DII DFR.ai - E-MAX Instruments, Inc.

DII DFR.ai - E-MAX Instruments, Inc.
DIRECTOR DII
16 BIT DFR
Complete Transient Fault Recording and
Analysis
WITH
SIGMA DELTA
CONVERSION
E-MAX Instruments, Incorporated
13 Inverness Way South
DIGITAL FAULT
RECORDER
E
Long Term Phasor Recording
Power Quality Monitoring
Continuous Recording
Complies with
NERC - PRC-002-1
NERC - PRC-018-1
Englewood, Colorado
80112
303.799.6640
e-maxinstruments.com
GENERAL DESCRIPTION
Using the Microsoft Windows 7® operating system, DII features complete Transient and Long-Term Phasor Data
Recording, Analysis, and Transmission. E-MAX DII has a maximum capacity of 128 Analog and 256 Digital
directly connected channels.
The networking capabilities of DII combined with Windows 7® provides the power and capacity to monitor and
collect data from other substation equipment. The TCP/IP addressing and data handling also allow
communications with a Master Station and other devices. The DII system includes complete remote control of
both the DII and any connected E-MAX DFRs.
Input Characteristics
Analog Channel Capacity:
8 - 128 inputs
Analog Input Range
Voltage Channels: 0 to 500 Vac rms
Current Channels; 0 to 200 Amps (E-MAX shunts or CTs)
Analog Isolation
2500 Volts rms, Channel-to-Channel and Channel-to-Ground
Frequency Response
DC-coupled w/6th order anti-aliasing filter
Sigma Delta
DC - 3000 Hz
Sampling Method
Individual 16 bit Sigma Delta Conversion
Sample Rate
5760 samples/channel/second with
11,520, 2880, 1440, 720 samples/channel/second (software selectable)
Digital Channel Capacity: 16 to 256 inputs
Input Configuration
Normally Open or Normally Closed (software selectable)
Input Voltage
60 - 185 Vdc / 120 Vac standard. Other supply voltages available.
Isolation
2500 Volts rms, Channel-to-Channel and Channel-to-Ground
Sensors
Software triggers (sensors) are standard for E-MAX Director DII DFRs. Each DFR locally stores the trigger
information. All trigger information is user-settable — locally or remotely.
Analog Sensors: Over-, Under- limit and rate software sensors on each channel
Symmetrical component, harmonic, frequency, swing and power sensors.
Operation Limiters Individual Channel: Software Settable up to 15 minutes per fault
Event Sensors: Trigger on ALARM (operate) and/or RTN (return-to-normal) for each channel.
E-MAX Instruments, Incorporated
13 Inverness Way South
Englewood, Colorado
80112
303.799.6640
e-maxinstruments.com
Processing of Record Data
The DII Recording System continuously monitors all channels. If triggered, the DII will record data to memory
and process according to user settings. This System automatically identifies fault type and calculates distance
to fault. All E-MAX DFR systems can print, display, fax, transmit and e-mail recorded and calculated data
automatically or upon operator request. Conversion of record data to COMTRADE and PQDIF formats may
be done automatically or upon operator request.
DFR and Power Quality Sensors
Single Phase - One Per Channel
Under Limit Sensors - rms setting
with Hysteresis
Rate of Change
Over Limit Sensors - rms setting
with Hysteresis
with Time Delay (selectable)
Rate of Change
Frequency Over and Under
Frequency Delta Trigger
10 - 100 percent
up to 5 %
up to 10 %
95 - 300
up to 5%
30 msecs
up to 50% per cycle
56 - 64 Hz
0.5 - 4 Hz
Three Phase Triggers
Positive Sequence
Negative Sequence
Zero Sequence
Real Power
Reactive Power
Apparent Power
0 - 150%
0 - 30%
0 - 30 %
Threshold and Step Change
Threshold and Step Change
Threshold and Step Change
Extended Triggers
Frequency and Delta Frequency
Power Triggers
Sequence Triggers
Total Harmonic Distortion
56 - 64 Hz
3 Phase, Real, Reactive, Apparent
3 Phase, Positive, Negative and Zero
5 - 50%
Swing Triggers
E-MAX Instruments, Incorporated
specified by crest to valley percentage
5 - 30 % setting and time swing of 0.5 to 4 cycles/second
13 Inverness Way South
Englewood, Colorado
80112
303.799.6640
e-maxinstruments.com
Analog Inputs:
Analog Input Range:
Accuracy:
Analog Isolation:
8 to 16 per Remote, up to 4 Remote Units.
Voltage: 0 to 500 Vac rms or Current: 0 to 200 Amp.
1 %, calibrated to .5%
2500 Volts rms
Sampling Rate:
Standard Base Sample Rate — 5760 samples/channel/second with 2880, 1440, 720 Hz,
samples/channel/second software programmable. 11520 samples/channel/second available.
Digital/Event Inputs:
1. Input Configuration
2. Input Voltage
3. Isolation
16 to 32 inputs per Remote, up to 4 Remote Units.
N.O. or N.C. (Software Selected)
125 Vdc Nominal standard —24, 48, 250 Vdc available
2500 VDC (To Ground) and between inputs
Sensors:
1. Analog Sensors
Auto-resetting standard
Over-, Under- limits and rate software sensors on each channels
Symmetrical component, harmonic, frequency swing sensors
Individual Channel: Software Settable up to 15 minutes per fault
Individual Programmable (N.O., N.C., Trigger on ALARM and/or RETURN)
Contact or voltage input
Complies with NERC PRC-002-1 and NERC PRC-018-1, PRC-002-2(draft). Records up to 99 Days.
Phasor recording - simultaneous with Transient recording.
Sample rate is software selectable: 1 sample/cycle, 1/2 sample/cycle, 1/4 sample/cycle, 1/8 sample/cycle
Programmable Record Length
90 days maximum length
Logs of signals, power, and frequency (optional)
2. Operation Limiters
3. Event Sensors
4. External Sensors
Continuous Recording
Long term Recording
High Speed Transient Recording:
Prefault Period:
Up to 10 seconds. Default setting: 10 cycles.
Postfault Period:
Minimum Record Length can be set with System Parameter file (0.5 sec default).
Maximum Postfault Time - Can be set for continuous data streaming to disk capacity. (Longest Postfault
captured to date: 31 minutes)
Record Storage:
Nonvolatile data storage on local SATA drive. Optional solid state drive.
Capacity determined by disk size and scan frequency.
16 bit
DC/DC Converter: 48 - 125 Vdc / 120 Vac. 250 Vdc Available. Current Limited / Overvoltage protected.
Resolution:
Power Supply:
Controller:
Graphic Output:
Atom N270 CPU. 2 Gb RAM standard
2 USB 2.0 Ports, 1 Parallel Port, PCI Hard Disk Controller.
Supports color inkjet, laser or dot matrix printers
Graphics display on optional monitor.
Data Storage:
Clock Options:
Clock Decoder
SATA Hard Disk. Solid State Disk (optional)
GPS Timing - GPS Receiver or IRIG B Decoder Internal (1 kHz or TTL), External GPS Clock, or Internal GPS
Accuracy: Better than 20 μs.
Communications Capability:
1. To Master Stations
Data/Fax Modem and Network cards available.
Automatic transmission of data files.
Functions with multiple-Master system.
Complete Remote Control
Up to 24 locations. (Up to 8 Fax numbers in each of three outputs.)
Software supports communication via TCP/IP
2. To Fax Machines
3. LAN and WAN
Software Supplied:
1. Master Station & Recorder
2. Communications
Environmental Characteristics:
Operating Temperature
Storage
Relative Humidity
Surge Withstand Capability:
Quality Certification:
Microsoft Windows 7® (Windows 10® available 4th quarter 2015).
Complete remote control, test and data retrieval, display and screen manipulation.
Remote setting of program and system parameters.
Complete data analysis software for Recorder and Master Station included.
Remote Control Computing Program - Communication Software
Network control and data transmission (Ethernet)
0O To 60O Centigrade
-20O to 65O Centigrade
0 to 95% R.H. non-condensing
ANSI C37.90.1 1989
ISO 9001:2008
INTERNATIONAL STANDARDS COMPLIANCE
Safety
IEC 60255-2
IEC 60255-4
IEC 60255-5
DFR DII - 1805.15
E-MAX Instruments, Incorporated
13 Inverness Way South
Englewood, Colorado
80112
303.799.6640
Immunity
IEC 61000-4-2
IEC 61000-4-3
IEC 61000-4-4
IEC 61000-4-6
e-maxinstruments.com