ups on-line rackmount models: ups vr-1.5kva / vr-3kva / vr
Computer Power
Rackmount Units:
VR-1.5KVA / VR-3KVA / VR-6KVA
Rackmount Online UPS
MODEL
Computer Power 1.5K (L)
PHASE
CAPACITY
1500 VA / 1350W
Computer Power3K (L)
Computer Power 6K (L)
Single phase with ground
3000 VA / 2400 W
2 phase In / 2 phase Out F 4 wires
6000 VA / 4800 W
INPUT
AC Cord and Connector
Input Voltage
10 AWG / L5-30P
16 AWG / 5-15P
Terminal Block
80-140VAC/115/120/127VAC(L-N)
200/208/220/230/240 (L-L)
80 - 150 VAC
Input Frequency Range
40 Hz ~ 70 Hz
Operating Frequency
Power Factor
UPS ON-LINE RACKMOUNT MODELS:
UPS VR-1.5KVA / VR-3KVA / VR-6KVA
50 Hz / 60 Hz Auto sensing
> 0.99
OUTPUT
Power Factor
Output Receptacles
0.9
4 # 5-15R
Output Voltage
Phase Angle
AC Voltage Regulation (Batt. Mode)
Output Frequency
Frequency Range (Batt. Mode)
Current Crest Ratio
0.8
2 # 5-20R / L5-30R
115/120/127 VAC
± 1%
50 Hz / 60 Hz Auto sensing
50 Hz ± 0.2 Hz or 60Hz ± 0.2 Hz
3:1
Typical Recharge Time
Charging Voltage
Zero
Pure Sinewave
86%
88%
89% (96% on ECO mode)
83%
85%
85%
12 V / 9 Ah
3
12 V / 9Ah
6
4 hours recover to 90% capacity
41.1 VDC ± 1%
Backup Time Full/ Half Load
INDICATORS
LCD Panel
50 Hz ± 0.1 Hz or 60Hz ± 0.1 Hz
< 2 % THD
Harmonic Distortion
Transfer Time
Waveform
EFFICIENCY
AC Mode
Battery Mode
BATTERY
Battery Type
Numbers
Terminal Block
110/115/120/127VAC(L-N)
200/208/220/230/240 (L-L)
0º / 120º / 180º / 240º
82.1 VDC ±1%
6 / 14 minutes
12 V / 9Ah
10 x 2
136 VDC ±1%
9 / 23 minutes
UPS status, Load level, Battery level, Input/Output voltage, Discharge timer, and Fault conditions
ALARM
Battery Mode
Low Battery
Beeps every 4 seconds
Beeps every second
Overload
Fault
Beeps twice every second
Continuously sounding
PHYSICAL
Dimension, D x W x H (mm)
Net Weight (kgs)
480 x 438 x 88 [2U]
600 x 438 x 88 [2U]
18.5
29
UPS:
668 X 438 X 133 [3U]
BATTERY: 580 X 438 X 133 [3U]
FEATURES:
• Continuous and clean power provided by our
UPS protects against downtime, data loss and
process interruption
• Friendly Led Display
• Full programable options
• Cold Start from batteries
• Double-conversion True Online UPS
• Input power factor correction 0.99
• 50Hz/60Hz frequency converter mode
• Programmable power management outlets
• Emergency power off function (EPO)
• Sealed lead acid maintenance free batteries
• ECO mode operation for energy saving (ECO)
• SNMP+USB+RS-232 multiple communications
• Smart battery charger design for optimized
battery performance
• Selectable output voltage via LCD panel
• Hot-swappable battery design
• Wide input voltage range for harsh environments
• Automatic Bypass for fault tolerance
• Generator compatible
• Two-year product warranty
• Protection for shortcuit and overload at the
output
83
ENVIRONMENT
Operational Humidity and Temperature
Noise Level
Operational Altitude
MANAGEMENT
Smart RS-232/USB
0-90 % RH @ 0- 40°C (non-condensing)
Less than 50dB @ 1 Meter
< 3000 meters
0-95% RH @ 0- 40°C (non-condensing)
Less than 60dB @ 1 Meter
Supports Windows® 2000/2003/XP/Vista/2008, Windows® 7, Linux, Unix, and MAC
Optional SNMP
• CD Software Included
• Protection for: Power Failure, Power Sag, Undervoltage,
Overvoltage, Electrical Line Noise,
Frequency Variation, Switching Transient
Power management from SNMP manager and web browser
Product specifications are subject to change without further notice
Distributed By:
ISO-9001 & ISO-14001 / IEEE C62-41 / EN62040-1-1
www.sy-g.com
Computer Power c December 2015
ISO-9001 & ISO-14001 / IEEE C62-41 / EN62040-1-1
Features Description:
Computer Power VR 3KVA Rear Panel
Computer Power VR 1.5KVA Rear Panel
Computer Power MODELS: 1.5, 3, 6KVA Online UPS
7
3
5
• LCD Display Panel
- Remaining backup time information
- Fault information
-Mute operation
-Output & Battery voltage information
- Programable outlets information
- Mode operation information
- Battery information
- Input & Battery voltage information
6
4
1
3
2
1. Output receptacles
2. Standard communication port (USB - RS232)
3. Modem surge protection RJ-45
4. Intelligent Slot
5. External Battery Access
6. Circuit Breaker
7. Epo
Computer Power VR 6KVA Rear Panel
Standard
communication
port (USB - RS232)
Epo
Battery
Module
VR 6KVA
Input Breaker
• Programmable power management outlets
With programmable power management outlets, users can easily
and independently control load segments (only 1.5 & 3 KVA). During power failure,
this feature enables users to extend battery time to mission-critical
devices by shutting down the non-critical devices.
Intelligent slot (SNMP)
AC - Input / Output
Batt Connector
• ECO mode operation for energy saving
Offers efficiency as high as 97% to cut energy usage & cost. UPS power application via static bypass, timely
returning to online double conversion when the need arises.
SNMP Card
• Emergency Power Off (EPO) Function
This feature can secure the personnel and equipment in case of fires or other emergencies.
• Higher accuracy for output voltage
With advanced control firmware, Computer Power series provides high accuracy within +/- 1% for output voltage.
It can be applied to precious test & IT equipment.
• Smart battery charger design to optimize battery performance
Computer Power 1-3KVA models are equipped with 2 stage charger design for optimized battery performance.
This feature extends the useful service life of batteries and optimizes battery recharge time.
• Easy access for external battery connection.
In the rear panel
www.sy-g.com
Batt Breaker
Batt Conectors
Optional SNMP Card (Integrated with ViewPower Pro software)
• 50/60 Hz Frequency Converter Mode
Lock output frequency at 50Hz or 60Hz to suit power sensitive equipments. These UPS models can be used as
frequency
converters: 50 Hz input / 60 Hz output or 60 Hz input / 50 Hz output. In frequency converter mode derate the
capacity by 60%
• SNMP+USB+RS-232 multiple communications for 1-3K models
This feature allows either USB or RS-232 communication port to work with SNMP interface simultaneously.
1
2
• Double-conversion True Online UPS
A true double conversion UPS will provide clean, high level quality power to fully protect mission-critical devices
such as sensitive networks, small computer centers, servers, telecom applications, as well as for industrial applications.
• Wide input voltage range
Computer Power can still provide stable power to connected devices under unstable power environments.
4 7
6
5
• Allows control and monitoring of multiple UPSs through RJ-45
network connection
• Real-time dynamic graphs of UPS data (voltage, frequency, load level,
battery level)
• Warning notifications via audible alarm, broadcast, mobile messenger,
e-mail and SNMP traps
• Historic data log stored in centralized PC database
• Simple firmware upgrade with one click • Password security
protection and remote access management
• Supports optional environmental monitoring detector for
temperature, humidity and smoke
• 2-year product warranty SNMP Card
• Support following protocols: http, SNMP, SNMP V2, SNMP V3
Software
UPS Management Software
* Allows control and monitoring of multiple UPSs via LAN and INTERNET
* User-friendly power analysis graphs
* Real-time dynamic graphs of UPS data
* Safely OS shutdown and protection from data loss during power failure
* Warning notifications via audible alarm, broadcast, mobile messenger, and e-mail
* Scheduled UPS on/off, battery test, programmable outlet control, and audible alarm control
* Password security protection and remote access management
* Supports multiple OS and local languages
Features Description:
Computer Power VR 3KVA Rear Panel
Computer Power VR 1.5KVA Rear Panel
Computer Power MODELS: 1.5, 3, 6KVA Online UPS
7
3
5
• LCD Display Panel
- Remaining backup time information
- Fault information
-Mute operation
-Output & Battery voltage information
- Programable outlets information
- Mode operation information
- Battery information
- Input & Battery voltage information
6
4
1
3
2
1. Output receptacles
2. Standard communication port (USB - RS232)
3. Modem surge protection RJ-45
4. Intelligent Slot
5. External Battery Access
6. Circuit Breaker
7. Epo
Computer Power VR 6KVA Rear Panel
Standard
communication
port (USB - RS232)
Epo
Battery
Module
VR 6KVA
Input Breaker
• Programmable power management outlets
With programmable power management outlets, users can easily
and independently control load segments (only 1.5 & 3 KVA). During power failure,
this feature enables users to extend battery time to mission-critical
devices by shutting down the non-critical devices.
Intelligent slot (SNMP)
AC - Input / Output
Batt Connector
• ECO mode operation for energy saving
Offers efficiency as high as 97% to cut energy usage & cost. UPS power application via static bypass, timely
returning to online double conversion when the need arises.
SNMP Card
• Emergency Power Off (EPO) Function
This feature can secure the personnel and equipment in case of fires or other emergencies.
• Higher accuracy for output voltage
With advanced control firmware, Computer Power series provides high accuracy within +/- 1% for output voltage.
It can be applied to precious test & IT equipment.
• Smart battery charger design to optimize battery performance
Computer Power 1-3KVA models are equipped with 2 stage charger design for optimized battery performance.
This feature extends the useful service life of batteries and optimizes battery recharge time.
• Easy access for external battery connection.
In the rear panel
www.sy-g.com
Batt Breaker
Batt Conectors
Optional SNMP Card (Integrated with ViewPower Pro software)
• 50/60 Hz Frequency Converter Mode
Lock output frequency at 50Hz or 60Hz to suit power sensitive equipments. These UPS models can be used as
frequency
converters: 50 Hz input / 60 Hz output or 60 Hz input / 50 Hz output. In frequency converter mode derate the
capacity by 60%
• SNMP+USB+RS-232 multiple communications for 1-3K models
This feature allows either USB or RS-232 communication port to work with SNMP interface simultaneously.
1
2
• Double-conversion True Online UPS
A true double conversion UPS will provide clean, high level quality power to fully protect mission-critical devices
such as sensitive networks, small computer centers, servers, telecom applications, as well as for industrial applications.
• Wide input voltage range
Computer Power can still provide stable power to connected devices under unstable power environments.
4 7
6
5
• Allows control and monitoring of multiple UPSs through RJ-45
network connection
• Real-time dynamic graphs of UPS data (voltage, frequency, load level,
battery level)
• Warning notifications via audible alarm, broadcast, mobile messenger,
e-mail and SNMP traps
• Historic data log stored in centralized PC database
• Simple firmware upgrade with one click • Password security
protection and remote access management
• Supports optional environmental monitoring detector for
temperature, humidity and smoke
• 2-year product warranty SNMP Card
• Support following protocols: http, SNMP, SNMP V2, SNMP V3
Software
UPS Management Software
* Allows control and monitoring of multiple UPSs via LAN and INTERNET
* User-friendly power analysis graphs
* Real-time dynamic graphs of UPS data
* Safely OS shutdown and protection from data loss during power failure
* Warning notifications via audible alarm, broadcast, mobile messenger, and e-mail
* Scheduled UPS on/off, battery test, programmable outlet control, and audible alarm control
* Password security protection and remote access management
* Supports multiple OS and local languages
Computer Power
Rackmount Units:
VR-1.5KVA / VR-3KVA / VR-6KVA
Rackmount Online UPS
MODEL
Computer Power 1.5K (L)
PHASE
CAPACITY
1500 VA / 1350W
Computer Power3K (L)
Computer Power 6K (L)
Single phase with ground
3000 VA / 2400 W
2 phase In / 2 phase Out F 4 wires
6000 VA / 4800 W
INPUT
AC Cord and Connector
Input Voltage
10 AWG / L5-30P
16 AWG / 5-15P
Terminal Block
80-140VAC/115/120/127VAC(L-N)
200/208/220/230/240 (L-L)
80 - 150 VAC
Input Frequency Range
40 Hz ~ 70 Hz
Operating Frequency
Power Factor
UPS ON-LINE RACKMOUNT MODELS:
UPS VR-1.5KVA / VR-3KVA / VR-6KVA
50 Hz / 60 Hz Auto sensing
> 0.99
OUTPUT
Power Factor
Output Receptacles
0.9
4 # 5-15R
Output Voltage
Phase Angle
AC Voltage Regulation (Batt. Mode)
Output Frequency
Frequency Range (Batt. Mode)
Current Crest Ratio
0.8
2 # 5-20R / L5-30R
115/120/127 VAC
± 1%
50 Hz / 60 Hz Auto sensing
50 Hz ± 0.2 Hz or 60Hz ± 0.2 Hz
3:1
Typical Recharge Time
Charging Voltage
Zero
Pure Sinewave
86%
88%
89% (96% on ECO mode)
83%
85%
85%
12 V / 9 Ah
3
12 V / 9Ah
6
4 hours recover to 90% capacity
41.1 VDC ± 1%
Backup Time Full/ Half Load
INDICATORS
LCD Panel
50 Hz ± 0.1 Hz or 60Hz ± 0.1 Hz
< 2 % THD
Harmonic Distortion
Transfer Time
Waveform
EFFICIENCY
AC Mode
Battery Mode
BATTERY
Battery Type
Numbers
Terminal Block
110/115/120/127VAC(L-N)
200/208/220/230/240 (L-L)
0º / 120º / 180º / 240º
82.1 VDC ±1%
6 / 14 minutes
12 V / 9Ah
10 x 2
136 VDC ±1%
9 / 23 minutes
UPS status, Load level, Battery level, Input/Output voltage, Discharge timer, and Fault conditions
ALARM
Battery Mode
Low Battery
Beeps every 4 seconds
Beeps every second
Overload
Fault
Beeps twice every second
Continuously sounding
PHYSICAL
Dimension, D x W x H (mm)
Net Weight (kgs)
480 x 438 x 88 [2U]
600 x 438 x 88 [2U]
18.5
29
UPS:
668 X 438 X 133 [3U]
BATTERY: 580 X 438 X 133 [3U]
FEATURES:
• Continuous and clean power provided by our
UPS protects against downtime, data loss and
process interruption
• Friendly Led Display
• Full programable options
• Cold Start from batteries
• Double-conversion True Online UPS
• Input power factor correction 0.99
• 50Hz/60Hz frequency converter mode
• Programmable power management outlets
• Emergency power off function (EPO)
• Sealed lead acid maintenance free batteries
• ECO mode operation for energy saving (ECO)
• SNMP+USB+RS-232 multiple communications
• Smart battery charger design for optimized
battery performance
• Selectable output voltage via LCD panel
• Hot-swappable battery design
• Wide input voltage range for harsh environments
• Automatic Bypass for fault tolerance
• Generator compatible
• Two-year product warranty
• Protection for shortcuit and overload at the
output
83
ENVIRONMENT
Operational Humidity and Temperature
Noise Level
Operational Altitude
MANAGEMENT
Smart RS-232/USB
0-90 % RH @ 0- 40°C (non-condensing)
Less than 50dB @ 1 Meter
< 3000 meters
0-95% RH @ 0- 40°C (non-condensing)
Less than 60dB @ 1 Meter
Supports Windows® 2000/2003/XP/Vista/2008, Windows® 7, Linux, Unix, and MAC
Optional SNMP
• CD Software Included
• Protection for: Power Failure, Power Sag, Undervoltage,
Overvoltage, Electrical Line Noise,
Frequency Variation, Switching Transient
Power management from SNMP manager and web browser
Product specifications are subject to change without further notice
Distributed By:
ISO-9001 & ISO-14001 / IEEE C62-41 / EN62040-1-1
www.sy-g.com
Computer Power c December 2015
ISO-9001 & ISO-14001 / IEEE C62-41 / EN62040-1-1
Was this manual useful for you? yes no
Thank you for your participation!

* Your assessment is very important for improving the work of artificial intelligence, which forms the content of this project

Download PDF