Rack PDUs MPX, MPH2 and MPE
Emerson Network Power – Power Distribution Units
Rack PDUs MPX, MPH2 and MPE
Your product range for the highest data center demands
The key aspects of this product range are:
H
igh availability for connected electrical loads.
O
ptimized energy and capacity management.
S
implified integration into management tools.
S
implified physical and electrical installation.
Overview: Emerson Network Power Rack PDUs for Europe
MPX-Adaptive Rack PDU
Features
MPX-R
MPX-B
MPH2-Managed Rack PDU
MPX-E
MPE Rack PDU
MPH2-R
MPH2-M
MPH2-C
MPH2-B
MPE
Modular
Remote
interface
*
Measurement
per phase
*
Measurement
per group
Measurement
per output
Switching
per output
Measurement
parameters
Input
Outputs
A, V, W, kWh, VA,
Hz, power factor,
crest factor
A, V, W, kWh, VA,
Hz, power factor
A, V, W, kWh, Hz
A, V, W, kWh, VA,
Hz, power factor,
crest factor
A,V,W,kWh, VA,
Hz, power factor,
crest factor
A,V,W,kWh, VA,
Hz, power factor
A,V,W,kWh, VA,
Hz, power factor
1 ph + 3 ph
max. 63 A
1 ph + 3 ph
max. 63 A
1 ph + 3 ph
max. 63 A
1 ph + 3 ph
max. 32 A
1 ph + 3 ph
max. 32 A
1 ph + 3 ph
max. 32 A
1 ph + 3 ph
max. 32 A
1 ph + 3 ph
max. 63 A
IEC C13 & C19
Schuko
IEC C13 & C19
Schuko
IEC C13 & C19
Schuko Switzerland
GST18
IEC C13 & C19
IEC C13 & C19
IEC C13 & C19
IEC C13 & C19
IEC C13 & C19
Schuko
Sensor
connections
*
The range of MPX and MPH2 accessories is almost identical, which simplifies administration!
* Only in conjunction with MPX-PEM monitored.
220 | Rack PDUs
Emerson Network Power – Power Distribution Units
DI-STRIP® Socket System
Your product range to cover basic requirements in all areas
The key aspects of this product range are:
R
obust design with the highest level of quality.
C
ost effective thanks to flexible and simple assembly.
N
umerous designs for all application areas in IT, network
technology, laboratories, and in the home.
Overview: Emerson Network Power DI-STRIP for Europe
Features
DI-STRIP® RM
DI-STRIP® M
DI-STRIP® E
A
A
1 ph + 3 ph
max. 16 A
1 ph + 3 ph
max. 16 A
1 ph + 3 ph
max. 16 A
IEC C13 & C19 Schuko, France, Switzerland
IEC C13 & C19 Schuko, France, Switzerland
IEC C13 & C19 Schuko, France, Switzerland
Local display
Remote interface
Measurement per phase
Measurement parameters
Input
Outputs
Rack PDUs | 221
MPX™
MPX™ – Adaptive Rack PDU
Respond to change and maximize profits
No-one can make definite predictions about the power-supply demands the future will bring. But one thing is certain: the versatile, adaptive MPX rack PDUs equip you with the wherewithal to face all eventualities. They enable
you to react quickly to changes in rack equipment and provide dynamic capacities, offering:
Modular hot-swap-enabled output power
Modular hot-swap-enabled communication
Modular input power.
Benefits of MPX
Adaptive capacity, distribution,
monitoring, control and administration of critical equipment.
Flexibility in reacting to constant
changes – modules can be regrouped
to accommodate altered requirements.
Only purchase what you really need
and utilize existing investments.
Reliable communication.
Developed for critical environments
Critical rack operating temperature – of up to 60° C suitable for high
temperatures inside racks.
Accurate voltage and current metering with tolerances of ±1 % offer a
comprehensive overview.
Energy and power metered with outstanding precision all the way through
to output level.
Extensive alert function; including notification before failure occurs.
Monitoring of environment conditions including alerts and alarms.
Notification upon failure or if individual components are removed.
Flexible, configurable input and
output distribution
The scalable design of the MPX rack
PDU allows on-site configuration that
meets the current requirements of the
IT equipment. It is the perfect solution
for coping with the ever increasing demands of expanding data centers. You
can set up your IT equipment at another location or add new components
to extend your environment. All you
need to do in this case is simply reconfigure the power supply and the power
distribution.
Hot-swap-enabled
output module
Simple
implementation for
quick start-up of IT
equipment.
Equipped to face the demands of
today and tomorrow
The MPX rack PDU supports a variety of
configurations for single-phase and
three-phase power inputs enabling
changes while retaining the distribution infrastructure.
Outputs and
modules
Outputs can be
controlled and measured
remotely thereby
increasing flexibility and
on-site security.
Modular input power.
Can be reconfigured for altered power demands; single-phase and three-phase input.
Module can be fitted on top or at the bottom.
222 | Rack PDUs
MPX™
The busbar (MPX™ PRC):
Serves as power and communication
distribution for all supported
modules. Available in two heights to
accommodate different rack heights.
Output module (MPX™ BRM):
Provides overload protection by distributing power to individual
servers. Available functions: Elementary, Branch Metering and
Output Metering with switch function.
Power-rail spacer:
Reserves unused space until needed for
an MPX™ module.
BDM™ local display module
Extended diagnostic functionality;
customer-convenient display. Features
include detailed information about alerts
and specific labeling for outputs.
SN sensors:
Consolidates environmental monitoring of temperature,
humidity and potential-free input contacts with the power
supply at rack level.
Communication module (RPC2):
Input module (MPX™ PEM):
Routes the input power to the busbar system of the
Elementary model (without RPC2™) and the version with
input metering (includes pre-installed RPC2™).
Installed in the power input module and
offers an extendable interface for network
communication, sensors and the local
display.
Rack PDUs | 223
MPX™
MPX™
Benefits of the modular MPX rack PDU
INPUT POWER
Configurable: 20 to 60 A (USA);
16 to 63 A (EU).
Single-phase and three-phase.
Cable routing possible from
above and below.
OUTPUT DISTRIBUTOR
Scalable, combination-compatible
and can be replaced during
operation
Single-phase NEMA 5-20R, IEC-C13,
IEC-C19, Schuko, Switzerland,
GST18.
Load balance.
MODULARITY
Input modules.
Output modules.
External display.
External sensors.
RPC2 communication card.
MONITORING
Three levels: Input level,
module level, output level.
Temperature and humidity.
Door contacts and floating break
input contacts.
REMOTE CONTROLLED SOCKETS
Socket level.
Featuring High Availability
Heat resistant up to 60° C ensuring reliable operation in the warm aisle.
Modular hot-swap-enabled output module, controller card and sensors;
can be exchanged or updated during operation.
Special switch relay (normally closed); connected servers have an
uninterrupted power supply even in the event of failure.
Redundant power supply for control electronics.
Fixed databus on the busbar.
Complete data tapping on the Power Entry Module (PEM) without any
additional external monitoring devices.
Proactive alert by additional metering of the neutral conductor and
crest factor (assessment of network quality facilitating early detection of
power-supply unit failures).
Maximum Flexibility and Scalability
All modules configured in line with requirements (patented quick-mount
fitting for safe installation).
One busbar for different networks and power levels – input module can
be freely selected. All other components are "hot-swap-enabled" when
running operation.
Mobile display for reading all MPX data on the rack.
Optical slot-space display (easy server slot-space identification at the push
of a button).
Highest Possible Power Levels in all Areas
Power feed of max. 3 x 63 A; optimal for Blade server applications.
Only one IP address for up to 4 rails with 24 modules.
Plug and Play for numerous sensors.
Extensive monitoring with a metering accuracy of ±1 % right through to
output level.
Module and sensor autodetect function with operating software.
Minimal power loss for MPX systems.
224 | Rack PDUs
MPX™
MPX™
Four equipment models for different requirements
The MPX modular rack PDU consists
of various components. The basic
element is a busbar, which is responsible for the power and communication distribution to the individual
modules. The input power is routed
via the MPX Power Entry Module
(MPX PEM) to the MPX system.
Different output modules (MPX
Branch Receptacle Modules, MPX
BRM) are available depending on
requirements. Four different variants
can be set up depending on the component population of the busbars:
1. MPX Elementary
Modular basic power distribution without metering and control function. An
upgrade to another equipment model
is quick and easy.
2. MPX Elementary Phase
Monitored
Modular power distribution with metering on input. An upgrade to a superordinate line is possible by populating
with appropriate output modules.
3. Branch-Monitored MPX
Modular power distribution with metering on input and each output module.
An upgrade or downgrade to another
line is possible if installed with
appropriate output modules.
4. Receptacle Managed MPX
Modular power distribution with input,
metering, each output module and
each output. Individual outputs can
also be switched on and off remotely.
A downgrade to another line is possible
if installed with the appropriate output
modules.
A combination of the "Elementary
Phase Monitored", "Branch-Monitored"
and "Receptacle Managed" lines on a
shared busbar is also possible and is one
of the exceptional features of the MPX.
Interfaces for the network communi­
cation, sensors and/or local display are
provided by the Rack PDU Card (RPC)
in the MPX PEM. The RPC Card enables
connection to an optional RPC Basic
Display Module (RPC BDM) to display
local status and alerts.
Output module
Receptacle Managed
Busbar (MPXT PRC)
Distributes power and
communication signals
to all modules.
Branch-Monitored
output module
(MPX BRM)
Spacer for busbars
Fills unused gaps until a
Liebert MPX module is
upgraded.
Output module
e. g. Elementary
(MPX BRM)
Input module
(MPX PEM)
Routes input power and
data (depending on the
module type) to the
busbar system.
Rack PDUs | 225
MPX™
MPX™ – Configuration models in Europe
Four equipment models
Order number
Length 1035
MPXPRC-V1035XXX
Length 1880
MPXPRC-V1880XXX
Length 2144
MPXPRC-V2146XXX
1ph 16A fest
MPXPEM-EHABXS30
Input Modules
3ph 16A fixed
3ph 32A fixed
3ph 63A fixed
Elementary
Output Modules
Branch-Monitored
Output Modules
Receptacle Managed
Output Modules
Sensors
External Display
MPX™
Receptacle Managed
MPXPEM-EHAEXQ30
MPXPEM-EHABXQ30
MPXPEM-EHAEXT30
MPXPEM-EHABXT30
MPXPEM-EHAEXR30
MPXPEM-EHABXR30
MPXPEM-EHBEXZ30
MPXPEM-EHBBXZ30
IEC-C13 L1
MPXBRM-EEBC7N1N
IEC-C13 L2
MPXBRM-EEBC7N2N
IEC-C13 L3
MPXBRM-EEBC7N3N
IEC-C19 L1
MPXBRM-EEBC4O1N
IEC-C19 L2
MPXBRM-EEBC4O2N
IEC-C19 L3
MPXBRM-EEBC4O3N
Schuko L1
MPXBRM-EEBC3P1N
Schuko L2
MPXBRM-EEBC3P2N
Schuko L3
MPXBRM-EEBC3P3N
Switzerland T23
MPXBRM-EEBC4S1N
Switzerland T23
MPXBRM-EEBC4S2N
Switzerland T23
MPXBRM-EEBC4S3N
GST18
MPXBRM-EEBC9U1N
GST18
MPXBRM-EEBC9U2N
GST18
MPXBRM-EEBC9U3N
IEC-C13 L1
MPXBRM-EBBC6N1N
IEC-C13 L2
MPXBRM-EBBC6N2N
IEC-C13 L3
MPXBRM-EBBC6N3N
IEC-C19 L1
MPXBRM-EBBC4O1N
IEC-C19 L2
MPXBRM-EBBC4O2N
IEC-C19 L3
MPXBRM-EBBC4O3N
Schuko L1
MPXBRM-EBBC3P1N
Schuko L2
MPXBRM-EBBC3P2N
Schuko L3
MPXBRM-EBBC3P3N
IEC-C13 L1
MPXBRM-ERBC6N1N
IEC-C13 L2
MPXBRM-ERBC6N2N
IEC-C13 L3
MPXBRM-ERBC6N3N
IEC-C19 L1
MPXBRM-ERBC4O1N
IEC-C19 L2
MPXBRM-ERBC4O2N
IEC-C19 L3
MPXBRM-ERBC4O3N
Schuko L1
MPXBRM-ERBC3P1N
Schuko L2
MPXBRM-ERBC3P2N
Schuko L3
MPXBRM-ERBC3P3N
1xTemp.
SN-Z01
3xTemp.
SN-Z02
3xT. + 1xHum
SN-Z03
1xTemp. Mod.
SN-T
Temp/Hum Mod.
SN-TH
2xDoor Mod.
SN-2D
3xInput Mod.
MPX™
Branch-Monitored
SN-3C
RPCBDM-1000
Different combinations available
226 | Rack PDUs
*Note: One-phase input modules can only be populated with L1 modules.
1ph 32A fixed*
MPX™
Elementary
Phase-Monitored
Upgrade possible
Busbar
MPX™
Elementary
MPX™
MPX™ – Input Module/Power Supply
Elementary and Monitored type
–The MPX PEM is fixed on the MPX PRC and
provides the connection to the power supply.
–Fixed-connection cable; 3 m long.
–With IEC60309 plug, 1Ph/N/PE 6h blue,
3Ph/N/PE 6h red.
Monitored type
–The MPX PEM provides connection to the
databus for data communication.
–Integrated RPC2 communication card enables
remote monitoring and maintenance of the
MPX modules.
–Provides the following phase-input data:
voltage, current, effective power, consumption
and frequency.
–Power alarm functions for individual phases and
their operating status are also supported.
–Further important features: Three displays
inform the user on the current status of
each individual input. An acoustic alarm is
activated at certain overload conditions.
–The communication card centralizes the
MPXs local and remote administration.
–Serves as the connection point for versatile
support options and devices, such as the display
module (RPC BDM), various sensors and
connection to other MPX™ or MPH2™ systems,
for example.
–Has RJ-45 ports for all connections (except USB
port) and does not require any special cabling.
DOS20153
Technical Data Interfaces:
–R
J-45 LAN port (10/100 MBit) – for local
network (LAN) connection via an Ethernet
cable.
– E xpansion / administration port for local
configuration using a computer / laptop,
for creating a link-up of several PDUs
(MPX or MPH).
– S erial interface RS232.
Dimensions in mm:
– Display port for connecting the RPC BDM
(display module).
– External sensor port for connecting optional
sensors.
– Remote management: Onboard Web
interface, CLI, SNMPv1,2,3, SSH, Telnet Syslog,
compatible with Avocent ACS, UMG & MPU,
SiteScan, DSView, Rack Power Manager,
Nform & Trellis as well as Nagios or other
management software programs.
– Authentication: local, remote: Active
Directory, LDAP, TACACS, Radius, Kerberos.
– Encryption: MD5, AES, DES.
M
aterial / Finish
– Enclosure: aluminum.
– Cover: sheet steel.
– Power contacts: silver-plated.
– Databus contacts: gold-plated
(only Monitored type)
Dimensions
– Width: 75 mm.
– Height: 65 mm.
– Feed cable: 3 m.
Color
– Enclosure: aluminum/RAL7021 dark-gray
Certification
– CE label in accordance with
Low Voltage Directive 2006/95/EC.
– EMC Directive 2004/108/EC.
– BV BG.
Scope of delivery
– 1 x MPX PEM power input module.
– Including connection cable.
– Including RPC2 communication card
(only Monitored type).
L
W
H
Feed
Load rating
Type
Order No.
UP
220
75
65
Fixed
230 VAC, max. 32 A
Elementary
MPXPEM-EHAEXQ30
1 unit
220
75
65
Fixed
230/400 VAC, max. 16 A
Elementary
MPXPEM-EHAEXT30
1 unit
220
75
65
Fixed
230/400 VAC, max. 32 A
Elementary
MPXPEM-EHAEXR30
1 unit
266
75
65
Fixed
230/400 VAC, max. 63 A
Elementary
MPXPEM-EHBEXZ30
1 unit
220
75
65
Fixed
230VAC,max.16A
Monitored
MPXPEM-EHABXS30
1 unit
220
75
65
Fixed
230 VAC, max. 32 A
Monitored
MPXPEM-EHABXQ30
1 unit
220
75
65
Fixed
230/400 VAC, max. 16 A
Monitored
MPXPEM-EHABXT30
1 unit
220
75
65
Fixed
230/400 VAC, max. 32 A
Monitored
MPXPEM-EHABXR30
1 unit
266
75
65
Fixed
230/400 VAC, max. 63 A
Monitored
MPXPEM-EHBBXZ30
1 unit
Conversion:
W = Width
n = Number of sockets
H = Height
F1 = Standard side panel
L = Length
F2 = Design side panel
S = Switch
19" = ideal for 19" components
U
= Standard rack unit
1 U = 44.45 mm
1 mm = 0.03937 inch
1 kg = 2.2046 pounds
UP = Packaging unit
Safe = child-proof
Replace .x with the number of the color combination you require: .1 = RAL 7035, .6 = RAL 7035/RAL 2003
Rack PDUs | 227
MPX™
MPX™ BRM – Output Module
–The MPX BRM enables the distribution
to the individual consumers.
–Each module taps a color-coded phase.
–All modules are protected against overload
with a 20 A circuit breaker.
–Modules can be exchanged during operation
thereby facilitating user-specific installation
without having to shut down the MPX.
–Up to 3 BRM output modules can be installed on
a 1,035 mm PRC busbar; up to 6 BRM output
modules can be installed on a 1,880 mm PRC
busbar.
DOS20153
Type E – Elementary
–Module for power distribution via respective
outputs.
Type B – Branch-Monitored
–Module for power distribution via respective
outputs with metering function on module
level.
–The MPX BRMs have LED ID indicator which
identifies every module with a number.
–Modules are administered in the software.
–Provides the following metered readings:
voltage, current, power, apparent power, kWh
and power factor.
–Power alarm functions and operating status are
supported.
Type R – Receptacle Managed:
–Module for power distribution via respective
outputs with metering function on module level
and output level.
–The MPX BRMs have LED ID indicator which
identifies every module with a number.
–Modules are administered in the software.
–Provides the following metered readings:
voltage, current, power, apparent power, kWh,
frequency, power factor and crest factor.
–Power alarm functions and operating status are
supported.
–Individual outputs can be switched on and off
remotely.
228 | Rack PDUs
M
aterial / Finish
– Enclosure: aluminum.
– Cover: sheet steel.
– Power contacts: sliver-plated.
–D
atabus contacts: gold-plated
(only type B and R).
Dimensions
– Width: 75 mm.
– Height: 65 mm.
Color
– Enclosure: aluminum/RAL7021 dark-gray
Certification
– CE label in accordance with Low Voltage
Directive 2006/95/EC.
– EMC Directive 2004/108/EC.
– BV BG.
Scope of delivery
– 1 x MPX PEM power output module.
– 1 x instruction manual.
L
n
Outputs
Load rating per output
Phase tap
Type Order No.
UP
266
7
IEC320 C 13
10 A
L1
E
MPXBRM-EEBC7N1N
1 unit
266
7
IEC320 C 13
10 A
L2
E
MPXBRM-EEBC7N2N
1 unit
266
7
IEC320 C 13
10 A
L3
E
MPXBRM-EEBC7N3N
1 unit
266
4
IEC320 C 19
16 A
L1
E
MPXBRM-EEBC4O1N
1 unit
266
4
IEC320 C 19
16 A
L2
E
MPXBRM-EEBC4O2N
1 unit
266
4
IEC320 C 19
16 A
L3
E
MPXBRM-EEBC4O3N
1 unit
266
3
Schuko CEE 7/4
16 A
L1
E
MPXBRM-EEBC3P1N
1 unit
266
3
Schuko CEE 7/4
16 A
L2
E
MPXBRM-EEBC3P2N
1 unit
266
3
Schuko CEE 7/4
16 A
L3
E
MPXBRM-EEBC3P3N
1 unit
266
4
Switzerland T23
16 A
L1
E
MPXBRM-EEBC4S1N
1 unit
266
4
Switzerland T23
16 A
L2
E
MPXBRM-EEBC4S2N
1 unit
266
4
Switzerland T23
16 A
L3
E
MPXBRM-EEBC4S3N
1 unit
266
9
GST18 3-pole
16 A
L1
E
MPXBRM-EEBC9U1N
1 unit
266
9
GST18 3-pole
16 A
L2
E
MPXBRM-EEBC9U2N
1 unit
266
9
GST18 3-pole
16 A
L3
E
MPXBRM-EEBC9U3N
1 unit
266
6
IEC320 C 13
10 A
L1
B
MPXBRM-EBBC6N1N
1 unit
266
6
IEC320 C 13
10 A
L2
B
MPXBRM-EBBC6N2N
1 unit
266
6
IEC320 C 13
10 A
L3
B
MPXBRM-EBBC6N3N
1 unit
266
4
IEC320 C 19
16 A
L1
B
MPXBRM-EBBC4O1N
1 unit
266
4
IEC320 C 19
16 A
L2
B
MPXBRM-EBBC4O2N
1 unit
266
4
IEC320 C 19
16 A
L3
B
MPXBRM-EBBC4O3N
1 unit
266
3
Schuko CEE 7/4
16 A
L1
B
MPXBRM-EBBC3P1N
1 unit
266
3
Schuko CEE 7/4
16 A
L2
B
MPXBRM-EBBC3P2N
1 unit
266
3
Schuko CEE 7/4
16 A
L3
B
MPXBRM-EBBC3P3N
1 unit
266
6
IEC320 C 13
10 A
L1
R
MPXBRM-ERBC6N1N
1 unit
266
6
IEC320 C 13
10 A
L2
R
MPXBRM-ERBC6N2N
1 unit
266
6
IEC320 C 13
10 A
L3
R
MPXBRM-ERBC6N3N
1 unit
266
4
IEC320 C 19
16 A
L1
R
MPXBRM-ERBC4O1N
1 unit
266
4
IEC320 C 19
16 A
L2
R
MPXBRM-ERBC4O2N
1 unit
266
4
IEC320 C 19
16 A
L3
R
MPXBRM-ERBC4O3N
1 unit
266
3
Schuko CEE 7/4
16 A
L1
R
MPXBRM-ERBC3P1N
1 unit
266
3
Schuko CEE 7/4
16 A
L2
R
MPXBRM-ERBC3P2N
1 unit
266
3
Schuko CEE 7/4
16 A
L3
R
MPXBRM-ERBC3P3N
1 unit
MPX™
MPX™ PRC – Power Distribution Unit / Communication Bus
–The MPX PRC is the basic element of the
MPX power distribution unit.
–Power and data transfer buses are integrated
across the entire length of the MP PRC.
–The MPX BRMs (output modules) and the MPX
PEM (power input module) are fixed on the MPX
PRC and, depending on the type, facilitate the
modules' power feed, output, monitoring and
management.
Material / Finish
– Busbar housing: aluminum.
– Busbars: copper.
– Databus: gold-plated.
Approvals
– CE label in accordance with Low Voltage
Directive 2006/95/EC.
– EMC Directive 2004/108/EC.
– BV BG.
Load rating
– Max. current: 3 x 63 A.
– Nominal voltage (L-N / L-L): 230 / 400 VAC.
Scope of delivery
– 1 x MPX PRC - power distribution unit /
communication bus.
– 1 x mounting kit.
Dimensions
– Width: 68 mm.
– Height: 24 mm.
DOS20153
Color
– Enclosure: aluminum.
L
W
H
U
Model
Order No.
UP
1035
68
24
23
1 PEM (220 mm) + 3 BRM
MPXPRC-V1035XXX
1 unit
42
1880
68
24
2144
68
24
1 PEM (220/266 mm) + 6 BRM
MPXPRC-V1880XXX
1 unit
1 PEM (220/266 mm) +7 BRM
MPXPRC-V2146XXX
1 unit
MPX™/MPH™/MPH2™/IMS™ – Sensors
DOS20153
–These sensors are designed for tool-less
installation in a Knürr Miracle / DCM rack, and is
also compatible with all other rack types.
–"Fixed" type sensors are attached to a cable.
–"Modular" type sensors can be connected to the
delivered cable.
–Plugged into the RPC-1000 or RPC2
communication card.
–Several sensors can be connected in rows.
–Automatically displayed in the MPX/MPH/
MPH2/IMS software.
–Temperature measurement range: 5 – 60° C.
–Accuracy: ± 0.5° C.
–Humidity measurement range: 10 – 95 %.
–Accuracy: ± 3.5 %.
Note
Sensors are not required for operating the MPX
or MPH, MPH2, IMS. However, a communication
card is needed.
Scope of delivery
– 1 x sensor with connection cable.
– 1 x instruction manual.
Cable length Type
Model
Order No.
UP
3660
Fixed
Temperature sensor, single
SN-Z01
1 unit
5180
Fixed
Temperature sensor, triple
SN-Z02
1 unit
5180
Fixed
Temperature sensor, triple + humidity sensor, single
SN-Z03
1 unit
2000
Modular
Temperature sensor, single
SN-T
1 unit
2000
Modular
Temperature sensor, single + humidity sensor, single
SN-TH
1 unit
2000
Modular
2 x door contact - input module*
SN-2D
1 unit
2000
Modular
3 x digital input
SN-3C
1 unit
* Suitable door contact switch: Order no.: 06.108.115.9
Rack PDUs | 229
MPX™
RPC BDM - 1000 Display Module
DOS20153
–Provides the local display of the monitored
data for all connected MPX/MPH/MPH2/IMS
systems.
–Operated with a navigation switch.
–Connected via a cable with the RPC, enabling
the user to place the displays where they can be
easily read in the given local space conditions.
–An individual display can be used for up to
four MPX/MPH/MPH2/IMS PDUs, which are all
connected in a PDU array.
Note
The display module is not required when
operating the MPX or MPH, MPH2, IMS.
However, a communication card is needed.
Scope of delivery
– 1 x RPCBDM-1000 display module.
– 1 x connection cable 2 m.
– 1 x mounting kit.
Order No.
UP
RPCBDM-1000
1 unit
BRM Power-Distribution Cable-Holder Clip Set
DOS20444
–Cable clips provide strain relief
for the feed lines of the network equipment.
–Cable clips are suitable for most IEC-C13 socket
plugs with a raised edge. (Must be checked for
suitability).
–Cable clips are sold in sets of 18 units.
Scope of delivery
– 1 x cable holder set (18 units).
How supplied
– In sets.
Note
– Optimal function only with cable connector
04.000.051.9.
– Can only be used with MPXBRM-EBBC6NxN
and MPXBRM-ERBC6NxN (x = 1 ,2, 3).
Order No.
UP
03.910.216.9
1 unit
Model
Order No.
UP
C20 plug in C19 socket
03.910.212.9 001
20 unit
Model
Order No.
UP
C14 plug in C13 socket
03.910.213.9 001
50 unit
395
SafetySleeve™ Cable Protection IEC C19
– SafetySleeves protect the feed lines of the
network equipment.
–They can be used on all C19 cables and fit onto
all PDUs.
DOS20493
Material / Finish
– PVC, black.
SafetySleeve™ Cable Protection IEC C13
– SafetySleeves protect the feed lines of the
network equipment.
–They can be used on all C13 cables and fit onto
all PDUs.
Material / Finish
– PVC, black.
DOS20494
230 | Rack PDUs
RPC2
RPC2 Communication Module for MPX, MPH2 and IMS
–For retrofitting to existing MPX , MPH and IMS
products.
–The communication card can be upgraded
during operation.
RPC2-KIT
Technical Data Interfaces
–R
J-45 LAN port (10/100 MBit) – for local
network (LAN) connection via an Ethernet
cable.
– E xpansion / administration port for local
configuration using a computer / laptop,
for creating a link-up of several PDUs
(MPX, MPH2 or IMS).
– S erial interface RS232.
– Display port for connecting the RPC BDM
(display module).
– External sensor port for connecting optional
sensors.
– Remote management: Onboard Web
interface, CLI, SNMPv1,2,3, SSH, Telnet Syslog,
compatible with Avocent ACS, UMG & MPU,
SiteScan, DSView, Rack Power Manager,
Nform & Trellis as well as Nagios or other
management software programs.
– Authentication: local, remote: Active
Directory, LDAP, TACACS, Radius, Kerberos.
– Encryption: MD5, AES, DES.
Order No.
UP
RPC2-KIT
1 unit
Rack PDUs | 231
MPH2™
MPH2™ – Managed Rack PDU
Monitoring and Control
The MPH2™ Managed Rack PDU is a power supply system with monitoring and control functions. The MPH2™
offers outstanding features such as easy rack-integration and management architecture as well as optimum
availability and energy efficiency.
Four MPH2™ versions are available:
Model/functions
MPHR
MPHM
MPHC
MPHB
Input / Group measurement
Output measurement
Output switching
Benefits of MPH2™
Monitors several parameters with defined thresholds
and alarm tools.
Monitors and controls individual outputs
and/or load and appliance groups.
A variety of measurements allow you to predict failing
conditions before they occur and proactively manage
connected equipment for maximum uptime.
Energy and power metering maximize the data center
power and cooling infrastructure.
Lowest power consumption of all switched-rack PDUs
lowers power costs and thermal load.
Up to four rack MPH2™ PDUs can be connected in a
Rack PDU Array™ thereby consolidating user-specific IP
connections and equipment monitoring.
MPH2™ savings for a typical data center
Typical rack PDU
with 24 outputs
MPH2™
Power consumption of PDU
(in Watt)
20
5
Annual energy consumption
of PDU (kWh)
176
44
Total proportion of the data center's energy consumption (kWh)*
333
83
Energy saving
75 %
Compared with a Switched Rack-PDU model
for a typical data center with a 1.9 PUE.
* according to Energy Logic calculations
Developed for critical environments
Industry-leading operating temperature of up to
60° C suitable for high temperatures inside racks.
Bistable relays ensure basic power supply even when
shortfalls occur elsewhere.
Accurate voltage and current metering up to outlet
level with ±1 % tolerances deliver reliable results.
Extensive alarm functions including notification when
an overload occurs in individual groups.
Monitoring of environment conditions
(temperature, humidity and input contacts) with
alerts and alarms.
Notification upon failure or if loads are removed in
individual racks.
kWh
333
75 % cost saving
83
Typical rack PDU
232 | Rack PDUs
MPH2TM
MPH2™
INPUT POWER
16 to 32 A (EU).
Single-phase and three-phase.
OUTPUT DISTRIBUTOR
IEC C13 and IEC C19.
Combination systems.
MODULARITY
Communication card.
External display.
External sensors.
MONITORING
Three various levels: Input level, group level,
output level
Temperature and humidity.
Door contacts and potential-free input contacts.
REMOTE CONTROLLED SOCKETS
Socket level.
MPH2™
MPH2™
Benefits
Highest availability levels
Modular communications card; can be replaced during
operation. This simplifies maintenance and increases
the level of availability.
Bistable relays in switchable designs; the server's power
supply is ensured even during outages.
Software-controlled overload protection – affected
outputs are switched off before the advance fuse is
activated.
Additional metering of the neutral conductor and of
the crest factor; possible faults that cause switch-off are
detected in advance.
Leading technology in many areas
Operating temperatures of up to 60 °C allow secure
operation in the warm aisle.
Metering accuracy of ± 1 % ensures reliable
measurement results.
Power losses of approx. 5 W, even in switchable models,
reducing electricity costs and minimizing the thermal
load.
234 | Rack PDUs
Industry-leading management properties
An integrated local display and an optional external
display facilitates flexible local management.
Onboard web interface and CLI/SSH interface; suitable
for both Windows and Linux administration.
A variety of authentication options and encrypted
protocols ensure integration into Enterprise Security
architectures.
SNMPv3 and IPv6 support so that current requirements,
particularly from the public sector, can be satisfied.
Simple integration into ENP solutions
Can be delivered pre-installed in Knürr racks to save
time and costs during installation in the data center.
Serial integration into Avocent UMG, ACS and MPU
guarantees redundant management access to the
MPH2.
Integration into ENP software solutions; the MPH2 is an
integral part of a comprehensive DCIM solution with
monitoring and control functions.
MPH2™
Colored clamps:
Colored labeling of supply.
Special tool-less Knürr DCM rack
fixture:
Lowers installation costs and extra space in
rack for cables and other components.
Communications module (RPC2™):
Offers extendable interfaces for network
communication, sensors and local display.
BDM™ local display module
Extended diagnostic functionality;
user-friendly display. Features include
detailed information about alerts and
specific labeling for outputs.
Connection cable with locking mechanism
Prevents IT cables from being accidentally
disconnected.
SN sensors:
Consolidates environmental monitoring of
temperature, humidity and potential-free input
contacts with the power supply at rack level.
Integrated display:
Provides easy access to important
information on the rack.
Ultra-flat circuit breakers:
Compact construction; minimizes
space requirements in the rack.
Flexible network cable input:
Simplifies installation in the rack PDU.
Cable and fixed wiring options:
Flexible power distribution; input-cable
can be connected locally.
Rack PDUs | 235
RPC2
Easy Integration into DCIM Systems
The rack PDUs MPH2™ and MPX™ as well as the in-line metering system MPXIMS™ can be managed both locally
and remotely.
Power data and sensor data are recorded
Conventional standardized protocols are used to ensure secure data transfer, management, and authentication.
As such, the products can be easily integrated into any existing network and any system architecture.
Flexible Local or Remote Management
Integrated standard displays on the DiStrip RM and
MPH2™ show all the key information required at the rack.
The optional local display BDM for the MPH2™ or MPX™
can be mounted in different locations depending on where
it can be read most easily.
Remote communication thanks to the modular hotswappable RPC2™ card ensures seamless expansion
options and easy servicing
S
upport for up to four PDUs within a single rack
PDU Array™: Minimizes the number of IP addresses
required.
S
upport for up to ten ambient sensors: Consolidates
power and environment monitoring at rack level.
S
upport for Web UI and CLI, with SSL and SSH:
Windows, Linux, and network administrators can use
their preferred form of communication with the rack
PDU.
S
upport for all conventional remote authentication
and encryption protocols: Products can be seamlessly
integrated into an existing security infrastructure.
S
upport for SNMP v1, v2, and v3: Allows for secure
communication via network management systems.
S
upport for IPv4 and IPv6: Future-proof IP support
for rack PDUs.
D
ata logging: All data is saved automatically, ensuring
easy troubleshooting without the need for additional
external management software.
236 | Rack PDUs
Power management with the following functions:
S
napshot of all electrical parameters at output, group,
phase, and general level.
S
napshot of the status and the measured values from
the ambient sensor.
T
hreshold configuration, alerts, and messages.
C
ontrol of individual outputs and groups.
S
tatus information and configuration of all outputs.
N
etwork management settings.
To enable central management of all rack PDUs within a
data center, the following software packages are available:
A
vocent Rack Power Manager, which includes access
and control functions to easily manage and monitor
your PDUs.
T
rellis Express, which provides a comprehensive view of
the devices in the data center.
L iebert Sitescan.
L iebert NFORM, which provides an overview of the
health status of relatively small to medium data centers.
Rack Power Manager boasts state-of-the-art monitoring
functions and allows intelligent server grouping over
multiple racks. You also benefit from customized reports
and scheduled standard reports, and have the option to
define thresholds for real-time alarms. As such, you obtain
high-quality information about the power supply
infrastructure of your data center, thereby allowing you to
make full use of the investment in PDUs.
RPC2
P
ower costs are measured and monitored.
H
istorical data is checked in capacity and consumption
reports.
The Trellis™ platform is a pioneering DCIM innovation
from Emerson Network Power. It not only reduces IT risks
but also increases operational efficiency, meaning it solves
current problems and prepares you for the future.
The real-time visualization, monitoring of the power
supply, and mobile access provided by the Trellis™
platform allow you to:
r educe inefficiencies without interrupting current
processes.
p
ostpone investments as you make better use of
existing resources, thereby improving the operating
profit.
i mprove Service Level Agreements with complete
transparency throughout the infrastructure.
g
ain a better insight into the data center and thus i
mprove overall efficiency.
Integration into the clear, easy-to-install Liebert NFORM
status monitoring software ensures the following:
R
ack PDUs are part of a consolidated monitoring
solution for data center infrastructure.
V
irtually any component in critical support equipment
can be monitored.
A
lerts and automatic actions in the event of a fault.
E vent management.
Integration into the scalable Liebert SiteScan® building
infrastructure management software ensures the
following:
R
ack PDUs are part of a consolidated monitoring
solution for data center infrastructure.
V
irtually any component in critical support equipment
can be monitored and controlled.
D
ata analysis and trend reports.
E vent management.
Make the Most of Your Rack PDU Investment
The rack PDUs MPX™, MPH2™, and MPXIMS™ can be fully integrated into the industry-leading KVM systems,
serial consoles, and infrastructure management systems from Emerson Network Power.
Integration into Avocent® Advanced Console Server,
MergePoint™ Unity KVM Switches and Universal
Management Gateway Appliances offers the following
advantages:
Rack PDUs are integrated into the out-of-band
management solution.
Rack PDUs become part of a consolidated
access and control solution.
The number of IP addresses required for
managing the rack PDUs is minimized.
DSView4 and rack PDUs together ensure:
Consolidated access to server control and the related access
control.
Easy assignment of IT equipment to the relevant rack PDU
outputs.
Integration into the management software
Avocent DSView™ 4, in which all data center
management functions are compiled on a
consolidated interface, allows for seamless
control of the data center for 24/7 operation.
The software provides secure, centralized out-ofband management of all connected IT and network
devices in complex and geographically dispersed data centers.
Rack PDUs | 237
MPH2™
MPH2™
– The MPH2 is a power distribution unit for
IT racks which provides metering of electrical
values. Depending on the model, individual
outputs can also be remote-controlled.
–The integrated RPC2 communications card
allows you to connect up to 4 MPH2 / MPX™
units as well as monitor and maintain all
connected units remotely. Up to 10 sensors
(temperature, air humidity, door contacts as
well as potential-free input contacts) can be
connected.
–The MPH2™ unit has an integrated display. In
addition, the optional external RPCBDM-1000
display module can easily be connected and
mounted on the rack.
–Special cables with locking mechanisms can be
connected to the outputs.
–Depending on the model, the connecting cable
for the MPH2 is attached to the housing (cable
length 3 m), also permitting a connecting cable
can be connected on site (model with connection unit).
MPH2™ Types
for Europe
Material / finish / color
– Closed housing, aluminum profile, finely
textured powder-coated top (RAL 7021),
Vampamid 6 0024 V0 (UL94) recyclable
plastic parts, finely textured and colored
(RAL 9005).
–Remote management: Onboard Web Interface,
CLI, SNMPv1,2,3, SSH, Telnet, integratable into
Avocent ACS, UMG & MPU, DSView, Rack Power
Manager, Nform & Trellis as well as Nagios or
other management software programs.
–Authentication: local, remote:
active directory, LDAP, TACACS, Radius, Kerberos. Encryption: MD5, AES, DES.
–Measurement parameters: Current (A), voltage
(V), real power (W), apparent power (VA),
consumption (kWh), power factor, frequency
and crest factor (only tapes M and R).
Accuracy: ±1 % (V, A).
Mechanical dimensions
– Vertical models:
Width x Depth x Length (mm):
56 x 50 x (see table).
– Horizontal models:
Width x Depth x Length (mm):
482,6 (440) x 250 x 44.
MPH2™ models
–M
PH2™ B – Metering per phase and per
group (only models with >16 A input power).
–M
PH2™ C – Metering per phase and per
group (only models with >16 A input power).
Each output can also be individually switched
remotely.
–M
PH2™ M – Metering per phase and per
group (only models with >16 A input power)
and per output.
–M
PH2™ R – Metering per phase and per
group (only models with >16 A input power)
and per output. Each output can also be
individually switched remotely.
Certification
– CE label in accordance with
Low Voltage Directive 2006/95/EC.
– EMC Directive 2004/108/EC.
– BV BG.
Model/functions
Scope of delivery
– MPH2™ rack PDU.
– Standard mounting bracket.
– Safety instructions.
– Quickstart guide.
MPHR
MPHM
MPHC
MPHB
Input / Group measurement
Output measurement
Output switching
Vertical models
Type
Input Values
Voltage
Input Connector
Current
Outputs
Length
C13
C19
(mm)
2
916.5
B
230V
16A
C20 inlet
17
B
230V
16A
C20 inlet
21
B
230V
16A
C20 inlet
30
6
2
B
230V
16A
IEC 60309 16A 1P+N+G
17
B
230V
16A
IEC 60309 16A 1P+N+G
21
Order Number
MPHB3241
916.5
MPHB3141
1736.5
MPHB1241
916.5
MPHB3242
916.5
MPHB3142
B
230V
16A
IEC 60309 16A 1P+N+G
30
6
1736.5
MPHB1242
B
230V
32A
IEC 60309 32A 1P+N+G
30
6
1736.5
MPHB1243
B
230V
32A
Connection unit
30
6
1736.5
MPHB1260
B
230/400V
3 x 16A
IEC 60309 16A 3P+N+G
30
6
1736.5
MPHB1244
1826.5
MPHB1545
1826.5
MPHB1345
B
230/400V
3 x 32A
IEC 60309 32A 3P+N+G
42
B
230/400V
3 x 32A
IEC 60309 32A 3P+N+G
18
12
6
B
230/400V
3 x 32A
IEC 60309 32A 3P+N+G
30
B
230/400V
3 x 32A
Connection unit
42
1826.5
MPHB1245
1826.5
MPHB1562
B
230/400V
3 x 32A
Connection unit
18
12
1826.5
MPHB1362
B
230/400V
3 x 32A
Connection unit
30
6
1826.5
MPHB1262
MPHC3341
C
230V
16A
C20 inlet
8
916.5
C
230V
16A
C20 inlet
16
1004
MPHC3141
C
230V
16A
C20 inlet
18
6
1736.5
MPHC1141
1736.5
MPHC1241
6
1736.5
MPHC1142
MPHC1242
C
230V
16A
C20 inlet
24
C
230V
16A
IEC 60309 16A 1P+N+G
18
C
230V
16A
IEC 60309 16A 1P+N+G
24
1736.5
C
230V
16A
IEC 60309 16A 1P+N+G
16
1004
MPHC3142
C
230V
32A
IEC 60309 32A 1P+N+G
18
1736.5
MPHC1143
238 | Rack PDUs
6
MPH2™
Type
Input Values
Voltage
Input Connector
Current
Outputs
C13
C
230V
32 A
IEC 60309 32 A 1P+N+G
24
C
230V
32 A
Connection unit
18
C
230V
32 A
Connection unit
24
C
230/400V
3 x 16 A
IEC 60309 16 A 3P+N+G
18
C
230/400V
3 x 16 A
IEC 60309 16 A 3P+N+G
24
C
230/400V
3 x 16 A
Connection unit
18
C
230/400V
3 x 16 A
Connection unit
24
C
230/400V
3 x 32 A
IEC 60309 32 A 3P+N+G
18
Length
Order Number
C19
(mm)
1736.5
MPHC1243
6
1736.5
MPHC1160
1736.5
MPHC1260
6
1736.5
MPHC1144
1736.5
MPHC1244
6
1736.5
MPHC1161
1736.5
MPHC1261
6
1736.5
MPHC1145
1736.5
MPHC1245
1736.5
MPHC1345
C
230/400V
3 x 32 A
IEC 60309 32 A 3P+N+G
24
C
230/400V
3 x 32 A
IEC 60309 32 A 3P+N+G
6
12
6
C
230/400V
3 x 32 A
Connection unit
18
C
230/400V
3 x 32 A
Connection unit
24
C
230/400V
3 x 32 A
Connection unit
6
1736.5
MPHC1362
M
230V
16 A
C20 inlet
8
916.5
MPHM3341
MPHM3342
12
1736.5
MPHC1162
1736.5
MPHC1262
M
230V
16 A
IEC 60309 16 A 1P+N+G
8
916.5
M
230V
16 A
C20 inlet
16
1004
MPHM3141
M
230V
16 A
C20 inlet
18
6
1736.5
MPHM1141
1736.5
MPHM1241
6
1736.5
MPHM1142
MPHM1242
M
230V
16 A
C20 inlet
24
M
230V
16 A
IEC 60309 16 A 1P+N+G
18
M
230V
16 A
IEC 60309 16 A 1P+N+G
24
1736.5
M
230V
16 A
IEC 60309 16 A 1P+N+G
16
1004
MPHM3142
M
230V
32 A
IEC 60309 32 A 1P+N+G
18
6
1736.5
MPHM1143
1736.5
MPHM1243
6
1736.5
MPHM1160
1736.5
MPHM1260
6
1736.5
MPHM1144
1736.5
MPHM1244
6
1736.5
MPHM1161
1736.5
MPHM1261
6
1736.5
MPHM1145
1736.5
MPHM1245
1736.5
MPHM1345
M
230V
32 A
IEC 60309 32 A 1P+N+G
24
M
230V
32 A
Connection unit
18
M
230V
32 A
Connection unit
24
M
230/400V
3 x 16 A
IEC 60309 16 A 3P+N+G
18
M
230/400V
3 x 16 A
IEC 60309 16 A 3P+N+G
24
M
230/400V
3 x 16 A
Connection unit
18
M
230/400V
3 x 16 A
Connection unit
24
M
230/400V
3 x 32 A
IEC 60309 32 A 3P+N+G
18
M
230/400V
3 x 32 A
IEC 60309 32 A 3P+N+G
24
M
230/400V
3 x 32 A
IEC 60309 32 A 3P+N+G
6
12
6
M
230/400V
3 x 32 A
Connection unit
18
M
230/400V
3 x 32 A
Connection unit
24
12
1736.5
MPHM1162
1736.5
MPHM1262
1736.5
MPHM1362
M
230/400V
3 x 32 A
Connection unit
6
R
230V
16 A
C20 inlet
8
916.5
MPHR3341
R
230V
16 A
IEC 60309 16 A 1P+N+G
8
916.5
MPHR3342
R
230V
16 A
C20 inlet
16
R
230V
16 A
C20 inlet
18
R
230V
16 A
C20 inlet
24
R
230V
16 A
IEC 60309 16 A 1P+N+G
18
R
230V
16 A
IEC 60309 16 A 1P+N+G
R
230V
16 A
R
230V
R
R
1004
MPHR3141
1736.5
MPHR1141
1736.5
MPHR1241
1736.5
MPHR1142
24
1736.5
MPHR1242
IEC 60309 16 A 1P+N+G
16
1004
MPHR3142
32 A
IEC 60309 32 A 1P+N+G
18
1736.5
MPHR1143
230V
32 A
IEC 60309 32 A 1P+N+G
24
230V
32 A
Connection unit
18
R
230V
32 A
Connection unit
24
R
230/400V
3 x 16 A
IEC 60309 16 A 3P+N+G
18
R
230/400V
3 x 16 A
IEC 60309 16 A 3P+N+G
24
R
230/400V
3 x 16 A
Connection unit
18
6
6
6
1736.5
MPHR1243
6
1736.5
MPHR1160
1736.5
MPHR1260
6
1736.5
MPHR1144
6
1736.5
MPHR1244
1736.5
MPHR1161
1736.5
MPHR1261
1736.5
MPHR1145
1736.5
MPHR1245
R
230/400V
3 x 16 A
Connection unit
24
R
230/400V
3 x 32 A
IEC 60309 32 A 3P+N+G
18
R
230/400V
3 x 32 A
IEC 60309 32 A 3P+N+G
24
R
230/400V
3 x 32 A
IEC 60309 32 A 3P+N+G
6
12
1736.5
MPHR1345
R
230/400V
3 x 32 A
Connection unit
18
6
1736.5
MPHR1162
1736.5
MPHR1262
12
1736.5
MPHR1362
R
230/400V
3 x 32 A
Connection unit
24
R
230/400V
3 x 32 A
Connection unit
6
6
Rack PDUs | 239
Emerson Network Power Rack PDUs
Hotizontal models
Type
Input Values
Voltage
Input Connector
Current
Outputs
C13
B
230V
16 A
C20 inlet
12
B
230V
16 A
C20 inlet
8
B
230V
32 A
IEC 60309 32A 1P+N+G
12
B
230V
32 A
IEC 60309 32A 1P+N+G
8
Order Number
C19
MPHB2141
2
MPHB2341
2
MPHB2343
MPHB2244
MPHB2143
B
230/400V
3 x 16 A
IEC 60309 16A 3P+N+G
12
B
230/400V
3 x 16 A
IEC 60309 16A 3P+N+G
2
6
B
230/400V
3 x 32 A
IEC 60309 32A 3P+N+G
2
6
M
230V
16 A
C20 inlet
9
M
230V
16 A
C20 inlet
6
M
230V
32 A
IEC 60309 32A 1P+N+G
9
M
230V
32 A
IEC 60309 32A 1P+N+G
6
M
230/400V
3 x 16 A
IEC 60309 16A 3P+N+G
9
MPHB2144
MPHB2245
MPHM2141
2
MPHM2441
MPHM2143
2
MPHM2443
MPHM2144
M
230/400V
3 x 16 A
IEC 60309 16A 3P+N+G
2
6
MPHM2344
M
230/400V
3 x 32 A
IEC 60309 32A 3P+N+G
2
6
MPHM2345
2
MPHR2441
2
MPHR2443
R
230V
16 A
C20 inlet
9
R
230V
16 A
C20 inlet
6
R
230V
32 A
IEC 60309 32A 1P+N+G
9
R
230V
32 A
IEC 60309 32A 1P+N+G
6
MPHR2141
MPHR2143
R
230/400V
3 x 16 A
IEC 60309 16A 3P+N+G
9
R
230/400V
3 x 16 A
IEC 60309 16A 3P+N+G
2
6
MPHR2344
R
230/400V
3 x 32 A
IEC 60309 32A 3P+N+G
2
6
MPHR2345
240 | Rack PDUs
MPHR2144
MPH2™
MPX™/MPH™/MPH2™/IMS™ – Sensors
DOS20153
–These sensors are designed for tool-less
installation in a Knürr Miracle / DCM rack, but
is also compatible with all other rack types.
–"Fixed" type sensors are attached to a cable.
–"Modular" type sensors can be connected to the
delivered cable.
–Plugged into the RPC-1000 or RPC2
communication card.
–Several sensors can be connected in rows.
–Automatically displayed in the MPX/MPH/
MPH2/IMS software.
–Temperature measurement range: 5 – 55° C.
–Accuracy: ± 0.5° C.
–Humidity measurement range: 10 – 95 %.
–Accuracy: ± 3.5 %.
Note
The sensors are not required for operating
the MPX or MPH, MPH2, IMS. However, a
communication card is needed.
Scope of delivery
– 1 x sensor with connection cable.
– 1 x instruction manual.
Cable length Type
Model
Order No.
UP
3660
Fixed
Temperature sensor, single
SN-Z01
1 unit
5180
Fixed
Temperature sensor, triple
SN-Z02
1 unit
5180
Fixed
Temperature sensor, triple + humidity sensor, single
SN-Z03
1 unit
2000
Modular
Temperature sensor, single
SN-T
1 unit
2000
Modular
Temperature sensor, single + humidity sensor, single
SN-TH
1 unit
2000
Modular
2 x door contact - input module*
SN-2D
1 unit
2000
Modular
3 x digital input
SN-3C
1 unit
* Suitable door contact switch: Order no.: 06.108.115.9
Liebert RPC BDM - 1000 Display Module
DOS20153
–Provides the local display of the monitored
data for all connected MPX/MPH/MPH2/IMS
systems.
–Operated with a navigation switch.
–Connected via a cable with the RPC, enabling
the user to place the displays where needed in
the given local space conditions.
–An individual display can be used for up to
four MPX/MPH/MPH2/IMS PDUs, which are all
connected in a PDU array.
Note
The display module is not required for operating
the MPX or MPH, MPH2, IMS. However, a
communication card is needed.
Scope of delivery
– 1 x RPCBDM-1000 display module.
– 1 x connection cable 2 m.
– 1 x mounting kit.
Order No.
UP
RPCBDM-1000
1 unit
Rack PDUs | 241
MPH2™
SafetyLock™ Connection Cable IEC C13 EU
– Connection cables have
integrated protection against
accidental disconnection.
–For straight locking from C14 to C13.
–Locking cables are sold in sets of 9 units.
Certification
– ENEC.
– VDE.
– CB scheme.
– RoHS compliant.
DOS20495
Technical data
– Standard: IEC 60320.
– Load rating: 250 Vac/10 A.
– Operating temperature: -25° C ~ +70° C.
– E xtraction force with locking function:
up to 120 N.
– Electric power cable: H05VV-F 3G 1.0 mm2.
– F lame retardance: Plug: UL 94V-2 or
better; cable: UL VW-1, IEC60332-1. Cat F2.
Color
– Black/white.
– Other colors available upon request.
Scope of delivery
– 9 x locking cables.
How supplied
– In sets.
DOS20496
L
Model
Order No.
UP
0.5 m
Black
03.951.450.0,001
9 unit
1.0 m
Black
03.951.450.0,002
9 unit
1.5 m
Black
03.951.450.0,003
9 unit
0.5 m
White
03.951.451.0,001
9 unit
1.0 m
White
03.951.451.0,002
9 unit
1.5 m
White
03.951.451.0,003
9 unit
DOS20497
SafetyLock™ Connection Cable IEC C19 EU
– Connection cables have
integrated protection against
accidental disconnection.
– For straight locking from C20 to C19.
–Locking cables are sold in sets of 6 units.
Approvals
– ENEC.
– VDE.
– CB scheme.
– RoHS compliant.
DOS20498
Technical data
– Standard: IEC 60320.
– Load rating: 250 Vac/16 A.
– Operating temperature: -25° C ~ +70° C.
– E xtraction force with locking function:
up to 120 N.
– Electric power cable: H05VV-F 3G 1.5 mm2.
– F lame retardance: Plug: UL 94V-2 or
better; cable: UL VW-1, IEC60332-1. Cat F2.
Color
– Black/white.
– Other colors available upon request.
Scope of delivery
– 6 x locking cables.
How supplied
– In sets.
DOS20499
DOS20500
242 | Rack PDUs
L
Model
Order No.
UP
0.5 m
Black
03.951.455.0,001
6 unit
1.0 m
Black
03.951.455.0,002
6 unit
1.5 m
Black
03.951.455.0,003
6 unit
0.5 m
White
03.951.456.0,001
6 unit
1.0 m
White
03.951.456.0,002
6 unit
1.5 m
White
03.951.456.0,003
6 unit
MPH2™
SpeedMountKit MPH2, MPE
–Installation of the rack PDUs MPH2 and MPE
without tools in Knürr DCM and InstaRack racks.
DSC00236
Rack type
Rack height
Order No.
UP
DCM
H2000
039514050001
1 unit
DCM
H2200
039514050003
1 unit
InstaRack
H2000
039514050002
1 unit
InstaRack
H2200
039514050004
1 unit
Design/Color
Order No.
UP
Blue
03.951.476.0.001
20 unit
Red
03.951.476.0.002
20 unit
Yellow
03.951.476.0.003
20 unit
Green
03.951.476.0.004
20 unit
Orange
03.951.476.0.005
20 unit
MPH2 / MPE – Color Coding
– Option for color coding power supply A or B.
–Option for color coding the individual phases /
groups.
– Installation without tools on MPH2 and MPE.
MPH2 / MPE – Color Coding
Rack PDUs | 243
MPE
MPE – Rack PDU
Reliable power distribution for data centers
The MPE Rack PDU is a power distribution unit for data center applications. It provides all the necessary functions
of a rack-based power distribution unit and guarantees reliable power distribution. A broad range of IT devices
and other sensitive electrical loads can be connected to it.
The MPE offers you the highest level of availability for
your critical loads.
I ts high operating temperature of up to 60°C makes it
suitable for installation in hot aisles (area at the back of
the rack).
2
0 A overload switch for many 32 A models that prevents the overload switch from triggering prematurely
at high temperatures and during start-up peaks.
Output cable with disconnection protection to prevent the IEC60320 connection cable from being unintentionally disconnected.
Stable aluminum housing supports the mechanical
stability of the housing.
Extra-large wire cross-sectional area of the input cable;
in three-phase models, this makes it possible to subject
the neutral wire to greater loads in the event that the
loads are unbalanced.
244 | Rack PDUs
Simple physical and electrical installation helps to keep
costs down.
E merson Network Power supplies the PDUs preinstalled in racks which saves extra work on-site.
F lexible cable entry facilitates installation in the rack.
V
ery low unit profile – even in the overload switch area
– leaves maximum installation space for other components as well as more space for air supply in the rack.
M
odels with fixed connection facilitate customer-side
connection of the input cable for special requirements.
" SpeedMount" function for installation in Knürr DCM /
InstaRack saves time and money in on-site installation.
G
reat model variety with power supply from up to
three-phase 32 A and a number of different outputs –
including country-specific with Schuko plug, UK or Switzerland.
MPE
INPUT POWER
16 to 63A (EU).
Single-phase and three-phase.
OUTPUT DISTRIBUTOR
IEC-C13 and IEC-C19, Schuko, UK.
Combination systems.
MODULARITY
Input cable.
Rack PDUs | 245
MPE
MPE – Rack PDU
– The MPE Rack PDU is a power distribution
unit for data center applications. It provides
all the necessary functions of a rack-based
power distribution unit and guarantees reliable
power distribution. A broad range of IT devices
and other sensitive electrical loads can be
connected to it.
–Special cables with a locking function can be
connected to the outputs.
–Depending on the model, the connecting cable
of the MPH2 is securely attached to the housing
(length of input lead: 3 m) or a connection cable
can be connected directly on site (models with
connection block).
–The PDU can be installed without any tools in
ENP Knürr racks or other housing systems with
the corresponding mountings.
–For 32 A models, the individual groups are
protected by a 20 A circuit breaker (hydraulic,
magnetic).
–The maximum operating temperature is 60°C
(not for MPE-3345-002, this type has 6 x 16A
miniature circuit breaker).
MPE1345
Input values
Input plug
Voltage
Current
100-240 V
16 A
100-240 V
16A
230 V
C19
C20 inlet
18
3
C20 inlet
24
16 A
IEC 60309 16A 1P+N+G
18
230 V
16 A
IEC 60309 16A 1P+N+G
24
230 V
32A
IEC 60309 32 A 1P+N+G
36
6
24
6
230 V
32A
IEC 60309 32 A 1P+N+G
32A
IEC 60309 32 A 1P+N+G
230 V
32A
Hardwired
36
6
24
6
230 V
32A
Hardwired
230 V
32A
Hardwired
230/400 V
3 x 16 A
IEC 60309 16 A 3P+N+G
36
12
230/400 V
3 x 16 A
IEC 60309 16 A 3P+N+G
36
6
230/400 V
3 x 16 A
IEC 60309 16 A 3P+N+G
230/400 V
3 x 16 A
Hardwired
36
12
36
6
3 x 16 A
Hardwired
3 x 16 A
Hardwired
Standards
– CE conformity: LVD, including the applicable
harmonized standards.
– CB certification: IEC 60950-1 (2nd Ed.).
– BV-BG certification (factory inspected).
Lengths
Schuko
3
230 V
230/400 V
Mechanical dimensions
– Width x depth x length (mm)
56 x 50 x (see table).
Outputs
C13
230/400 V
Material / Surface / Color
– Closed housing, aluminum profile, upper
section powder-coated in RAL 7021 fine
structure, plastic parts Vampamid 60024 V0
(UL94) recyclable, dyed fine structure RAL
9005.
Order No.
(mm)
826,5
MPE-3141
826,5
MPE-3241
826,5
MPE-3142
826,5
MPE-3242
1736,5
MPE-1243
3
1736,5
MPE-1543
18
1736,5
MPE-1643
1736,5
MPE-1260
3
1736,5
MPE-1560
18
1736,5
MPE-1660
1736,5
MPE-1144
3
1736,5
MPE-1444
18
1736,5
MPE-1644
1736,5
MPE-1161
3
1736,5
MPE-1461
18
1736,5
MPE-1661
230/400V
3x32A
IEC 60309 32A 3P+N+G
6
826,5
MPE-3345-002
230/400 V
3 x 32 A
IEC 60309 32A 3P+N+G
36
6
1736,5
MPE-1245
230/400 V
3 x 32 A
IEC 60309 32A 3P+N+G
24
12
230/400 V
3 x 32 A
IEC 60309 32A 3P+N+G
24
6
230/400 V
3 x 32 A
IEC 60309 32A 3P+N+G
230/400 V
3 x 32 A
IEC 60309 32A 3P+N+G
48
230/400 V
3 x 32 A
Hardwired
36
6
230/400 V
3 x 32 A
Hardwired
24
12
230/400 V
3 x 32 A
Hardwired
24
6
230/400 V
3 x 32 A
Hardwired
230/400 V
3 x 32 A
Hardwired
246 | Rack PDUs
1736,5
MPE-1345
3
1736,5
MPE-1545
18
1736,5
MPE-1645
3
18
48
1736,5
MPE-1745
1736,5
MPE-1262
1736,5
MPE-1362
1736,5
MPE-1562
1736,5
MPE-1662
1736,5
MPE-1762
MPE
SafetyLock™ Connection Cable IEC C13 EU
– Connection cables have
integrated protection against
accidental disconnection.
–For straight locking from C14 to C13.
–Locking cables are sold in sets of 9 units.
Certification
– ENEC.
– VDE.
– CB scheme.
– RoHS compliant.
DOS20495
Technical data
– Standard: IEC 60320.
– Load rating: 250 Vac/10 A.
– Operating temperature: -25° C ~ +70° C.
– E xtraction force with locking function:
up to 120 N.
– Electric power cable: H05VV-F 3G 1.0 mm2.
– F lame retardance: Plug: UL 94V-2 or
better; cable: UL VW-1, IEC60332-1. Cat F2.
Color
– Black/white.
– Other colors available upon request.
Scope of delivery
– 9 x locking cables.
How supplied
– In sets.
DOS20496
L
Model
Order No.
UP
0.5 m
Black
03.951.450.0,001
9 unit
1.0 m
Black
03.951.450.0,002
9 unit
1.5 m
Black
03.951.450.0,003
9 unit
0.5 m
White
03.951.451.0,001
9 unit
1.0 m
White
03.951.451.0,002
9 unit
1.5 m
White
03.951.451.0,003
9 unit
DOS20497
SafetyLock™ Connection Cable IEC C19 EU
– Connection cables have
integrated protection against
accidental disconnection.
– For straight locking from C20 to C19.
–Locking cables are sold in sets of 6 units.
Approvals
– ENEC.
– VDE.
– CB scheme.
– RoHS compliant.
DOS20498
Technical data
– Standard: IEC 60320.
– Load rating: 250 Vac/16 A.
– Operating temperature: -25° C ~ +70° C.
– E xtraction force with locking function:
up to 120 N.
– Electric power cable: H05VV-F 3G 1.5 mm2.
– F lame retardance: Plug: UL 94V-2 or
better; cable: UL VW-1, IEC60332-1. Cat F2.
Color
– Black/white.
– Other colors available upon request.
Scope of delivery
– 6 x locking cables.
How supplied
– In sets.
DOS20499
L
Model
Order No.
UP
0.5 m
Black
03.951.455.0,001
6 unit
1.0 m
Black
03.951.455.0,002
6 unit
1.5 m
Black
03.951.455.0,003
6 unit
0.5 m
White
03.951.456.0,001
6 unit
1.0 m
White
03.951.456.0,002
6 unit
1.5 m
White
03.951.456.0,003
6 unit
DOS20500
Rack PDUs | 247
DI-STRIP®
DI-STRIP® – Basic Rack-PDU
Robust PDUs with useful equipment features
Features
Closed sheet-steel extrusions and
ideal integration into Knürr rack
systems deliver high stability and
torsional strength.
Best possible conductivity: Fulllength brass busbar provided with
many models.
Double spring contacts for reliable
and low contact resistance.
248 | Rack PDUs
The DI-STRIP product family meets a broad range of data center power
distribution requirements for IT applications, computer networking,
laboratories and home sector.
Specially configured for the growing number of electronic components in
network switching racks or server racks. Available with different accessories,
such as circuit breakers, overvoltage protection, mains filter, master-slave
function, emergency stop switch, fault-current circuit-breaker, local and remote
power metering.
DI-STRIP®
INPUT POWER
Single-phase or three-phase.
Up to 22 kVA.
Simple input supply.
OUTPUT DISTRIBUTOR
NEMA 5-20R single-phase, IEC C13 and C19,
combination systems.
Schuko, France, Switzerland.
MODULARITY
More connectivity with expansion unit for
Basic Rack PDU GST18.
FORM FACTOR
Vertical mounting (0 U).
Rack installation.
Workstation mounting.
LOCAL MONITORING
Fixed display.
REMOTE MONITORING
Secure Web and SNMP interfaces
with Liebert Nform.
OVERLOAD PROTECTION
Circuit breakers/fuses per branching
cable/output as required.
Rack PDUs | 249
DI-STRIP®
Benefits
Optimal phase distribution
across the entire rack with
color-coded identification
of the individual phases.
Up to 48 different plug options
per PDU: shortens the cable
distance between the PDU and
the consumer.
One of the most compact PDUs
on the market: measures only
44.4 x 45.5 mm, which saves space
even on a 600 mm-wide rack.
Simple and quick installation
on the rack extrusion: reduces
installation and wiring costs.
250 | Rack PDUs
Emerson Network Power Rack
DI-STRIP
PDUs®
Highest possible security and availability with:
Closed sheet-steel extrusions that deliver high stability
and torsional flexibility.
Extensive certification compliant with the international
Standard.
Double spring contacts for reliable and low contact
resistance.
Unbalanced load monitoring prevents feed-cable overload of 3-phase feed (only DI-STRIP versions M and RM).
Optimal load monitoring for server installation
(only DI-STRIP versions M and RM).
Individual output-backup with DI-STRIP BladePower
and Pizza Power.
Reliable power distribution at full power delivered by full-length brass busbars.
A
Maximum flexibility attained due to:
Internationally compatible configurations and options.
Power cable lengths of 2.5 m or 4 m for more spatial
flexibility.
Rotating current indicator in 90° steps
(only M and RM DI-STRIP versions).
Tool-less installation, which means quick and easy
extension in the rack (only with DI-STRIP HighPower).
Extremely low operating costs:
Installation in the rack is rapid and easy requiring
minimal space and reduced installation time.
Automatic background-light reduction reduces the rack
PDU power loss (only with M and RM DI-STRIP versions).
Especially flat housing extrusion, providing full accessibility to the 19" level on 600 mm wide server racks.
B
C
Can be fitted to a rack or workstation.
Highly compact construction; minimizes space requirements in the rack.
Color-coded phase allocation (L1, L2, L3).
Rack PDUs | 251
DI-STRIP®
DI-STRIP®
European Equipment Models
DI-STRIP models
Functions
Input power
Outputs
Technical description
Euro socket system IEC 320
Basic power distribution
1 x 16 A
3.68 kVA
IEC60320
C13 & C19
Page 230
TriplePower
Basic power distribution
3 x 16 A
11 kVA
IEC60320
C13 & C19 & Schuko
Page 230
Classic
Basicpower distribution/extra
large distance between the sockets
1 x 16 A
3.68 kVA
Schuko, France, Switzerland
Page 232
Compact
Basic power distribution
1 x 16 A
3.68 kVA
Schuko, France, Switzerland
Page 232
Protector FI
Fault-current circuit-breaker
FI
1 x 16 A
3.68 kVA
Schuko, France, Switzerland
Page 233
Protector LS
Circuit breaker (LS)
FI
1 x 16 A
3.68 kVA
Schuko, France, Switzerland
Page 233
Protector FI/LS
Combination FI + LS
1 x 16 A
3.68 kVA
Schuko, France, Switzerland
Page 234
Protector Emergency Stop
Emergency stop switch
1 x 16 A
3.68 kVA
Schuko, France, Switzerland
Page 234
Protector Emergency Stop FI/LS
Combination emergency stop + FI + LS
1 x 16 A
3.68 kVA
Schuko, France, Switzerland
Page 235
Power Cleaner
Mains filter
1 x 16 A
3.68 kVA
Schuko, France
Page 235
Safety Basic
Overvoltage protection
1 x 16 A
3.68 kVA
Safety Standard
Mains filter + overvoltage protection
1 x 16 A
3.68 kVA
Schuko, France, Switzerland
Page 237
Master Slave
Master Slave
1 x 16 A
3.68 kVA
Schuko, France
Page 238
Combi
Combination Master Slave +
overvoltage protection + mains filter
1 x 16 A
3.68 kVA
Schuko, France
Page 238
M (metered)
Phase current metered reading, local
1 x 16 A, 1 x 32 A, 3 x 16 A
3.32 A to 22 kVA
IEC60320
C13 & C19 & Schuko
Page 239
RM (remote metered)
Phase current metered reading local +
remote
1 x 16 A, 1 x 32 A, 3 x 16 A
3.32 A to 22 kVA
IEC60320
C13 & C19 & Schuko
Page 239
252 | Rack PDUs
Schuko, France, Switzerland
Page 236
DI-STRIP®
DI-STRIP® Euro Socket System, IEC 320
DOS00458
– Optionally with illuminated switch; 2-pole
switching.
– 19" installation option.
–Euro socket combinations of IEC 320 C13 and
C19 sockets.
– Feed cable: H05VV-F 3G 1.5/2.5 mm2.
– Feed cable: 2.5 m / 5 m.
Approvals/certificates
– CE label in accordance with
Low Voltage Directive 2006/95/EC.
– EMC Directive 2004/108/EC.
– BV BG.
– CB scheme.
– CSA (only models with IEC60320 input).
Color
– Enclosure: RAL 7035, light-gray.
– Plastic parts: RAL 7021 dark-gray.
DOS00460
Material / Finish
–H
ousing: closed sheet steel extrusion,
zinc-passivated, powder-coated texture.
–P
lastic parts: Vampamid 6 0024 VO (UL94),
recyclable.
DOS20062
Dimensions
–H
eight: 45.5 mm.
–W
idth of housing: 44.4 mm (= 1 U).
Scope of delivery
– 1 x socket strip.
– 2 x mounting brackets.
DOS20102
DI-STRIP® TriplePower® Euro Socket System
– Feed cable: H05VV-F 5 G 2.5 mm2.
–Feed cable: 2.5 m (optional with IEC60309 plug,
3Ph/N/PE 6h).
– Easy mounting on the rack extrusion.
– Standard feed 3 x 16 A.
–Ideal for implementing redundancy
(e.g. 96 A with redundant feed).
– Color-coded phase allocation.
– Optimum distribution across the entire
rack height (23 U and 41 U).
– Alternative to 3-phase GST18 system.
Approvals/certificates
– CE label in accordance with
Low Voltage Directive 2006/95/EC.
– EMC Directive 2004/108/EC.
– BV BG.
– CB scheme.
– IEC 320.
Color
– Enclosure: RAL 7035, light-gray.
– Plastic parts: RAL 7021 dark-gray.
DOS20126
Material/ Finish
–H
ousing: closed sheet steel extrusion,
zinc-passivated, powder-coated texture.
–P
lastic parts: Vampamid 6 0024 VO (UL94),
recyclable.
Load rating
– 100-240/173-415 Vac.
– Input: 3 x 16 A.
– Output: 10 A (C13).
– Output: 16 A (C19 / Schuko).
Dimensions
– Height: 45.5 mm.
– Width of housing: 44.4 mm (= 1 U).
Scope of delivery
– 1 x socket strip.
– 2 x mounting brackets.
Rack PDUs | 253
DI-STRIP®
Knürr DI-STRIP® Classic
– Optionally with illuminated switch; 2-pole
switching.
– Socket rotation: 45°.
– Feed cable: H05VV-F 3G 1.5 mm2.
–Optionally with Euro plug, IEC320 for UPS
application.
DOS00403
Material / Finish
–H
ousing: closed sheet steel extrusion,
zinc-passivated, powder-coated texture.
–P
lastic parts: Vampamid 6 0024 VO (UL94).
– I nternal conductor: full-length busbars, brass.
Dimensions
–D
istance between sockets: 100 mm.
–H
eight: 45.5 mm.
–W
idth of housing: 44.4 mm (= 1 U).
– F eed cable: 2.5 m.
Approvals/certificates
– CE label in accordance with
Low Voltage Directive 2006/95/EC.
– EMC Directive 2004/108/EC.
– BV BG.
– CB scheme.
– VDE GS.
Color
– RAL 7035, light-gray.
Load rating
– 100-240 Vac/16 A (output Schuko and UTE).
– 100-240 Vac/10A (outputs Switzerland).
Scope of delivery
– 1 x socket strip.
– 2 x mounting brackets.
Knürr DI-STRIP® Compact
DOS00401
with switch.
– Optionally with illuminated switch; 2-pole
switching.
– 19" installation option (for length 483 mm).
–2 versions: standard side panel or design side
panel.
– Socket rotation: 45°.
– Feed cable: H05VV-F 3G 1.5 mm2.
– Molded right angle plug.
–Optionally with Euro plug, IEC320 for UPS
applications.
Material / Finish
–H
ousing: closed sheet steel extrusion,
zinc-passivated, powder-coated texture.
–P
lastic parts: Vampamid 6 0024 VO (UL94),
recyclable.
– I nternal conductor: full-length busbars, brass.
254 | Rack PDUs
Dimensions
–D
istance between sockets: 50 mm.
–H
eight: 45.5 mm.
–W
idth of housing: 44.4 mm (= 1 U).
– F eed cable: 2.5 m.
Approvals/certificates
– CE label in accordance with
Low Voltage Directive 2006/95/EC.
– EMC Directive 2004/108/EC.
– BV BG.
– CB scheme.
– VDE GS.
Color combination
– Final digit of order number .1:
RAL 7035, light-gray.
– Final digit of order number .6:
housing RAL 2003 pastel orange.
– Plastic parts: RAL 7035, light-gray.
Load rating
– 100-240 Vac/16 A (output Schuko and UTE).
– 100-240 Vac/10 A (outputs Switzerland).
Scope of delivery
– 1 x socket strip.
– 2 x mounting brackets.
DI-STRIP®
Knürr DI-STRIP® Protector FI
DOS20065
with FI circuit breaker
Protector FI
– F ault-current circuit breaker for user
protection.
–P
rotection against indirect contact by
disconnection of the circuit when inadmissibly
high contact voltage occurs through bodily
contact with electrical equipment.
–A
dditional protection against direct contact.
–R
esidual operating current Ig = 10 mA for
alternating and pulsating direct fault currents.
–1
9" installation option (for length 483 mm).
– S ocket rotation: 45°.
– F eed cable: H05VV-F 3G 1.5 mm2.
–M
olded right angle plug.
Material/ Finish
–H
ousing: closed sheet steel extrusion,
zinc-passivated, powder-coated texture.
–P
lastic parts: Vampamid 6 0024 VO (UL94),
recyclable.
– I nternal conductor: full-length busbars, brass.
Dimensions
– Distance between sockets: 50 mm.
– Height: 78 mm.
– Width of housing: 44.4 mm (= 1 U).
– Feed cable: 2.5 m.
Approvals/certificates
– CE label in accordance with
Low Voltage Directive 2006/95/EC.
– EMC Directive 2004/108/EC.
– BV BG.
– CB scheme.
Color combination
– Final digit of order number .1:
RAL 7035, light-gray.
– Plastic parts: RAL 7035, light gray.
Load rating
– 100–240 Vac/16 A.
Scope of delivery
– 1 x socket strip.
– 2 x mounting brackets.
Knürr DI-STRIP® Protector LS
DOS00692
with circuit breaker.
Protector LS
– Circuit breaker for overload and short circuit.
–P
rotects cables and lines by switching off
rapidly in the event of a short circuit and
defined delayed switch-off when overloads
occur.
– Circuit breaker: 16 A.
– Trip characteristics: type B, 2-pole.
– 19" installation option (for length 483 mm).
– Socket rotation: 45°.
– Feed cable: H05VV-F 3G 1.5 mm2.
– Molded right angle plug.
Approvals/certificates
– CE label in accordance with
Low Voltage Directive 2006/95/EC.
– EMC Directive 2004/108/EC.
– BV BG.
– CB scheme.
– VDE GS.
Material/ Finish
–H
ousing: closed sheet steel extrusion,
zinc-passivated, powder-coated texture.
–P
lastic parts: Vampamid 6 0024 VO (UL94),
recyclable.
– I nternal conductor: full-length busbars, brass.
Load rating
– 100–240 Vac/16 A.
Color combination
– Final digit of order number .1:
RAL 7035, light-gray.
– Plastic parts: RAL 7035, light gray.
Scope of delivery
– 1 x socket strip.
– 2 x mounting brackets.
Dimensions
– Distance between sockets: 50 mm.
– Height: 78 mm.
– Width of housing: 44.4 mm (= 1 U).
– Feed cable: 2.5 m.
Rack PDUs | 255
DI-STRIP®
Knürr DI-STRIP® Protector FI / LS
DOS00693
Protector FI / LS
– Fault current switch and circuit breaker.
–P
rovides a combination of user, overload and
short circuit protection.
–R
esidual operating current Ig = 30 mA for
alternating and pulsating direct fault currents.
–C
ircuit breaker 16 A (Schuko and France) /
10A (Switzerland).
– Trip characteristics, type B, 2-pole.
– 19" installation option (for length 483 mm).
– Socket rotation: 45°.
– Feed cable: H05VV-F 3G 1.5 mm2.
– Molded right angle plug.
Material / Finish
–H
ousing: closed sheet steel extrusion,
zinc-passivated, powder-coated texture.
–P
lastic parts: Vampamid 6 0024 VO (UL94),
recyclable.
– I nternal conductor: full-length busbars, brass.
Dimensions
– Distance between sockets: 50 mm.
– Height: 78 mm.
– Width of housing: 44.4 mm (= 1 U).
– Feed cable: 2.5 m.
Approvals/certificates
– CE label in accordance with
Low Voltage Directive 2006/95/EC.
– EMC Directive 2004/108/EC.
– BV BG.
– CB scheme.
Color combination
– Final digit of order number .1:
RAL 7035, light-gray.
– Plastic parts: RAL 7035, light-gray.
Load rating
– 100–240 Vac/16 A (Schuko and France).
– 100–240 Vac/10 A (Switzerland).
Scope of delivery
– 1 x socket strip.
– 2 x mounting brackets.
Knürr DI-STRIP® Protector Emergency Stop
DOS20059
– With 2-pole emergency stop switch for
user protection.
–For manually disconnecting consumers in
an emergency.
–Phase and neutral conductors are separated
safely.
–Switch must be intentionally unlocked to
restart.
– 19" installation option (for length 483 mm).
– Socket rotation: 45°.
– Feed cable: H05VV-F 3G 1.5 mm2.
– Molded right angle plug.
M
aterial / Finish
–H
ousing: closed sheet steel extrusion,
zinc-passivated, powder-coated texture.
–P
lastic parts: Vampamid 6 0024 VO (UL94),
recyclable.
– I nternal conductor: full-length busbars, brass.
Dimensions
–D
istance between sockets: Classic: 100 mm,
Compact: 50 mm.
– Height: 101 mm.
– Width of housing: 44.4 mm (= 1 U).
– Feed cable: 2.5 m.
256 | Rack PDUs
Approvals/certificates
– CE label in accordance with
Low Voltage Directive 2006/95/EC.
– EMC Directive 2004/108/EC.
– BV BG.
– CB scheme.
Color combinations
– Final digit of order number .1:
RAL 7035, light gray.
– Plastic parts: RAL 7035, light gray.
Load rating
– 100–240 Vac/16 A.
Scope of delivery
– 1 x socket strip.
– 2 x mounting brackets.
DI-STRIP®
Knürr DI-STRIP® Protector Emergency Stop FI /LS
DOS00456
– With 2-pole emergency stop switch
for user protection.
– For protecting operating personnel.
–For manually disconnecting consumers in
an emergency.
–Phase and neutral conductors are separated
safely.
–Switch must be intentionally unlocked to
restart.
–Socket rotation: 45°.
–Feed cable: H05VV-F 3G 1.5 mm2.
–Molded right angle plug.
Material/ Finish
–H
ousing: closed sheet steel extrusion,
zinc-passivated, powder-coated texture.
–p
lastic parts: Vampamid 6 0024 VO (UL94),
recyclable.
– I nternal conductor: full-length busbars, brass.
Dimensions
–D
istance between sockets: Compact: 50 mm.
–H
eight: 101 mm.
–W
idth of housing: 44.4 mm (= 1 U)
– F eed cable: 2.5 m.
Approvals/certificates
– CE label in accordance with
Low Voltage Directive 2006/95/EC.
– EMC Directive 2004/108/EC.
– BV BG.
– CB scheme.
Color combinations
– Final digit of order number .1:
RAL 7035, light-gray.
– Plastic parts: RAL 7035, light-gray.
Additionally:
– With 2-pole fault-current switch and circuit
breaker
– Provides a combination of user, overload and
short circuit protection.
Load rating
– 100–240 Vac/16 A.
Scope of delivery
– 1 x socket strip.
– 2 x mounting brackets.
Knürr DI-STRIP® Power Cleaner
DOS20061
–High-frequency glitches generally occur
in switching processes ranging from 100 kHz to
5 MHz. This high-frequency rate overloads the
mains frequency and affects adjacent electronic
equipment. The mains filter attenuates this
high-frequency rate.
–The attenuation behavior is harmonized with
the typical interference spectrum.
–The mains filter works in both directions: where
glitches from the equipment to the socket strip
are also filtered from the mains.
–19" installation option (for length 483 mm).
–Socket rotation: 45°.
–Feed cable: H05VV-F 3G 1.5 mm2.
–Molded right angle plug.
Material / Finish
–H
ousing: closed sheet steel extrusion,
zinc-passivated, powder-coated texture.
–P
lastic parts: Vampamid 6 0024 VO (UL94),
recyclable.
– I nternal conductor: full-length busbars, brass.
Dimensions
– Distance between sockets: 50 mm.
– Height: 45.5 mm.
– Width of housing: 44.4 mm (= 1 U).
– Feed cable: 2.5 m.
Approvals/certificates
– CE label in accordance with
Low Voltage Directive 2006/95/EC.
– EMC Directive 2004/108/EC.
– BV BG.
– CB scheme.
Color combination
– Final digit of order number .1:
RAL 7035, light-gray.
– Final digit of order number .6:
housing RAL 2003 pastel orange.
– Plastic parts: RAL 7035, light-gray.
Technical data
– Nominal voltage: max. 250 Vac, 50 Hz.
– Nominal current, max. 16 A.
– Filter compliant with VDE 0565-3
(EN 60939-1).
Scope of delivery
– 1 x socket strip.
– 2 x mounting brackets.
– 2 x 19" mounting brackets (additionally with
19" installation option).
Rack PDUs | 257
DI-STRIP®
Knürr DI-STRIP® Safety Basic
DOS20068
with overvoltage protection
–For protection against transient overvoltage
from the mains, which, for example, are caused
by switching machines on and off.
–When critical overvoltages occur, the connection to the mains is cut off.
–Once the protective conductor has been triggered, the green function display light is not
illuminated. Thus, the socket strip can no longer
be used.*
–Basic equipment protection is classified as class
3 (category D).
–For optimal protection, class 1 and 2 (categories
B and C) protective equipment must be installed in the building.
–19" installation option (for length 483 mm).
–Socket rotation: 45°.
–Feed cable: H05VV-F 3G 1.5 mm2.
–Molded right angle plug.
Material / Finish
–H
ousing: closed sheet steel extrusion,
zinc-passivated, powder-coated texture.
–p
lastic parts: Vampamid 6 0024 VO (UL94),
recyclable.
– I nternal conductor: full-length busbars, brass.
Dimensions
–D
istance between sockets: 50 mm.
–H
eight: 45.5 mm.
–W
idth of housing: 44.4 mm (= 1 U).
Approvals/certificates
– CE label in accordance with
Low Voltage Directive 2006/95/EC.
– EMC Directive 2004/108/EC.
– BV BG.
– CB scheme.
Color combination
– Final digit of order number .1:
RAL 7035, light-gray.
– Final digit of order number .6:
housing RAL 2003 pastel orange.
– Plastic parts: RAL 7035, light-gray.
Technical data
– Appliance class: Type 3 as per DIN EN 61643-11.
– Requirement class: category D as per VDE
0675-6.
– Mains voltage: 230 VAC.
– Nominal current, max. 16 A.
– Discharge surge current (8/20 μs): 10 kA.
– Reaction time: ‹ 25 ns.
– Safety level (at 100 A varistor peak current):
L with respect to N: ‹ 800 V, L / N with respect to
PE: ‹ 1500 V.
Scope of delivery
– 1 x socket strip.
– 2 x mounting brackets.
* Send the socket strip to the manufacturer for the protective conductor to be replaced!
258 | Rack PDUs
DI-STRIP®
Knürr DI-STRIP® Safety Standard
DOS20069
– Standard safety models consist of a combined
overvoltage protection/mains filter element.
–Protects against transient overvoltages from
the mains, which, for example, are caused by
switching machines on and off.
–When critical overvoltages occur, connection to
the mains is cut off.
–Once the protective conductor has been
triggered, the green function display light is not
illuminated. The socket strip can thus no longer
be used.*
–Basic equipment protection is classified as class
3 (category D).
–For optimal protection, class 1 and 2 (categories
B and C) protective equipment must be
installed in the building.
–High-frequency glitches are generally caused
by switching processes in an operation from
100 kHz to 5MHz.
–This high-frequency rate overloads the mains
frequency and affects adjacent electronic
equipment. The mains filter attenuates this
high-frequency rate.
–The attenuation behavior is harmonized with
the typical interference spectrum.
–19" installation option (for length 483 mm).
–Socket rotation: 45°.
–Feed cable: HO5VV-F 3G 1.5 mm2.
–Molded right angle plug.
Material/ Finish
–H
ousing: closed sheet steel extrusion,
zinc-passivated, powder-coated texture.
–P
lastic parts: Vampamid 6 0024 VO (UL94),
recyclable.
– I nternal conductor: full-length busbars, brass.
Dimensions
– Distance between sockets: 50 mm.
– Height: 45.5 mm.
– Width of housing: 44.4 mm (= 1 U).
– Feed cable: 2.5 m.
Approvals/certificates
– CE label in accordance with
Low Voltage Directive 2006/95/EC.
– EMC Directive 2004/108/EC.
– BV BG.
– CB scheme.
Color combination
– Final digit of order number .1:
RAL 7035, light-gray.
– Final digit of order number .6:
housing RAL 2003 pastel orange.
– Plastic parts: RAL 7035, light-gray.
Technical data
– Mains voltage: 230 VAC.
– Nominal current: max. 16 A / 10 A.
– Discharge surge current (8/20 μs): 10 kA.
– Reaction time: ‹ 25 ns.
– Safety level (at100 A varistor peak current):
L with respect to N: ‹ 800 V, L / N with respect
to PE: ‹ 1500 V.
– Overvoltage protection
– Appliance class: Class 3 – as per
DIN EN 61643-11.
– Requirement class: Category D as per
VDE 0675-6.
– Mains filter: as per VDE 0565 (EN 60939).
Scope of delivery
– 1 x socket strip.
– 2 x mounting brackets.
* Send the socket strip to the manufacturer for the safety arrester to be replaced!
Rack PDUs | 259
DI-STRIP®
Knürr DI-STRIP® Master-Slave
–Slave plugs will switch on if master switches on.
–Note:
–T
he master consumer's power intake must
always exceed the switch-on threshold. When
switching off the master consumer, the power
intake must fall below the switch-off threshold.
–1
9" installation option (for length 483 mm).
– S ocket rotation: 45°.
– F eed cable: H05VV-F 3G 1.5 mm2.
–M
olded right angle plug.
DOS20070
Material / Finish
–H
ousing: closed sheet steel extrusion,
zinc-passivated, powder-coated texture.
–P
lastic parts: Vampamid 6 0024 VO (UL94),
recyclable.
– I nternal conductor: full-length busbars, brass.
Dimensions
–D
istance between sockets: 50 mm.
–H
eight: 45.5 mm.
–W
idth of housing: 44.4 mm (= 1 U).
– F eed cable: 2.5 m.
Approvals/certificates
– CE label in accordance with
Low Voltage Directive 2006/95/EC.
– EMC Directive 2004/108/EC.
– BV BG.
– CB scheme.
– VDE GS.
Color combination
– Final digit of order number .1:
RAL 7035, light-gray.
– Plastic parts: RAL 7035, light-gray.
Load rating
– Max. 250 Vac/16 A.
Technical data
– Switching-threshold setting range
– On: 20 - 200 mA (approx. 55 mA on delivery).
– Off: 16 - 160 mA (approx. 44 mA on delivery).
– Switching delay: 550 ms, ± 20 %.
– Electronic module: 2-pole switching.
Scope of delivery
– 1 x socket strip.
– 2 x mounting brackets.
Knürr DI-STRIP® Combi
DOS00325
with master-slave overvoltage protection
and mains filter.
–Master-slave with overvoltage protection and
mains filter.
– Automatic consumer switching.
–Combines Master-Slave and Safety Standard
(page 260) functions.
– Socket rotation: 45°.
– Feed cable: H05VV-F 3G 1.5 mm2.
– Molded right angle plug.
Material / Finish
–H
ousing: closed sheet steel extrusion,
zinc-passivated, powder-coated texture.
–P
lastic parts: Vampamid 6 0024 VO (UL94),
recyclable.
– I nternal conductor: full-length busbars, brass.
Dimensions
–D
istance between sockets: 50 mm.
–H
eight: 45.5 mm.
–W
idth of housing: 44.4 mm (= 1 U).
– F eed cable: 2.5 m.
Approvals/certificates
–C
E label in accordance with
Low Voltage Directive 2006/95/EC.
– E MC Directive 2004/108/EC.
– BV BG.
–C
B scheme.
260 | Rack PDUs
Color combination
– Final digit of order number .1:
RAL 7035, light-gray.
– Plastic parts: RAL 7035, light-gray.
Technical data
– With overvoltage protection and mains filter.
– Mains voltage: max. 250 VAC.
– Nominal current: 16 A.
– Requirement class: D (protection as per
VDE 0675).
– Surge current resistance (8/20 μs wave):
Max. 10 kA.
– Protection level (1.5/50 μs wave):
‹ 1500 V (L + N against PE).
– Master-slave function:
– Switching-threshold setting range
– On: 20 - 200 mA (approx. 55 mA on
delivery).
– Off: 16 - 160 mA (approx. 44 mA on
delivery).
– Switching delay: 550 ms ± 20 %.
– Electronic module: 2-pole switching.
Scope of delivery
– 1 x socket strip.
– 2 x mounting brackets.
DI-STRIP®
Knürr DI-STRIP® M
DOS80002
– Large LCD display for clear view.
–Effective metering of alternating current
displayed per phase (single-phase or 3-phase,
depending on model).
–LCD display rotation in 90° steps.
–Display contrast can be adjusted.
–Unbalanced-load warning display with 3-phase
model.
–Signals indicate load changes.
–Automatic reduction of background light.
–Feed cable: 4 m H05VV—F 5 G 4 mm2
(PizzaPower M).
–Feed cable: 2.5 m H05VV-F 5 G 2.5 mm2
(TriplePower M).
–Feed cable: 2.5 m H05VV-F 3G 1.5 mm2
(DI-STRIP Compact M, DI-STRIP IEC320 M).
Material/ Finish
– PizzaPower® model; Housing: sheet steel,
zinc-passivated, powder-coated.
– Other models: Housing: closed sheet steel
extrusion, zinc-passivated, powder-coated
texture.
–P
lastic parts: Vampamid 6 0024 VO (UL94),
recyclable.
Approvals/certificates
– CE label in accordance with
Low Voltage Directive 2006/95/EC.
– EMC Directive 2004/108/EC.
EN61326-1, EN61000-3-2, EN61000-3-3.
– FCC Class B.
– CB scheme (TriplePower M, DI-STRIP compact
M, IEC320M, ampere meter GST18i).
Color
– PizzaPower M model; Housing:
RAL 9005 black.
– Other models; Housing:
RAL 7035 light-gray.
– Plastic parts: RAL 7021 dark-gray.
Scope of delivery
– 1 x socket strip with ampere meter.
– 2 x mounting brackets.
– 2 x 19" mounting brackets (with 19"
installation option).
Note
Other models (e.g C 19 outputs)
available on request.
Knürr DI-STRIP® RM
DOS80002
–Displays real RMS value for the
alternating current per phase.
–LCD display rotation in 90° steps.
–Display bright/dark switchover.
–Warning display for unbalanced load.
–Signals indicate load changes.
–Automatic darkening of background light
for energy saving.
Material / Finish
– PizzaPower model; Housing: sheet steel,
zinc-passivated, powder-coated.
– Other models; Housing: closed sheet steel
extrusion, zinc-passivated, powder-coated
texture.
– Plastic parts: Vampamid 6 0024 VO (UL94),
recyclable.
Data interface:
–The plug strip can be integrated into the
network via an RJ45 plug.
–Access is possible without special software
via a remote browser.
–Three variable limit values and a warning for
unbalanced loads can be specified.
–The module enables access for up to 5 users or
administrators; access is password-protected.
–The software displays the name and location of
the PDU; this information can be entered by an
administrator.
–The user can specify a static IP address or access
using DHCP.
–Firmware updates can be made via a web
browser.
–Supported protocols: HTTP, SNMP (Traps, SET,
GET), Syslog.
Dimensions
– Width: 84 mm (PizzaPower), 44.4 mm
(others).
– Height: 60 mm (PizzaPower), 44.4 mm
(others).
Color
– PizzaPower model; Housing: RAL 9005 black.
– Other models; Housing: RAL 7035 light-gray.
– Plastic parts: RAL 7021 dark-gray.
Approvals
– CE label in accordance with Low Voltage
Directive 2006/95/EC.
– EMC Directive 2004/108/EC.
– BV BG.
Scope of delivery
– 1 x socket strip (PDU) with remote ampere
meter.
– 1 x mounting bracket.
– 1 x instruction manual.
Rack PDUs | 261
DI-STRIP®
DI-STRIP Model
Input Values
Voltage
Input Connector
Current
Outputs
C13
C19
Schuko
L
UTE
S
F1
F2
19"
Safe
Order No.
Type 13
Euro plug IEC320 system
With feed cable
Euro input in plug
panel
Euro input on side
panel
230V
16 A
Schuko CEE7/7
6
333
03.600.006.1
230V
16 A
Schuko CEE7/7
9
483
03.602.009.1
230V
10 A
IEC60320 C13
12
483
03.600.312.1
230V
16 A
IEC60320 C19
15
3
783
03.600.418.1
230V
16 A
IEC60309 1ph/N/PE 6h
15
3
783
03.600.518.1
230V
10 A
IEC60320 C14 inlet
6
383
03.622.006.1
230V
10 A
IEC60320 C14 inlet
9
483
03.622.009.1
230V
10 A
IEC60320 C14 inlet
6
333
03.622.706.1
230V
10 A
IEC60320 C14 inlet
9
433
03.622.709.1
230V
10 A
IEC60320 C14 inlet
6
383
03.624.706.1
230V
10 A
IEC60320 C14 inlet
9
483
03.624.709.1
10
483
03.632.010.1
With overload
protection 10 A
Schuko CEE7/7
230V
10 A
GST18 input
in side panel
230V
16 A
GST18
6
383
03.600.206.1
230/400V
3 x 16 A
none
24
1033
03.600.024.1
230/400V
3 x 16 A
none
48
1833
03.600.048.1
230/400V
3 x 16 A
IEC60309 3ph/N/PE 6h
24
1033
03.600.824.1
230/400V
3 x 16 A
IEC60309 3ph/N/PE 6h
48
1833
03.600.848.1
230/400V
3 x 16 A
IEC60309 3ph/N/PE 6h
18
6
1133
03.600.524.1
230/400V
3 x 16 A
IEC60309 3ph/N/PE 6h
36
6
1733
03.600.542.1
230/400V
3 x 16 A
IEC60309 3ph/N/PE 6h
6
483
03.600.506.1
230/400V
3 x 16 A
IEC60309 3ph/N/PE 6h
833
03.300.812.1
230/400V
3 x 16 A
IEC60309 3ph/N/PE 6h
18
833
03.600.521.1
230/400V
3 x 16 A
IEC60309 3ph/N/PE 6h
18
833
03.300.521.1
230/400V
3 x 16 A
IEC60309 3ph/N/PE 6h
21
833
03.600.821.1
230/400V
3 x 16 A
IEC60309 3ph/N/PE 6h
45
1733
03.600.845.1
230/400V
3 x 16 A
IEC60309 3ph/N/PE 6h
36
1733
03.300.542.1
TriplePower
12
3
3
6
PizzaPower
230V
32 A
IEC60309 1ph/N/PE 6h
7
400
03.631.007.1
230V
32 A
none
7
400
03.631.807.1
230V
32 A
IEC60309 1ph/N/PE 6h
12
720
03.631.124.1
230V
32 A
IEC60309 1ph/N/PE 6h
24
960
03.631.240.1
230V
32 A
IEC60309 1ph/N/PE 6h
21
1017
03.631.214.1
230/400V
3 x 32 A
IEC60309 3ph/N/PE 6h
21
933
03.631.021.1
230/400V
3 x 32 A
none
21
933
03.631.821.1
230/400V
3 x 32 A
IEC60309 3ph/N/PE 6h
6
408
03.631.006.1
230/400V
3 x 32 A
IEC60309 3ph/N/PE 6h
9
12
939
03.631.912.1
230/400V
3 x 32 A
IEC60309 3ph/N/PE 6h
36
1362
03.631.360.1
230/400V
3 x 32 A
IEC60309 3ph/N/PE 6h
18
1002
03.631.186.1
4
4
6
BladePower
230V
32 A
IEC60309 1ph/N/PE 6h
2
3
375
03.630.005.1
230/400V
3 x 32 A
IEC60309 3ph/N/PE 6h
6
9
740
03.630.015.1
230V
32 A
none
2
3
375
03.630.805.1
230/400V
3 x 32 A
none
6
9
740
03.630.815.1
230V
16 A
Schuko CEE7/7
17
1783
03.300.067.X
230V
16 A
Schuko CEE7/7
13
1383
03.300.063.X
230V
16 A
Schuko CEE7/7
9
983
03.300.059.X
230V
16 A
Schuko CEE7/7
5
583
03.300.055.X
230V
16 A
Schuko CEE7/7
16
1733
03.302.066.X
230V
16 A
Schuko CEE7/7
12
1333
03.302.062.X
230V
16 A
Schuko CEE7/7
8
933
03.302.058.X
230V
16 A
Schuko CEE7/7
4
533
03.302.054.X
Classic
262 | Rack PDUs
DI-STRIP®
DI-STRIP Model
Input Values
Input Connector
Outputs
C13
C19
Schuko
L
UTE
S
F1
F2
19"
Safe
Order No.
Voltage
Current
Type 13
230V
16 A
Schuko CEE7/7
13
1383
03.400.063.X
230V
16 A
Schuko CEE7/7
9
983
03.400.059.X
230V
16 A
Schuko CEE7/7
5
583
03.400.055.X
230V
16 A
Schuko CEE7/7
8
933
03.402.058.X
230V
10 A
SEV 1011 T12
13
1383
03.701.063.1
230V
10 A
SEV 1011 T12
9
983
03.701.059.1
230V
10 A
SEV 1011 T12
5
583
03.701.055.1
230V
10 A
SEV 1011 T12
16
1733
03.703.066.1
230V
10 A
SEV 1011 T12
8
933
03.703.058.1
230V
16 A
Schuko CEE7/7
15
883
03.300.015.X
230V
16 A
Schuko CEE7/7
11
732
03.300.111.X
230V
16 A
Schuko CEE7/7
11
683
03.300.011.X
230V
16 A
Schuko CEE7/7
7
532
03.300.107.X
230V
16 A
Schuko CEE7/7
7
483
03.300.007.X
230V
16 A
Schuko CEE7/7
8
483
03.300.008.1
230V
16 A
Schuko CEE7/7
4
382
03.300.104.X
230V
16 A
Schuko CEE7/7
4
333
03.300.004.X
230V
16 A
Schuko CEE7/7
14
883
03.302.014.X
230V
16 A
Schuko CEE7/7
10
732
03.302.110.X
230V
16 A
Schuko CEE7/7
10
683
03.302.010.X
230V
16 A
Schuko CEE7/7
6
532
03.303.106.X
230V
16 A
Schuko CEE7/7
6
532
03.302.106.X
230V
16 A
Schuko CEE7/7
6
483
03.302.006.X
230V
16 A
Schuko CEE7/7
7
483
03.302.007.1
230V
16 A
Schuko CEE7/7
3
382
03.302.103.X
230V
16 A
Schuko CEE7/7
3
333
03.302.003.X
230V
10 A
IEC60320 C14
8
483
03.300.308.1
230V
16 A
IEC60320 C20
8
483
03.300.408.1
230V
16 A
GST18
6
583
03.302.206.1
230V
16 A
GST18
3
433
03.302.203.1
230V
16 A
GST18
7
533
03.300.207.1
230V
16 A
GST18
4
383
03.300.204.1
230V
16 A
Schuko CEE7/7
11
683
03.400.011.X
230V
16 A
Schuko CEE7/7
7
532
03.400.107.X
230V
16 A
Schuko CEE7/7
7
483
03.400.007.X
230V
16 A
Schuko CEE7/7
4
333
03.400.004.X
230V
16 A
Schuko CEE7/7
10
683
03.402.010.X
230V
16 A
Schuko CEE7/7
6
483
03.402.006.X
230V
16 A
Schuko CEE7/7
3
333
03.402.003.X
230V
16 A
GST18
7
533
03.400.207.1
230V
16 A
GST18
4
383
03.701.011.1
230V
10 A
SEV 1011 T12
11
683
03.701.007.1
230V
10 A
SEV 1011 T12
7
483
03.701.004.1
230V
10 A
SEV 1011 T12
4
333
03.703.110.1
230V
10 A
SEV 1011 T12
10
732
03.703.1101
230V
10 A
SEV 1011 T12
6
483
03.703.006.1
230V
10 A
SEV 1011 T12
3
382
03.703.103.1
230V
10 A
SEV 1011 T12
3
333
03.703.003.1
Classic
Compact
UPS application
Protector FI
230V
16 A
Schuko CEE7/7
13
883
03.304.013.1
230V
16 A
Schuko CEE7/7
9
683
03.304.009.1
230V
16 A
Schuko CEE7/7
5
483
03.304.005.1
230V
16 A
Schuko CEE7/7
483
03.404.005.1
5
Rack PDUs | 263
DI-STRIP®
DI-STRIP Model
Input Values
Voltage
Input Connector
Current
Outputs
C13
C19
Schuko
L
UTE
S
F1
F2
19"
Safe
Order No.
Type 13
Protector LS
230V
16 A
Schuko CEE7/7
13
883
03.308.013.1
230V
16 A
Schuko CEE7/7
9
683
03.308.009.1
230V
16 A
Schuko CEE7/7
5
483
03.308.005.1
230V
16 A
Schuko CEE7/7
483
03.408.005.1
5
Protector FI/LS
230V
16 A
Schuko CEE7/7
13
883
03.310.013.1
230V
16 A
Schuko CEE7/7
9
683
03.310.009.1
230V
16 A
Schuko CEE7/7
5
483
03.310.005.1
230V
16 A
Schuko CEE7/7
9
683
03.410.009.1
230V
16 A
Schuko CEE7/7
5
483
03.410.005.1
230V
10 A
SEV 1011 T12
483
03.711.005.1
5
Protector emergency stop switch
Compact
230V
16 A
Schuko CEE7/7
230V
16 A
Schuko CEE7/7
6
10
483
03.326.006.1
683
03.426.010.1
683
03.328.008.1
Protector emergency stop switch FI/LS
230V
16 A
Schuko CEE7/7
8
230V
16 A
Schuko CEE7/7
13
883
03.312.013.X
230V
16 A
Schuko CEE7/7
9
683
03.312.009.X
230V
16 A
Schuko CEE7/7
5
483
03.312.005.X
230V
16 A
GST18
483
03.612.206.1
Power Cleaner
6
Safety Basic
230V
16 A
Schuko CEE7/7
10
732
03.316.110.1
230V
16 A
Schuko CEE7/7
10
683
03.316.010.X
230V
16 A
Schuko CEE7/7
6
483
03.316.006.X
230V
16 A
Schuko CEE7/7
4
383
03.316.004.1
230V
16 A
GST18
4
433
03.316.204.1
230V
16 A
GST18
483
03.616.206.1
230V
16 A
Schuko CEE7/7
483
03.416.006.1
230V
16 A
Schuko CEE7/7
13
883
03.318.013.X
230V
16 A
Schuko CEE7/7
9
732
03.318.109.X
230V
16 A
Schuko CEE7/7
9
683
03.318.009.X
230V
16 A
Schuko CEE7/7
5
532
03.318.105.X
230V
16 A
Schuko CEE7/7
5
483
03.318.005.X
230V
16 A
GST18
230V
16 A
Schuko CEE7/7
230V
10 A
SEV 1011 T12
6
6
Safety Standard
6
5
5
483
03.618.206.1
483
03.418.005.X
483
03.719.005.1
Master-Slave
230V
16 A
Schuko CEE7/7
9
683
03.314.009.1
230V
16 A
Schuko CEE7/7
5
483
03.314.005.1
230V
16 A
Schuko CEE7/7
483
03.414.005.1
5
Combi (technical description on page 238)
230V
16 A
Schuko CEE7/7
9
733
03.320.009.1
230V
16 A
Schuko CEE7/7
5
533
03.320.005.1
M
230V
32 A
IEC60309 1ph/N/PE 6h
7
483
03.636.007.1
230/400V
3 x 32 A
IEC60309 3ph/N/PE 6h
21
933
03.636.021.1
230/400V
3 x 16 A
IEC60309 3ph/N/PE 6h
21
1033
03.606.821.1
230/400V
3 x 16 A
IEC60309 3ph/N/PE 6h
45
1833
03.606.845.1
230/400V
3 x 16 A
IEC60309 3ph/N/PE 6h
18
6
1133
03.606.824.1
230/400V
3 x 16 A
IEC60309 3ph/N/PE 6h
36
6
1733
03.606.842.1
230V
16 A
Schuko CEE7/7
483
03.306.006.1
230V
16 A
Schuko CEE7/7
483
03.606.009.1
230V
16 A
GST18
233
03.606.200.1
264 | Rack PDUs
6
9
DI-STRIP®
DI-STRIP Model
Input Values
Voltage
Input Connector
Current
Outputs
C13
C19
Schuko
L
UTE
S
F1
F2
19"
Safe
Order No.
Type 13
RM
230V
16 A
Schuko CEE7/7
8
733
03.307.008.1
230V
16 A
Schuko CEE7/7
17
1183
03.307.017.1
230V
16 A
Schuko CEE7/7
9
633
03.607.009.1
230V
16 A
Schuko CEE7/7
18
933
03.607.018.1
230/400V
3 x 16 A
IEC60309 3ph/N/PE 6h
24
1133
03.607.825.1
230/400V
3 x 16 A
IEC60309 3ph/N/PE 6h
45
1833
03.607.845.1
230/400V
3 x 16 A
IEC60309 3ph/N/PE 6h
18
6
1233
03.607.824.1
230/400V
3 x 16 A
IEC60309 3ph/N/PE 6h
36
6
1833
03.607.842.1
230V
32 A
IEC60309 1ph/N/PE 6h
24
1111
03.637.023.1
230V
32 A
IEC60309 1ph/N/PE 6h
12
4
871
03.637.016.1
230V
32 A
IEC60309 1ph/N/PE 6h
21
4
1168
03.637.025.1
230/400V
3 x 32 A
IEC60309 3ph/N/PE 6h
6
563
03.637.006.1
230/400V
3 x 32 A
IEC60309 3ph/N/PE 6h
6
12
995
03.637.018.1
230/400V
3 x 32 A
IEC60309 3ph/N/PE 6h
21
1022
03.637.021.1
230/400V
3 x 32 A
IEC60309 3ph/N/PE 6h
18
6
1157
03.637.024.1
230/400V
3 x 32 A
IEC60309 3ph/N/PE 6h
36
6
1751
03.637.042.1
Outputs:
C13
= IEC60320 C13
C19
= IEC60320 C19
Schuko = Protective contact plug DIN 49440
UTE
= France Standard CEE 7-V
Type 13 = Switzerland, type 13
F2
= Design side panel (for installing at workstation)
= Length in mm
19"
= Suitable for 19" installation
S
= Switch
safe
= Child-proof
F1
= Standard side pane (for rack mounting)
L
Rack PDUs | 265
DI-STRIP®
3-Phase in Rack with GST18
Features
Requirement
Constant energy increase requirements in the rack caused by high
packing densities (e.g. 1 U Pizza
servers, blade servers, etc.) (1)
Solution
3-phase distributor with GST18
plug system, e.g. 96 A with
redundant feed. (2)
1. DOS20147
2. DOS20132
3. DOS20142
4. DOS20135
Benefits (3, 4)
– Modularity.
– Plug-in capability (no wiring
required).
– Can be expanded.
– Cascadable.
– Easy implementation of
redundancies/UPS-secured circuits.
– Combination of DIN Schuko /
IEC320 Euro systems.
– Any installation position can be
selected.
– Good alternative to 3-phase
DI-STRIP Triple Power.
Power Supply Cable, 3-Phase
Accessories for GST 18 Plug System
Color
– Black.
–GST 18 socket for connecting GST18i5
distributor block with 3 phases.
– 5-pole (L1, L2, L3, N, PE) 250/400 V ~.
– Cable: H05VV-F 5G 2.5 mm2.
DOS20104
L
Order No.
UP
2000
04.000.048.0
1 unit
Order No.
UP
04.000.038.9
1 unit
GST18i5 Distributor Block, 3-Phase
– For individual connection at the customer.
– Modular plug-in connection.
–3-phase distribution on various socket strips.
– Including mounting panel.
DOS20103
266 | Rack PDUs
Color
– Black.
DI-STRIP®
Power Supply Cable, Single Phase
Accessories for GST 18 Plug System
– Mains plug CEE/VII: GST18 socket (Wieland).
– Cable: H05VV-F3G 1.5 mm2.
Color
– White.
L
Order No.
UP
2000
04.000.040.0
1 unit
5000
04.000.041.0
1 unit
DOS00467
Connection Cable
Accessories for GST 18 Plug System
– GST 18 plug.
– GST 18 socket.
– Cable: H05VV-F3G 1.5 mm2.
DOS00469
Color
– For color coding circuits (e.g. UPS).
L
Model
Order No.
UP
200
White
04.000.042.0
1 unit
200
Black
04.000.042.9
1 unit
500
White
04.000.037.0
1 unit
500
Black
04.000.037.9
1 unit
1000
White
04.000.044.0
1 unit
1000
Black
04.000.044.9
1 unit
5000
White
04.000.045.0
1 unit
Order No.
UP
04.000.046.0
1 unit
Order No.
UP
04.000.047.0
1 unit
DOS20105
GST18 Socket
– With threaded connection for cross-section
1.5 – 2.5 mm2 with cable strain relief.
– For individual connection.
Color
– White.
DOS00471
GST18 Plug
– With threaded connection for cross-section
1.5 – 2.5 mm2 with cable strain relief.
–For individual, further cabling.
Color
– White.
DOS00470
Rack PDUs | 267
DI-STRIP®
Mains Cable for Euro Socket Strip
For DIN 49 440 and French/Belgian Standard
– Mains plug CEE/VII: Euro socket IEC 320.
– Cable: H05VV-F 3G 1 mm2.
Mains voltage
– 250 VAC.
Nominal current
– 10 A.
DOS00076
L
Order No.
UP
2000
04.000.054.9
1 unit
6000
04.000.053.9
1 unit
L
Order No.
UP
2000
04.000.055.9
1 unit
L
Order No.
UP
2000
04.000.056.9
1 unit
Mains Cable for Euro Socket Strip
For Swiss Standard
– Mains plug: Type 12 - Euro socket IEC 320.
– Cable: H05VV-F 3G 1 mm2.
Mains voltage
– 250 VAC.
Nominal current
– 10 A.
DOS00077
Mains Cable for Euro Socket Strip
For British Standard
–Mains plug: Type BS 1363 IEC320 Euro socket.
– Cable: H05VV-F 3G 1 mm2.
DOS00078
Mains voltage
– 250 VAC.
Nominal current
– 10 A.
Euro Connection Cable
–
–
–
–
DOS00519
Mains plug: IEC 320.
Euro socket IEC 320.
Cable: H05VV-F 3G 1 mm2.
USA: SJT AWG18 with USA approval.
L
Model
Order No.
UP
EU
04.000.051.9
1 unit
900
USA
04.000.052.9
1 unit
Conversion:
n = Number of sockets
U
S = Switch
F1 = Standard side panel
UP = Packaging unit
F2 = Design side panel
= Standard rack unit
Safe = child-proof
19" = ideal for 19" components
Replace .x with the number of your color combination: .1 = RAL 7035, .6 = RAL 7035/RAL 2003
268 | Rack PDUs
Nominal current
– 10 A.
900
Dimensions in mm:
L = Length
Mains voltage
– 250 VAC.
1 mm = 0.03937 inch
1 kg = 2.2046 pounds
DI-STRIP®
SafetySleeve™ Cable Protection IEC C19
– SafetySleeves protect the feed lines of the
network equipment.
–Compatible with all C19 cables and fit onto
all PDUs.
DOS20493
Material / Finish
– PVC, black.
Model
Order No.
UP
C20 plug in C19 socket
03.910.212.9 001
20 unit
Model
Order No.
UP
C14 plug in C13 socket
03.910.213.9 001
50 unit
SafetySleeve™ Cable Protection IEC C13
– SafetySleeves protect the feed lines of the
network equipment.
–Compatible with all C13 cables and fit onto
all PDUs.
Material / Finish
– PVC, black.
DOS20494
Dimensions in mm:
Conversion:
L = Length
n = Number of sockets
U
S = Switch
F1 = Standard side panel
UP = Packaging unit
F2 = Design side panel
= Standard rack unit
1 mm = 0.03937 inch
1 kg = 2.2046 pounds
Safe = child-proof
19" = ideal for 19" components
Replace .x with the number of your color combination: .1 = RAL 7035, .6 = RAL 7035/RAL 2003
Rack PDUs | 269
Emerson Network Power Rack PDUs
Rack PDU Support
and Warranty Options
Emerson Network Power offers you various options to ensure that you get the support you need in the event of a
fault. You can get in touch with your usual contact person directly or contact us by phone or e-mail.
Technical Support
W
ebsite:
www.EmersonNetworkPower.eu
T
elephone:
+800 1155 4499
E -mail:
liebert.upstech@emerson.com
Warranty Extension
When you purchase PDUs from us, you also have the option of ordering
warranty extensions for certain models. The following overview shows you the
various options available for increasing your service level.
Order No.
Warranty term (months)
24
36
60
MPH2 B Version (all B models)
free of charge
WE1Y-MPH2VB
WE3Y-MPH2VB
MPH2 R, C, M Versions (all R, C, M models)
free of charge
WE1Y-MPH2VRCM
WE3Y-MPH2VRCM
MPX Components (excluding sensors and display)
free of charge
WE1Y-MPX
WE3Y-MPX
If a warranty case should unfortunately arise for your product, we will decide
whether to repair or replace the defective product based on the type of defect
in question. Please contact your usual sales contact in such cases.
270 | Rack PDUs