that provide zone or point annunciation, as well as common control capabilities. VS control panels also supports graphic
annunciation with optional graphic annunciator interface modules.
Each interface provides common control and 32 LEDs.
Programming and remote diagnostics
Signals with a difference
VS Series NACs are configurable to fully support the advanced
signaling technology of Kidde Genesis and Enhanced Integrity notification appliances. These devices offer precision synchronization
of strobes to UL 1971 standards. For Genesis devices, enabling
this feature allows horns to be silenced while strobes on the same
two-wire circuit continue to flash until the panel is reset.
A complete line of accessories
VS Series life safety systems are supported by a complete line of
analog/addressable detectors, modules and related equipment.
Consult the Ordering Information section for details.
Dimensions
Kidde VS Series life safety systems are simple to set up, yet offer
advanced programming features that put these small building
panels into a class of their own. The auto programming feature
quickly gets the panel operational using factory default settings.
Basic zone and point settings can be programmed through the
front panel interface, so the system is up and running in no time.
For more advanced system configuration and correlation groups
programming, VS Series systems interface to a PC running compatible VS-CU software. This option offers full system configuration in the familiar Windows® operating environment. Connection is
made to a laptop through the panel’s optional RS-232 communications port, which can also be used to connect a system printer.
Among the many innovative features of VS Series control panels
is the optional network card. This module provides a standard
10/100 Base T Ethernet® network connection that permits access
to the control panel from any remote location with the correct
communications protocols. The connection can be used to download to the panel from the VS-CU, or upload and view system
reports using the VS-CU.
Available system reports include:
• Correlation groups
• Device maintenance
• Internal status
• System status
• Dialer
(3) Backbox with Door Attached
(2) Semi-flush mounting Holes
(4) Backbox with door and trim kit attached.
Panel dimensions, in (cm)
Model
D1*
D2
D3
D4
D5*
D6
D7
D8
D9
VS4
28.0
(71.1)
3.85
(9.8)
9.0
(22.8)
22.0
(55.8)
15.75
(40.0)
10.25
(26.0)
4.9
(12.4)
30.1
(76.4)
2.7
(6.8)
VS1
21.5
(54.6)
3.85
(9.8)
7.5
(19.0)
15.5
(39.4)
14.25
(36.2)
10.25
(26.0)
4.9
(12.4)
23.6
(59.9)
2.7
(6.8)
* Add 1-1/2 in. (3.81 cm) to D1 and D5 dimensions for trim kit. The trim kit
provides 0.75 inches (1.9 cm) of trim to the top, bottom, and sides of the backbox.
V85005-0135
D ATA S H E E T
Not to be used for installation purposes. Issue 1
10-11-16
Page 2 of 8
• Device details
• History
• System configuration
• Walk test
• CO runtime
(1) Surface Mounting Holes
System Layout
VS4
Any combination of two single- or dual device loop modules
Standard Loop: 250 points (one expansion slot)
V-SLC2-2 Expander, Loop 1 of 2: 250 points
Up to 125 sensors and 125 modules per loop
V-SLC2-1 Expander Loop: 250 points (one expansion slot)
(one expansion slot)
V-SLC2-2 Expander, Loop 2 of 2: 250 points
Up to 20,000 feet of wiring per loop
Four Class B or two optional Class A NACs
Four Class B or two optional Class A NACs
Optional 10 A or 6.5 A Booster
Ethernet (SA-ETH)
Up to eight remote annunciators
DACT/Dialer (SA-DACT)
RS-232 (SA-232)
Sixteen Conventional IDCs,
two additional NACs with RZI16-2 module
Relays: Two Form C, one Form A
Each VS4 panel has room for up to two device loop
controller modules in any combination of single or
dual 250-device loops. VS4 comes with one loop
that supports up to 125 detectors and 125 modules.
Panel Layout
4
5
3
6
2
VS1
00:00:00
7
8
01/01/07
,
9
Loop supports up to 64 intelligent devices of any type.
10
Up to 20,000 feet of wiring.
11
12
1
13
Two Class B or two optional Class A NACs
Optional 10 A or 6.5 A Booster Power Supply
Up to eight remote annunciators
Ethernet (SA-ETH)
DACT/Dialer (SA-DACT)
RS-232 (SA-232)
Relays: Two Form C, one Form A
Each VS1 panel ships with one device loop controller that supports 64 devices of any type. This panel’s device capacity cannot
be expanded.
Page 3 of 8
1
2
3
4
5
6
7
8
9
10
11
12
13
Transformer
Main AC wiring block & fuse holder
RS-232 card connector (J3)
Dialer card connection (J8)
Ethernet card connector (J1)
Main circuit board
Panel backbox enclosure
Operator interface
SLC card connector (J7)
Class A card connector (J2)
Tie wrap mounts
LED expander connector (J6)
Standby batteries
V85005-0135
D ATA S H E E T
Not to be used for installation purposes. Issue 1
Wiring & Configuration
Device loop
The system provides one device loop circuit with a total capacity
of 125 detectors and 125 module addresses. The loop circuit is
supervised for opens, shorts, and grounds.
Circuit
specifications
Device loops
Communication
line voltage
Circuit current
Circuit
impedance
Isolators
Signal
Synchronization
VS4
One Class B or A
One Class B or A loop,
loop, supporting 125
supporting 64 devices of
detectors and 125
any kind.
modules. Expandable to
four loops.
Maximum 20 V peak-to-peak
0.5 A max
66Ω total, 0.5 µF, max
Class B wiring
64 maximum
Loop 1 SEC
Data Line
+
Supported on a system-wide
basis (all device loops)
+
when using an addressable
notification+ appliance
Loop 1 PRI
circuit (NAC) module and+ Genesis or Loop
Enhanced
Loop
device
device
Integrity notification
appliances.
Loop card
Class B wiring
SLC A
Class A wiring
-
Loop 1 SEC
SLC B
VS1
+
-
+
+
+
-
-
Loop
device
Loop
device
Loop 1 PRI
Loop card
-
SLC A
+
SLC B
-
+
+
-
-
Loop
device
Loop
device
Loop 1 SEC
Data Line
Loop 1 PRI
Loop card
+
Data Line
NAC1 -
Specifications
VS4
NAC1+
NAC2 -
Circuit Type
4 Class B or 2 Class ANAC2+
+
+
- VS1 EOLR
+
2 Class
B or 2+Class A
-
+
Impedance
NAC1+
NAC2 EOLR
+
NAC2+
Synchronization
TB2
(4)
Alarm, trouble, and supervisory relay (TB3)
The trouble relay is normally-open, held closed,
and opens on any trouble event or when the
panel is de-energized. The supervisory relay is
normally-open, and closes on any supervisory
event. The alarm relay changes over on any
alarm event.
Type
Voltage
(2) Supervisory
(3) Alarm
(4) Smoke/Aux
CH2 (+) IN
Class B
+
+
-
NAC1+
EOLR
NAC2 NAC2+
+
+
-
–
CH2 (-) IN
Class A
Channel 1 Channel 2
Channel 1 Channel 2
–
TB4
+
+
-
Annunciator
–
+
+
+
-
NAC1 -
Terminal wiring location
–
–
Circuit specifications
TB4
Device loops
Class B (Style Y) or Class A (Style Z)
Annunciator
Circuit voltage
2.55 V
CH1 (+) IN
Circuit current
30 mA max
CH1 (-) IN
Circuit
Up to 8 annunciators or 4000 feet
impedance
+
+
+
-
Supervisory
Form A
24 VDC at 1 A resistive
Annunciator loop (TB4)
The control panel provides a connection for up to eight serially
driven and supervised remote annunciators.
Channel 1 Channel 2
+
+
+
-
Trouble
Form C
24 VDC at 1 A resistive
Relay circuits can only be connected to power-limited sources.
Class A wiring
TB2
–
TB4
Annunciator
CH1 (+) IN
CH1 (+) IN
CH1 (-) IN
CH1 (-) IN
TB2
NAC3 NAC3+
NAC4 NAC4+
+
+
EOLR
TB2
Page 4 of 8
+
+
CH2 (+) IN
CH2 (-) IN
–
–
TB4
Annunciator
CH1 (+) IN
CH1 (-) IN
CH2 (+) IN
CH2 (-) IND
V85005-0135
ATA S H E E T
Not to be used for installation purposes. Issue 1
10-11-16
Marking
indicates output signal polarity when the circuit is active. Polarity reverses
Class A wiring
whenNAC1
the -circuit is not active. Wire notification appliances accordingly. Notification
+
+
appliance
polarity shown in active state.
NAC1+
NAC2 +
+
NAC2+
-
CH2 (+) IN
CH2 (-) IN
Channel 1 Channel 2
+
TB6
+
TB6
TB6
NO
(1) Trouble
+
Class B wiring
NAC2+
NC
+
Class B wiring
NAC2 -
NO
(3)
Note: Any current above 0.5 amp connected to both Aux
1 and 2 will reduce the total available NAC power by that
amount.
+
with SA-CLA module
24 VFWR
Class B wiring
6.0 A total, 2.5 A max.NAC1 - 3.75 A total, 2.5 A max.
+
+
per circuit at 120/230NAC1+ per circuit
at 120/230
VAC 60 Hz.
VAC 60 Hz.
EOLR
NAC2 5.0 A total, 2.5 A max.NAC2+ 3.0 A +total, 2.5+A max.
per circuit at 230 TB2
VAC
per circuit at 230 VAC
NAC3 50 Hz.
+ 50 Hz. +
+
NAC3+
26 Ω total,
0.35 µF max
EOLR
NAC4 EOLR
+
15 K Ω, ½ W +
+
NAC4+
Supported
system-wide
TB6
TB2
Voltage
Current
NAC1+
NC
(2)
Circuit specifications
Circuit voltage
21.9 to 28.3 V
range
Resettable circuit
24 VDC nominal at 500 mA
(Aux power 2)
Continuous circuit
24 VDC nominal at 500 mA.
(Aux power 1)
Use this circuit for powering
two-wire smoke detectors.
Alarm
Notification
appliance circuits (TB2)
Loop 1 SEC
+
VS4 control panels +come +equipped with four notification appliance
Loop 1 PRI
circuits.
+VS1 control- panels
- come with two NACs. Each circuit can
Loop
Loop
be individually
configured
for
continuous, temporal, synchronized,
device
device
Loop card
Data Line
Class B wiring
and coded output.
NAC1 -
NO
Relay specifications
Class A wiring
NAC1 -
Auxiliary & smoke power outputs (TB3)
TB3
The control panel provides two auxiliary power
outputs that can be used for powering ancillary
equipment such as remote annunciators and two (1)
wire smoke detectors. Aux 2 can be software
selected to operate continuously. The circuit is
supervised for shorts and grounds.
Option Cards
Kidde VS Series panels are supported by a complete line of modules and related equipment that enhance performance and extend
system capabilities. Option cards plug directly into the control
panel main circuit board or are connected to it with a ribbon cable.
After installation, terminals remain accessible. The cabinet provides ample room for wire routing, keeping wiring neat at all times.
RZI16-2 Remote Zone Interface Module
Single and Dual Loop Controller Cards
The V-SLC2-1 is a single loop controller card that can be used
with the VS1 as a replacement for the standard 64-point loop, or
with the VS4 as a 250-point expansion module.
The RZI16-2 Addressable Remote Zone Interface Module is an
addressable device that provides connections for sixteen Class B
Initiating Device Circuits and two Class B Supervised Output
Circuits. The inputs and outputs can be configured individually for
several device types.
The V-SLC2-2 is a 500-point dual loop controller card for the VS4
that provides two IDC circuits, each with 125 detector addresses
and 125 module addresses.
Specifications
Device Addresses
Wiring
Operating Voltage
Operating Current
(fully loaded loop)
V-SLC2-1
V-SLC2-2
VS4: one loop, 250
device addresses
VS4: two loops, 500
device addresses
VS1: 64 addresses
Class B or Class A
24 VDC
Standby: 55 mA
Standby: 45 mA
Alarm: 80 mA
Alarm: 70 mA
Note: These ratings do not include the use of two-wire smoke modules.
Communication Line
Voltage
Terminal Rating
Circuit Current
Max total loop
resistance
Max total loop
capacitance
Isolators
Ground Fault
Impedance
Operating
Environment
Max. 20.6 V peak-to-peak
12 to 18 AWG (0.75 to 2.5 mm )
0.5 A max.
66 Ω
2
0.5 μF
64 isolators maximum per loop (total both
isolator bases and modules)
0 to 5 kΩ
32 to 120°F (0 to 49°C)
0 to 93% noncondensing at 90°F (32°C)
SA-ETH Ethernet Interface Card
SA-ETH wiring
The SA-ETH card provides a
To network
connection standard 10/100 Base T EtherNetwork cable
net network connection for
connecting to an intranet, a local
network, or the Internet. The
card can be used to download
configuration programming from
the VS-CU to the panel.
Ethernet card
The Ethernet card is installed on
the plastic assembly and connects to the main circuit board
via a ribbon cable.
SA-ETH specifications
Ethernet
10/100 Base T
Operating environment
Temperature 32 to 120°F (0 to 49°C)
Humidity 0 to 93% RH, noncondensing at 90°F
(32°C)
Page 5 of 8
The RZI16-2 requires 18 consecutive addresses on the Signaling
Line Circuit (SLC). Addresses are assigned electronically. There are
no address switches to set.
The RZI16-2 incorporates two 8-segment DIP switches that are
used to select the Alarm or Supervisory default device type for
each of the 16 IDC circuits. The module also includes one 4-segment DIP switch used to select the default Relay or NAC output
device type. Device types other than the default are accomplished
through programming.
RZI16-2 Specifications
Voltage
24V/Aux nominal:
Supervisory current:
Alarm current:
24V/Aux minimum:
24V/Aux maximum:
NAC1, NAC2 nominal:
Current
Standby current
for 4.7 k EOL (U.S.)
Standby current for
3.9 k EOL (Canada)
Alarm current
at nominal voltage
Relay outputs
Quantity
Type Rating (pilot duty)
Input circuit wiring
resistance
Initiating device circuits
Quantity
EOL resistor
Zone voltage
Alarm current
Alarm impedance range
Trouble impedance range
Supervised output circuits
EOL resistor
Quantity
Short circuit detection
Open circuit detection
Contact ratings
Compatible cabinets
24 VDC
250 mA at 24 VDC nominal
1000 mA
18.4 VDC
26.4 VDC
24 VDC
4.8 mA/ circuit
5.7 mA/ circuit
31.1 mA/ circuit
2
Programmable 24 VDC at 2.5 A
25 Ω per wire
16
4.7 kΩ (U.S.); 3.9 kΩ Canada
22.78 V for 4.7 kΩ (U.S.)
22.08 V for 3.9 kΩ (Canada)
31.1 mA/ channel at nominal voltage
< 680 Ω
> 5.55 kΩ
15 kΩ
2
< 2.6 kΩ
> 61.9 kΩ
24 VDC at 2.5 A (5 A for two NACs)
MFC(A), VS4, APS
V85005-0135
D ATA S H E E T
Not to be used for installation purposes. Issue 1
SA-DACT Dialer
The SA-DACT provides communications between the control
panel and the central station over a telephone line system. It
transmits system status changes (events) to a compatible digital
alarm communicator receiver over the public switched telephone
network. The dialer is capable of single, dual, or split reporting
of events to two different account and telephone numbers. The
modem feature of the SA-DACT can also be used for uploading
and downloading panel configuration, history, and current status
to a PC running the VS-CU.
SA-DACT
wiring
Phone line 2
Phone line 1
Phone cables
(supplied)
To wall
phone jack
RJ31 jacks
The dialer phone lines connect to
connectors on the dialer’s main
circuit board. Phone line 1 connects
to connector J4 and phone line 2
connects to connector J1.
The SA-DACT queues messages and transmits them based on priority (alarm, supervisory,
trouble, and monitor). Activations are transmitted before restorations.
The SA-DACT is installed on the plastic assembly and connects to
the main circuit board via a ribbon cable.
SA-DACT specifications
Phone line type
One or two loop-start lines on a public,
switched network
Phone line connector
RJ-31/38X (C31/38X)
Communication formats
Contact ID (SIA DC-05)
Operating environment
Temperature 32 to 120°F (0 to 49°C)
Humidity 0 to 93% RH, noncondensing at 90°F
(32°C)
Compatible DACRs
Receiver
Ademco
FBII
Osborne-Hoffman
Bosch
Silent Knight
Sur-Gard
Models
685
CP220
OH 2000
D6600
9800
SG-MLR1, MLR2
Formats
Contact ID
Contact ID
Contact ID
Contact ID
Contact ID
Contact ID
SA-232 RS-232 interface
The SA-232 card provides an RS-232 interface with VS panels. It can be used for
connecting a printer to the control panel
to print system events. The card also
can be used for connecting a computer
to download a configuration program
from the VS-CU to the control panel.
SA-232 wiring
GND (black wire)
TXD (white wire)
RXD (red wire)
The RS-232 card is installed on the plastic assembly and connects to the main circuit board via a ribbon
cable.
SA-232 specifications
Operating voltage
Terminal rating
Operating environment
Temperature
Humidity
Standard EIA-232
12 to18 AWG (0.75 to 2.5 sq mm)
32 to 120°F (0 to 49°C)
0 to 93% RH, noncondensing at 90°F (32°C)
SA-CLA Class A Module (VS1 only)
The SA-CLA card provides Class A capability for NAC wiring.
Its terminal block provides the wiring connection for NAC return
wiring. The card is required for annunciator Class A wiring even
though this wiring does not return to the SA-CLA card. The SACLA is compatible with VS1 control panels only. VS4 panels are
Class A Ready. The SA-CLA is installed directly to the control
panel circuit board using its plastic standoffs and plug connection.
SA-CLA specifications
Operating voltage
24 VFWR
Operating current
3.75 A FWR total at 120/230 VAC 60 Hz
3.0 A FWR total at 230 VAC 50 Hz
2.5 A max per circuit
Circuit impedance
26 ohms, 0.35uF
Terminal rating
12 to18 AWG (0.75 to 2.5 sq mm)
Operating environment
Temperature 32 to 120°F (0 to 49°C)
Humidity 0 to 93% RH, noncondensing at 90°F
(32°C)
D16L-VS LED Display Expander (VS4 only)
The D16L-VS LED Display Expanders provide LED annunciation for up to 16 zones. It provides two LEDs for each zone. Two
D16L-VS LED display expanders can be installed in each VS4
panel.
(1) LED 1
(2) LED 2
(3) LED Expander 1
(4) LED Expander 2
(5) Alarm/non-alarm
and trouble zone LEDs
V85005-0135
D ATA S H E E T
Not to be used for installation purposes. Issue 1
10-11-16
Page 6 of 8
Specifications
Device loops
VS1
VS4
1 loop Class B or Class A (Styles 4, 6, 7) supporting up to
64 device addresses (any combination of detectors and
modules)
1 loop, expandable to 4, Class A or B (Styles 4, 6, 7),
each loop supporting up to 250 device addresses (125
detectors and 125 modules max.). Addresses 1 to 125 are
for detectors and addresses 126 to 250 are for modules
Maximum T-taps: 63
(each device can be on its own branch)
Notification appliance
circuits
Maximum T-taps/loop: 124
2 Class B (Style Y), Class A (Style Z) optional
4 Class B (Style Y) or 2 Class A (Style Z)
3.75 A FWR total at 120/230 VAC 60 Hz
6.0 A FWR total at 120/230 VAC 60 Hz
3.0 A FWR total at 230 VAC 50 Hz
5.0 A FWR total at 230 VAC 50 Hz
2.5 A FWR each max. per circuit
2.5 A FWR each max. per circuit
120 VAC, 60 Hz, 1.3 A max.
120 VAC, 60 Hz, 2.0 A max.
230 VAC, 50-60 Hz, 0.62 A max.
230 VAC, 50-60 Hz, 0.97 A max.
Base panel current standby
155 mA
172 mA
Base panel current alarm
204 mA
267 mA
Input zones
16 max.
32 max.
Remote annunciator
8 drops max., RS-485 Class B, Class A is optional
8 drops max., RS-485 Class A or B
Data line length: 4,000 ft. (1,219 m)
Data line length: 4,000 ft. (1,219 m)
Primary power
Operating voltage
24 VDC panel
Auxiliary power output
circuit
Aux power 1: 500 mA, 24 VDC
Aux power 2: 500 mA, 24 VDC (1 A possible if you reduce total available NAC power by 500 mA)
Output: 28.3 to 21.9 VDC, special application
Note: For a list of compatible devices, see the VS1 and VS4 Series Compatibility List (P/N 3102354-EN)
Loop circuit
Maximum loop resistance: 66 Ω
Maximum loop capacitance: 0.5 µF
Communication line voltage: Maximum 20.6 V peak-to-peak
Operating current (fully loaded loop) Stand by: 55 mA/45 mA
Alarm: 125 mA/115 mA (not including two-wire smoke modules)
Circuit current: 0.5 A max. Style 4, 6, and 7 wiring
Max. resistance between isolators: Limited only by overall wire run lengths
64 isolators maximum per loop (total both isolator bases and modules)
Batteries
Type: Sealed lead acid
Voltage: 24 VDC
Charging current: 2.47 A max. Amp hour capacity: 26 Ah
Standby operation: 24 hour or 60 hour
Placement: Up to two 10 Ah batteries will fit in the VS1 control panel cabinet and two 18 Ah batteries will fit in the VS4
control panel cabinet. If larger batteries are required, use a battery cabinet.
SA-DACT dialer
Phone line type: One or two loop-start lines on a public, switched network
Phone line connector: RJ-31/38X (C31/38X)
Communication formats: Contact ID (SIA DC-05)
Operating current Standby/Alarm: 41 mA Max.: 100 mA
FCC registration number: GESAL01BSADACT
Industry Canada Registration number: 3944A-SADACT
Ringer equivalence number: 0.1B
Ground fault impedance
0 to 5 kΩ
Alarm contact
Form C N.O. 24 VDC at 1 A (resistive load)
Trouble contact
Form C 24 VDC at 1 A (resistive load)
Supervisory contact
Form A N.O. 24 VDC at 1 A (resistive load)
Environmental
Temperature: 0 to 49°C (32 to 120°F) Relative humidity: 0 to 93% noncondensing
Terminal rating
All terminals rated for 12 to 18 AWG (0.75 to 2.5 mm²)
Page 7 of 8
V85005-0135
D ATA S H E E T
Not to be used for installation purposes. Issue 1
Ordering Information
Part
Technology that saves lives
Contact us...
Email: kidde.fire@fs.utc.com
Web: Kidde.com/EngineeredSystems
Kidde is a UTC brand.
1016 Corporate Park Drive
Mebane, NC 27302
© 2016 United Technologies Corporation.
All rights reserved.
Description
VS4 Fire Alarm Systems
VS4-G
Four loop system with one 250-point loop installed. 110v, gray door.
VS4-G-2
Four loop system with one 250-point loop installed. 230v, gray door.
VS4-G-2-PG Four loop system with one 250-point loop installed. 230v, gray door, Portuguese.
VS4-G-2-SP Four loop system with one 250-point loop installed. 230v, gray door, Spanish.
VS4-GC
Four loop system, one 250-point loop installed. 110v, gray door, LED strips, Canada.
VS4-GD
Four loop system, one 250-point loop installed. 110v, gray door, with dialer.
VS4-GF
Four loop system, one 250-point loop. 110v, gray door, LED strips, French Canada.
VS4-G-PG
Four loop system with one 250-point loop installed. 110v, gray door, Portuguese.
VS4-G-SP
Four loop system with one 250-point loop installed. 110v, gray door, Spanish.
VS4-R
Four loop system with one 250-point loop installed. 110v, red door.
VS4-R-2
Four loop system with one 250-point loop installed. 230v, red door.
VS4-RD
Four loop system, one 250-point loop installed. 110v, red door, with dialer.
SA-TRIM2
VS4 Flush mount trim, black.
VS1 Fire Alarm Systems
VS1-G
One loop system with one 64-point loop installed. 110v, gray door.
VS1-G-2
One loop system with one 64-point loop installed. 230v, gray door.
VS1-G-2-PG One loop system with one 64-point loop installed. 230v, gray door, Portuguese.
VS1-G-2-SP One loop system with one 64-point loop installed. 230v, gray door, Spanish.
VS1-GD
One loop system, one 64-point loop installed. 110v, gray door, with dialer.
VS1-GL
One loop system, one 64-point loop installed. 110v, gray door, English Canada.
VS1-GL-F
One loop system, one 64-point loop installed. 110v, gray door, French Canada.
VS1-G-PG
One loop system with one 64-point loop installed. 110v, gray door, Portuguese.
VS1-G-SP
One loop system with one 64-point loop installed. 110v, gray door, Spanish.
VS1-R
One loop system with one 64-point loop installed. 110v, red door.
VS1-R-2
One loop system with one 64-point loop installed. 230v, red door.
VS1-RD
One loop system, one 64-point loop installed. 110v, red door, with dialer.
SA-TRIM1
VS1 Flush mount trim, black
Option Cards
V-SLC2-1
V-SLC2-2
RZI16-2
SA-DACT
SA-232
SA-ETH
SA-CLA
D16L-VS
D8RY-VS
Expansion module, one 250-device loop. For VS4 only.
Expansion module, two 250-device loops, 500 devices total. For VS4 only.
Remote Zone Interface Module. 16 Class B IDCs, 2 Class B Output. Bracket included.
Dual Line Dialer/Modem, supports Contact ID, mounts in cabinet on base plate.
RS-232 Serial Port for connection to printers & computers, mounts in cabinet.
Ethernet Port, Slave, mounts in cabinet on base plate.
Class A adapter module. Provides Class A capacity on NACs. Mounts in cabinet on
main board. VS1 systems only.
LED Annunciator module, 16 X 2-LED zones (4 programmable for sup). Mounts in
cabinet to right of LCD display. For VS4 only.
Canada only: LED Annunciator module, two LEDs per zone, 16 zones (4 alarm only,
8 supervisory only, 4 alarm or supervisory). Mounts in cabinet. For VS4 only.
Accessories
CTM
City Tie Module. 2-gang. Connection to a local energy fire alarm box.
MFC-A
Multifunction Fire Cabinet, 8" x 14" x 3.5" - red.
BC-1
Battery Cabinet. 14.0" x 18.25" x 7.25". Holds two 12V24A batteries.
BC-1R
Battery Cabinet - Red. 14.0" x 18.25" x 7.25". Holds two 12V24A batteries.
GSA-REL
Releasing Module
BC-1EQ
Seismic hardening Kit for VS Series panels. Includes battery hardening for
BC-1 enclosure and components to harden panel internal components.
Programming Tools
VS-CU
VS Series configuration and diagnostics utility.
260097
RS232 cable, 4 conductor, DB9 PC interface
V85005-0135
D ATA S H E E T
Not to be used for installation purposes. Issue 1
10-11-16
Page 8 of 8