Output interfaces

Output interfaces
EN
Output interfaces
TDS20061xx
HVAC Modbus Slave interface
The TDS20061xx is the HVAC Modbus Slave which must be used in combination with the
TDS14061 to realize HVAC integration.
The TDS20061xx can be one of the following brands:
TDS20061DA = Daikin
TDS20061ME = Mitsubishi Electric (max. 50 indoor units)
TDS20061TO = Toshiba
TDS20061SY = Sanyo
TDS20061HI = Hitachi
TDS20061PA = Panasonic
APPLICATION
Interface for control of HVAC systems. Can support up to 10
outdoor units. To be combined with TDS14061.
CONNECTIONS
HVAC SYSTEM BUS
For TDS20061DA (DAIKIN):
Connect the F1/F2 terminals from TDS20061DA with F1/F2
Out/Out terminal from D3-net which is located on an outdoor or
indoor unit of the HVAC system. Do not connect the
TDS20061DA HVAC system bus to the terminals on one of the
indoor units (F1/F2 In/Out).
CHARACTERISTICS
Functionality’s
Supported functionalities (Depends on HVAC system):





5 Modes: Auto,Heat,Cool,Dry,Vent
Adjustable speed (airflow)
Set temperature
Measured room temperature
HVAC error codes
For TDS20061ME (MITSUBISHI ELECTRIC):
Connect the M1/M2 terminals from TDS20061ME with the
M1/M2 terminal from M-net which is located on an outdoor or
indoor unit of the HVAC system.
LCD display
16x2 characters.
For TDS20061TO (TOSHIBA):
Connect the U1/U2 terminals from TDS20061TO with the
U1/U2 terminal from TCC-link net which is located on an
outdoor or indoor unit of the HVAC system.
SETTINGS
Configuration
Automatically with TDS14061.
DIP switches inside TDS20061DA
Any non-VRV unit (indoor units for residential use) that can be
extended with Daikin D3-net will be compatible with
TDS20061DA.
In accordance, 4 DIP switches inside the TDS20061DA need to
be switched ON (default OFF) ONLY if no centralized VRV
controller is installed.
If non-VRV units are used, each Multi/Split/SkyAir indoor unit
has to be provided with a communications interface from
Daikin. Contact Daikin for more info on these interfaces and
possibilities.
DIP switches inside TDS20061ME
Any non-VRF unit (indoor units for residential use) that can be
extended with the M-net will be compatible with TDS20061ME.
In accordance, 4 DIP switches inside the TDS20061ME need
to be switched ON (default OFF) ONLY if no centralized VRF
controller is installed.
For TDS20061HI (HITACHI):
Connect the 1/2 terminals from TDS20061HI with the 1/2
terminal from H Link-net which is located on an outdoor or
indoor unit of the HVAC system.
MODBUS data + power
2 x 2 x 0,5mm², unshielded.
This connection should be connected to the TDS14061 HVAC
Modbus Master interface with the supplied cable.
POWER CONSUMPTION
Max. 80mA
DIMENSIONS
115 W x 63 H x 32 D (mm)
NET | GROSS WEIGHT
0,230 kg | 0,350 kg
INSTALLATION
DIN-rail mounting
6.5 modules wide
PACKAGING CONTENT
TDS20061xx interface
Cable for connecting with TDS14061
HVAC brand specific Remote Controller (the wall
control panel).
For service reasons it is recommended to provide the brand
specific remote controller panel(s). This allows the HVAC
technician to service his system in the usual way without the
need of TELETASK system knowhow (see also the remark
below).
STORAGE
Temperature
-20°C to +65°C
Relative humidity
15% to 85%
REMARK FOR TDS20061HI HITACHI
 It is necessary to install the HITACHI local wired remote
controllers of the HITACHI HVAC system to guarantee optimal
compatibility and functionality!!!
©, TELETASK, GENT, 2016
For TDS20061SY (SANYO):
Connect the U1/U2 terminals from TDS20061SY with the
U1/U2 terminal from S3-net which is located on an outdoor or
indoor unit of the HVAC system.
IP PROTECTION RATE
IP30
122
Version August 2016
TELETASK can’t be responsible for potential errors in the data sheets and technical documentation. Changes in the product features can be made at any time, without prior notice
EN
Output interfaces
OPERATING RANGE
Temperature
0°C to +45°C max.
LIMITED WARRANTY
2 years
Relative humidity
5% to 80% at 25°C (no humidity/condense)
DEVICE COMPATIBILITY LIST:
DAIKIN
TDS20061DA
 Remark: Alternatively Daikin
VRV units can also be
integrated with your
TELETASK DoIP system by
means of the IP Software
license TDS15200 in
combination with the Daikin
iTouch Ethernet interface.
For more details see
datasheet TDS15200.
MITSUBISHI ELECTRIC
TDS20061ME
 Remark: Alternatively
Mitsubishi Electric VRF units
can also be integrated with
your TELETASK DoIP system
by means of the IP Software
license TDS15200 in
combination with the Mitsubishi
Electric GB50 or AG150
Ethernet gateway.
Outdoor unit types
Indoor unit types
RXYQ-M/P (VRV II,VRV III)
RXYK (VRV)
RXYSQ-M/P (VRV Small)
RXY-M
RWEYQ
REYQ
FXCQ
FXNQ
FXLQ
FXFQ
FXKQ
FXZQ
FXDQ
FXSQ
FXAQ
Multi, Split and Sky Air systems
FXUQ
will also be compatible when using FXMQ
D3 Net interfaces (KRP928 or
FXHQ
DTA112)
VKM
VAM
Outdoor unit types
Indoor unit types
PUHY
PURY
PQHY
PQRY
PUMY
PUHYP250YJM-A
PKFY
PFFY-PVKM
PLFY-P-VCM
PEFY-P-VMS1
PFFY-P-VLRM
PCFY-P-VGM
PLFY-P-VLMD
PEFY-P-VMM
PFFY-P-VLEM
PLFY-P-VBM
PMFY-P-VBM
PEFY-P-VMH
PEFYP50VMA-E
PEFYP100VMA-E
PEFYP32VMA-E
PEFY-P63VMA(L)-E
For more details see
datasheet TDS15200.
Any non VRF unit (indoor units for residential use)
that can be extended with the M-net will be
compatible with TDS20061ME.
TOSHIBA
TDS20061TO
©, TELETASK, GENT, 2016
Outdoor unit types
Indoor unit types
MCY-MAP.HT
MMY-MAP.T8
MMY-MAP.HT8
MMY-MAP.FT8
MMU-AP.H
MMU-AP.YH
MMD-AP.SPH
MML-AP.H
MMD-AP.HFE
MMU-AP.MH
MMD-AP.BH
MMC-AP.H
MML-AP.BH
MMU-AP.WH
MMD-AP.H
MMK-AP.H
MMF-AP.H
123
Version August 2016
TELETASK can’t be responsible for potential errors in the data sheets and technical documentation. Changes in the product features can be made at any time, without prior notice
EN
Output interfaces
SANYO
TDS20061SY
HITACHI
TDS20061HI
PANASONIC
TDS20061PA
©, TELETASK, GENT, 2016
Outdoor unit types
Indoor unit types
MFL
EFL
SPW_CO
SPW-C
SPW-CR
SGP-EZ
SGP-EW
NWFL
NDHP
NPFL
NPFL
NDSLP
NKFL
NFFL
NDLP
NK2FL
NFMFL
SPW-X
SPW-XM
SPW-ADR
SPW-SR
SPW-LDR
SPW-FUR
SPW-K
SPW-FMR
SPW-FTR
SPW-FR
SPW-KR
SPW-UMR
SPW-U
Outdoor unit types
Indoor unit types
RAS-FSN
RAS-FXNE
RCI
RPC
RPFI
RCD
RPK
RPI
RPF
Outdoor unit types
Indoor unit types
Not yet available
Not yet available
124
Version August 2016
TELETASK can’t be responsible for potential errors in the data sheets and technical documentation. Changes in the product features can be made at any time, without prior notice
EN
Output interfaces
SCHEMATIC DRAWING
©, TELETASK, GENT, 2016
125
Version August 2016
TELETASK can’t be responsible for potential errors in the data sheets and technical documentation. Changes in the product features can be made at any time, without prior notice
Was this manual useful for you? yes no