Maintenance Bypass Panel (MBP)
Installing the CAN I/O Board
Measurements in mm/in

114.5/4.48
107/4.21
Installation

5/0.19
58.5/2.3
Maintenance Bypass Panel (MBP)
CAN I/O Board

About this manual

The MBP CAN I/O Board should be used for both Smart-UPS® VT,
MGE™ Galaxy™ 3500 parallel configurations, or for Symmetra MW
parallel configurations. Pages 2 (Smart-UPS VT, MGE Galaxy 3500) and
3 (Symmetra MW) show the cable connections for the three UPS series.
This unit contains components that are sensitive to electrostatic
discharge (ESD). Follow proper ESD procedures to avoid
severe damage to electronic components.

110 mm/4.33 in free space for ABus cables to ensure recommended bending radius
 Drill one 4.5 mm (1.7 in) hole in a grounded surface in the Maintenance Bypass Panel (MBP)
in the upper left corner according to the measurements on the illustration above.
 Drill seven 4.7 mm (1.8 in) holes for the remaining marked holes in the MBP for the nylon stand offs.

Nylon stand off

Metal stand off

Thickness of metal
must be between
1 mm (0.039 in) and
1.5 mm (0.059 in)
MBP CAN I/O Board


 Insert the 7 nylon stand offs (supplied) in the prepared holes.
 Fasten the board to the nylon stand offs by pushing it gently in place.
 Attach the board with the supplied stay, bolt and nut to the upper left corner.
990-2873F-001
*990-2873F-
08/2009

10/0.39
41.5/1.63
74.5/2.93
98.5/3.88
166.5/6.55
236/9.29
246/9.68
This installation sheet contains information on how to install the MBP
CAN I/O Board into a Maintenance Bypass Panel.
Electrical Hazard. All power and control wiring must
be installed by a qualified electrician and must comply
with applicable local and country codes.


Smart-UPS VT, MGE Galaxy 3500 cable connections
Maintenance Bypass Panel MBP
 The ABus cable 1x30 m (1x98.42 ft) is provided with this MBP I/O
UPS (a)

Terminator
0M-0765

Parallel
Communication
Box 0G-9352
MBP I/O Board
0P4533B
Earth fault
sensor
ID 0
Terminator
0W03914
 External lamp supply Vac or Vdc, max. 250 Vac, 5A. The supply
Relay
Board
should be taken from the mains/utilty side.
To
charging
control
switch

Pbus 2

XR Battery
Enclosure 1a
Connection
Plane 0P4910
Abus
Terminator
0W03914
Board 0P4533.
Connect the ABus cable to X134A on the boards and run the cables
(in conduits if applicable) to the UPS. One ABus terminator is also
provided with the board.

To J200 of
next XR
Battery
Enclosure
 Insertion of terminators in “IN” ports on Parallel Operation Box on
UPS (a) and in “OUT” ports on Parallel Operation Box on UPS (d).
 Relay output.
 When pins 7 and 8 are closed, the UPS charges batteries with a pre-
defined percentage (0-25-50-75-100%) of maximum power, to be
used in generator applications, or if special codes requires control of
charging.
Contactor functions.

UPS (b)

Connection
Plane 0P4910
Abus
Terminator
0M-0765

Parallel
Communication
Box 0G-9352
MBP I/O Board
0P4533B
Earth fault
sensor
ID 1
XR Battery
Enclosure 1b
Relay
Board
Pbus 2

To
charging
control
switch
To J200 of
next XR
Battery
Enclosure
X173 Function
X172
Function
1,2
Q1 input breaker to UPS
1, 2
Not in use
3, 4
Q2 output breaker from UPS
3, 4
H2 permission to operate Q2
5, 6
Q3 manual bypass breaker
5, 6
H3 permission to operate Q3
7, 8
Q4 common output breaker
7, 8
H4 permission to operate Q4
9, 10 Q5 input breaker to Static
Bypass
9, 10
H5 permission to operate Q5
11, 12 Not in use
11, 12 Lamp supply max 230V, 5A
Replicate
Replicate
UPS (d)

Terminator
0M-0765
Abus

Parallel
Communication
Box 0G-9352
MBP I/O Board
0P4533B
Earth fault
sensor
ID 2
Terminator
0W03914
X178
Function
1,2
3, 4
24Vdc trip of input breaker
1, 2
C1 Energy for EPO trip
3, 4
C1 Energy for EPO trip
5, 6
24Vdc trip of output breaker
Contactors X128, X129, X174 and X177 are not in use.
Relay
Board
To
charging
control
switch
Pbus 2

XR Battery
Enclosure 1d
Connection
Plane 0P4910
X176 Function
Terminator
0W03914

2
To J200 of
next XR
Battery
Enclosure
Note: A Smart-UPS VT and MGE Galaxy 3500 parallel
configuration can consist of up to four units.
Symmetra MW cable connections
 The capacitors are energy storage for Emergency Power Off (EPO)
400-600 kW systems
Maintenance Bypass Panel MBP

when no other source is available C1= 33000μF. Recommended size
depending on power consumption of trip relays on breakers.
Capacitor voltage should be 40 Vdc.
800-1600 kW systems

Maintenance Bypass Panel MBP
Relay
Board


Relay
Board


Abus
Abus

MBP I/O Board 1 Earth fault
sensor
0P4533B

MBP I/O Board 2
0P4533B
UPS A
Earth fault
sensor
External Bypass
Static Switch
Single
System
 15 conductor cable is shielded twisted pair provided by APC by
Schneider Electric.
 Emergency Power Off (EPO) outage to UPS connection plane.
 Emergency Power Off (EPO) outage to External Bypass Static Switch
connection plane.
 External lamp supply Vac or Vdc, max. 250 Vac, 5A.
 24 Vdc shunt trip for back feed protection.
Note: The ABus and PBus cables are delivered with the
Symmetra MW system, and must be installed on site.
Parallel
System






Relay
Board
Relay
Board


Abus
Abus


MBP I/O Board 2 Earth fault
sensor
0P4533B
Single
System
MBP I/O Board 1
0P4533B
UPS B
Earth fault
sensor
UPS A
Parallel
System
*) This is an example of 2 units in parallel. For more and up to 4 units in
total the number of CAN Boards should be equal to the number of units.


Relay
Board

Abus

MBP I/O Board 3
0P4533B
Earth fault
sensor
UPS B
*) This is an example of 2 units in parallel. For more and up to 4 units in
total the number of CAN Boards should be equal to the number of units.
3