tag: ah_cu-1a model: 40ruaa08a2a6

tag: ah_cu-1a model: 40ruaa08a2a6
By guy at 12:05 pm, Jul 10, 2015
SUBMITTAL ***FOR APPROVAL***
TAG: AH_CU-1A
MODEL: 40RUAA08A2A6-0A0A0_38AUZA07A0A5-0A0A0
SPLIT SYSTEM AIR HANDLER_CONDENSING UNIT
Project
66 Orland Square Dr. Landlord Renovations
Location
Orland Park, IL
Contractor
Classic Air, Inc.
Engineer
Cartland Kraus
Date
June 22, 2015
Table Of Contents
Project: 66 Orland Square Dr. Landlord Renovations
Prepared By:
06/22/2015
12:06PM
AH_CU-1A .............................................................................................................................................................................3
Unit Report ............................................................................................................................................................................................... 4
Performance Summary............................................................................................................................................................................. 6
Acoustic Summary ................................................................................................................................................................................. 11
Certified Drawing .................................................................................................................................................................................... 13
Commercial Split Systems Builder 1.33
Page 3 of 19
AH_CU-1A
Project: 66 Orland Square Dr. Landlord Renovations
Prepared By:
06/22/2015
12:06PM
AH_CU-1A
AH_CU-1A
Submittal Cover Sheet
Unit Report
Performance Summary Report
Acoustic Summary
Certified Drawings
Commercial Split Systems Builder 1.33
Page 4 of 19
Unit Report For AH_CU-1A
Project: 66 Orland Square Dr. Landlord Renovations
Prepared By:
06/22/2015
12:06PM
Unit Report
Outdoor Unit Parameters
Unit Quantity: .................................................. 1
Unit Model: ............................................. 38AUZ
Unit Size: ................................................ 6 Tons
Voltage: ............................................... 208-3-60 V-Ph-Hz
Condenser Coil: ....................................... Al/Cu
No. of DX Circuits:........................................... 1
System Parameter
System Quantity: ............................................. 1
Refrigerant Type: ................................. PURON
Compressor Quantity: ..................................... 1
Compressor Type:................................... Scroll
Std. Capacity Steps:.................................... 100
Std. Min. Outdoor Temp(Cooling): ............. 35.0 °F
No. of Outdoor fans: ........................................ 2
Indoor Unit Parameters
Unit Model: ............................................ 40RUA
Unit Size: ............................................. 7.5 Tons
No. of Splits: .................................................... 1
Voltage: ............................................... 208-3-60 V-Ph-Hz
Outdoor Unit Dimensions and Weight
Unit Length: ........................................... 4' 11.4''
Unit Width: .............................................. 3' 9.9''
Unit Height: ............................................. 3' 6.4''
Unit Shipping Weight:.................................. 389 lb
Unit Operating Weight: ................................ 389 lb
Indoor Unit Dimensions and Weight
Unit Length: ............................................. 4' 1.0''
Unit Width:............................................... 2' 4.2''
Unit Height: ............................................. 4' 8.1''
Unit Shipping Weight: .................................. 404 lb
Unit Operating Weight: ................................ 404 lb
Warranty Information (Note: for US & Canada only)
NOTE: Please see Warranty Catalog 808-218 for explanation of policies and ordering methods.
Ordering Information
Part Number
Base Unit - Outdoor
Description
38AUZA07A0A5-0A0A0
1
Base Unit
Al/Cu Condensing Coil
Standard Refrigerant Options
Service Options - None
Electrical Options - None
Packaging Options - Standard
Standard Electrical Mechanical Controls
Single Stage
Base Unit - Indoor
40RUAA08A2A6-0A0A0
Accessories
VST2800
Quantity
1
1
1
1
1
1
1
1
Base Unit
Std Static, Std Eff Motor/ Medium Drive
Cabinet Paint - None
None- No Controller
1
1
1
Venstar Commercial Programmable Thermostat
1
Commercial Split Systems Builder 1.33
Page 5 of 19
Unit Report For AH_CU-1A
Project: 66 Orland Square Dr. Landlord Renovations
Prepared By:
CAECOMZR001B00
CASUSPEN001A00
CAELHEAT013A00
Economzer - Enthalpy Controlled for Indoor Unit
Overhead Suspension Brackets for Indoor Unit
35.0 kW, 240-3-60 Electric Heater
Commercial Split Systems Builder 1.33
06/22/2015
12:06PM
1
1
1
Page 6 of 19
Performance Summary For AH_CU-1A
Project: 66 Orland Square Dr. Landlord Renovations
Prepared By:
06/22/2015
12:06PM
Performance Summary
System: .................................................................................................................. 38AUZ007/40RUA008
System Quantity: ....................................................................................................................................... 1
Altitude: .................................................................................................................................................. 0.0 ft
EER @ ARI Conditions: ....................................................................................................................... 11.5
IEER:.................................................................................................................................................... 12.2
Suction Line Loss: .................................................................................................................................. 1.4 °F
System meets the Energy Star EER rating.
Liquid and Suction Line Sizing
Pipe Length
0 - 25
26 - 50
51 - 75
76 - 100
101 - 125
Liquid Line Size
3/8
3/8
1/2
1/2
1/2
Suction Line Size
7/8
7/8
1 1/8
1 1/8
1 1/8
Outdoor Unit Parameters
Unit Quantity: 1
PartNumber: 38AUZA07A0A5-0A0A0
Unit Model: 38AUZ
Unit Size:
6 Tons
Condenser Coil:
Al/Cu
No. of DX Circuits:
1
Voltage:
208-3-60
V-Ph-Hz
Clg Ent Air DB:
95.0
°F
Outdoor Electrical Data
Unit Voltage: 208-3-60
V-Ph-Hz
Total Compressor Power of Unit #1:
NA
Voltage Range Min: 187
V
Voltage Range Max: 253
V
Compressor Quantity: 1
Fan Motors Qty:
2
Notice: Outdoor unit elect. data is based on 208-3-60
Control Panel SCCR: 5kA RMS at Rated Symmetrical Voltage
Outdoor Electrical Data on Units produced on or prior to 02/08/2015
Unit#1 MCA: 27.0
Amps
Unit#1 MOCP:
45.0
Amps
Compressor RLA:
19
Compressor LRA:
123
Outdoor Electrical Data on Units produced on or after 02/09/2015
Unit#1 MCA: 28.0
Amps
Unit#1 MOCP:
45.0
Amps
Compressor RLA:
19.6
Compressor LRA:
136
Indoor Unit Parameters
PartNumber: 40RUAA08A2A6-0A0A0
Unit Model: 40RUA
Unit Size:
7.5 Tons
Coil Rows: 4
No. of Splits: 1
Voltage:
208-3-60
V-Ph-Hz
Actual Airflow:
2400.0 CFM
Standard Airflow:
2400.0 CFM
Total Clg Cap.(Gross): 75.4
MBH
Sensible Clg Cap.(Gross):
59.3
MBH
Commercial Split Systems Builder 1.33
Page 7 of 19
Performance Summary For AH_CU-1A
Project: 66 Orland Square Dr. Landlord Renovations
Prepared By:
Ent Air DB: 80.0
Ent Air WB: 67.0
Ent Enthalpy: 31.44
Lvg Air DB: 57.1
Lvg Air WB: 57.1
Lvg Enthalpy: 24.45
Coil Bypass Factor:
06/22/2015
12:06PM
°F
°F
BTU/lb
°F
°F
BTU/lb
NA
Accessory Heating
Heating Type:Electric
Acc Htg Capacity:
89.74
Acc Htg Ent. Air Temp: 60.0
Acc Htg Lvg. Air Temp:
Acc Heater Nominal Voltage:
Acc Heater Nominal kW:
Acc Heater Actual Voltage:
Acc Heater FLA:
73.0
Acc Stage 1 Actual kW:
Acc Stage 2 Actual kW:
MBH
°F
94.6
°F
208-3-60
35.0
kW
208-3-60
amps
15.0
kW
11.3
kW
Indoor Supply Fan
Indoor Unit External Static:
0.75
in wg
Economizer Loss:
0.07
in wg
Grille Loss: 0.00
in wg
Plenum Loss: 0.00
in wg
Acc. Heating Loss:
0.07
in wg
Total Ext Static:
0.89
in wg
Fan Speed: 783
RPM
Fan Power: 0.95
BHP
Fan Motor Max:
2.40
BHP
Fan Motor FLA:
6.9
Amps
Motor and Medium Static Drive Required.
Selected Medium Static Drive Range: 733 - 949
Indoor Electrical Data
Unit Voltage: 208-3-60
V-Ph-Hz
Unit MCA:
99.8
Amps
Unit MOCP: 100.0
Amps
Notice: Indoor unit elect. data is based on 208-3-60
Acoustics
Sound Power Levels, db re 10E-12 Watts
Outdoor Unit (dB)
A-Weighted Total Level
63Hz
125Hz
250Hz
500Hz
1000Hz
2000Hz
4000Hz
8000Hz
Sound Message
84.6
89.3
85.0
82.0
82.7
80.2
75.2
71.0
66.0
Sound for AUZ007
Indoor Unit
(dB,Ducted)
88.4
95.3
91.3
87.3
86.3
82.3
80.3
76.3
NA
Sound for RUA008
Acoustic Notes:
1. 38AUZ07-12 units are in accordance with ARI 270-2008 Sound Rating of Unitary Equipment.
2. The sound data for all 38AUZ14 units are based on upon
a limited amount of actual testing with the estimated sound
power data being generated from this data in accordance with ARI 370-2001 for Large Outdoor Refrigerating and Air-Conditioning
Equipment.
Commercial Split Systems Builder 1.33
Page 8 of 19
Performance Summary For AH_CU-1A
Project: 66 Orland Square Dr. Landlord Renovations
Prepared By:
06/22/2015
12:06PM
3. The indoor duct sound power data is estimated based on the ASHRAE calculation approach from the ASHRAE handbook 1987
HVAC Systems and Applications, Chapter 52.
4. The acoustic center of the unit is located at the geometric center of the unit.
5. All estimated sound power levels, dB re 1 Pico watt should not be guaranteed or certified as being the actual sound power levels.
Commercial Split Systems Builder 1.33
Page 9 of 19
Performance Summary For AH_CU-1A
Project: 66 Orland Square Dr. Landlord Renovations
Prepared By:
Advanced Accoustics Parameters
1. Unit height above ground: .................................... 1.0
2. Horizontal distance from unit to receiver: ........... 20.0
3. Receiver height above ground: ............................ 5.7
4. Height of obstruction: ........................................... 0.0
5. Horizontal dist. from obstruction to receiver: ........ 0.0
6. Horizontal dist. from unit to obstruction: ............... 0.0
06/22/2015
12:06PM
ft
ft
ft
ft
ft
ft
Detailed Acoustics Information
Octave Band Center Frequency, Hz
Sound Power Levels at Unit's Acoustic Center (Lw), dB
A-Wgted Sound Power Levels at Unit's Acoustic Center (LwA), dBA
Sound Press. Levels at Dist. Specified above (Lp), dB
A-Wgted Sound Press. Levels at Dist. Specified above (LpA), dBA
63
89.3
63.1
65.0
38.8
125
85.0
68.9
60.7
44.6
250
82.0
73.4
57.7
49.1
500
82.7
79.5
58.4
55.2
1k
80.2
80.2
55.9
55.9
2k
75.2
76.4
50.9
52.1
4k
71.0
72.0
46.7
47.7
8k
66.0
64.9
41.7
40.6
Overall
92.2
84.6
67.9
60.3
Calculation methods used in this program are patterned after the ASHRAE Guide; other ASHRAE Publications and the AHRI Acoustical
Standards. While a very significant effort has been made to insure the technical accuracy of this program, it is assumed that the user
is knowledgeable in the art of system sound estimation and is aware of the tolerances involved in real world acoustical estimation.
This program makes certain assumptions as to the dominant sound sources and sound paths which may not always be appropriate to
the real system being estimated. Because of this, no assurances can be offered that this software will always generate an accurate
sound prediction from user supplied input data. If in doubt about the estimation of expected sound levels in a space, an Acoustical
Engineer or a person with sound prediction expertise should be consulted.
Commercial Split Systems Builder 1.33
Page 10 of 19
Performance Summary For AH_CU-1A
Project: 66 Orland Square Dr. Landlord Renovations
Prepared By:
06/22/2015
12:06PM
40RUA008 with Standard Capacity Coil
3
1200 RPM
1100 RPM
Static Pressure (in. wg.)
1000 RPM
2
900 RPM
SC
800 RPM
5.00 BHP
700 RPM
1
RP
600 RPM
500 RPM
3.70 BHP
400 RPM
1.00 BHP
1.30 BHP
0
0
1
2
3
4
2.00 BHP
3.00
BHP
2.90
BHP
2.40
BHP
5
Airflow (CFM - thousands)
RPM = 783 BHP = 0.95 Maximum RPM = 1200 Maximum HP = 2.40
Shaded Area - Recommended Operating Range
SC - System Curve RP - Rated Point MP - Minimum Point
Commercial Split Systems Builder 1.33
Page 11 of 19
Acoustic Summary For AH_CU-1A
Project: 66 Orland Square Dr. Landlord Renovations
Prepared By:
06/22/2015
12:06PM
Acoustic Summary
Outdoor Unit Parameters:
Tag Name: ............................................. AH_CU-1A
Unit Model: .................................................... 38AUZ
Unit Size: ....................................................... 6 Tons
System Type: ................................Dx Cooling Only
Refrigerant Type: ........................................ PURON
Compressor Quantity: ............................................ 1
Compressor Type:.......................................... Scroll
Advanced Accoustics Parameters
1. Unit height above ground: .................................... 1.0
2. Horizontal distance from unit to receiver: ........... 20.0
3. Receiver height above ground: ............................ 5.7
4. Height of obstruction: ........................................... 0.0
5. Horizontal distance from obstruction to receiver: . 0.0
6. Horizontal distance from unit to obstruction: ........ 0.0
Detailed Acoustics Information
ft
ft
ft
ft
ft
ft
Octave Band Center Frequency, Hz
Sound Power Levels at Unit's Acoustic Center (Lw), dB
A-Wgted Sound Power Levels at Unit's Acoustic Center (LwA), dBA
Sound Press. Levels at Dist. Specified above (Lp), dB
A-Wgted Sound Press. Levels at Dist. Specified above (LpA), dBA
63
89.3
63.1
65.0
38.8
125
85.0
68.9
60.7
44.6
250
82.0
73.4
57.7
49.1
500
82.7
79.5
58.4
55.2
1k
80.2
80.2
55.9
55.9
2k
75.2
76.4
50.9
52.1
4k
71.0
72.0
46.7
47.7
8k
66.0
64.9
41.7
40.6
Overall
92.2
84.6
67.9
60.3
Calculation methods used in this program are patterned after the ASHRAE Guide; other ASHRAE Publications and the AHRI Acoustical
Standards. While a very significant effort has been made to insure the technical accuracy of this program, it is assumed that the user
is knowledgeable in the art of system sound estimation and is aware of the tolerances involved in real world acoustical estimation.
This program makes certain assumptions as to the dominant sound sources and sound paths which may not always be appropriate to
the real system being estimated. Because of this, no assurances can be offered that this software will always generate an accurate
sound prediction from user supplied input data. If in doubt about the estimation of expected sound levels in a space, an Acoustical
Engineer or a person with sound prediction expertise should be consulted.
Acoustic Notes:
1. 38AUZ07-12 units are in accordance with ARI 270-2008 Sound Rating of Unitary Equipment.
2. The sound data for all 38AUZ14 units are based on upon
a limited amount of actual testing with the estimated sound
power data being generated from this data in accordance with ARI 370-2001 for Large Outdoor Refrigerating and Air-Conditioning
Equipment.
3. The indoor duct sound power data is estimated based on the ASHRAE calculation approach from the ASHRAE handbook 1987
HVAC Systems and Applications, Chapter 52.
4. The acoustic center of the unit is located at the geometric center of the unit.
5. All estimated sound power levels, dB re 1 Pico watt should not be guaranteed or certified as being the actual sound power levels.
Indoor Unit Parameters:
Tag Name: ............................................. AH_CU-1A
Unit Model: ....................................................40RUA
Unit Size: .................................................... 7.5 Tons
System Type: ................................Dx Cooling Only
External Static Pressure: ................................... 0.89 in wg
Fan Speed: ........................................................ 783 RPM
Fan BHP: .......................................................... 0.95 BHP
Octave Band Center Frequency, Hz
Sound Power,dB
A-Weighted Sound Power, dBA
31
NA
NA
63
95.3
69.1
125
91.3
75.2
250
87.3
78.7
500
86.3
83.1
1k
82.3
82.3
2k
80.3
81.5
4k
76.3
77.3
8k
NA
NA
Total
97.8
88.4
Notes:
1. The above estimated duct sound power levels are based upon the ASHRAE calculation approach from the ASHRAE 1987 HVAC
Systems and Applications handbook, Chapter 52.
2. Since this data is calculated, these sound power levels may be different than the actual sound power levels.
Commercial Split Systems Builder 1.33
Page 12 of 19
Acoustic Summary For AH_CU-1A
Project: 66 Orland Square Dr. Landlord Renovations
Prepared By:
06/22/2015
12:06PM
3. The acoustic center of the units is located at the geometric center of the unit.
Commercial Split Systems Builder 1.33
Page 13 of 19
Certified Drawing for AH_CU-1A
Project: 66 Orland Square Dr. Landlord Renovations
Prepared By:
06/22/2015
12:06PM
Certified Drawing
Commercial Split Systems Builder 1.33
Page 14 of 19
Certified Drawing for AH_CU-1A
Project: 66 Orland Square Dr. Landlord Renovations
Prepared By:
Commercial Split Systems Builder 1.33
06/22/2015
12:06PM
Page 15 of 19
Certified Drawing for AH_CU-1A
Project: 66 Orland Square Dr. Landlord Renovations
Prepared By:
Commercial Split Systems Builder 1.33
06/22/2015
12:06PM
Page 16 of 19
Certified Drawing for AH_CU-1A
Project: 66 Orland Square Dr. Landlord Renovations
Prepared By:
06/22/2015
12:06PM
DIMENSIONS (cont.)
OVERHEAD SUSPENSION ACCESSORY
40RU
UNIT SIZES 07-12
(FRONT)
UNIT SIZES 14-25
(FRONT)
UNIT SIZES 28, 30
(FRONT)
NOTE: Dimensions in [ ] are millimeters.
C09485
17
Commercial Split Systems Builder 1.33
Page 17 of 19
Certified Drawing for AH_CU-1A
Project: 66 Orland Square Dr. Landlord Renovations
Prepared By:
06/22/2015
12:06PM
DIMENSIONS (cont.)
ELECTRIC HEAT ACCESSORY
40RU
UNIT SIZES 07 - 12
UNIT SIZE 14 - 30
C09489
40RU
UNIT SIZE
14 --- 25
28, 30
A
1'-3 1 /
B
4
[387.4]
1'-3 3 /8
[390.5]
4'-6 3 /
C
8
[1381.1]
5'-4 7 /8
[1636.8]
25/
16
[58.7]
2 1 / 16
[52.4]
D
2'-1 1 /
E
10 5 /
4
[641.4]
2'-6 3 / 16
[766.8]
F
8
[269.9]
1'- 1 /4
[311.2]
1'-4
[406.4]
1'-7
[482.6]
G
1'-4 5 /
H
16
[414.3]
1'-4 5 /16
[414.3]
1'-6 3 /
J
4
[476.3]
1'-10
[558.8]
1- 7 /
8
[327.0]
1-4 7 /16
[417.1]
NOTE : Dimensions in [ ] are millimeters.
23
Commercial Split Systems Builder 1.33
Page 18 of 19
Certified Drawing for AH_CU-1A
Project: 66 Orland Square Dr. Landlord Renovations
Prepared By:
06/22/2015
12:06PM
DIMENSIONS (cont.)
ECONOMIZER ACCESSORY
40RU
UNIT SIZES 07-12
UNIT SIZES 14 - 25
UNIT SIZES 28, 30
NOTE:
1. For horizontal unit applications, economizer can be attached to end of unit opposite duct connections.
2. Dimensions in [ ] are millimeters.
C09488
22
Commercial Split Systems Builder 1.33
Page 19 of 19
Venstar Programmable Thermostat
T2800
STANDARD FEATURES:
• Up to 3-Occupied, 1-Unoccupied periods per day, with copy command for easy programming
• Accepts humidification/dehumidification control module (Venstar part number ACC0430)
• Auto changeover, 3-stage heat, 2-stage cool for use with gas/electric, heat pump, electric & hydronic heat
• Configurable for manual changeover, also configurable programmable or non-programmable
• Adjustable deadbands and timers
• 3 configurable outputs for maximum flexibility (MISC1, MISC2, MISC3)
• Extra 6th and 7th outputs (beyond our standard thermostat)
• Smart Fan (keeps the fan from running during unoccupied periods)
• Smart recovery
• Display shows both heating an cooling setpoints and room temperature simultaneously
• All programming and setpoints stored in non-volatile memory, and are never lost in power failure
• Service filter and service UV lamp indicators
• Red/Green LED shows whether thermostat is calling for heating or cooling
• 5-minute compressor time guard and adjustable cycle limit, both defeatable for servicing equipment
• Outdoor sensor ready with high and low temperature of the day
• Thermoglow backlit electro-luminous display and backlit color coded keys and legends
• Accepts accessory IR Remote Control system (Venstar part number ACC0431)
• Accepts accessory EZ Programmer (Venstar part number ACC0432)
• For accessory locking cover use (Venstar part number ACC0620)
MODEL:
JOB NAME:
LOCATION:
BUYER:
ENGINEER:
T2800
QUANTITY:
DATE:
BUYER P.O.#:
Was this manual useful for you? yes no
Thank you for your participation!

* Your assessment is very important for improving the work of artificial intelligence, which forms the content of this project

Download PDF

advertising