F4 Four Zone Type 5
F4 Four Zone Type 5
Conventional Fire Alarm Panel
F4RS-3EAT5 and F4FS-3EAT5
Head Office
Wellington
Product Overview:
Pertronic Industries’ Four Zone Type 5 Fire Alarm panel is designed for low cost Fire Alarm systems.
It is modified to meet requirements for small residential applications and is NZS 4512:2010 compliant. Support is
provided for Pertronic Indicating Manual Call-Points, Indicating Heat Detectors and System Sensor Smoke
Detectors with the facility to internally mount one 20W Evacuation amplifier.
PO Box 35-063
Standard Features:
Naenae, 5011
‘Normal’, ‘Defect’ and per circuit ‘Fire’ indication on front panel
Lower Hutt
‘Internal Bell Cut-Off’ and ‘External Bell Cut-Off’ (BCO)
17 Eastern Hutt Rd
Alarm reset available from a front panel key-switch
Trial Evacuation key-switch
Wingate
Detectors automatically reset at end of the Hush period
Lower Hutt 5019
Fire & Defect C/O relays with Fire relay Isolate switch
Tel (04) 567-3229
Automatic Alarm Verification Facility (AVF) provides substantial
Fax (04) 567-3644
www.pertronic.co.nz
sales@pertronic.co.nz
tech@pertronic.co.nz
protection against transient false alarm activation
Monitored Bell circuit with up two 100 Vrms line amplifiers with
voiced Evacuation message
‘Battery Absent’ detection circuitry
Earth Leakage monitoring
Integrated piezo alarm and ‘Piezo on Defect’ warning
System ‘Defect’ LED indicates source of fault
Door Interlock
Brigade ‘Isolate’ and ‘Test’ switches
Electrically isolated interface to an alarm transmitter (SGD)
‘Bell Only’ configuration available (on Circuit 4) to monitor DBA
Type 5 Features
Auckland Office
Optional Zonal Hush button temporarily silences local sounders for 2
minutes if they have been activated by Smoke detectors within that zone
Detectors are automatically reset at the end of the Hush period
Zone 1 can be configured as a global Brigade calling zone
Zone 4 may be configured as a normal Zone or to monitor a Sprinkler (DBA) circuit
‘NOT CONNECTED TO FIRE SERVICE’ LED indicator
PO Box 15-867
New Lynn
Auckland 0640
Global Hush Circuit:
359 Onehunga Mall
Hushes All Sounders generated by any Zone, except Zone 4 if configured as DBA Input
Onehunga
Subsequent activation of another Detector/MCP on any other zone over-rides the Hush period
Auckland 1061
Available with Non-Brigade Connected panels – must not be used on NZS 4512:2010 compliant systems
Tel (09) 633-0226
Detector Circuits
Fax (09) 633-0228
Four zones terminated with 10 k EOL resistors
Supports up to 40 System Sensor Smoke detectors and unlimited Pertronic indicating Heat Detectors and
indicating Manual Call-Points per Zone circuit
Smoke detectors operate after a 1 second Alarm Verification Facility (AVF) delay
Indicating Heat detectors and indicating Manual Call-Points give instantaneous (< 0.5 sec) response
Normally-open switches provide Zonal Hush facility
Zone circuit self-test on start-up and every 24-hour
Sounder Circuit
Bell circuit Relay: 12 Vdc, 5 A – up to two Pertronic EVAC20W12V Amplifiers monitored with 56 k EOL
resistors
Four Speaker circuits, one per Zone and one Global Hush circuit. Further spurring is not allowed
Recommended Sounders: 2WTA-B Detector-Sounder or Pertronic PS1 Sounder
Optional Features:
Front or Rear Service cabinet
Brigade connection available using an internally mounted Pertronic SGD7 or SGD8 transmitter
Specifications
Electrical:
ISO 9001: 2008
International Standards
Certifications
QAC/R64/0012
Battery:
Environmental:
Mechanical:
Cabinet: FS or RS
Power Supply
230Vac, 50Hz, 5W
13.7Vdc, 400mA.
Quiescent Current
28mA at 12Vdc
Defect Current
32mA at 12Vdc
Alarm Current
155mA at 12Vdc
- plus Sounder load
Battery Charger
Integral Float Charger
13.7Vdc, 350mA
Battery Type
Sealed lead acid (gelcell)
12Vdc, 7AHr - internally mounted
Operating Temperature Range
0 to +40 oC
Humidity
10 to 95% RH (non-condensing)
Dimensions
(H x W x D mm)
350 x 245 x 80
Weight
2.2Kg
- excluding battery
Material
1.2mm mild steel,
powder coated
Colour
Beige
- other colours optional
Power Supply Timer: Automatic 24-Hour load test with automatic ‘Battery Absent’ detection circuitry
0016-F4-3 T5 Four Zone Type 5 Conventional Fire Alarm Panel Iss 4.1 20160601
Benefits:
The F4-3EAT5 provides a cost effective Type 5 solution for residential applications
The speakers and detectors are monitored for open or short-circuit conditions
Long battery standby period of up to 7 days
Optional Zonal or Global Hush button(s) facility enables speakers to be silenced for 2 minutes, allowing investigation of alarm
Detectors automatically reset at the end of the Hush period
Panel Silence and Evacuate facility
System Wiring:
Product Codes
NZS Code
Description
NZS Code
F4RS-3EAT5
F4FS-3EAT5
F4T5SCNT
2151
B401
SGD7
F4-RMAX
F4 RS Type 5 Rear Service Fire Panel with 20W Amplifier
F4 FS Type 5 Front Service Fire Panel with 20W Amplifier
F4 Type 5 Sound Control Board with hush
2151 Low Pro Photo Detector excl Base
B401 2-Wire Conventional Base
SGD Board Version 7
Remote LED Mimic/Aux Relay Module
EVAC20W12V
PSS1-R
PSS1-W
AMRH
IHDB-V
CPPIN-3T
Head Office:
17 Eastern Hutt Rd, Wingate, Lower Hutt 5019
Telephone (04) 567-3229 Fax (04) 567-3644
PERTRONIC INDUSTRIES LTD
www.pertronic.co.nz
sales@pertronic.co.nz
tech@pertronic.co.nz
Description
Evacuation Amplifier 20W, 12V, 4512:2010
Pertronic Sounder Speaker 1W Flush - Red
Pertronic Sounder Speaker 1W Flush - White
Remote Hush Unit
Indicating Heat Detector, Blue (57°C)
Conventional Indicating Call-Point
Auckland Office:
59 Onehunga Mall, Onehunga, Auckland 1061
Telephone (09) 633-0226 Fax (09) 633-0228
‘Pertronic’ and ‘Firetronix’ are registered trademarks of Pertronic Industries Ltd
Was this manual useful for you? yes no
Thank you for your participation!

* Your assessment is very important for improving the work of artificial intelligence, which forms the content of this project

Download PDF

advertising