Mains Ionisation Smoke Alarm

Mains Ionisation Smoke Alarm
KF10R
PRODUCT
Mains Ionisation
Smoke Alarm
DESCRIPTIONMains-powered ionisation smoke alarm
that can be interlinked with up to 23 other
Rechargeable
Kidde mains alarms, be they ionisation, optical or
sealed-in Lithium cell
heat. Once interlinked, the detection of the relevant danger
back-up version
by an individual unit will sound across all the connected alarms.
KEY FEATURES
l
Interlink with up to 23 Firex hard-wired alarms – all alarms sound if danger is detected
l
Alarm memory – identifies source unit within interconnecting network
l
Reduced energy consumption – lower lifetime running costs
l
ombined Test/HushTM button allows regular testing of alarm function and can be used to
C
temporarily silence nuisance alarms
l
Auto reset after activation
l
Tamper-resistant locking device – prevents unauthorised removal without the use of a tool
l
Mains operation – Built-in rechargeable Lithium back-up tamper-proof battery
* compared to
previous Firex alarms
WHERE TO USE
Ionisation alarms are for use in areas where there is danger from fast-flaming fires.
This mains-powered unit complies with UK Building Regulations for new housing and associated
standards (Grade D BS 5839, Part 6) and should be installed by a qualified electrician. It can be
used throughout the home, except in the kitchen where a Firex Heat Alarm is recommended.
M
odel
KF10R
Power Supply
230V mains-powered with rechargeable Lithium battery back-up
Temperature Range
0ºC to + 40ºC
Humidity Range
Up to 93% Relative Humidity (RH) non-condensing
Storage and Transport -20ºC to +60ºC and 5–95% relative humidity (RH) non-condensing
Alarm Dimensions
185 x 185 x 40mm
Bracket Dimensions
133 x 133 x 6mm
Alarm Weight
199g
Warranty
6 years (including battery)
Approvals
BSI certified to BS EN14604:2005
GENERAL FEATURES
CE tested and certified
For more information or to contact Kidde Sales:
01753 766 392
kiddesafetyeurope.co.uk
EN14604:2005
Licence no: KM524754
0086-CPD-535595
15
EN14604:2005
MAINS SMOKE ALARMS
SHEET 09 / 2015
KF10R
PRODUCT
Mains Ionisation
Smoke Alarm
POWER SOURCE
SENSOR TYPE
TECHNICAL
SPECIFICATION
230V Mains
Ionisation*
Sensor
Ionisation, circular metal chamber with 24-slot entry portals
Source
Americium 241 (<1.0 microcurie, 37kBq)
Button TestSimulates the effect of smoke within the sensing chamber, checks electronics and sounder
Automatic Self-test
Circuitry is tested and unit beeps (chirps) if fault is detected
Supply Voltage
230V AC, 50 Hz (nominal UK voltage)
Power Consumption < 15mA
Connection
Push-in/snap-fit type connector with 150mm long flying leads (supplied)
Battery Back-up
Non user-replaceable 3 x 3V rechargeable Vanadium Pentoxide Lithium cells (VL2330)
Power-on Indicator
Continuous green LED
Alarm SounderElectronic piezo-electric sounder (T3 pattern sound - three pulses - space - three pulses) with
soldered contacts
Sound Output85dB (A) minimum at 3 metres
PACKAGED
SPECIFICATION
Alarm Frequency
3.2 kHz typical
Dust Protection
In-built foam gasket in rear of alarm to prevent dust ingress into rear of the alarm
Alarm Status
Red LED flashes approx once every five minutes = normal operation
Red LED flashes once a second = sensing smoke (sounder alarm sounds)
Red LED flashes once every ten seconds = in hush condition (auto-reset after 15 minutes)
Interconnection
Up to 24 Firex and Kidde ‘Slick’ units (smoke, heat and CO) can be hardwire interconnected with optional control (see below)
Optional Controls
Wired Remote Test and Hush Unit (REMTH) allows test and hush of interlinked units
Optional Pattresses
SMK23RU also has integral switchable relay for operating remote devices
SMK4896 – Surface mounting base for added ease of installation
Fixing
Mounting bracket ring supplied with two ‘T’ slot fitting option
57mm spacing to a maximum of 90mm for standard screw fittings on back boxes
Bracket has 50mm diameter central access hole for cabling
Plastics used
NORYL – Cover, main body and mounting bracket
Lead-Free Status
All Firex alarms are lead-free
BOX
Order CodeKF10R
Pack Dimensions
135 x 135 x 50mm
Pack Weight270g
UPC Barcode0-047871-259700
Case Quantity6
* This product is designed to
detect products of combustion
using ionisation technology.
This product contains 0.9
microcurie of Americium 241,
a radioactive material.
Case Dimensions
145 x 280 x 160mm
Case Weight1.7Kg
ITF Outer Code
100-47871-259707
MAINS SMOKE ALARMS
For more information or to contact Kidde Sales:
SHEET 09 / 2015
01753 766 392
kiddesafetyeurope.co.uk
Was this manual useful for you? yes no
Thank you for your participation!

* Your assessment is very important for improving the work of artificial intelligence, which forms the content of this project

Download PDF

advertising