E85005-0134 – EST3X Life Safety Control System

E85005-0134 – EST3X Life Safety Control System
EST3X
LIFE SAFETY
&
INCIDENT MANAGEMENT
EST3X
Head End
EST3X
Initiating
Devices
Submittal Guide
Networked intelligent life safety with voice audio
Notification
Appliances
Hazardous Location
Devices
Door Holders
& Relays
S
e
Se
e
w
e w
hat’s
h
at
's
le
possib
possible
w.
no
now
...
LIFE SAFETY
&
INCIDENT MANAGEMENT
EST3X
Head End
Project: ___________________________
Contact: ___________________________
Date:
___________________________
Initiating
Devices
Thank you for giving us the opportunity to provide this submittal for an EST3X
Life Safety System. EST3X represents some of the most technologically
advanced innovations the life safety industry has ever seen – innovations that
will make your building and its occupants safe and secure.
comprehensive presentation of related system components and devices.
Products we are submitting for your consideration are indicated by a
checkmark in the margins of the pages that follow.
Notification
Appliances
This guide provides a summary of these innovations and includes a
More detailed information can be found in individual data sheets dedicated
useful product information, are available electronically on our LifeLines
CD-ROM. This exhaustive collection of life safety related literature is fully
searchable.
Thank you for giving us the opportunity to provide this submittal. Please do
not hesitate to contact us should you require further information.
_____________________________
Door Holders
& Relays
Hazardous Location
Devices
to each product. All these sheets, along with guide specifications and other
EST3X
Head End
Initiating
Devices
Submittal Guide
Networked intelligent life safety with voice audio
EST3X
Notification
Appliances
Hazardous Location
Devices
Door Holders
& Relays
vii
EST3X Submittal Guide
Intelligent fire alarm solutions for small buildings
© 2016 United Technologies Corporation
All rights reserved. Specifications subject to change without notice.
EDWARDS is a UTC brand.
1016 Corporate Park Drive, Mebane, NC 27302
E85005-0134
Wiring diagrams provided herein are for information and reference only and are not to be used for installation purposes. Consult the appropriate installation documents for wiring and configuration details.
This guidebook is for information only and is not intended as a substitute for verbatim legislated requirements. For
authoritative specifications regarding the application of life safety, security, and access control systems, consult
current editions of applicable codes and standards. For authoritative interpretation of those codes and standards,
consult your local authority having jurisdiction.
While every effort has been made to ensure the accuracy and completeness of this guidebook, the authors and
publishers assume no responsibility for errors, inaccuracies, omissions, or any inconsistencies herein.
EST, Genesis Series, and Signature Series are trademarks of United Technologies Corporation.
EST3X
Life Safety Solutions
1
EST3X represents the latest generation of life safety
control panels for mid to
large multi-message displays
and innovative controls, intuitive interfaces, and bold colored
cabinets — these systems capture the
imagination, and catch the eye. But behind
New microprocessors and chipsets take full advantage of
the latest advances in computing technology, leading to
smarter, faster, higher-capacity processing and more efficient designs. EST3X’s patented Voltage Boost™ technology, for example, delivers consistent voltage – even
at low battery power – resulting in lighter cable requirements and/or longer runs. That saves time and money.
High performance processing also leads to powerful net-
The wide range of EST3X configurations include stand-
Notification Appliances
31
Wall Strobes, Horns & Chimes......................................... 33
Low Frequency Horns and Horn-Strobes........................ 34
LED Strobes and Horn-Strobes....................................... 34
Outdoor Horns & Strobes................................................ 35
Wall Speakers & Speaker-Strobes................................... 36
Ceiling Speakers, Horns & Strobes.................................. 37
Outdoor Speakers & Strobes........................................... 38
LED Strobes and Horn-Strobes....................................... 39
High Power Speaker Arrays............................................. 39
Medium Power Speaker Arrays....................................... 40
Audible Signals................................................................ 41
Harsh Environment Signals.............................................. 42
Accessories..................................................................... 43
Hazardous Location Devices
45
Initiating Devices............................................................. 46
Notification Appliances.................................................... 47
Door Holders & Relays
48
Door Holders................................................................... 48
Relays............................................................................. 48
SPDT Relays................................................................... 49
Door Holders
& Relays
working features and versatile digital audio functionality.
CO, Smoke and Heat Detectors...................................... 20
Fire Detectors.................................................................. 21
Duct Smoke Detectors.................................................... 21
Detector Bases............................................................... 22
Detector Accessories...................................................... 23
Input/Output Modules..................................................... 24
Pull Stations.................................................................... 30
Hazardous Location
Devices
the LCD display is where they really shine.
Intelligent Analog Initiating Devices 19
Notification
Appliances
large sized applications. With
Initiating
Devices
System Layout and Wiring................................................. 2
Assembly.......................................................................... 3
Dimensions....................................................................... 3
Control Panels................................................................... 4
Option Cards..................................................................... 4
Local Rail Modules............................................................ 6
Control and Display......................................................... 10
Network Audio................................................................ 11
Remote Annunciation...................................................... 13
FireWorks........................................................................ 15
Power Supplies............................................................... 16
Network Accessories...................................................... 17
EST3X
Head End
EST3X Network
alone operation, networking with up to eight nodes, or
integration with an EST3 network comprising as many as
64 nodes — complete with mass notification capabilities
and display of security events.
ix
See what’s
possible now.
D e t e c t i o n
&
A l a r m
S i n c e
1 8 7 2 .
Mass Notification • Smoke Detection • Graphical Monitoring and Control • Instant Messaging • Aspirating Smoke Detectors • Industrial
Signaling • Voice Evacuation • Smoke Control • Fire Suppression • Intercom • Timekeeping • CO Detection • Heat Detection •
Audible & Visible Signaling • Voicemail Messaging • Duct Smoke Detection • Giant Voice • Electronic Signage • Area of Rescue
EST3X
Local and Remote Annunciation
Up to 30 R-Series LCD, LED annunciators and driver interface
cards may be configured for each
node on the EST3X network. No
additional nodes are required for
annunciation purposes. In addition,
Up to 30 R-Series annunciators
may be configured for each
EST3X supports EST3 network
node on the EST3X network.
annunciators, while GCI and GCIX
driver interface cards provide cost-effective graphic annunciation solutions. And all annunciator inputs and outputs are
easily programmable through the rules and labels function of
EST3X’s Software Definition Utility.
Power to Count On
EDWARDS’ patented Voltage Boost™ technology delivers a
consistent 22.5 Vdc – even at low battery power. This means
lighter gauge cable can be used for equivalent distances compared with conventional power supplies, or longer wire runs on
the same gauge cable. Either way, this breakthrough technology saves time and equipment costs, making EST3X not only a
high-performance solution — but a cost-effective one as well.
EST3X’s four on-board Notification Appliance Circuits
are fully synchronized to UL 1971 standards — without the
need for external modules or other electronics. It’s ample
10-amp power supply is finely tuned to get the most out of
EDWARDS’ widely-acclaimed low profile Genesis notification
appliances.
Door Holders
& Relays
Seamless System Integration
EST3X borrows much from it’s larger sibling, the venerable
EST3 Life Safety Platform. And for good reason: by integrating with the EST3 networking and computing environment,
an EST3X control panel can serve as a cost-effective remote
node for extinguishing, smoke control, or even mass notifica-
tion functions — all within the same compliance framework.
Retrofits and expansions benefit enormously from this arrangement, but programming and equipment management
for new installations is equally efficient as a result of these
shared resources. EST3X will accommodate up to three EST3
modules on its own rail assembly, giving it access to such
proven EST3 successes as zoned amplifiers, conventional device circuits, modem communicators, and RS-485 functions.
Meanwhile, installers familiar with EST3 configuration will find
that the two systems share many of the same programming
and diagnostic conventions.
Hazardous Location
Devices
High Capacity Audio
EST3X features a full eight channels
of integrated digital audio with up to
two minutes of on-board programmable message storage. An optional high quality paging microphone An optional paging microphone
provides local, as well as
gives live access to local, as well as
remote, audio functions.
remote, audio functions. Auxiliary
inputs are available for mass notification operations, and ZA
Series amplifiers may be mounted directly on the EST3X rail
assembly.
p. 2
p. 3
p. 3
p. 4
p. 4
p. 6
p. 10
p. 11
p. 13
p. 17
p. 15
p. 16
p. 17
Notification
Appliances
Strong Networking
Networking is among EST3X’s strong suits. Highly efficient
RS485 connectivity, plus fiber-optic communications deliver
faster response times and more sophisticated diagnostic
capabilities, while cost-effective remote annunciation solutions
keep basic monitoring and control always within reach.
A simple EST3X network can comprise up to eight
nodes – enough to serve the needs of most campuses and
larger buildings. Its ability to join an EST3 network with as
many as 64 nodes extends EST3X’s reach into mass notification applications, security reporting, as well as making it an
ideal candidate for retrofits.
System Layout and Wiring
Assembly
Dimensions
Control Panels
Option Cards
Local Rail Modules
Control and Display
Network Audio
Remote Annunciation
Network Accessories
FireWorks
Mass Notification
Power Supplies
Initiating
Devices
Application flexibility is where EST3X’s leading edge computing power is put to best use. This generation of control panels
is equally at home as the center of a simple single-building
standalone system as it is when part of a sophisticated life
safety network serving thousands of points across multiple
buildings. Optional voice evacuation bridges the gap left by
other mid-range systems, and makes these panels a costeffective solution for most applications.
EST3X
Head End
EST3X Head End
Head End
1
EST3X
Head End
EST3X
Head End
System Layout and Wiring
Up to six intelligent analog loops hosting as many as 250 devices each.
SLC1
SLC2
Standard
3-SDC1
SLC3
SLC4
SLC5
3-SDDC1
(occupies one
LRM expansion slot)
 Signature (initiating) Data Circuit
SLC6
3-SDDC1
(occupies one
LRM expansion slot)
Required for Class A only
To two-wire smoke detector
Auxiliary power, +24 V
Auxiliary power, common
Four 3-amp Class B NACs. Four Class A NACs with CLA-PS10.
NAC 1
NAC 2
NAC 3
BB
NAC 4
LOOP1
S
H
A S P BB
24+ C
WM
KR
LOOP1L 1
OOP1 AUX
A
SFS1-CPU Main Board
If shielding is used, it must be
continuous and free from earth
ground.
All wiring is power limited.
 Notification Appliance Circuits
PS10-4B
Power
supply
Up to three EST3X Local Rail Modules including:
•Signature Series Drivers
•Zoned Amplifiers
•Modem Communicators
•Network Short Haul Modems
•Fiber Optic Communications Interfaces
•Hardwired Initiating Device Modules
+
Normal
Active +
Up to three Control/Display Modules
+
+
+
+
+
EOL
resistor
+
Wiring is supervised and power limited.
TB2 terminal marking indicates signal polarity when
the circuit is not active. Polarity reverses when
the circuit is active. For proper circuit supervision,
break the wire run at each notification appliance
and install the EOL resistor at the end of the circuit.
FireWorks
 Network data circuit
Ethernet
(3X-ETH)
A
NETWORK
OUT
IN
A BB
R
X
1
RS-232
Aux. Power: 24
VDC, 1.0 A total
3X-NET/3X-FIB
R
T
S
1
C
O
M
1
A
RS-485
BUS
B
RS-485
BUS
SFS1-CPU Main Board
Relays:
3 Form C
Up to 30 Class B
Annunciators.
4,000 ft. max.
T
X
1
To next
network
node
Class A only
 Network data circuit, Class B audio
A
NETWORK
OUT
IN
A BB
R
X
1
T
X
1
R
T
S
1
C
O
M
1
A
RS-485
BUS
B
RS-485
BUS
SFS1-CPU Main Board
3X-FIB8/NET8
To next
network
node
3-ASU/3X-PMI
Primary Audio Data
Or...
 Network data circuit, Class A audio
A
NETWORK
OUT
IN
A BB
R
X
1
T
X
1
R
T
S
1
C
O
M
1
A
RS-485
BUS
B
RS-485
BUS
SFS1-CPU Main Board
UL Listed Signaling
UL Listed Security
2
UL Listed Life Safety Detection
UL Listed Mass Notification
3-ASU/3X-PMI
Primary Audio Data
UL Listed Signaling
UL Listed Life Safety Detection
To next
network
node
EST3X
Head End
EST3X
Head End
Assembly
EST3X systems are designed for quick assembly and easy access in the field. Components
are modular and require no special tools to service or replace.
The SFS1-CPU main board
mounts to the Electronics Chassis.
The 3-SFS1 Electronics Chassis provides
the mounting, internal power, and data
distribution for the SFS1-CPU main board
and up to three local rail modules. It
installs over the PS10-4B Power
Supply.
SLC1
Signaling
line circuit
Initiating
Devices
Network,
annunciator,
RS-232 circuits
Two cables connect the PS10-4B
Power Supply to the back of the SFS1CPU main board.
Chassis
Assembly
Common
Relay
Outputs
SFS1-CPU
Main Board
SLC2 Signaling
line circuit
Dimensions
Notification
Appliances
The backbox is designed for semiflush or surface mounting. Conduit
and nail knockouts, keyhole style mounting holes, and wide wiring
troughs facilitate quick installation.
PS10-4B
Power
supply
SFS1-CPU
Main Board
LQFP
7RSYLHZ
%DFNER[
Hazardous Location
Devices
The 4X-LCD assembly mounts to hinge
pins on the CPU and connects with a
single ribbon cable.
SFS1-CPU
Main Board
6LGHYLHZ
6LGHYLHZ
%RWWRPYLHZ
Note: Add 0.25 in (0.64 cm). to height and width dimensions to allow for knockouts
when framing in the backbox for semiflush mounting.
3
Door Holders
& Relays
4X-LCD
User Interface
EST3X
Head End
EST3X
Head End
SUBMIT

Control Panels
Data Sheet E85005-0133
EST3X control panels come complete with
user interface, CPU, one loop with second
loop expansion, three option card slots,
four Class B NACs, universal 110/220v
10 amp power supply. Specify 3-SDC1
for second loop.
Model
Door Color
Language
3x-SFS1BBronzeEnglish
3x-SFS1RRedEnglish
3x-SFS1Bi BronzeSelectable
3x-SFS1Ri
Red Selectable
PS10-4B Power Supply Card
SFS1-CPU Main Board
The PS10-4B
Power Supply
Card provides
the required
power and related supervision
functions for the
control panel, as
well as filtered,
regulated power
to the rail chassis modules. It
also provides
24 VDC for operating ancillary
equipment.
The SFS1-CPU
main board processes all information from modules
installed within the
cabinet as well as
data received from
other panels over
the network data riser. When a network
card is installed,
the CPU employs
a command set to
determine its type.
LINE
NEUTRAL
EGND
36%
3RZHU6XSSO\&DUG
J1
6)6&380$,1%2$5'
-
/223B%
/223B%
683B1&
683B&
683B12
/223B$
/223B$
$/$50B1&
$/$50B&
$/$50B12
60.B3:5
/223B%
75%/B12
/223B%
75%/B&
75%/B1&
&
N
C
C
TROUBLE
N
O
N
O
C
N
A
ALARM
N
C
N
O
C
N
C
B
+
B
-
S
H
LOOP1
SUP
A
+
A
-
LOOP1
S P B
B
MW +
K R
LOOP1
1
24+
C
AUX
SFS1-CPU
Main Board
;/&'
-
J5
J2
NAC AUX 1 NAC AUX 2 NAC AUX 3 NAC AUX 4
+
12VDC
+
-
+
-
+
N.C.
-
+
-
N.C.
RD
-
-
($(&&$5'
-
+
NETWORK
AUDIO
AUDIO
AUDIO
AUDIO
A OUT
B OUT
OUT
A IN
B IN
IN
B
B
A
A
+
+
+
+
+
+
-
6)6&380$,1%2$5'
-
BU
NORMAL
+ 12VDC
BK
-
ACTIVE
+
+
-
15 k Ω EOLR
+
+
-
15 k Ω EOLR
+
+
-
15 k Ω EOLR
+
+
-
15 k Ω EOLR
R
X
1
T
X
1
R
T
S
1
C
O
M
1
A
RS-485
BUS
+
B
RS-485
BUS
+
AUX
C
24+
LOOP2
B
B
+
LOOP2
2
S P
MW A
+
K R-
LOOP2
S
B A B
H +
-
6$0($66/&
1(7:25.B287B$
1(7:25.B287B$
56B%86B%
1(7:25.B,1B%
56B%86B%
1(7:25.B,1B%
$8',2B$,1
56B%86B$
56B%86B$
&20
$8',2B$,1
$8',2B$287
576
7;
$8',2B$287
$8',2B%,1
5;
$8',2B%,1
$8',2B%287
$8',2B%287
Option Cards
3-SDC1 Signature Data Circuit Card
The 3-SDC1 Signature Data Circuit Card provides one Class A or Class B signaling line circuit (SLC1) that supports up to 125 Signature Series detectors and 125
Signature Series module addresses. The module also provides a connection for
powering conventional two-wire smoke detector circuits on Signature Series modules. EST3X comes standard with one 3-SDC1 card installed as SLC1. An optional
second 3-SDC1 card may be installed to provide SLC2, thus doubling system
signaling line capacity.
4
3-SDC1 Signature Data Circuit Card
Standard
SDC1 card
for SLC1
Optional
SDC1 card
for SLC2
SFS1-CPU
Main Board
Data Sheet E85005-0133
EST3X
Head End
Ethernet Adapter Cards
3X-ETH1 Ethernet Adapter Card
The 3X-ETH1 adapter card provides a standard 10/100 Base-T Ethernet network
connection for panel programming, diagnostics, status monitoring and connection
to FireWorks Graphical User Interface.
3X-ETH1 Ethernet Adapter for programming and diagnostics remotely.

SFS1-CPU
Main Board
3X-ETH
card
EST3X
Head End
The SFS1-CPU supports one of the following three adapter cards...
SUBMIT
Data Sheet E85005-0133
3X-ETH2 Ethernet Adapter Card
The 3X-ETH2 adapter card provides all the function of the 3X-ETH1 plus the added capability of communicating to
compatible digital alarm receivers. Please refer to the EST3X UL Compatibility List for the latest compatible receivers.
Data Sheet E85005-0133
Initiating
Devices
3X-ETH2 Ethernet Adapter for Digital Alarm Recievers, programming, and diagnostics.
3X-ETH3 Ethernet Adapter Card
The 3X-ETH3 adapter card provides all the function of the 3X-ETH2 plus the added capability of sending email messages as well as SMS text messages by means of email-to-text.
3X-ETH3 Ethernet Adapter for email, Digital Alarm Recievers, programming, and diagnostics. Data Sheet E85005-0133
3X-NET Network Adapter Card
3x-NET
RS485, Class B or Class A wiring. For connection to EST3 systems.
3X-NET8 RS-485 Network Card
3x-NET8
RS485, eight node max. Class B or Class A wiring. Use on 3-SFS systems only.
3X-FIB8 Fiber Optic Network Card
The 3X-FIB8 fiber optic network module gives an EST3X panel the ability to network up to
eight panels. Both Class A and Class B connections are supported. The module consists of
the adapter card and electronics card. The 3x-FIB8 supports SMXLO2 Series single mode
fiber optic transceivers, as well as MMXVR multimode transeivers. It provides terminals for connecting a 24 VDC backup power source to maintain data transmissions in the event the panel
is powered down.Note: All networked panels must have the 3X-FIB8 network card installed.
3x-FIB8
Fiber, eight node max. Uses MMXVR, SMXHI2, SMXLO2. Use on 3-SFS systems only.
3X-NET
card
Data Sheet E85005-0133
SFS1-CPU
Main Board
Hazardous Location
Devices
The 3X-NET8 RS-485 network card gives an SFS1-CPU main board the ability to network
through dedicated copper wire up to eight EST3X control panels. The card supports Class B
and Class A wiring. Note: All networked panels must have a 3X-NET8 network card installed.
Notification
Appliances
The 3X-NET network adapter card gives an SFS1-CPU main board the ability to network with
64 nodes on an EST3 network. The card supports Class B and Class A wiring. The 3X-NET
adapter card provides two independent RS 485 circuits: one for network data
communications and one for digital audio communications.
SFS1-CPU
Main Board
3X-NET8
card
Data Sheet E85005-0133
SFS1-CPU
Main Board
3X-FIB8
adapter
card
Data Sheet E85005-0133
Door Holders
& Relays
PS10-4B
Power
supply
CLA-PS10 Class A Adapter Card
The CLA-PS10 Class A Adapter Card is an optional card used to convert the four Class B
notification appliance/auxiliary power circuits on the power supply card to Class A.
CLA-PS10 Class A Adapter, PS10 NAC’s
CLA-PS10
Class A
Adapter Card
Data Sheet E85005-0133
5
EST3X
Head End

Local Rail Modules
Up to three Local Rail Modules (LRMs) conveniently mount to the EST3X chassis
assembly, away from high voltages. Each module features removable terminal blocks
and simple plug-in connectors. LRMs include Zoned Amplifiers, Signature Loop Controllers, Conventional Hardwired Modules, and Off Premise Signaling Modules. Control
Display Modules are mounted on the local rail modules.
Signature Driver Controller Modules
Local Rail
Local Rail
Module
Removable
Terminal Blocks
The 3-SSDC1 and 3-SDDC1 Signature Driver Controller modules provide
an intelligent interface between the SFS1-CPU module and Signature Series
devices. Each module contains its own microprocessor used to coordinate,
process and interpret information received from and sent to Signature devices. Power and communications is received directly from the control panel
rail assembly. The 3-SSDC1 Single Signature Driver Controller module supports one Signature Data circuit, while the 3-SDDC1 Signature Dual Driver
Controller module supports two Signature circuits. Both modules occupy
one rail space in the fire alarm control cabinet and provide removable field
wiring terminals to aid installation.
Innovative design gives the 3-SSDC1/3-SDDC1 and Signature devices truly
“distributed intelligence”. Signature detectors and modules have their own
on-board microprocessor communicating with the loop controller in a fully
digital communication format. This increases the accuracy of the information
coming to and from the loop controller by reducing the effects of capacitance
and noise.
Class A Configuration Shown (Typical)
SDC #1 Smoke
Power
+
+
Circuit #1
1
2
3
4
5
6
7
8
9
10
To TB1 on 3-SDDC1 Module
3-SDDC1
SIGNATURE
DUAL
DRIVER
CONTROLLER
MODULE
TB1
TB2
To TB2 on 3-SDDC1 Module
1
2
SDC #2 Smoke
Power
Class A Configuration Shown (Typical)
6
3
4
5
6
7
8
+
Circuit #2
9
10
+
EST3X
Head End
SUBMIT
With decentralized intelligence much of the decision making moves from the
loop controller to the devices. Advanced fire detection algorithms processed
within the Signature devices effectively end unwanted alarms. Environmental
compensation and multiple sensing element decision making operations are
resident in the devices. Intelligent devices allow the Signature Controllers to
execute communication and system functions with greater speed and low
baud rates, increasing the accuracy of information transmitted between the
loop controller and devices.
To enhance survivability of the system the 3-SSDC1/3-SDDC1 supports a
standalone mode for Signature devices. Two catastrophic failure modes are
supported. If the SFS1-CPU fails, the loop controller will continue to poll its
devices. If an alarm is detected it will be sent on the local rail communication
bus and received by other local rail modules. A common alarm condition
throughout the panel will result. If the local rail module (3-SSDC1/3-SDDC1)
fails, and a device (smoke or module) detects an alarm, specialized circuitry
will make the node aware of the alarm condition. SFS1-CPU will communicate
the alarm condition to the rest of the network. Having multiple redundant
modes is paramount in a life safety system.
3-SSDC1
Single Signature Driver Controller, c/w one 3-SDC1 Data Sheet E85010-0129
3-SDDC1
Dual Signature Driver Controller, c/w two 3-SDC1s Data Sheet E85010-0129
3-SDC1
Signature Device Card - upgrades a 3-SSDC1 to a 3-SDDC1 Data Sheet E85010-0129
3-SDC1-HC
Signature Device Driver High Capacity Card
Data Sheet E85010-0129
EST3X
Head End
SUBMIT
CLASS A WIRING
LOOP
Monitor
Module
Monitor
Module
Control
Module
Isolator
Module
Photo- Monitor
electric Module
Smoke Detector
Class A
Return Wiring
Circuit #1
+
1
Addressable Analog Device Controller
+
2
3
4
5
6
7
8
9
10
To TB1 on 3-AADC1 Module
3-AADC1
Addressable Analog Module
Initiating
Devices
The 3-AADC1 Addressable Analog Circuit Module is a local rail module used on the EST3X
system. The module requires one connection on the rail chassis. The module can support
99 addressable analog sensors and 99 addressable modules. The controller also features a
hinged front panel for a Control Display Module, available in a variety of LED and/or switch
configurations.
EST3X
Head End
Heat
Monitor Ionization Isolator PhotoModule
Smoke Module electric Detector
Detector
Smoke Detector

Data Sheet E85010-0128
Initiating Device Circuit (Hardwired) Module
1 4
EOL
4
5
6
7
8
NAC IN
1/2
IDC #4
IDC #3
IDC/NAC #2
3
9
10
To TB1 on Module
TB1
RX TX
JP1 JP2
3
2
1
3
2
1
1
1
2
2
3
3
JP3 JP4
TB2
7
6
5
4
3
2
1
NAC IN
7/8
8
IDC #5
9
IDC #6
10
IDC/NAC #8
Four of the eight 3-IDC8/4 circuits are convertible to
Class B notification appliance circuits. The circuits employ traditional reversing polarity operation for polarized
bells, horns, and strobes.
2
Hazardous Location
Devices
All circuits may be programmed for non-verified or
verified smoke operation. Ranges include open circuit,
shorted condition, and high and low impedance (relative to the main impedance setting). This allows the use
of various detectors of similar impedance, as well as
4-state European alarm circuit operation.
1
Notification
Appliances
The 3-IDC8/4 also configures for use with N.O. contacts
and supports supervised supervisory and monitor circuits with latching or non-latching operations. When the
monitor operation is used with the non-latching function,
the circuit serves as a supervised event follower. This
efficiently covers critical fan and damper operations.
Circuits can annunciate on the 3-LCD, control display
modules, or at any other display device on the network.
IDC/NAC #7
Flexibility built right into the IDC module allows connection of normally open contact devices, and traditional
2-wire smoke detectors.
IDC/NAC #1
The 3-IDC8/4 is ideal for retrofit projects where existing wiring, smoke
detectors and signals may not need replacing.
2 3
Detector Base
Notification appliance circuits are arranged in pairs. Each pair distributes 3.5
Amps at 24 Vdc from the local rail or a single riser. Riser sources supported
include 24 V @ 3.5 A, which can be pulsed (temporal pattern) for audible
signals, or up to 70 Vrms @ 100W audio source for speakers.
Detector Base
INITIATING DEVICE CIRCUIT (IDC)
Connect to IDC 3, 4, 5, or 6
IDC/NAC 1, 2, 7, or 8
+
+
+
+
+
Door Holders
& Relays
+
EOL
NOTIFICATION APPLIANCE CIRCUIT (NAC)
Connect to IDC/NAC 1, 2, 7, or 8
3-IDC8/4
Initiating Device Circuit Module
Data Sheet E85010-0061
7
EST3X
Head End

Off Premise Signaling Module
The 3-OPS supports three separate off premises signaling modes of operation:
‘Old’ style reverse polarity operation has only a single reversed
polarity output. In the normal state the output is 24 Vdc current
limited to 6 mA. In the alarm state the polarity reverses. Should the
ALARM Polarity Reverses
(+)
EST3X panel go into trouble from the normal state, the voltage is
TROUBLE Power off
ALARM has priority
removed from the output terminals of the 3-OPS. This change will
be detected by the central station as a trouble. Alarm always has
priority over trouble. Trouble relay contacts must be configured for normally-closed operation.
10
9
8
7
6
5
4
3
‘New’ style reverse polarity operation allows the 3-OPS to output three
independent reversing polarity signals. These are alarm, supervisory, and
trouble. In each case an active condition causes the terminal output voltage
to reverse. Should the central station detect a loss of voltage, the condition
is due to line failure. When configured for “new” style operation, a set of
trouble contacts is available.
City Tie connection. In this configuration the 3-OPS has
terminals for a local energy master fire alarm box. The
module operates into a 14 ohm coil and supervises the city
tie connection for open conditions. Trouble relay contacts
are configurable for normally-open or normally-closed.
2
1
10
9
8
7
6
5
4
3
2
1
TROUBLE RELAY
TERMINALS 1 & 2
(+)
ALARM
(+)
(+)
10
9
8
7
6
5
4
3
2
1
TROUBLE RELAY
TERMINALS 1 & 2
TROUBLE
SUPERVISORY
MASTER BOX
(+)
Note: Trouble relay contacts are
configurable for N.O or N.C
MUNICIPAL
CIRCUIT
3-OPS
Off Premise Signaling Module
Data Sheet E85010-0075
Fiber Optics Communications Interface
Fiber optic communications provide a high level of immunity from electrical
noise. Circuits are power limited and suitable for use through hazardous
atmospheres. Fiber optic circuits also provide a high level of security and
are resistant to the effects of moisture.
A
audio
RX
TX
B
audio
RX
TX
A
audio
RX
TX
B
audio
RX
TX
A
audio
RX
TX
B
audio
RX
TX
A
audio
RX
TX
B
audio
TX
RX
A DATA
A AUDIO
TX
B DATA
B AUDIO
RX
TX
RX
A DATA
A AUDIO
TX
B DATA
RX
B AUDIO
TX
RX
A DATA
TX
A AUDIO
TX
B DATA
RX
RX
TX
B AUDIO
RX
TX
RX
TX
TX
RX
RX
TX
RX
TX
TX
RX
RX
AUDIO AUDIO
B IN B OUT
- +
+
TX
AUDIO AUDIO
A IN
A OUT
- +
+
RX
OUT
IN
A B
B
- +
-
TX
RX
TX
CPU with 3-FIBMB
Network
A
+
TX
RX
RX
AUDIO AUDIO
B IN B OUT
- +
+
B data
AUDIO AUDIO
A IN
A OUT
- +
+
A data
OUT
IN
A B
B
- +
-
TX
RX
B data
CPU with 3-FIBMB
Network
A
+
TX
RX
A data
AUDIO AUDIO
B IN B OUT
- +
+
B data
RX
TX
TX
TX
RX
A DATA
RX
A AUDIO
AUDIO AUDIO
B IN B OUT
- +
+
TX
AUDIO AUDIO
A IN
A OUT
- +
+
TX
OUT
IN
A B
B
- +
-
RX
CPU with 3-FIBMB
Network
A
+
B DATA
Maintain physical separation
or two-hour fire rating
RX
The 3X-FIB supports from one to four single or multi mode transceivers. The
SMXLO2 standard output single mode transceiver is suitable for distances
up to approximately 8.7 miles (14km). The SMXHI2 high output single mode
transceiver is available to span distances up to approximately 24 miles (40km).
For multi mode applications, the MMXVR transceiver is suitable for distances
up to approximately 8,000ft (2,400m).
AUDIO AUDIO
A IN
A OUT
- +
+
A data
The 3X-FIB electronics card
plugs right into the CPU. A
ribbon cable connects the 3-CPU directly to the 3X-FIB fiber interface card.
The interface card mounts in the ½ footprint space in a chassis or enclosure.
OUT
IN
A B
B
- +
-
B data
Network
A
+
A data
EST3X networks easily configure to single or multi mode fiber optic or
combination fiber optic/copper 3-CPU Class A network and audio fiber-optic connections
networks using the 3X-FIB Fiber
CPU with 3-FIBMB
Optic Communications Interface
and the appropriate fiber optic
Fiber-optic network
Fiber-optic audio
transceivers.
data riser
data riser
B AUDIO
EST3X
Head End
SUBMIT
From 3-ASU primary audio data
8
3X-FIB
Fiber Optic Communications Interface c/w 3-CHAS7/3-CAB5 mounting brackets
Data Sheet E85010-0131
SMXLO2 Plug-In standard output single mode transceiver for 3-FIBMB
Data Sheet E85010-0131
SMXHI2 Plug-In high output single mode transceiver for 3-FIBMB
Data Sheet E85010-0131
MMXVR Plug-In standard output multi mode transceiver for 3-FIBMB
Data Sheet E85010-0131
EST3X
Head End
SUBMIT
Modem Communicator
The Modem Communicator is a two-way local rail module that performs a variety
of off-premise communications functions for the EST3X system unavailable on any
other system. The module has provisions for supervising two loop-start telephone
lines. It features a modular jack for telephone line connections, as well as database
download from a PC. The Modcom’s configuration and firmware can also be updated
from any network node.
EST3X
Head End

Modcom series modules occupy a single local rail space and can be mounted in any
node on the network. Any EST3X Control/Display module can be mounted on the
face of a Modcom series module. Power for the Modcom is supplied by the EST3X
system supply.
Initiating
Devices
The Modcom provides an enhanced level of survivability in the event of a network
CPU failure by notifying the Central Monitoring Station of the failure and entering a
degraded mode of operation. In degraded mode, the Modcom can transmit a default
fire alarm message during a fire alarm condition.
Two versions of the Modcom are available:
3-MODCOM - This internal modem is a V.32bis 14.4K baud full duplex modem. The
modem permits the remote upload and download of system data via a telephone line.
Each Modcom can buffer up to 500
events in its event queue. It reviews all active events in the queue and
identifies the highest priority event and dials the associated receiver. The
Modcom then identifies all other events in the queue that
are destined to the same receiver as the highest priority
YELLOW
event. All event information for that receiver is then transmitted. The next high priority event is identified and the
BLACK
process repeated.
PREMISES
SURGE
PROTECTOR RING
(RED)
4
TIP
(GREEN)
5
3
6
7
2
1
8
RJ31X
8 PIN MODULAR
CONNECTOR FOR
PHONE LINE #1
4
3-MODCOMP
7
1
RJ31X
8 PIN MODULAR
CONNECTOR FOR
PHONE LINE #2
8
7 Ft.
(2.13 M)
LINE 1
LINE 2
MODCOM
3-Modcom
Typical Wiring
Modem/Dialer (DACT) version Data Sheet E85010-0107
Modem/Dialer (DACT) w/TAP Protocol Data Sheet E85010-0107
Door Holders
& Relays
3-MODCOM
6
2
(front view)
The answering machine override feature permits Modcom modules to be
installed on a standard telephone line. The Modcom series also has the ability
to detect Type 2 and Type 3 distinctive ringing patterns, permitting it to share
its phone lines with other devices and still have a unique phone number for
incoming calls.
5
Hazardous Location
Devices
The Modcom series has been designed for installation on
the same phone lines with other devices such as faxes
and answering machines. The module makes its first dial out attempt on
either of the two phone lines that is not in use. This prevents unnecessary
interruption of calls in progress by the line seizure relays. In the event that
both lines are busy, the module seizes one of the busy lines. A fixed DACT
testing time can be set at an off-hour, e.g. 2:00am, again minimizing interruptions.
TO PHONE LINE #2
(WIRED SAME AS
PHONE LINE #1)
3
PHONES
Notification
Appliances
3-MODCOMP – In addition to all modem and dialer (DACT) functions of the
3-MODCOM, the 3-MODCOMP can dial directly into paging systems using Telelocator
Alphanumeric Protocol (TAP). Alphanumeric system data can be sent to a single pager
or groups of pagers. Some pager services can forward messages via e-mail and Fax.
9
EST3X
Head End
EST3X
Head End
SUBMIT

Control and Display
EST3X sets a new standard in front-panel life safety control interfaces. Its exclusive SpeedTouch™ rotary control offers nimble
forward and back scrolling through events and options, while a
mere tap of the control selects items with fluid motion. Its extralarge backlit display reveals up to eight concurrent messages,
and switch/LED strips
provide abundant space
for meaningful labels.
And for end users, large
tactile control buttons
instill confidence and
promote quick response
when time is of the essence.
The main display
mounts to the CPU, while control/display modules mount to local rail modules
on the inner chassis. Simple-to-understand multi-color LEDs and switches help
the emergency user display information and execute system commands with confidence.
Control Display Modules
Data Sheet E85005-0133
EST3X Control Display modules provide the emergency user with the simplest of interfaces: lights and switch controls.
Control Display Modules install over local rail modules.
4x-12/S1GY
12 Switches, 1 Green, 1 yellow LED per switch.
4x-12/S1RY
12 Switches, 1 red, 1 yellow LED per switch.
4x-12SR
12 Switches with 12 red LEDs.
4x-24R
24 red LEDs.
4x-6/3S1G2Y
Six groups of 3 switches with 1 LED each.
4x-6/3S1GYR
Six groups of 3 switches with 1 LED each.
4x-4/3SGYWR
Four groups of 3 switches and 4 LEDs. green, red, yellow and white LEDs.
10
EST3X
Head End
SUBMIT
Network Audio
Configuring EST3X audio is a matter of selecting components for installation in standard fire
alarm cabinet assemblies. EST3X uses zoned amplifiers. This reduces wire runs and space
needs at a central location. Audio control equipment and zoned amplifiers use the same system
power supplies as fire alarm components. All these components are supported by a common
standby battery. Where multiple nodes make up the system, a single pair of wires carries eight
channels of digital audio between nodes.
EST3X
Head End

3X-PMI Paging Microphone Interface
SFS1-CPU
NETWORKA
OUT
IN
AA
BB
++-
UDIO
A IN
AUDIOA
A OUT
+-
+-
UDIO
B IN
+-
Network
option
card
installed
AUDIO
B OUT
R
X
1
+-
T
X
1
R
T
S
1
C
O
M
AB
RS-485
BUSB
-+ +
1
Initiating
Devices
The 3X-PMI Paging Microphone Interface provides controls
for emergency voice/alarm communications. It consists
of an audio mounting bracket, EAEC Emergency Audio
Evacuation Controller card, audio enclosure, and paging
microphone.
RS-485
US
-
Network
option
card not
installed
KEY_OUT
Remote
microphone
AUDIO_OUT
SHIELD
MN-PASM
EAEC
3X-PMI
KEYA
AUDIO
DATA
UDIO
Notification
Appliances
UL 864 and
UL 2572 listed
equipment with
compatible
ratings
MN-FVPN
AUX OUTA UX IN
REMOTE MIC
Paging Microphone Interface
Data Sheet E85005-0133
VISUAL NOTIFICATION
APPLIANCE CIRCUIT
+
+
+
+
+
+
EST3X audio amplifiers decode and re-expand
the eight multiplexed audio signals on the network audio riser. Under command of the network,
one of the available eight signals is selected to be
distributed over the speaker circuit. Command
and control signals for the amplifier are sent and
received via the network data riser in response
to programming.
1
10
2
3
4
5
6
7
8
9
10
1
2
3
4
5
6
7
8
9
10
1
2
3
4
5
6
7
8
9
10
1
2
3
4
5
6
7
8
9
10
AUDIO
AMPLIFIER
MODULE
AUDIO
AMPLIFIER
MODULE
AUDIO
AMPLIFIER
MODULE
AUDIO
AMPLIFIER
MODULE
(BACKUP)
(ZONE #1)
(ZONE #2)
(ZONE #3)
9
8
7
6
5
4
3
2
1
10
9
8
7
6
5
4
3
2
1
10
9
8
7
6
5
4
3
2
1
10
9
8
7
6
5
4
3
Hazardous Location
Devices
Zoned Audio Amplifiers
2
1
COMMON ENCLOSURE
AUDIO NOTIFICATION
3-ZA20A
20 Watt Zoned Amplifier w/Class A/B Audio & Class A/B 24 VDC outputs
Data Sheet E85010-0057
3-ZA20B
20 Watt Zoned Amplifier w/Class B Audio & Class B 24 VDC outputs
Data Sheet E85010-0057
3-ZA40A
40 Watt Zoned Amplifier w/Class A/B Audio & Class A/B 24 VDC outputs
Data Sheet E85010-0057
3-ZA40B
40 Watt Zoned Amplifier w/Class B Audio & Class B 24 VDC outputs
Data Sheet E85010-0057
Door Holders
& Relays
APPLIANCE CIRCUIT
Amplifiers are available in 20 or 40 watt versions,
with supervised, power limited 25 Vrms or 70Vrms
outputs. The amplifier output is wired to a single
speaker zone. Each amplifier has a 1 KHz temporal tone generator used as evacuation signal in the
event of a fault with the network audio circuit. In the event of an on-line amplifier failure, a standby
amplifier may be configured for automatic replacement of any on-line amplifier configuration. 20 and
40 watt amplifiers also provide an independently controlled supervised, power limited 24 Vdc notification appliance circuit rated at 3.5 amps. All field wiring connections are made via plug-in connectors.
11
EST3X
Head End
EST3X
Head End
SUBMIT

Intelligent Audio Amplifiers
Shield Optional
To Next Amp
Channel 1 Input
Audio Output
Signature Series amplifiers are high-efficiento Speakers or
Signature device
From Channel 1
cy switch mode audio amplifiers available
Output Return
Signal Source
Class A Only
1Vrms or 25Vrms
in 30 and 50 watt sizes. Amplifiers have
From Output of
From Channel 2
Backup Amp
two input channels supporting dual chanSignal Source
1Vrms or 25Vrms
nel or single channel audio applications.
To Backup Input
To Next Amp
of Next Amp
Output Voltage
Channel 2 Input
Signature amplifiers are ideally suited for
Selection Jumper
To 24 VDC
To
Next
From
Previous
distributed audio applications and small Signature Device
Signature Device
centrally banked applications. The audio
output is configurable as 25Vrms or 70Vrms in Class B or Class A wiring configurations. Speakers can connect directly
to the output of the amplifier or the amplifier output can run as an audio riser to Signature modules where speaker zone
selection is made. Each amplifier has a built-in 1kHz tone generator and provision for a back up amplifier. On-board
status LEDs provide quick visual indication of amplifier status.
Status LEDs
Status LEDs
SIGA-AA30
30 Watt Intelligent Audio Amplifier
Data Sheet E85010-0089
SIGA-AA50
50 Watt Intelligent Audio Amplifier
Data Sheet E85010-0089
RM1
Banked Audio Amplifiers
Banked Amplifiers provide EST3X with
economy audio configurations for single
and some dual channel applications. Model
3-ZA20A/B Zoned Amplifiers at the EST3X
control panel provide channel sources for
banked amplifiers. 3-ZA20A/B amplifiers
can select any of EST3X’s eight audio channels as a signal source.
A special interface module, the 3-ATPINT, accepts analog audio signals at 25
or 70Vrms from EST3X’s Zoned Amplifiers and passes these signals to the
1B3125 and 1B3250 Audio Power Amplifiers via an Amplifier Terminal Panel
(ATP). The 3-ATPINT mounts in the ATP.
RM1
CC2
CC2
Data
Channel 1
Amplifier
ATP
Channel 2
Amplifier
RKU Equipment Rack
The ATP Audio Terminal Panel interfaces one or two audio power amplifiers and monitors utility power, charges and
supervises standby batteries, and provides switch-over to standby. The amplifier bank is monitored and controlled
through Signature Series modules.
EST3X
Central Banked Amplifiers
Data Sheet E85010-0085
1B3125
Audio Power Amplifier — 125 Watts
Data Sheet E85010-0011
1B3250
Audio Power Amplifier — 250 Watts
Data Sheet E85010-0013
ATP
Amplifier Terminal Panel
Data Sheet E85003-2741
3-ATPINT
ATP Interface Module
Data Sheet E85010-0085
SIGA-RM1/MRM1 Riser Monitor Module
Data Sheet E85001-0535
RKU 12
19-inch Equipment Rack
EST3X
Power
Fire Alarm
Supervisory
Ground Fault
Trouble
Controls Enabled
Ack/Silence
Reset
Signal Silence
Drill
Lamp Test
RLCD-C
Power
Fire Alarm
Supervisory
Ground Fault
Trouble
Controls Enabled
Head End
Ack/Silence
SUBMIT
RLCD
Remote Annunciation
Power
Fire Alarm
Supervisory
Ground Fault
Trouble
Controls Enabled
Power
Fire Alarm
Supervisory
Ground Fault
Trouble
Controls Enabled
Ack/Silence
Ack/Silence
Reset
Reset
Signal Silence
Signal Silence
Drill
Drill
Lamp Test
Lamp Test
RLED-C
RLCD-C
Power
Fire Alarm
Supervisory
Ground Fault
Trouble
Controls Enabled
Power
Fire Alarm
Supervisory
Ground Fault
Trouble
Controls Enabled
Power
Fire Alarm
Supervisory
Ground Fault
Trouble
Controls Enabled
Ack/Silence
Ack/Silence
Ack/Silence
Reset
Reset
Signal Silence
Signal Silence
Drill
Drill
Lamp Test
Lamp Test
Lamp Test
RLCD-C
RLCD
RLCD-C
RLED24
Power
Fire Alarm
Supervisory
Ground Fault
Trouble
Controls Enabled
Power
Fire Alarm
Supervisory
Ground Fault
Trouble
Controls Enabled
Power
Fire Alarm
Supervisory
Ground Fault
Trouble
Controls Enabled
Ack/Silence
Ack/Silence
Ack/Silence
R-Series Annunciators
Reset
Signal Silence
Drill
Lamp Test
Lamp Test
Lamp Test
RLCD
RLCD
RLED-C
Power
Fire Alarm
Supervisory
Ground Fault
Trouble
Controls Enabled
Annunciator
Power
Fire Alarm
Supervisory
Ground Fault
Trouble
Controls Enabled
CH1 (+) IN
Reset
Reset
CH1 +
CH1 (–) IN
Signal Silence
CH1 (–) IN
Signal Silence
Drill
Drill
CH1 –
CH1 (+) IN
Ack/Silence
Ack/Silence
Lamp Test
Lamp Test
CH1 (+) OUT
CH2 +RLED-C
RLED24
CH2 –
LISTED 24 VDC
SUPPLY
CH1 (–) OUT
CH1 (–) OUT
CH2 (+) IN
CH2 (+) IN
CH2 (–) IN
CH2 (–) IN
CH2 (+) OUT
CH2 (+) OUT
CH2 (–) OUT
CH2 (–) OUT
24 VDC +
24V (+) IN
24 VDCRLED24
–
24V (–) IN
Class A Wiring
CH1 (+) OUT
RLED-C
24V (+) IN
24V (–) IN
RLED24
24V (+) OUT
24V (+) OUT
24V (–) OUT
24V (–) OUT
GROUND
GROUND
Annunciator
Annunciator
CH1 (+) IN
CH1 (+) IN
R-Series annunciators and expanders are
mounted on a standard 4-inch square electrical
box, using the included mounting ring. They can
also be surface mounted in locking steel enclosures. Three different enclosures are available.
A keyswitch and graphic annunciator interface is
available for R-Series annunciator applications.
The keyswitch enables or disables common
controls. The graphic annunicator interface
cards supports 32 LEDs and 16 switches on
the graphic panel display.
CH1 (–) IN
CH1 +
Remote
Annunciators CH1 (–) IN
CH1 (+) OUT
CH1 (+) OUT
–
CH1
RLCD
LCD text annunciator
without
common
controls.
English. CH1 (–) OUT
CH1 (–) OUT
Data Sheet E85005-0128
RLCD-R CH2 (+) IN
CH2 (+) IN English. Red. LCD text annunciator
without common controls.
Data Sheet E85005-0128
RLCDF LCD text annunciator
without common controls.
French. CH2 (+) OUT
CH2 (+) OUT
RLCD-C LCD text annunciator with common controls. English. CH2 (–) IN
LISTED 24 VDC
SUPPLY
24 VDC +
CH2 (–) IN
CH2 (–) OUT
CH2 (–) OUT
24V (+) IN
24V (+) IN
24V (+) OUT
24V (+) OUT
24V (–) OUT
24V (–) OUT
Data Sheet E85005-0128
Data Sheet E85005-0128
Data Sheet E85005-0128
RLCD-CF LCD text annunciator with common controls. French. Data Sheet E85005-0128
RLED-C 16-pair LEDGROUND
zone annunciator with common
controls. English. GROUND
Data Sheet E85005-0128
RLED-CR 16-pair LED zone annunciator with common controls. English. Red. Data Sheet E85005-0128
RLED-CF 16-pair LED zone annunciator with common controls. French. Data Sheet E85005-0128
Annunciator
First Expander
Second Expander
Remote Expanders
IN
OUT
IN
OUT
RLED24 OUT 24-pair LED zone
expander
with expander
cable
and zone card insert. V (–)
V (–)
V (–)
V (–)
V (–)
RLED24RV (+)
24-pair LED zone
with expander
V (+) expander
V (+)
V (+) cable
V (+)and zone card insert. Red. F
F
F
F
F
C
C
C
C
C
Enclosures E
E
E
E
E
RA-ENC1 D One-position enclosure
D
D for Remote Annunciator.
D
D
RA-ENC2 B Two-position enclosure
for Remote Annunciator
and one Remote Expander. B
B
B
B
LSRA-SB
Data Sheet E85005-0128
Data Sheet E85005-0128
Data Sheet E85005-0128
Data Sheet E85005-0128
Three-position enclosure for Remote Annunciator and two Remote Expanders. Data Sheet E85005-0128
Surface Mount Box - for single R Series annunciator.
Data Sheet E85005-0128
A
A
A
A
Accessories
RKEY Remote key switch on plate for enabling or disabling common controls. Data Sheet E85005-0128
27193-16 Data Sheet E85005-0128
Electrical box, surface mount, white, single-gang, for RKEY.
Door Holders
& Relays
RA-ENC3 A
Hazardous Location
Devices
RLCD-CR LCD text annunciator
with common controls.
Red. 24V (–) IN
24V (–English.
) IN
24 VDC –
Notification
Appliances
FACP
RS-485
Each EST3X node can accommodate
up to 30 R-Series and graphic annunciators.
R-Series Annunciators are high-performance
devices that offers LCD or LED annunciation.
Models are available with and without common
controls.
Initiating
Devices
Annunciator
FACP
RS-485
EST3X
Head End

Lamp Test
13
EST3X
Head End
EST3X
Head End
SUBMIT

Network Accessories
Network Short Haul Modem
EST3X networks easily configure for use over existing copper telephone lines using the
3‑NSHM Short Haul Modem Communications Interface. The 3-NSHM electronics card
plugs into the SFS1-CPU Main Board. A ribbon cable connects the SFS1-CPU directly to
the modem interface card. The interface card mounts to the control panel back box. No
local rail space is used.
3-NSHM1
Network Short Haul Modem, single modem connection Data Sheet E85010-0113
3-NSHM2
Network Short Haul Modem, two modem connections Data Sheet E85010-0113
Ground Fault Detection Module
The GFD module is designed to detect ground
fault conditions on either of two independent
power or data circuits. Each circuit must be
balanced with respect to ground. The module will detect when the resistance between
any of the monitored conductors and earth
ground drops below 10 K Ohms. Two LEDs
are provided to indicate the conductor with
the ground condition.
GFD
Circuit Pair 1 IN
Circuit Pair 2 IN
+
+
-
-
+
+
-
-
16 15 14 13 3-2-1 12 11 10 9
Circuit Pair 1 OUT
Circuit Pair 2 OUT
JP1
LED 1
LED 2
8 7 6 5
4 3 2 1
To earth ground
From UL/ULC listed
fire alarm panel [4]
24 VDC+
+
24 VDC-
-
From IDC or
previous GFD
Ground Fault Detection Module
To next GFD
or EOLR [3] [4]
+
-
Data Sheet E85010-0115
Graphic Annunciation
Driver Module
The GCI series of graphic annunicator drivers allow the EST3X control
panel to display events on an LED-based graphic annunciator. The GCI
annunciator card supports 32 LEDs on the graphic panel display. It includes
status LEDs and an internal buzzer. The GCIX adder card communicates
with the GCI card and provides an additional 48 LEDs and 24 switch connection points. The graphic cards are supplied with snap track mounting.
They are attached to a plastic mounting rail that requires two EIA panels.
24VDC FROM 3-PPS/M
OR 3-BPS/M POWER RISER
RS-485 NETWORK DATA
FROM PREVIOUS PANEL
24VDC TO NEXT
POWER MODULE
RS-485 NETWORK DATA
TO NEXT PANEL
The annunciator communicates with the control panel on the RS 485 data
riser, which can be configured for Class A or Class B communication. The
annunciator does not provide ground fault isolation. The driver card and
expansion cards communicate with and are powered by the control panel
or by an approved power supply. Always ensure that National and Local
approvals and requirements are met when selecting a graphic panel supplier.
GCI
Graphic Annunciator Driver.
Data Sheet E85005-0133
GCIX
Graphic Annunciator Driver Expander. Outputs for 48 LEDs, 24 switch inputs.
Data Sheet E85005-0133
14
EST3X
Head End
SUBMIT
FireWorks
FireWorks is an incident management command and control platform that
comprises hardware, software, and networking components that together
provide a powerful and cohesive Mass Notification and Life Safety solution.
Sophisticated networking technology allows it to integrate seamlessly with
EDWARDS life safety solutions, yet FireWorks remains fully interoperable
with third-party equipment, making it ideal for system upgrades or new
installations alike.
Initiating
Devices
FireWorks can automatically trigger programmed responses to facility
events, or it can act as an operator interface for manual control. The
FireWorks user interface provides a clear, concise, and coordinated
view of any situation by presenting information strategically.
EST3X
Head End

Five configurable graphical viewports offer simultaneous insight
into different aspects of an incident, while the underlying software
dynamically manages content in each viewport based on real-time
events and user interaction. Facility maps, live video feeds, audio
channels, protocol information, and fingertip control over vital equipment all come together instantly within view of an operator facing events
that require solid information and split second timing.
For more information please refer to
Data Sheet E85006-0068.
Notification
Appliances
Supporting every FireWorks workstation is a sophisticated network backbone – strong
enough to handle coordinated critical control functions from as many as fifty client workstations and many other devices, yet flexible enough to manage integration with third-party
mass notification systems.
Redundant server options eliminate risk of communications breakdowns by providing
alternate data paths that regenerate communications in the event of signal loss. FireWorks
can operate on an existing local area network, or provide facility access from anywhere in
the world via secured Virtual Private Network (VPN) connections.
Servers and Workstations
Server/Workstation. Xeon processor, 128 GB RAM, RAID1 500GB array, dual power supplies. FW-UL6W
Workstation. i7 Intel processor, 32 GB RAM, RAID1 500GB SSDs. Single power supply. Hazardous Location
Devices
FW-UL6S
Sofware
FW-CGS
Standalone package. Allows full 5 viewport display. Includes FW-FIREKEYUSB. No common control. FW-CGSUL
Standalone package. Allows full 5 viewport display. Includes FW-FIREKEYUSB. With common control. Non-Redundant Servers:
FW-NSZ5FP, 5 seat.
FW-NS15FP, 15 seat.
Redundant Servers:
FW-RSZ5FP, 5 seat.
FW-RS15FP, 15 seat.
FW-NCZZFP
Non-Redundant Server Client license. FW-RCZZFP
Redundant Server Client license. FW-RS25FP, 25 seat.
FW-RS50FP, 50 seat.
Software options
85012-0019
WebClients:
FireWorks Software DVD only.
FW-1S, One seat.
FW-4S, Four seats (Requires FW-1S).
FW-10S, (Requires FW-1S & FW-4S).
Sofware for Communication to DACRs and/or IPMON1000. FW-FAST
FAST AutoCAD® reader and panel building sofware for FireWorks Server or Standalone system. FW-HSSD5
VESDA HLI Interface for up to 5 nodes. Each server must have its own FW-HSSX1. FW-HSSD20
VESDA HLI Interface for up to 20 nodes. Each server must have its own FW-HSSX1. Door Holders
& Relays
FW-DARCOM
FW-IPMON1000 Interface for up to 1,000 connections to iO Series panels. Requires FW-DARCOM software option. Monitors
FW-22LCDWTS 22-inch 16:9 LCD 115 Vac 1680x1050 resolution capacitive touch screen with integral speakers. FW-42LCDWTS 42-inch 16:9 LCD 115 Vac 1920x1080 resolution surface acoustic wave touch screen. See Data Sheet E85006-0068 for complete FireWorks ordering information.
15
EST3X
Head End
EST3X
Head End
SUBMIT

Mass Notification
VoIP Encoder/Decoder
EDWARDS Voice over Internet Protocol (VoIP) encoder/decoder units allow for the use of
Transmission Control Protocol/Internet Protocol (TCP/IP) to transmit supervised digital audio
for mass notification and life safety applications.
MN-FVPN
MN-FVPN VoIP Encoder/Decoder.
Data Sheet E85010-0143
Mass Notification Serial Communications/LAN interface
The MN-COM1S is a TCP/IP to RS-232 interface with one RJ-45 port and one RS-232
port. It is used in mass notification settings to connect a FireWorks workstation to an EST3
control panel.
MN-COM1S
FireWorks Communications Ethernet Port, Command & Control. Data Sheet E85010-0144
Ethernet Network I/O Module
The EDWARDS MN-NETLRY4 Network Relay provides four unsupervised input zones and
four normally-open relays to and from FireWorks V1.6 or greater over an Ethernet (TCP/IP)
network. This module is particularly well-suited for mass notification, life safety applications,
and other monitoring or output applications. It is also ideal for interfacing to third-party systems.
MN-NETRLY4
Ethernet controllable multi I/O unit, 4 input 4 relay outputs
Related Equipment (Data Sheet E85010-0144)
MN-BRKT1
MN-FVP mounting bracket for EST3 enclosures MN-BRKT3
MN-FVP mounting bracket for APS-(6)(10)A power supplies MN-FVPB1
Polymer mounting bracket for MN-FVPN MN-FVPN
Fire VoIP encoder/decoder, includes power and audio cables MN-PASM2
SIGA -RM1/MRM1
MN-ABPM
16
MN-FVPN preamp signal supervisory booster module Riser Supervision Module Audio Bridge (Panel mount 3-ATPINT) Data Sheet E85010-0149
EST3X
Head End
SUBMIT
Managed Ethernet Switches
EST3X
Head End

The MN-FNS Series managed Ethernet switches are advanced managed
switch solutions that provide for a fully scalable Ethernet network to support virtually any life safety application. These networks may be dedicated
for use by mass notification systems or where permitted, may be part of a
non-dedicated facility network.
Initiating
Devices
MN-FNS switches are field-tested and designed for use with EST3X FireWorks® Computer Platforms, EST3, and
other EDWARDS panels and panel networks. They may also interface to non-dedicated facility networks, and even
to competing control panels through existing network infrastructure. This makes them ideal for many retrofit applications. MN-FNS Ethernet switches may be interconnected to build spoke format networks, as well as Class B, Class
X, Mesh, and Hybrid systems. MN-FNS Series Ethernet switches are powered by Cisco® Technologies and are listed
to UL 864 and ULC S527.
Dedicated Class X
1
2
1
–
DC-B
+
8X
LARM
1
COM
Fiber
1
2
1
IN1
2X
7X
8X
–
DC-A
+
–
DC-B
+
LARM
1
COM
IN2
2
4X
1X
±12/24/48
0.5-2.0A
IN1 IN2 OUT
8X
1X
IE 2000
2
Fiber
–
DC-B
+
LARM
1
2
1
1
COM
7X
8X
Fiber
8X
1
2
1
7X
8X
–
DC-A
+
–
DC-B
+
LARM
COM
IE 2000
–
DC-A
+
±12/24/48
0.5-2.0A
Fiber
IN1
–
DC-B
+
LARM
IN1 IN2 OUT
5X
8X
1
2
1
1
COM
IN2
2
EXPRESS
SETUP
USB EXP SYS
IN2
REF
2
IN1
Ether net
2X
REF
2
2
IN1
Protocol
Ethernet Switches & Power Supplies
MN-FNS4C2F3
4 Fast Ethernet (RJ45), 2 GB SFP, Layer 3 Lite. 24 VDC.
Data Sheet E85010-0153
MN-FNS8C18F2
Rack-mount, 8 Fast Ethernet (RJ45), 16 FE SFP, 2 GB, Layer 2.
Data Sheet E85010-0153
MN-FNS8C18FAC
100-250 VAC/VDC power supply module, primary or backup. Data Sheet E85010-0153
MN-FNS8C18FDC
24 VDC power supply module, primary or backup.
Data Sheet E85010-0153
MN-FNS8C2F3
8 Fast Ethernet (RJ45), 2 GB, SFP/RJ45, Layer 3 Lite, 24 VDC.
Data Sheet E85010-0153
Data Sheet E85010-0153
MN-BRKT3F
Data Sheet E85010-0153
MN-BRKT8C18F
EST3 cabinet mounting bracket .
Data Sheet E85010-0153
MN-FNSRMK1
MN-FNS8C18F Series switch installation kit. Data Sheet E85010-0153
MN-FNS4HDK1
MN-FNS4 Series switch holder bracket. Data Sheet E85010-0153
MN-FNS8HDK1
MN-FNS8 Series switch holder bracket. Data Sheet E85010-0153
Switch mounting bracket for APS6A/10A Series power supplies.
Tranceiver Modules (Dual filament, LC Connectors)
MN-FNSFEDSM10K
Single mode fiber, , FE, 0m to 10km, 9.5 dB fiber budget, 1310nm.
Data Sheet E85010-0153
MN-FNSFEMM2K
Multimode fiber, FE, 0m to 2km, 9 dB fiber budget, 1310nm.
Data Sheet E85010-0153
MN-FNSGBDSM70K
Single mode fiber, GB, 10m to 70km, 17.2 dB fiber budget, 1550nm.
Data Sheet E85010-0153
Door Holders
& Relays
Ethernet Switch Mounting Hardware
MN-BRKT1F
Switch mounting bracket for EST3 enclosures
Hazardous Location
Devices
Resilient
2
4X
1X
±12/24/48
0.5-2.0A
1
REF
2
IN1
1X
IE 2000
IN1 IN2 OUT
5X
Cat 5
EXPRESS
SETUP
USB EXP SYS
IN2
REF
2
2X
–
DC-A
+
IN1 IN2 OUT
8X
4X
1X
±12/24/48
0.5-2.0A
USB EXP SYS
5X
Cat 5
EXPRESS
SETUP
IN2
REF
2
1X
IE 2000
USB EXP SYS
5X
Cat 5
EXPRESS
SETUP
CONSOLE
7X
–
DC-A
+
IN1 IN2 OUT
8X
2X
±12/24/48
0.5-2.0A
USB EXP SYS
5X
4X
1X
CONSOLE
8X
1X
IE 2000
CONSOLE
7X
Cat 5
EXPRESS
SETUP
CONSOLE
2X
CONSOLE
4X
Notification
Appliances
Cat 5
1X
1X
17
EST3X
Head End
EST3X
Head End
SUBMIT

Power Supplies
Remote Booster Power Supply
The Remote Booster Power Supply is a self-contained 24 Vdc power supply designed to augment fire alarm audible
and visual power requirements as well as provide power for auxiliary, access control and security applications. The
booster contains all of the necessary circuits to monitor and charge batteries, control and supervise four Class B or two
Class A NAC circuits and monitor two controlling inputs from external sources. It also provides the ability to synchronize
Genesis series strobes to UL 1971 requirements, and offers independent horn control over two wires.
For comprehensive configuration and wiring details, refer to the BPS Application Guide, 85001-0582.
BPS6A
BPS6A/230
BPS10A
BPS10A/230
3-TAMP
6.5 Amp Booster Power Supply
Data Sheet E85005-0125
6.5 Amp Booster Power Supply (220V)
Data Sheet E85005-0125
10 Amp Booster Power Supply
Data Sheet E85005-0125
10 Amp Booster Power Supply (220V)
Data Sheet E85005-0125
Tamper switch
Data Sheet E85005-0125
Auxiliary Power Supplies
The Auxiliary Power Supply offers the same advantages as the BPS above, but is supplied
with its own extra large enclosure providing space for up to two 24 Ah batteries and additional
option modules in a number of mounting configurations. Option modules can be installed
on the mounting brackets inside the enclosure or on an MP2L mounting plate at the top of
the enclosure. The SIGA-REL, and SIGA-UIO2/6/6R can also be mounted at the top of the
enclosure.
APS6A
APS6A/230
APS10A
APS10A/230
6.5 Amp Auxiliary Power Supply
Data Sheet E85005-0127
6.5 Amp Auxiliary Power Supply (220V)
Data Sheet E85005-0127
10 Amp Auxiliary Power Supply
Data Sheet E85005-0127
10 Amp Auxiliary Power Supply (220V)
Data Sheet E85005-0127
Batteries and Battery Cabinets
Data Sheet E85010-0127
12 Volt Batteries
12V1A2 (1.2 Ah)
12V4A (4.5 Ah)
12V24A (26 Ah)
12V6A5 (7.2 Ah)
12V40A (40 Ah)
6 Volt Batteries
6V8A (8 Ah)
6V10A (12 Ah)
Battery Cabinets
BC-1 (holds up to two 40 Ah batteries)
BC-2 (holds up to two 17 Ah batteries)
3-RCC used as large battery enclosure.
18
12V10A (11 Ah)
12V50A (50 Ah)
12V17A (18 Ah)
12V65A (65 Ah)
EST3X
Intelligent Initiating Devices
Signature Series
Intelligent Analog
Initiating Devices
CO, Smoke and Heat Detectors p. 20
Fire Detectors p. 21
Duct Smoke Detectors p. 21
Detector Bases p. 22
Detector Accessories p. 23
Input/Output Modules p. 24
Standard
Pull Stations p. 30
SDC1 card
for SLC1
Optional
SDC1 card
for SLC2
EST3X’s Signature Series
intelligent analogaddressable system is an entire family of life safety detectors as well as mounting bases, multiple-function input
and output modules, and user-friendly maintenance and
service tools.
Self-diagnostics and History Log – Signature Series
devices constantly run self-checks to provide important
maintenance information. The results of these checks are
automatically updated and permanently stored in the device’s
non-volatile memory.
Fast Stable Communication – Built-in intelligence means
less information needs to be sent between the device and
the Signature Loop Controller, making the circuit less sensitive to noise and wire characteristics. This renders shielded
wiring unnecessary. In fact, existing wiring can be used by
Signature Series devices in most retrofit situations.
Testing & Maintenance – Each detector automatically
identifies when it is dirty or defective and causes a “dirty detector” message. The detector’s sensitiv­ity measurement can
also be transmitted to the loop controller. A sensitivity report
may be printed to satisfy NFPA sensitivity mea­surements.
The user-friendly maintenance program shows the current
state of each detector and other pertinent messages. When
the CO sensor’s electrochemical cell reaches its end of life,
the detector signals a trouble condition to the control panel.
3-SDC1 Signature Data Circuit Card
Hazardous Location
Devices
On-board processing and distributed intelligence also results
in advanced features that save time and money...
Automatic Device Mapping – The Signature Loop Controller learns where each device’s serial number address is
installed relative to other devices on the circuit. This mapping function is invaluable for tracking down unexpected
or missing device addresses, or finding changes to wiring.
The System Definition Utility program also uses this mapping feature to produce system layout or As-Built drawings
showing such details as banch wiring (T-taps), device types
and their addresses.
Notification
Appliances
Signature Series detectors continually monitor the protected
space with their on-board sensors, which are finely tuned to
detect the characteristic properties of combustion. Detection
data is gathered and run through sophisticated algorithms
that track the sensor readings over time to known signatures
of fires. Only when a match is found will an alarm condition
occur. This means that a Signature Series detector can
distinguish between a harmless puff of dust and a wisp of
smoke; between hot, humid weather and a serious life safety
condition.
Initiating
Devices
SFS1-CPU
Main Board
Signature (initiating) Data Circuit
The 3-SDC1 Signature Data Circuit Card provides one Class A or Class
B signaling line circuit (SLC1) that supports up to 125 Signature Series
detectors and 125 Signature Series module addresses. The module also
provides a connection for powering conventional two-wire smoke detector
circuits on Signature Series modules. EST3X comes standard with one
3-SDC1 card installed as SLC1. An optional second 3-SDC1 card may be
installed to provide SLC2, thus doubling system signaling line capacity.
Required for Class A only
Door Holders
& Relays
To two-wire smoke detector
Auxiliary power, +24 V
Auxiliary power, common
BB
LOOP1
S
H
A S P BB
24+ C
WM
KR
LOOP1L 1
OOP1 AUX
A
SFS1-CPU Main Board
If shielding is used, it must
be continuous and free from
earth ground.
All wiring is power limited.
19
EST3X
Intelligent Initiating Devices

Carbon Monoxide
and Fire Detectors
Initiating
Devices
EST3X
Head End
SUBMIT
In addition to integrated smoke and heat sensors, Signature Series combination life
safety devices include electrochemical carbon dioxide sensors. CO detection has
rapidly become a standard part of life safety strate­gies. Monitored CO detection is
becoming mandated with increasing frequency in all types of commercial applications,
but particularly in occupancies such as hotels, rooming houses, dormitories, day care
facilities, schools, hospitals, assisted living facilities, and nursing homes. In fact, more
than half of the U.S. population already lives in states requiring the installation of CO
detectors in some commercial occupancies. Car­bon monoxide is the leading cause of
accidental poisoning deaths in America. Known as the “Silent Killer,” CO is odorless,
tasteless, and colorless. It annually claims nearly 500 lives, and results in more than
15,000 hospital visits.
Intelligent Carbon Monoxide (CO) Detector
The SIGA-COD detects carbon monoxide from any source of combustion and analyzes the sensor data to determine
when to initiate a CO-related life safety event.
SIGA-COD
Intelligent Carbon Monoxide Detector
Data Sheet E85001-0648
Intelligent Multisensor Optical Smoke Detector with CO Sensor
Includes an optical smoke sensor and a carbon monoxide sensor. The detector analyzes the smoke sensor independently from the CO sensor, and can report a smoke/fire alarm separate from a CO-related life safety alarm.
SIGA-PCD
Intelligent Multisensor Smoke and CO Detector
Data Sheet E85001-0651
Intelligent Multisensor Optical Smoke Detector with Heat and CO Sensors
Includes a photoelectric smoke sensor, a fixed-temperature heat sensor, and a carbon monoxide sensor. The detector
analyzes the smoke and heat sensors independently from the CO sensor, and can report a smoke/fire alarm separate
from a CO-related life safety alarm.
20
SIGA-PHCD
Intelligent Multisensor Smoke, Heat, and CO Detector
Data Sheet E85001-0649
EST3X
Intelligent Initiating Devices
SUBMIT

Fire Detectors
Intelligent Optical Smoke Detector
The workhorse of modern fire alarm systems, this devices includes a photoelectric smoke sensor to detect smoke.
SIGA-PD
Intelligent Optical Smoke Detector
Data Sheet E85001-0646
Initiating
Devices
Intelligent Rate-of-rise and Fixed Temperature Heat Detector
Includes a rate-of-rise and a fixed-temperature sensor to detect heat from fire.
SIGA-HRD
Intelligent fixed temperature/Rate-of-rise heat detector
Data Sheet E85001-0647
Intelligent Multisensor Optical Smoke and Heat Detector
Contains a fixed-temperature heat sensor to detect heat from fire and a photoelectric smoke sensor to detect smoke.
Unlike simple multi-criteria detectors, the SIGA-PHD can report the heat and photo elements as separate event types
— or together. This permits the photo element of the detector to report, for example, a supervisory event during the
day, and an alarm event at night – while the heat element always reports an alarm.
SIGA-PHD
Intelligent Multisensor Smoke and Heat Detector
Notification
Appliances
Data Sheet E85001-0650
Duct Smoke Detectors
Remote
test station
Alarm relay output
Duct smoke
detector
Return
air
Duct smoke
detector
Supply
air
HVAC
unit
Alarm relay output
Remote
test station
FACP
Hazardous Location
Devices
SuperDuct Detectors
Less than two inches deep, SuperDuct intelligent smoke detectors are ideal
for installation in ductwork, where space is always at a premium. Offering
the most advanced and most reliable performance in its class, SuperDuct
represents the perfect balance of practical design and advanced technology.
SuperDuct detectors feature a unique design that speeds installation and
simplifies maintenance. Removable dust filters, conformally coated circuit
boards, and optional water-resistant gaskets keep contaminants away
from components, ensuring years of trouble-free service. When cleaning
is required, the assemblies come apart easily and snap back together in
seconds.
Intelligent SuperDuct Detector
Data Sheet E85001-0584
SD-PH
Protective housing for high humidity environments
Data Sheet E85001-0584
Sampling Tubes
SD-T8 (8”)
SD-T42 (42”)
SD-T18 (18”)
SD-T60 (60”)
SD-T24 (24”)
SD-T78 (78”)
Remote Test Stations
SD-TRM (magnetic)
SD-TRM (keyed)
SIGA-LED (Remote alarm LED)
Accessories
SD-GSK (cover gasket kit)
SD-MAG (Test magnet kit)
SD-VTK (Air velocity test kit, stoppers only)
SIGA-SDPCB (PCB/Signature sensor kit)
Door Holders
& Relays
SIGA-SD
SD-T36 (36”)
SD-T120 (120”)
21
EST3X
Intelligent Initiating Devices
EST3X
Head End
SUBMIT

Detector Bases
Sounder
Base UL
approved
for sleeping
areas!
Sounder
Sounder
Listed 24
V EOL
3
Supervising
Equipment
AUX_RISER +
AUX_RISER -
Audible (Sounder) Bases
CO system wiring
for detector
Tone
Generator
Signature Series Sounder Bases add audible output
operation of bases
functions to Signature Series smoke and CO detectors.
Bases can operate as independent local alarms, or as
part of a zone or system alarm with synchronized audible output. The SIGA-AB4G-LF is UL listed for
sleeping areas and other applications requiring 520 Hz low frequency audible tones.
Initiating
Devices
SLC +
SLC -
SIGA-AB4G-LF
Low Frequency Audible (Sounder) Base for CO and Fire Detectors
Data Sheet E85001-0640
SIGA-AB4GT
Audible (Sounder) Base for CO and Fire Detectors
Data Sheet E85001-0640
SIGA-TCDR
Temporal Pattern Generator for SIGA-AB4GT, SIGA-AB4G-LF
Data Sheet E85001-0640
SIGA-AB4G
Audible (Sounder) Base for SIGA-PS Detectors Only
Data Sheet E85001-0640
AB4G-SB
Surface Box for Audible Bases
Data Sheet E85001-0640
Standard Detector Bases
Standard detector bases provide roomside wiring terminals. They mount to
North American one-gang box, 3½ or 4-inch octagon boxes, or 4-inch square
electric box. Bases for 4-inch square boxes include the SIGA-TS4 Trim Skirt to
conceal the electric box and provide a finished appearance.
SIGA-SB
SIGA-SB4 (with trim skirt)
Standard Detector Base
Data Sheet E85001-0245
Isolator Detector Base
Isolator detector bases provide room-side wiring terminals and includes a built-in
line fault isolator. Models with integral switches allow the detector to be removed
from its base without causing the isolator to operate. Mounts to North American
one-gang box, 3½ or 4-inch octagon boxes, or 4-inch square electrical boxes.
Bases for 4-inch square boxes include the SIGA-TS4 Trim Skirt to conceal the
electrical box and provide a finished appearance.
SIGA-IB
SIGA-IB4 (with trim skirt)
Isolator Detector Base
Data Sheet E85001-0245
Relay Detector Base
This base includes a relay. Normally-open or closed operation is selected during
installation. The dry contact is rated for 1 amp (pilot duty) @ 30 Vdc. The relay’s
position is supervised to avoid accidentally jarring it out of position. The relay
base does not support the SIGA-LED remote LED. It mounts to North American one-gang boxes, 3½ or 4-inch octagon boxes, or 4-inch square electrical
boxes. Bases for 4-inch square boxes include the SIGA-TS4 Trim Skirt to conceal
the electrical box and provide a finished appearance.
22
SIGA-RB
SIGA-RB4 (with trim skirt)
Relay Detector Base
Data Sheet E85001-0245
EST3X
Detector Accessories
SIGA-TCDR Temporal Pattern Generator
Intelligent Initiating Devices
SUBMIT
AUX_RISER_IN +
AUX_RISER_OUT +
A
1

2
From previous device
SLC_IN +
To next device
SLC_OUT +
The SIGA-TCDR Temporal Pattern Generator is an addressable
device that generates sound patterns for carbon monoxide (CO) and fire signals for the
AB4GT sounder base. The control panel sends synchronization and channel commands to
the SIGA-TCDR; the channel selection determines the pattern.
SIGA-TCDR
Temporal Pattern Generator for AB4GT Sounder Base
Initiating
Devices
Data Sheet E85001-0623
Detector Mounting Plate
The SIGA-DMP Detector Mounting Plate is a 7-inch (178mm) square mounting plate designed
to provide convenient mounting of Signature Series intelligent smoke detectors in raised floor
or plenum applications. The detector mounting plate may also be installed in low velocity
ducts that have a maximum width of up to 36-inches (915mm) and a maximum height of up
to 36-inches (915mm).
SIGA-DMP
Detector Mounting Plate
Data Sheet E85001-0255
Notification
Appliances
Remote LED
The remote LED connects to the SIGA-SB or SIGA-SB4 Standard Base. It features a North
American size one-gang plastic faceplate with a white finish and red alarm LED.
SIGA-LED
Data Sheet E85001-0245
Hazardous Location
Devices
Remote Alarm LED
Trim Skirt Use the SIGA-TS Trim Skirt to give Signature detectors a finished look and hide surface
imperfections around the detector’s base. Supplied with all four-inch detector bases, the
SIGA-TS4 can also be ordered separately. Use the black model with SIGA-IPHSB.
SIGA-TS
Detector Trim Skirt (white)
Data Sheet E85001-0245
SIGA-TSB
Detector Trim Skirt (black)
Data Sheet E85001-0245
SIGA-TS4
Detector Trim Skirt (white) – for 4-inch box
Data Sheet E85001-0245
Detector Guard
Door Holders
& Relays
Constructed of sturdy 16-guage steel, the SIGA-DG Smoke Detector Guard is designed
SIGA-PS smoke detectors from damage or tampering. The advanced louver system allows
smoke detectors to be installed at their listed spacing and has no effect on operating sensitivity.
SIGA-DG
SIGA-DGSB
Smoke Detector Guard
Data Sheet E85001-0359
Detector Guard Surface Mount Accessory
Data Sheet E85001-0359
23
EST3X
Intelligent Initiating Devices
EST3X
Head End
SUBMIT

Signature Series
Input/Output Modules
Signature Series input/output modules are extremely flexible and
Initiating
Devices
powerful devices that gather analog information from the slave devices
Plug-in UIOs
connected to them and convert this data into digital signals. They are
with motherboard
available in models that mount in standard one- or two-gang electrical
boxes, as well as versions that plug into UIO motherboards.
Standard two-gang mount
The actual function of each module is determined by its installerselected personality code. This is downloaded to the module from the
Signature Loop Controller during system configuration. Because they are intelligent devices, all decisions are made
at the module. This allows lower communication speed but very fast control panel response time and less sensitivity
to line noise and loop wiring properties. As a result, twisted or shielded wire is not required.
Application
Voice messages
Waterflow Switches
Class A indicating and initiating circuits,
two-wire smoke detectors
Class B Initiating Circuits:
Door Closers, Fans, Dampers
Telephone Power and Audible/Visual Signal
Power Selector, Strobe Synchronization
Sounder Base power
Fire Suppression
Fault detection
Module
Digital Messaging Module
Waterflow/Tamper Module
Universal Class A/B
Module
Class B Input Module
Monitor Module
Control Relay Module
Signal Module
Signature Series intelligent
input/output modules feature
multiple user-set personality
codes that define the module’s
behavior.
Reversal Relay Module
Releasing Module
Isolator Module
UIO Motherboard
Module mounting and installation options
Plug-in (UIO)
Module
Signature Series input/output modules are available in models that
feature two mounting options: standard mount and plug-in.
Standard mount models are installed to North American two-gang
or one-gang electrical boxes, making them ideal for locations where
only one module is required. Separate I/O and data loop connections
are made to each module.
Cabinet or electrical enclosure
Plug-in UIO
RM
ALA
FIRE DULE
MO
Plug-in UIO modules mount to UIO mothStandard mount
erboards. Two- and six-module UIO
(one- or two-gang)
motherboards are available, making them ideal for installations
where more than one module is required. Motherboards can
accommodate individual risers for each on-board module,
or shared risers in any combination with their UIO
modules. All wiring connections are made
to terminal blocks on the motherboard.
UIO assemblies may be mounted in either
cabinets, or standard electrical enclosures.
24
EST3X
Intelligent Initiating Devices
SUBMIT

Audio Preamp Riser
Digital Message Module
OUT
IN
1 2 3 4
TB7 TB1
1 2 3 4
TB2
The SIGA-MDM Digital Message Module provides custom
pre-recorded voice messaging. Two standard factory prerecorded messages are included. Each module can store two
_
+
30 second messages in its non-volatile EEPROM memory.
A microphone/line-level audio input stereo jack and output
stereo jack, as well as record and playback switches are
conveniently located on top of the module. Programming in
_
+
the Signature Data Controller provides all control instructions;
extra wiring for monitoring or controlling circuits is not required. Up to 47 modules can be
cascaded together. The SIGA-MDM is available as a plug-in module only.
MSG 1
MSG 1
NORMAL
MSG 2
NORMAL
MSG 2
SDC
To Signature
Loop
Controller
(SLC)
SDC
ACTIVE
CLIP
4
3
2
1
LINE
ACTIVE
CLIP
MIC.
MIC.
P1
LINE
REC.
LINE
P2
REC.
LINE
IN
IN
HEAD
TB15
HEAD
TB8
1 2 3 4
First
To Other
SIGA Devices
SIGA-MDM
Intelligent Digital Message Module
PLAY
PHONES
TB9
24 Vdc To
Other Loads
4
3
2
1
Initiating
Devices
PLAY
PHONES
1 2 3 4
Downstream
Jumper
24 Vdc
From Power Supply
Data Sheet E85001-0363
Notification
Appliances
Universal Class A/B Module
The Universal Class A/B Module is used to connect initiating, appliance, or two-wire smoke
circuits in either Class A or Class B configurations. The plug-in version can also be used as a
Class A dry contact initiating device circuit. The actual function of this module is determined
by the “personality code” selected by the installer. Up to fifteen personalities are available.
SIGA-UM
SIGA-MAB
SIGA-UM
SIGA-MAB
Universal Class A/B Module (Two-gang standard mount)
Data Sheet E85001-0275
Universal Class A/B UIO (Plug-in) Module
Data Sheet E85001-0275
Hazardous Location
Devices
Class B Input Module
The Class B Input Module is used to connect Class B normally-open Alarm, Supervisory, or
Monitor type dry contact initiating device circuits. The standard-mount version is available with
either one or two input connections. The plug-in version accepts two input connections. The
actual function of this module is determined by the “personality code” selected by the installer.
A total of four personalities are available.
SIGA-CT1/CT2
SIGA-MCT2
SIGA-CT1
Single Input Module (One-gang standard mount)
Data Sheet E85001-0241
SIGA-CT2
Dual Input Module (One-gang standard mount)
Data Sheet E85001-0241
SIGA-MCT2
Dual Input UIO (Plug-in) Module
Data Sheet E85001-0241
Door Holders
& Relays
25
EST3X
Intelligent Initiating Devices
Initiating
Devices
EST3X
Head End
SUBMIT

Signal Module
The Signal Module is used to connect, upon command from the loop controller, supervised
Class B signal or telephone circuits to their respective power inputs. Models are available with
one or two power inputs. These may be either polarized 24 Vdc to operate audible and visual
signal appliances, or 25 and 70Vrms to operate audio evacuation speakers and firefighter’s
telephones. The actual function of this module is determined by the “personality code” selected
by the installer. A total of three personalities are available.
SIGA-CC1
SIGA-MCC1
Single Input Signal Module (Two-gang standard mount)
Data Sheet E85001-0237
Single Input Signal UIO (Plug-in) Module
Data Sheet E85001-0237
SIGA-CC2
Dual Input Signal Module (Two-gang standard mount)
Data Sheet E85001-0237
SIGA-MCC2
Dual Input Signal UIO (Plug-in) Module
Data Sheet E85001-0237
SIGA-CC2A
Dual Input Signal Module with Class A Operation (Two-gang mount) Data Sheet E85001-0609
SIGA-MCC2A
Dual Input Signal UIO with Class A Operation (Plug-in) Module
Data Sheet E85001-0609
Control Relay Module
The Control Relay Module provides a Form C dry relay contact to control external appliances
such as door closers, fans, dampers etc. This device does not provide supervision of the
state of the relay contact. Instead, the on-board microprocessor ensures that the relay is in
the proper ON/OFF state. Upon command from the loop controller, the relay activates the
normally open or normally-closed contact. This module supports only one personality: no user
configuration is required.
SIGA-CR
Control Relay Module (One-gang standard mount)
Data Sheet E85001-0239
SIGA-MCR
Control Relay UIO (Plug-in) Module
Data Sheet E85001-0239
SIGA-CRH
High Power Control Relay Module (One-gang standard mount)
Data Sheet E85001-0644
Polarity Reversal Relay Module
The Polarity Reversal Relay Module provides a Form C dry relay contact to power and activate a
series of SIGA-AB4 Audible Sounder Bases. Upon command from the Signature loop controller,
the SIGA-CRR reverses the polarity of its 24 Vdc output, thus activating all Sounder Bases on
the data loop. This module supports only one personality: no user configuration is required.
SIGA-CRR
SIGA-MCRR
Polarity Reversal Relay Module (One-gang standard mount)
Data Sheet E85001-0239
Polarity Reversal Relay UIO (Plug-in) Module
Data Sheet E85001-0239
Riser Monitor Module
The SIGA-RM1 Riser Monitor Module is an intelligent device that monitors the integrity of 24
Vdc, 25 Vac, and 70 Vac circuits, as well as telephone riser signals. Upon the loss of a signal,
the Riser Monitor Module causes the fire alarm control panel to indicate an alert status. Personality codes downloaded to the Riser Monitor Module during system configuration determine
its function.
SIGA-RM1
SIGA-MRM1
26
Riser Monitor Module (One-gang standard mount)
Data Sheet E85001-0535
Riser UIO (Plug-in) Module
Data Sheet E85001-0535
EST3X
Intelligent Initiating Devices
SUBMIT

Synchronization Output Module
The Synchronization Output Module is an intelligent device that connects a supervised output
circuit to a 24 Vdc riser. The output wiring is monitored for open circuits and short circuits.
A short circuit will cause the fire alarm control panel to inhibit the activation of the audible/
visual signal circuit so the riser is not connected to the wiring fault. Upon command from the
Signature loop controller, the Auto-Sync Output Module connects the output circuit to the
riser input. The output circuit operates polarized audible and visual appliances that have an
adjustable resynchronizing feature.
SIGA-CC1S
SIGA-MCC1S
Synchronization Output Module (One-gang standard mount)
Data Sheet E85001-0543
Synchronization Output UIO (Plug-in) Module
Data Sheet E85001-0543
Initiating
Devices
Input/Output Module
The Input/Output Module is an intelligent device that provides the following
modes of operation:
•
Output with monitor input
•
Input/programmable output
•
Input/direct output
SIGA-IO
SIGA-MIO
Input/Output Module (One-gang standard mount)
Data Sheet E85001-0533
Input/Output UIO (Plug-in) Module
Data Sheet E85001-0533
Notification
Appliances
Waterflow/Tamper Module
The SIGA-WTM Waterflow/Tamper Module is a two circuit intelligent module. Circuit 1 is for Class
B normally-open waterflow alarm switches. When the input contact is closed for approximately 16
seconds, an “alarm” signal is sent to the loop controller. Circuit 2 is for Class B normally open dry
contact supervisory and tamper switches. When the input contact is closed, an “active” signal is
sent to the loop controller. Conditions on both circuits are latched at the module.
SIGA-WTM
Waterflow/Tamper Module (One-gang standard mount)
Data Sheet E85001-0297
Hazardous Location
Devices
Isolator Module
The SIGA-IM Isolator Module is an intelligent device that allows part of the Signature data loop
to continue operating in the event of a short circuit. The module can be wired into a Class
A data loop at any point. A maximum of 96 isolator modules can be installed on one circuit.
If a fault occurs, the isolator cuts power to all devices beyond the isolator on the loop. Once
activated, the line fault isolator continuously checks the faulted side of the loop to determine
if the short still exists. When the fault is cleared, the module automatically restores the entire
data loop to its normal condition.
SIGA-IM
Fault Isolator Module (Two-gang standard mount)
Data Sheet E85001-0271
Door Holders
& Relays
Monitor Module
The SIGA-MM1 is a single-circuit intelligent module that includes a Class B normally-open dry
contact. This is used for monitoring input from devices such as fans, dampers, and doors.
When the input contact is closed, an “active” signal is sent to the loop controller. The active
condition is not latched at the module.
SIGA-MM1
Monitor Module (One-gang standard mount)
Data Sheet E85001-0297
27
EST3X
Intelligent Initiating Devices

Universal Input/Output (UIO) Motherboards
Signature Series Universal Input/Output Module Motherboards provide mounting
and wiring terminations for up to six Signature Series plug-in UIO (SIGA-“M” series) modules. UIO motherboards snap into a rigid extruded track (included) with
mounting pads for convenient mounting into a variety of equipment enclosures. UIO
modules plug into the board and are held securely in place with captive machine
screws. All field wiring connects to terminal blocks on the motherboard, which
R
permits rapid removal and replacement of modules for troubleshooting.
6
UIO
The SIGA-UIO2R provides mounting and wiring terminations for up to two UIO
modules, and the SIGA-UIO6R provides mounting and wiring terminations for up
to six UIO modules. Both motherboards feature a riser #1 input and a riser #2 input
2R
bus. Jumpers on riser #1 input (between modules), facilitate sharing a single riser
UIO
among more than one module. This significantly reduces wiring requirements. Removing the jumpers provides
Module Input/Output Wiring
separate riser inputs to each adjacent module. Riser #2 input is
fixed to each module position and cannot be split.
Initiating
Devices
EST3X
Head End
SUBMIT
The SIGA-UIO6 provides mounting and wiring
terminations for up to six UIO modules. This motherboard provides two riser inputs that are common
to all modules.
UIO motherboards mount inside the MFC-A cabinet
or other suitable UL-listed electrical enclosure. Each
MFC-A will hold one UIO2R motherboard or one
UIO6 or UIO6R motherboard complete with their
full complement of modules.
Data In
Signature
Data
Circuit
Riser 2 Input
common to
all SIGA-UIO
Modules
Data Out
Jumpers Connect
Riser Input #1
Between Modules
Individual Riser 1 Input to each SIGA-UIO module
SIGA-UIO2R Universal Input/Output Module Board with Riser Inputs — 2 Module Positions
Data Sheet E85001-0365
SIGA-UIO6R Universal Input/Output Module Board with Riser Inputs — 6 Module Positions
Data Sheet E85001-0365
SIGA-UIO6
Data Sheet E85001-0365
Universal Input/Output Module Board — 6 Module Positions
Related Equipment
MFC-A
27193-11
Surface Mount Box - Red, One-gang
27193-16
Surface Mount Box - White, One-gang
27193-21
Surface Mount Box - Red, Two-gang
27193-26
Surface Mount Box - White, Two-gang
235196P
Bi-polar Transient Protector (use with all Signal Modules)
SIGA-MP1
Signature Module Mounting Plate, 1 footprint
SIGA-MP2
Signature Module Mounting Plate, 1/2 footprint
SIGA-MP2L
Signature Module Mounting Plate, 1/2 extended footprint
28
Multi-function Cabinet (for UIO and Releasing modules)
EST3X
Intelligent Initiating Devices
SUBMIT

Releasing Module
The Signature Series Releasing Module (SIGA-REL) is an analog addressable
module that works with fire suppression systems designed to release extinguishing gas. Its primary function is the control of sprinkler pre-action routines and the
initiation of suppression system deluge functions. The module is easily configured
in the field and offers a wide range of options that prevent the unnecessary release
of extinguishing agent.
Initiating
Devices
The SIGA-REL is a network component consisting of:
• Two supervised release circuits
• Two supervised pre-release circuits
• One supervised manual
Abort
release input circuit
Manual Release
• One supervised abort circuit for N/O abort switch
• One first alarm output
relay (Form C Contact)
+
SIGA-REL
First alarm output
Form C 3 A @24 Vdc
SW1-SW8
TB3
TB6
_
+
_
TB2
+
TB1
_
Signature data out
+
_
DS2
DS4
+
DS3
DS5
DS6 DS7
TB5
_
_
+
+
TB4 _
_
+
Pre-release CCT2 (steady)
Pre-release CCT1 (pulsed 15/60)
RELA-EOL
Available releasing module accessories include dedicated pull stations, abort switches and service switches. Together with the SIGAREL, they comprise a complete fire suppression package.
24 Vdc out
DS1
1
2
3
4
Release CCT1
Notification
Appliances
The releasing module includes a built-in timer that inhibits the deluge
function during the pre-action routine. One of four pre-action routines,
may be selected by means of dip-switches on the module. The
duration of automatic and manual time delays, as well as the abort
time settings are also selectable with dip-switches. The SIGA-REL
mounts inside an MFC-A cabinet or other suitable UL-listed electrical
enclosure. Each MFC-A will hold one SIGA-REL.
Signature data in
24 Vdc in
RELA-EOL
1
2
3
4
Release CCT2
SIGA-REL
Analog addressable releasing module
Data Sheet E85001-0531
RELA-ABT
Abort station
Data Sheet E85001-0531
RELA-SRV
Service disconnect station
Data Sheet E85001-0531
276A-REL
Manual releasing station (single-action)
Data Sheet E85001-0531
278A-REL
Manual releasing station (double-action)
Data Sheet E85001-0531
RELA-EOL
Polarized end-of-line relay
Data Sheet E85001-0531
Hazardous Location
Devices
Door Holders
& Relays
29
EST3X
Intelligent Initiating Devices
Initiating
Devices
EST3X
Head End
SUBMIT

Manual Pull Stations
SIGA-270
SIGA-270P
276-K2
270-GLR
276B-RSB
TB2
Single Action Pull Stations
SIGA-270 series manual pull stations are made from
die-cast zinc and finished with red epoxy powdercoat paint. With positive pull-lever operation, one
pull on the station handle breaks the rod and turns
in a positive alarm. Where two-stage operation is required, SIGA-270P pre-signal models are equipped
with a general alarm (GA) keyswitch.
REAR VIEW
Red LED
(Alarm/Active)
8
7
4
3 2 1
Green LED
(Normal)
TB1
DATA IN (+)
DATA OUT (+)
DATA IN (-)
DATA OUT (-)
To Next Device
From Signature Controller
or Previous Device
One Stage Fire Alarm Station, English Markings
Data Sheet E85001-0279
Two Stage (Pre-signal) Fire Alarm Station, English Markings
Data Sheet E85001-0279
GA Key — for pre-signal station
Data Sheet E85001-0279
20 Break-rods — for SIGA-270 series Data Sheet E85001-0279
Surface Mount Box, Red — for SIGA-270 series
Data Sheet E85001-0279
REAR VIEW
Double Action Pull Stations
The double action, single stage SIGA-278 station is a
contemporary style manual station made from durable
red LEXAN. To initiate an alarm, first lift the upper door,
then pull the alarm handle.
TB2
Red LED
(Alarm/Active)
8
7
4
3 2 1
Green LED
(Normal)
TB1
DATA IN (+)
DATA OUT (+)
DATA IN (-)
DATA OUT (-)
From Signature Controller
or Previous Device
To Next Device
SIGA-278
Double Action (One Stage) Fire Alarm Station, English Markings
Data Sheet E85001-0279
276B-RSB
Surface Mount Box, Red — for SIGA-278 series
Data Sheet E85001-0279
276-GLR
20 Break-rods — for SIGA-278 series
Data Sheet E85001-0279
Manual Station Relocator
The Manual Station Relocator is designed to lower the height of a fire alarm pull station to meet ADA
requirements. Most existing pull stations are mounted 60 inches (1524mm) or higher above the floor.
The Relocator lowers the height to 48 inches (1220mm) without the need for pulling new wires or
moving the existing electrical box.
RR-32RL
Pull Station Relocator
Data Sheet E85001-0351
Stopper II
This unique device helps prevent false alarms without restricting legitimate ones. It consists of a tamperproof clear LEXAN polycarbonate shield and frame that fits easily over manual pull stations. When lifted,
it sounds a piercing warning horn.
STI-1100 (Flush)
STI-1130 (Surface)
Stopper II with Horn
Data Sheet E85001-0491
STI-1200 (Flush)
STI-1230 (Surface)
Stopper II without Horn
Data Sheet E85001-0491
STI-3100 (2" Spacer)
STI-3004 (Conduit Insert)
Spacers
Data Sheet E85001-0491
STI-3002 (Gasket)
STI-3003 (Conduit Gasket)
Weatherproofing
Data Sheet E85001-0491
30
EST3X
Notification
Appliances
EDWARDS notification appliances are high-performance devices finely
N o t i fi c a t i o n A p p l i a n c e s
Wall Strobes, Horns & Chimes p. 33
Low Frequency Horns and Horn-Strobes p. 34
LED Strobes and Horn-Strobes p. 34
Outdoor Horns & Strobes p. 35
Wall Speakers & Speaker-Strobes p. 36
Ceiling Speakers, Horns & Strobes p. 37
Outdoor Speakers & Strobes p. 38
LED Strobes and Horn-Strobes p. 39
High Power Speaker Arrays p. 39
Medium Power Speaker Arrays p. 40
Audible Signals p. 41
Harsh Environment Signals p. 42
Accessories p. 43
tuned to deliver maximum output in exchange for the lowest possible current draw. Covering the entire spectrum of life safety applications, these
devices are durable, dependable, and virtually maintenance-free. And they
support a wide range of mounting options that make them ideal for new
construction and retrofit applications alike.
Class B Notification Appliance Circuit with Genesis Signals
and Signal Master for independent sounder and strobe
control and synchronisation
Field Wiring
Notification appliances may be configured
for Class A or Class B wiring. Genesis
combination horn-strobes, when used
with the innovative Signal Master Module,
support independent horn control over
a single pair of wires and precision
synchronization that exceeds UL
requirements. This reduces wiring time while
meeting the requirements of even the most
demanding application.
Notification
Appliances
Notification Appliance Circuit
Class B with separate strobe and horn circuits
Notification Appliance Circuit
Class A with combination horn-strobe circuit
Device Wiring, Horn-strobes
To listed fire alarm control panel
(supervised amplifier signal circuit
– 25.2 or 70.7V rms)
+
+
To listed fire alarm control panel
(supervised signal circuit
– 20-24 Vdc)
+
+
Polarity shown in
alarm condition
S
S-
S+
C
SPKR
S
S-
S+
C
SPKR
Hazardous Location
Devices
Device Wiring, Speaker-strobes
To next device
or end of line
device
All appliances feature #18 - #12 AWG terminals
– ideal for long runs, existing wiring
Syncrhonization Sources
On a common circuit, strobes flash once per second (1
fps) within 10 milliseconds over a two-hour time period. A
synchronization source is required to comply with UL 1971
synchronization standards. Temporal setting (private mode
only): synchronized to temporal output on the same circuit.
The following control panels, power supplies, and modules
provide synchronization sources that enable Genesis strobe
devices to comply with UL 1971 synchronization standards:
SIGA-CC1S, SIGA-MCC1S, SIGA-CC2A, SIGA-MCC2A,
G1M-RM, BPS6A, BPS10A, APS6A, APS10A, EST3X, iO64,
iO500, VS1, VS2, VM, E-FSA64, E-FSA250, Fireshield Plus.
Door Holders
& Relays
Strobe Syncrhonization
31
EST3X
N o t i fi c a t i o n A p p l i a n c e s
EST3X
Head End
Genesis Visual
& Audible Signals
A complete line engineered to
deliver innovative features and
superb output.
The award-winning Genesis line of products represents
excellence in fire alarm notification with looks, features, and
performance benefits designed with your project in mind.
Wall strobes, horns, and chimes about the size of a deck
of playing cards offer a discreet alternative to bulky devices,
Initiating
Devices
while speakers and ceiling models with clean modern lines
Wall Strobes, Horns, Chimes,
p. 33
blend inconspicuously with their surroundings.
Signaling on-demand
Though designed for discretion, Genesis signals are also
Low Frequency Horns and HornStrobes, p. 34
engineered to command attention. Wall-penetrating high
dB output and patented FullLight strobe technology immerse the protected area with levels of light and sound
that simply can’t be ignored – all in exchange for the low-
Notification
Appliances
Ceiling Horns,
Horn-Strobes, p. 34
est current demands of any device in their class.
Genesis brings on-demand signaling to every application with an unparalleled range of field-configurable
options: horns and chimes with high/low dB output
Outdoor Horns, Horn-Strobes,
p. 35
settings; speakers with multiple wattage tap selections;
and strobes with selectable candela output and flash
rate – options that put you in the driver’s seat when time
is short, budgets slim, and manpower at a premium. It
also means fewer parts to stock, less inventory to worry
Wall Speakers and Speaker-strobes,
p. 36
about, and the flexibility to meet changing demands – on
the fly – without having to reinstall equipment or order
more parts!
Ceiling Speakers, Speaker-strobes,
p. 37
Application flexibility
Whether you’re designing for a new landmark structure,
or simply retrofitting a local strip mall, competitivelypriced Genesis signals bring value, good looks, and
installation flexibility to every application. Contact ED-
Outdoor Speakers, Speaker-Strobes,
p. 38
32
LED Strobes and Horn-Strobes,
p. 39
WARDS today to learn how your signal solutions can be
the model of discretion.
EST3X
N o t i fi c a t i o n A p p l i a n c e s
SUBMIT

Genesis Series Wall Models
Wall Strobes,
Horns & Chimes
Genesis signals feature textured housings in architecturally neutral white or
traditional fire red. An ingenious iconographic symbol indicates the purpose
of the device. This universal symbol is code-compliant and is easily recognized by all building occupants regardless of what language they speak.
models with “FIRE” and “ALERT” markings are also available.
Genesis strobes offer 15 to 110 candela output, which is selectable with a conveniently-located switch on the side of the
device. The candela output setting remains clearly visible even after final installation, yet it stays locked in place to prevent
unauthorized tampering. (Data Sheet E85001-0573)
White housing
no marking
G1-VM
White housing
with “FIRE”
G1F-VM
Red housing
no marking
G1R-VM
G1F-V1575
Red housing
with “FIRE”
Fire Alarm Appliances
(with “Running Man” icon)
G1RF-VM
Strobe only (15/30/75/110 cd)
G1RF-V1575
Strobe only (15/75 cd¹), 24 V
White housing
no marking
White housing
with “FIRE”
Red housing
no marking
Red housing
with “FIRE”
Fire Alarm Appliances
(with “Running Man” icon)
G1-HD
G1F-HD
G1R-HD
G1RF-HD
G1-HDVM
G1F-HDVM
G1R-HDVM
G1RF-HDVMHorn-strobe (15/30/75/110, high/low dB)
Horn only (high/low dB)
G1F-HDV1575
G1RF-HDV1575Horn-strobe (15/75 cd¹, high/low dB), 24 V
G1F-P
G1RF-P
G1-P
G1R-P
Notification
Appliances
Genesis Horns and Horn-strobes reach output levels as high as 99 dB and features a unique multiple frequency tone that
results in excellent wall penetration and an unmistakable warning of danger. Horns may be configured for either coded or noncoded signal circuits. They can also be set for low dB output with a jumper cut that reduces horn output by about 5 dB.
(Data Sheet E85001-0573)
Steady horn (not compatible with Signal Master)
Hazardous Location
Devices
Genesis mass notification appliances bring the same high-performance fire alarm features and unobtrusive design to
mass notification applications. Available with amber lenses and optional “ALERT” housing labels, they are ideal for applications that require differentiation between fire alarm and mass notification alerts. (Data Sheet E85001-0573)
White housing
no marking
White housing
with “ALERT”
Mass Notification Appliances
(with no “Running Man” icon)
G1WN-VMA
G1WA-VMA
Strobe only, amber lens (A/B/C/D cd settings)
G1WN-VMC
G1WA-VMC
Strobe only, clear lens (15/30/75/110 cd)
Genesis chimes and chime-strobes produce a pleasing mellow tone. When steady (non-stroked) voltage is applied, the
chime automatically pulses at 60 strokes per minute, or may be field-configured for temporal output. When installed with a
GIM Signal Master Module, the chime may also be field-configured for coded operation, which enables the chime output
to match the rate that voltage is applied to the circuit. Chimes may be set for low dB output with a jumper cut that reduces
sound output by about 5 dB. (Data Sheet E85001-0574)
White housing
Red housing
Chimes and Chime-strobes
G1-CVM
G1R-CVMChime-strobe (15/30/75/110, high/low dB)
G1-C
G1R-C
Door Holders
& Relays
Chime only (high/low dB)
Trim plates for wall horns, chimes, and strobes are ideal for covering openings left behind during retrofits.
White plate
White plate
Red plate
no marking
with “FIRE”
no “FIRE”
G1T
G1T-FIRE
G1RT
Red plate
White plateFire with “FIRE”
with “ALERT”
G1RT-FIRE
G1WT-ALERT
Trim Plates
Trim plate for 2-gang or 4” boxes
¹ 15/75 cd models provide fixed output. The 15 cd output component complies with UL1971. The 75 cd output component complies with UL 1638.
33
EST3X
N o t i fi c a t i o n A p p l i a n c e s

Genesis G4LF Series Wall Models
Low Frequency (520 Hz)
Horns and Horn-Strobes
UL
compliant
signals for
sleeping
areas!
G4LF Series notification appliances provide the benefits of Genesis life safety signals with
output suitable for sleeping areas and other applications requiring low frequency audible tones.
These high-performance appliances generate a crisp 520 Hz tone in the standard 3-3 temporal pattern. An optional setting configures the appliance for continuous audible output — a
critical feature for notification appliance circuits that are coded with a CDR-3 coder module.
All G4LF appliances feature field-configurable high and low dB output settings. Horn-Strobe
models feature field-selectable 15, 30, or 75 cd output settings.
G4LFWN-HVM
Horn-Strobe, 520 Hz, White Housing, No Marking, 15/30/75 cd
Data Sheet E85001-0639
G4LFWF-HVM
Horn-Strobe, 520 Hz, White Housing, FIRE Marking, 15/30/75 cd
Data Sheet E85001-0639
G4LFRN-HVM
Horn-Strobe, 520 Hz, Red Housing, No Marking, 15/30/75 cd
Data Sheet E85001-0639
G4LFRF-HVM
Horn-Strobe, 520 Hz, Red Housing, FIRE Marking, 15/30/75 cd
Data Sheet E85001-0639
G4LFWN-H
Horn, 520 Hz, White Housing, No Marking
Data Sheet E85001-0639
G4LFWF-H
Horn, 520 Hz, White Housing, FIRE Marking
Data Sheet E85001-0639
G4LFRN-H
Horn, 520 Hz, Red Housing, No Marking
Data Sheet E85001-0639
G4LFRF-H
Horn, 520 Hz, Red Housing, FIRE Marking
Data Sheet E85001-0639
Notification
Appliances
Initiating
Devices
EST3X
Head End
SUBMIT
Genesis GC Series Ceiling Models
Strobes and
Horn-Strobes
Genesis ceiling strobes are available in low- or high-candela output models featuring
15 to 95, or 95 to 177 cd output. The setting is selectable with a conveniently-located
switch that remains clearly visible even after final installation, yet it is locked in place
to prevent unauthorized movement after installation.
Genesis horn output reaches as high as 99 dB (peak) and features a unique multiple
frequency tone that results in excellent wall penetration. Horns may be set for low
dB output with a jumper cut that reduces horn output by about 5 dB.
Ceiling Strobes
Data Sheet E85001-0557
Ceiling Horn-strobes
Data Sheet E85001-0559
All models are rated for both wall and ceiling installation.
Fire Alarm Appliances
All fire alarm appliances come
with the “Running Man” Icon
White housing
no marking
White housing
with “FIRE”
Strobe, 15/30/75/110 (standard output) cd, selectable
GC-VM
GCF-VM
Strobe, 95/115/150/177 (high output) cd, selectable
GC-VMH
GCF-VMH
Horn-strobe, 15/30/75/110 (standard output) cd, selectable
GC-HDVM
GCF-HDVM
Horn-strobe, 95/115/150/177 (high output) cd, selectable
GC-HDVMH
GCF-HDVMH
Mass Notification Appliances
White housings
No “Running Man” Icon
Clear lens
no marking
Clear lens
Amber lens
with “ALERT”
no marking
Red housing
with “FIRE”
GCFR-VM
GCFR-HDVM
Amber lens
with “ALERT”
Strobe, four standard cd settings
GCWN-VMC
GCWA-VMC
GCWN-VMA
GCWA-VMA
Strobe, four high output cd settings
GCWN-VMHC
GCWA-VMHC
GCWN-VMHA
GCWA-VMHA
34
EST3X
N o t i fi c a t i o n A p p l i a n c e s
SUBMIT

Genesis WG4 Series Wall Models
Weatherproof Horns
and Horn-Strobes
Genesis WG4 Series horns and horn-strobes are among the most versatile emergency signals of their kind. NEMA 4X rated for indoor or outdoor use, they are suitable for a wide range of wet and harsh environments with a listed operating temperature range of as low as -31°F to as high as 151°F (-35°C to 66°C).
Refer to Data Sheet E85001-0628 -- Genesis Outdoor Horns and Strobes for details.
Field Configuration
Signal In —
Signal Out —
Signal In +
Signal Out +
Genesis WG4 strobes feature four selectable light output settings. Cd selections are changed by removing the cover and
simply sliding the switches to the desired setting, which remains
visible through a small window on the front of the device after the
cover is replaced. Genesis Horn-strobes may also be
configured for high or low dB output and temporal flash. This
battery-saving feature is intended for private mode signaling only.
WG4RF-H
WG4RF-HVMC
WG4WF-H
WG4WF-HVMC
WG4RN-H
WG4RN-HVMC
WG4WN-H
Notification
Appliances
—/+ designations indicate the signal polarity
required to activate the device.
WG4WN-HVMC
Light Output
Standard Candela Horn-strobes
UL 1971
UL 1638
CAN/ULC-S526
Indoor
Outdoor @ -35°C
Outdoor @ -40°C
Standard/rating
UL 1971
UL 1638
CAN/ULC-S526
Indoor
Outdoor @ -35°C
Outdoor @ -40°C
Strobe Switch Position
D
C
B
A
102cd 123cd 147cd 161cd
41cd
50 cd 60 cd 65 cd
11 cd 14 cd 17 cd 18 cd
White housing
no marking
White housing
with “FIRE”
Red housing
no marking
Red housing
with “FIRE”
WG4WN-H
WG4WF-H
WG4RN-H
WG4RF-H
Horn Only
WG4WN-HVMC
WG4WF-HVMC
WG4RN-HVMC
WG4RF-HVMC
Horn-Strobe, standard cd output
WG4WN-HVMHC
WG4WF-HVMHC
WG4RN-HVMHC
WG4RF-HVMHC Horn Only, high cd output
Hazardous Location
Devices
Standard/rating
High Candela Horn-strobes
Strobe Switch Position
D
C
B
A
15 cd 29 cd 70 cd 87 cd
6 cd
12 cd 28 cd 35 cd
1 cd
3 cd
8 cd
10 cd
Outdoor Fire Alarm Appliances
WG4WTS (white)
WG4RTS (red)
Surface Skirt for Genesis WG4 Appliances
74347U (white)
449 (red)
Surface mount box, outdoor rated
WG4GSKT
Door Holders
& Relays
WG4 Mounting Accessories
Genesis WG4 Full Body Mounting Gasket for Smooth Surfaces
For Audible Sounder Bases, see Intelligent Initiating Devices.
35
EST3X
Genesis
high fidelity
o
Speakers are als
low
UL compliant
ls
frequency signa
for sleeping
areas!
SUBMIT
EST3X
Head End
N o t i fi c a t i o n A p p l i a n c e s
 Genesis G4 Series Wall Models
Speakers and
Speaker-strobes
Genesis speakers combine high performance output with a low
profile design to deliver a life safety audio solution that’s as versatile
as it is effective. Protruding no more than one inch from the wall,
these appliances blend inconspicuously with any decor. All speakers feature selectable ¼, ½, 1, or 2 watt operation.
Candela and wattage settings remain
clearly visible even after final installation.
The ingenious Genesis G4E
Mass Notification Expander
provides a separate,
independently-controlled
strobe that fits behind a
Genesis G4 Series speaker
or speaker-strobe. (Data
Sheet E85001-0610)
Initiating
Devices
Speaker-strobes feature field-configurable candela output, selectable with a conveniently-located switch on the bottom of the device.
Genesis high fidelity Speakers are can generate UL compliant low
frequency signals now required for sleeping areas!
Speakers and speaker-strobes (Data Sheet E85001-0642)
Notification
Appliances
White housing
no marking
White housing
with “FIRE”
Red housing
no marking
Red housing
with “FIRE”
Fire Alarm Speakers
(with “Running Man” icon)
G4-S2
G4F-S2
G4R-S2
G4RF-S2
25 V Speaker
G4-S7
G4F-S7
G4R-S7
G4RF-S7
70 V Speaker
G4-S2VM
G4F-S2VM
G4R-S2VM
G4RF-S2VM
25 V Speaker-strobe (15/30/75/110 cd settings)
G4-S7VM
G4F-S7VM
G4R-S7VM
G4F-S7V1575
70 V Speaker-strobe (15/30/75/110 cd settings)
G4RF-S7V1575 70 V Speaker (15/75 cd)
High fidelity speakers and speaker-strobes meet new standards for audible tones in sleeping areas and produce
crisp, clear voice audio output that is highly intelligible over large areas. (Data Sheet E85001-0642)
White housing
no marking
White housing
with “FIRE”
Red housing
no marking
Red housing
with “FIRE”
Fire Alarm Speakers
(no “Running Man” icon)
G4HFN-S2
G4HFWF-S2
G4HFRN-S2
G4HFRF-S2
25 V Speaker
G4HFN-S7
G4HFWF-S7
G4HFRN-S7
G4HFRF-S7
70 V Speaker
G4HFN-S2VM
G4HFWF-S2VM G4HFRN-S2VM
G4HFRF-S2VM 25 V Speaker-strobe (15/30/75/110 cd settings)
G4HFN-S7VM
G4HFWF-S7VM G4HFRN-S7VM
G4HFRF-S7VM 70 V Speaker-strobe (15/30/75/110 cd settings)
High fidelity mass notification speakers and speaker-strobes feature optional amber lenses and “ALERT” lettering on
white housings, and meet new standards for audible tones in sleeping areas. (Data Sheet E85001-0642)
Clear lens
“ALERT”
Amber lens
no marking
Amber lens
“ALERT”
High Fidelity Mass Notification Speakers
— white housing, no “Running Man icon”
G4HFWA-S2VMC
G4HFWN-S2VMA
G4HFWA-S2VMA
25 V Speaker-strobe (A/B/C/D cd settings)
G4HFWA-S7VMC
G4HFWN-S7VMA
G4HFWA-S7VMA
70 V Speaker-strobe (A/B/C/D cd settings)
Speaker only models:
G4HFWA-S2 (25 V, “ALERT” marking)
G4HFWA-S7 (70 V, “ALERT” marking)
Mass notification speakers and speaker-strobes feature amber lenses and optional “ALERT” lettering. They are ideal for
applications that require differentiation between fire alarm and mass notification alerts. (Data Sheet E85001-0642)
Clear lens
no marking
Clear lens
“ALERT”
Amber lens
no marking
Amber lens
“ALERT”
Mass Notification Speakers
— white housing, no “Running Man” icon
G4WN-S2VMC
G4WA-S2VMC
G4WN-S2VMA
G4WA-S2VMA 25 V Speaker-strobe (A/B/C/D cd settings)
G4WN-S7VMC
G4WA-S7VMC
G4WN-S7VMA
G4WA-S7VMA 70 V Speaker-strobe (A/B/C/D cd settings)
G4EWF-C
G4EWN-A
G4EWA-A
Mass notification expander, white
G4ERN-A
G4ERA-A
Mass notification expander, red
G4EWN-C
Speaker-only models, 25 V:
G4WN-S2 (no marking)
G4WA-S2 (“ALERT” marking)
Speaker-only models, 70 V:
G4WN-S7 (no marking)
G4WA-S7 (“ALERT” marking)
36
EST3X
N o t i fi c a t i o n A p p l i a n c e s
Genesis
high fidelity
o
Speakers are als
low
UL compliant
ls
frequency signa
for sleeping
areas!
Genesis GC Series Ceiling Models
Speakers and
Speaker-Strobes
The Genesis line of multi-candela and multi-wattage ceiling
signals feature all the hallmarks that have made Genesis
products a big hit with designers, engineers, building owners, and installers everywhere. Precision timing electronics, and low current draw bring the benefits of the popular
Genesis wall-mount models to ceiling applications. These
signals are 30 percent slimmer than comparable signals
on the market. They are compatible with standard 4-inch
(10 cm) square electrical boxes and don’t require extension
rings or trim plates.
SUBMIT

Select
15/30/75/95
and 95/115/150/177
candela output!
Select
¼, ½, 1, or 2
watt operation!
Data Sheet E85001-0641
Fire Alarm Speakers and Speaker-strobes
White housing
no marking
White housing
with “FIRE”
Red housing
with “FIRE”
All fire alarm appliances come
with the “Running Man” Icon
GC-S2VM
GCF-S2VM
25 V Speaker-strobe (15/30/75/110 cd setting)
GC-S2VMH
GCF-S2VMH
25 V Speaker-strobe (95/115/150/177 cd setting)
GCF-S7VM
70 V Speaker-strobe (15/30/75/110 cd setting)
GC-S7VMH
GCF-S7VMH
GC-S2
GCFR-S2
Speaker-only models, 25 V
GC-S7
GCFR-S7
Speaker-only models, 70 V
Notification
Appliances
GCF-S7
70 V Speaker-strobe (95/115/150/177 cd setting)
High Fidelity Fire Alarm Speakers and Speaker-Strobes
White housing
no marking
White housing
with “FIRE”
Red housing
no marking
Red housing
with “FIRE”
All fire alarm appliances come
with the “Running Man” Icon
GCHFWN-S2VMC
GCHFWF-S2VMC
GCHFRN-S2VMC
GCHFRF-S2VMC
GCHFWN-S2VMCH
GCHFWF-S2VMCH
GCHFRN-S2VMCH
GCHFRF-S2VMCH 25 V Spkr + 95/115/150/177 cd strobe
25 V Spkr + 15/30/75/110 cd strobe
GCHFWN-S7VMC
GCHFWF-S7VMC
GCHFRN-S7VMC
GCHFRF-S7VMC
GCHFWN-S7VMCH
GCHFWF-S7VMCH
GCHFRN-S7VMCH
GCHFRF-S7VMCH 70 V Spkr + 95/115/150/177 cd strobe
GCHFWN-S2
GCHFWF-S2
GCHFRN-S2
GCHFRF-S2
Speaker-only models, 25 V
GCHFWN-S7
GCHFWF-S7
GCHFRN-S7
GCHFRF-S7
Speaker-only models, 70 V
70 V Spkr + 15/30/75/110 cd strobe
Hazardous Location
Devices
High Fidelity Mass Notification Speakers and Speaker-strobes
Clear lens
with “ALERT”
Amber lens
no marking
Amber lens
with “ALERT”
White housings
No “Running Man” Icon
GCHFWA-S2VMC
GCHFWN-S2VMA
GCHFWA-S2VMA
25 V Speaker, four standard cd settings
GCHFWA-S2VMCH
GCHFWN-S2VMAH
GCHFWA-S2VMAH
25 V Speaker, four high cd settings
GCHFWA-S7VMC
GCHFWN-S7VMA
GCHFWA-S7VMA
70 V Speaker, four standard cd settings
GCHFWA-S7VMCH
GCHFWN-S7VMAH
GCHFWA-S7VMAH
70 V Speaker, four high cd settings
GCHFWA-S2 (25 V, “ALERT” marking)
GCHFWA-S7 (70 V, “ALERT” marking)
Speaker-only models
Door Holders
& Relays
Mass Notification Speakers and Speaker Strobes
Clear lens
no marking
Clear lens
Amber lens
with “ALERT”
no marking
GCWN-S2VMA
Amber lens
with “ALERT”
GCWN-S2VMC
GCWA-S2VMC
GCWN-S2VMHC
GCWA-S2VMHC GCWN-S2VMHA GCWA-S2VMHA Speaker-strobe, 25 V, four high output cd settings
GCWN-S7VMC
GCWA-S7VMC
GCWN-S7VMHC
GCWA-S7VMHC GCWN-S7VMHA GCWA-S7VMHA Speaker-strobe, 70 V, four high output cd settings
GCWN-S2 (25 V)
GCWA-S2 (25 V, “ALERT”)
GCWN-S7VMA
GCWA-S2VMA
White housings
No “Running Man” Icon
GCWA-S7VMA
GCWN-S7 (70 V)
Speaker-strobe, 25 V, four standard cd settings
Speaker-strobe, 70 V, four standard cd settings
GCWA-S7 (70 V, “ALERT”)
Speaker-only models
37
EST3X
N o t i fi c a t i o n A p p l i a n c e s
EST3X
Head End
SUBMIT

Genesis Series Wall Models
Outdoor Speakers
and Speaker-Strobes
Genesis WG4 Series speakers and speaker-strobes are among the most
versatile emergency signals of their kind. NEMA 4X rated for indoor or
outdoor use, they are suitable for a wide range of wet and harsh environments with a listed operating temperature range of as low as -31°F to as
high as 151°F (-35°C to 66°C).
Initiating
Devices
Refer to Data Sheet E85001-0627 -- Genesis Outdoor Speakers and Strobes for details.
Field Configuration
SPKR SPKR +
STROBE STROBE +
Notification
Appliances
Genesis WG4 speakers may be set 70- or 25-Volt
operation, and for ¼, ½, 1, or 2 watt operation.
Strobe models feature four selectable light output
settings. Wattage and cd selections are changed
by removing the cover and simply sliding the
switches to the desired settings, which remain visible through a small window on the front of the device after the cover is replaced. Genesis speakerstrobes may also be configured for temporal flash.
This battery-saving feature is intended for private
mode signaling only. To set the device for temporal
flash, snip the jumper at JP1.
WG4RF-S
WG4RF-SVMC
WG4WF-S
WG4WF-SVMC
WG4RN-S
SPKR SPKR +
STROBE STROBE +
S3: Speaker
voltage
S1:
wattage
S2:
Candela
WG4RN-SVMC
JP1: Strobe temporal
mode selection
WG4WN-S
WG4WN-SVMA
WG4WA-SVMA WG4WA-SVMC
White housing
no marking
White housing
with “FIRE”
Red housing
no marking
WG4WN-S
WG4WF-S
WG4RN-S
WG4RF-S
25/70 V Speaker
WG4WN-SVMC
WG4WF-SVMC
WG4RN-SVMC
WG4RF-SVMC
25/70 V Speaker-strobe (15/29/70/87 cd)
WG4WF-SVMHC
WG4RN-SVMHC
WG4RF-SVMHC 25/70 V Speaker-strobe (102/123/147/161 cd)
Red housing
with “FIRE”
WG4WN-SVMC
Fire Alarm Speakers
Genesis mass notification speakers and speaker-strobes bring the same high-performance fire alarm features and
unobtrusive design to mass notification applications. Available with amber lenses and optional “ALERT” lettering, they are ideal
for applications that require differentiation between fire alarm and mass notification alerts.
White housing
no marking
White housing
“ALERT”
Mass Notification Speakers
— white housing, no “Running Man” icon
WG4WN-SVMA
WG4WA-SVMA
25/70 V Speaker-strobe, amber lens (13/25/5962 cd output)
WG4WN-SVMHA
WG4WA-SVMHA
25/70 V Speaker-strobe, amber lens (84/101/125/130 cd output)
WG4WA-SVMC
25/70 V Speaker-strobe, clear lens (15/29/70/87 cd output)
WG4WA-SVMHC
25/70 V Speaker-strobe, clear lens (102/123/147/161 cd output)
WG4WA-S
25/70 V Speaker
WG4WN-SVMHC
Trim skirts
38
WG4WTS (white) WG4RTS (red)
Surface Skirt for Genesis WG4 appliance family.
EST3X
N o t i fi c a t i o n A p p l i a n c e s
SUBMIT

Genesis GL Series Wall Models
LED Strobes
Genesis GL Series horns and LED strobes break the current draw barrier with
innovative technology that not only makes them inexpensive to install and operate, but also allows them to maintain the sleek low-profile design that has made
Genesis appliances a favorite among facility owners, architects, and designers.
Horn-Strobe models feature field-selectable 15, 30, 75, or 110 cd output settings. Horn-strobe and horn-only appliances feature field-configurable high/low
dB and temporal/steady audible output.
White housing
no marking
White housing
with “FIRE”
Red housing
no marking
Red housing
with “FIRE”
All fire alarm appliances come
with the “Running Man” Icon
GL1WN-HDVMC
GL1WF-HDVMC
GL1RN-HDVMC
GL1RF-HDVMCHorn-Strobe
GL1WN-HD
GL1WF-HD
GL1RN-HD
GL1RF-HDHorn-only
GL1WN-VMC
GL1WF-VMC
GL1RN-VMC
GL1RF-VMCStrobe-only
GL1WN-TP (white) GL1RN-TP (red)
GL1WN-BB1G (white)
GL1RN-BB1G (red) Trim Plate for four-inch square boxes
One-gang surface box
Mass Notification
Notification
Appliances
High Power Speaker Arrays
Hyperspike High Power Speaker Arrays (HPSA) employ exclusive technology that delivers
lightweight and acoustically sophisticated solutions for outdoor mass notification installations.
These rugged units are among the industry’s smallest in physical size, yet they reproduce
some of the clearest (up to 0.91 STI, source-dependant) and loudest (up to 126 dBA Fast @
1m) audio signals available. Loudspeaker heads are as small as 13.2” (33.5 cm) in diameter
and 24.7” (62.7 cm) in height. A single panel unit weighs as little as 16 lb (7.3 kg).
Color: Tan
Color: Gray
Hazardous Location
Devices
Hyperspike assemblies are AC powered with DC backup. They come with a lockable NEMA 4
Electronics Control Cabinet (ECC) that holds the amplifier and battery charger, and a lockable
NEMA 4 battery enclosure. Loudspeakers come pre-assembled with an eight foot (2.4 meter)
¾-inch liquid-tight flexible conduit whip and wire leads. Batteries and battery enclosures are
ordered separately.
HPSA Assemblies
1600 Watt Class
MN-HS16T5P
MN-HS16G5P 1600 Watts, 360° Dispersion, 5 Active Panels
MN-HS16T3P
MN-HS16G3P 960 Watts, 230° Dispersion, 3 Active Panels
Data Sheet E85001-0637
MN-HS16T2P
MN-HS16G2P 640 Watts, 185° Dispersion, 2 Active Panels
Data Sheet E85001-0637
MN-HS16T1P
Data Sheet E85001-0637
Data Sheet E85001-0637
MN-HS32G5P 3200 Watts, 360° Dispersion, 5 Active Panels
Data Sheet E85001-0637
MN-HS32T3P
MN-HS32G3P 1920 Watts, 230° Dispersion, 3 Active Panels
Data Sheet E85001-0637
MN-HS32T2P
MN-HS32G2P 1280 Watts, 185° Dispersion, 2 Active Panels
Data Sheet E85001-0637
MN-HS32T1P
MN-HS32G1P 640 Watts, 120° Dispersion, 1 Active Panel
Data Sheet E85001-0637
6400 Watt Class
MN-HS64T5P
MN-HS64G5P 6400 Watts, 360° Dispersion, 5 Active Panels
Data Sheet E85001-0637
MN-HS64T3P
MN-HS64G3P 3840 Watts, 230° Dispersion, 3 Active Panels
Data Sheet E85001-0637
MN-HS64T2P
MN-HS64G2P 1280 Watts, 185° Dispersion, 2 Active Panels
Data Sheet E85001-0637
MN-HS64T1P
MN-HS64G1P 640 Watts, 120° Dispersion, 1 Active Panel
Data Sheet E85001-0637
Door Holders
& Relays
MN-HS16G1P 320 Watts, 120° Dispersion, 1 Active Panel
3200 Watt Class
MN-HS32T5P
39
EST3X
N o t i fi c a t i o n A p p l i a n c e s
EST3X
Head End
SUBMIT

Mass Notification
Medium Power Speaker Arrays
EST brand Hyperspike Series Medium Power loudspeakers employ exclusive HyperSpike technology to deliver lightweight and acoustically sophisticated solutions for large indoor and smaller outdoor mass notification installations.
Please refer to Data Sheet E85001-0638 for product details and complete ordering information.
Notification
Appliances
Initiating
Devices
Omnidirectional 650-Watt Loudspeakers
The MN-HSMP650 Series has a 360° omnidirectional sound dispersion pattern and can
handle 650 Watts of crystal-clear audio power. It is rated for indoor and outdoor use and
hangs from eyebolts or is mounted to a two-inch OD mast.
MN-HSMP650G
Loudspeaker assembly, 650 Watt, Gray Housing.
MN-HSMP650P5T
Loudspeaker assembly, 650 Watt, Tan Housing.
MN-HSMP650G70
Loudspeaker assembly, 650 Watt, Gray with internal 70.7 VRMS transformer, blocking capacitor.
MN-HSMP650T70
Loudspeaker assembly, 650 Watt, Tan with internal 70.7 VRMS transformer, blocking capacitor.
MN-HSMP650P5GAC
MN-HSMP650E5G
Loudspeaker assembly, 650 Watt. AC operation with DC backup, Gray.
MN-HSMP650E5T
Loudspeaker assembly, 650 Watt, Gray. AC operation with DC backup, Tan.
Loudspeaker assembly, 650 Watt, Gray with amplifier and electronics. 110V/60Hz operation only. Omnidirectional Indoor-rated 300-Watt Loudspeakers
The MN-HSMP300DF is a grey indoor-rated omnidirectional unit rated for 300 Watts of continuous audio power. These units are eyebolt-mounted.
MN-HSMP300DF1
MN-HSMP300DF170
Omnidirectional Loudspeaker, 300 Watt.
Omnidirectional Loudspeaker, 300 Watt with internal 70.7 VRMS transformer, blocking capacitor.
Directional 200-Watt Loudspeakers
The MN-HSMP200D is a directional loudspeaker that handles 200 Watts of continuous audio.
Units feature 60° x 30° sound dispersion and are suitable for indoor or outdoor applications.
They come complete with mounting bracket.
MN-HSMP200D1
MN-HSMP200D170
40
Directional Loudspeaker, 200 Watt.
Directional Loudspeaker, 200 Watt with internal 70.7 VRMS transformer and blocking capacitor.
EST3X
N o t i fi c a t i o n A p p l i a n c e s
SUBMIT

Audible Signals
Fire Alarm Bells
EDWARDS fire alarm bells are of the underdome type with heavy-duty mechanisms. Gongs
are made of selected alloy steel to generate the loud, resonant tones. For weatherproof application, optional surface weatherproof backboxes are available.
323D-10AW (Grey)
323D-10AR (Red)
10-inch Single Stroke, Diode — 20-24Vdc
Data Sheet E85001-0333
439D-6AW (Grey)
439D-6AR (Red)
6-inch Vibrating, Diode — 20-24Vdc
Data Sheet E85001-0333
439D-10AW (Grey)
439D-10AR (Red)
10-inch Vibrating, Diode — 20-24Vdc
Data Sheet E85001-0333
Multiple Tone Signal The 5530MD-24AW is a weatherproof heavy-duty industrial, tone-selectable, signaling device capable of producing volume-controlled, high-decibel tones. It uses a microprocessor
circuit to create 27 distinctive tones. A single tone may be selected by setting a miniature
dip switch within the unit.
5530MD-24AW
27-Tone Selectable Signal — 24Vdc
Data Sheet E85001-0415
Notification
Appliances
Multi-purpose Loudspeaker
The HPSA15 loudspeaker is a high-efficiency double re-entrant loudspeaker that operates within a
nominal frequency response range of 400-14,000 Hz, and provides audible output of 120 dB (peak
at one meter) at the rated power level. It includes a versatile, three-way, 25/70.7 V line transformer
that meets a variety of distributed system needs. The transformer is adjustable by means of a
convenient seven-position, watts/impedance selection switch.
15-watt loudspeaker, red
Data Sheet E85001-0591
HPSA15G2570
15-watt loudspeaker, gray
Data Sheet E85001-0591
Hazardous Location
Devices
HPSA15R2570
Door Holders
& Relays
41
EST3X
N o t i fi c a t i o n A p p l i a n c e s
EST3X
Head End
SUBMIT
 Enhanced Integrity Series
Harsh Environment
North American
2-gang electrical box
Mounting Plate
Signals
Surface Box (optional)
Housing
Single Captive Mounting Screw
All Enhanced Integrity devices are UL 1971 listed for both wall and ceiling orientation. Enhanced Integrity strobes meet the latest UL1971 synchronization requirements when used with the G1M Signal Master. Integrity devices are shipped
with wall mount style “FIRE” lens markings. Other lens markings are available.
First Device
To Fire Alarm
Control Panel
Signal Circuit
+
Horn/Strobe
H+
HS+
S-
Horn/Strobe
H+
HS+
S-
To Next Device
or EOL Resistor
-
+
Initiating
Devices
Re-Entrant Speakers and Speaker-Strobes
Re-entrant speakers feature a sealed, high efficiency compression driver that’s both weatherproof and
vermin proof. This makes them ideal for public places and outdoor areas such as parking garages
and transport terminals. All Integrity speakers include a DC Blocking Capacitor that permits electrical
supervision of the audio distribution circuit. Models for 25Vrms and 70Vrms circuits are available.
Fire Alarm Appliances, clear lenses, Data Sheet E85001-0317
Notification
Appliances
15/75 cd
30 cd
110 cd
757-7A-RS25
757-7A-RS25W 757-3A-RS25W 757-8A-RS25W 757-1A-R25W Speaker-strobe, 25 V, white housing
757-7A-RS70
757-7A-RS70W 757-3A-RS70W 757-8A-RS70W 757-1A-R70W Speaker-strobe, 70 V, white housing
Mass Notification Appliances, amber lenses, Data Sheet E85001-0317
757-7A-RS25WA (12/75 cd) 757-8A-RS25WA (88 cd) Speaker-strobe, 25 V, white housing
757-3A-RS25
757-3A-RS70
757-7A-RS70WA (12/75 cd) 757-8A-RS25
Speaker only
757-8A-RS70
757-1A-R25
757-1A-R70
757-8A-RS70WA (88 cd) Speaker-strobe, 25 V, red housing
Speaker-strobe, 70 V, red housing
Speaker-strobe, 70 V, white housing
Temporal Horns and Horn-Strobes
During installation, the Horn is configured for steady or temporal tone signal. When temporal output
is selected, all Horns on a common two-wire circuit are self-synchronized. Integrity Series Horns
emit a low frequency “growling” tone that demands attention. Horns can be configured for either
high output (98 dBA) or low output (94 dBA); and are listed for outdoor use.
757-1A-T (Red)
757-1A-TW (White) Temporal Horn
Data Sheet E85001-0341
757-7A-T (Red)
757-7A-TW (White) Temporal Horn-Strobe, 15/75cd
Data Sheet E85001-0341
757-4A-T (Red)
757-4A-TW (White) Temporal Horn-Strobe, 75cd
Data Sheet E85001-0341
757-8A-T (Red)
757-8A-TW (White) Temporal Horn-Strobe, 110cd
Data Sheet E85001-0341
4” Square Box Mount Strobes
405 Series strobes are self-synchronized to flash at one fps across their full operating voltage range.
UL 1971 synchronization requirements are achieved when used with the G1M Signal Master. Strobes
must be connected to signal circuits that output a constant (not pulsed) voltage. A diode is used to
allow full signal circuit supervision. 405 Series strobes are suitable for outdoor use and installed to
a standard four-inch square electrical box.
405-5A-T (Red)
405-5A-TW (White)
Strobe - 15 cd
Data Sheet E85001-0305
405-7A-T (Red)
405-7A-TW (White)
Strobe - 15/75
Data Sheet E85001-0305
405-3A-T (Red)
405-3A-TW (White)
Strobe - 30 cd
Data Sheet E85001-0305
405-6A-T (Red)
405-6A-TW (White)
Strobe - 60 cd
Data Sheet E85001-0305
405-8A-T (Red)
405-8A-TW (White)
Strobe - 110 cd
Data Sheet E85001-0305
CS-405-7A-T (15/75 cd)
CS-405-8A-T (110 cd)
Strobe - Weatherproof (red)
Data Sheet E85001-0305
42
EST3X
N o t i fi c a t i o n A p p l i a n c e s
SUBMIT

Accessories
Bell/Strobe Plate
The bell/strobe plate is ideal for renovation and retrofit projects, and new construction.
It is equipped with an EDWARDS self-synchronizing strobe and is designed to allow onsite mounting of the 439 series Vibrating Bell, providing instant conversion to Bell/Strobe
audible/visual signal appliances. The strobe is designed for 20 to 24Vdc operation and
must be connected to signal circuits which output a constant (not pulsed) voltage. A
diode is used to allow full signal circuit supervision.
403-5A-R (15 cd) 403-7A-R (15/75 cd) 403-3A-R (30 cd) 403-8A-R (110 cd) Data Sheet E85001-0441
Genesis Signal Master
The Signal Master adds enhanced features to Genesis and Integrity strobes
and Horn-Strobes. It is a dual-purpose module that provides UL 1971 required
precision synchronization for connected Integrity and Genesis strobes, and
independent control for connected Genesis Horns over a single pair of wires.
G1M
G1M-RM
Snap-on
(piggyback) model
Remote 1-gang
mount model
Genesis Signal Master – Snap-on (piggyback)
Data Sheet E85001-0545
Genesis Signal Master – Remote 1-Gang Mount
Data Sheet E85001-0545
Notification
Appliances
Integrity Lens Marking Kits
Integrity strobes are shipped with wall mount style “FIRE” lens markings. Where ceiling mount, other languages or different lens markings are required, optional LKW and LKC series Lens Marking Kits are available. Lens marking sleeves
snap right over the strobe lens providing a quick, easy, change.
LKW-1R (Wall orientation)
LKW-1 (Wall orientation)
“FIRE” (Red)
LKC-1 (Ceiling orientation)
“FIRE”
LKW-2 (Wall orientation)
LKC-2 (Ceiling orientation)
“FEU”
LKW-3 (Wall orientation)
LKC-3 (Ceiling orientation)
“FIRE/FEU”
LKW-4 (Wall orientation)
LKC-4 (Ceiling orientation)
“SMOKE”
LKW-5 (Wall orientation)
LKC-5 (Ceiling orientation)
“HALON”
LKW-6 (Wall orientation)
LKC-6 (Ceiling orientation)
“CO2”
LKW-7 (Wall orientation)
LKC-7 (Ceiling orientation)
“EMERGENCY”
LKW-8 (Wall orientation)
LKC-8 (Ceiling orientation)
“ALARM”
LKW-9 (Wall orientation)
LKC-9 (Ceiling orientation)
“FUEGO”
LKW-10 (Wall orientation)
LKC-10 (Ceiling orientation) “ALERT”
Hazardous Location
Devices
Mounting Accessories
Integrity Speakers, Speaker/strobes
 960A-4SF Flush Box, Indoor
 757A-SB
Surface Box, Red, Indoor
 757A-SBW Surface Box, White, Indoor
Integrity Re-entrant speakers, Speaker/strobes
 960A-4SF Flush Box, Indoor
 757A-SB
Surface Box, Red, Indoor
 757A-SBW Surface Box, White, Indoor
 757A-WB Weatherproof Box, Red, Surface
 757A-WBW Weatherproof Box, White, Surface
Integrity Chimes, Chime/strobes
 757A-SB
Surface Box, Red, Indoor
 757A-SBW Surface Box, White, Indoor
Genesis Signals
 27193-11 Horn-strobe Surface Box, Red, Indoor
 27193-16 Horn-strobe Surface Box, White, Indoor
 G4RB
Speaker Surface Box, Red, Indoor
 G4B
Speaker Surface Box, White, Indoor
 G4ERB
G4 Dual-strobe Format Surface box, Red
 G4EWB
G4 Dual-strobe Format Surface box, White
Horn/siren Combination
 349
Weatherproof Backbox
Fire Alarm Bells and CS-405 Series
 449
Weatherproof Backbox
Door Holders
& Relays
Integrity Temporal Horn, Horn/strobe
 757A-SB
Surface Box, Red, Indoor
 757A-SBW Surface Box, White, Indoor
 757A-WB Weatherproof Box, Red, Surface
 757A-WBW Weatherproof Box, White, Surface
Genesis G4B Speaker
Surface Box
43
EST3X

Notification
Appliances
Initiating
Devices
EST3X
Head End
SUBMIT
44
N o t i fi c a t i o n A p p l i a n c e s
EST3X
Hazardous Location
Devices
Hazardous Location Devices
Initiating Devices p. 44
Notification Appliances p. 45
EDWARDS hazardous location devices provide reliable life safety protection and emergency signaling in areas where
atmospheres could become harsh or explosive. All hazardous location devices are UL rated under the full range of
classifications set out in the National Electrical Code.
The following classification definitions are an interpretive summary based on the latest edition of the National Electrical Code (NEC, NFPA 70). Refer to the latest editions of NFPA 497M, NFPA 70 and the UL Hazardous Location
Equipment Directory for current and more detailed information. For more information on NEMA classifications, refer
to NEMA Standards Publication No. 250.
Hazardous Location Classifications
Classes
Class I - Hazardous Gases. Class I locations are areas in which flammable gases or vapors are or may be present in the air in quantities
sufficient to produce explosive or ignitable mixtures.
Typical Class I Hazardous Areas
• Spray painting and finishing areas
• Utility gas plants
• Petroleum refining production plants
• Petroleum dispensing locations
• Dry cleaning facilities
• Dip tanks containing combustibles or flammable liquids
• Plant facilities extracting solvents
• Inhalation anesthetics areas
• Process facilities manufacturing pyroxylin type plastics
Class II - Hazardous Dusts. Class II locations represent areas that are
hazardous due to the presence of combustible dust.
Class III - Hazardous Fibers. Class III locations have easily ignitable
fibers or flyings present, but not likely to be suspended in air in quantities
sufficient to produce ignitable mixtures in the atmosphere.
* Except if wood flour (dust), which is Class II Group G, is present
Groups
Class I and II locations are divided by the NFPA into Group
designations identifying specific gases, vapors and dusts by
characteristic similarities that relate to specific equipment
construction requirements. Class III locations are not divided
into separate group designations.
Class I Groups
Group A. Atmospheres containing acetylene.
Group B. Atmospheres containing hydrogen, fuel and
combustible process gases containing more than 30 percent
hydrogen by volume, or gases or vapors of equivalent hazard
such as butadiene, ethylene oxide, propylene oxide, and
acrolein.
Group C. Atmospheres such as ethyl ether, ethylene, or
other gases or vapors of equivalent hazard.
Group D. Atmospheres containing acetone, ammonia,
benzene, butane, cyclopropane, ethanol, gasoline, hexane,
methanol, methane, natural gas, naphtha (petroleum), propane, or gases or vapors of equivalent hazard.
Class II Groups
Group E. Atmospheres containing combustible metal dusts,
including aluminum, magnesium, and their commercial
alloys, or other combustible dusts whose particle size, abrasiveness and conductivity present similar hazards in the use
of electrical equipment.
Door Holders
& Relays
Typical Class III Hazardous Areas
• Textile mills
• Woodworking plants*
• Furniture manufacturers*
• Cotton gins
• Cotton seed milling plants
• Flax plants
• Carpet manufacturers
The Location Classes are broken down by the NFPA into
Divisions 1 and 2, defining different levels of risk. In general,
the risk of there being a hazardous presence of flammable/
combustible/ignitable materials is higher for Division 1 than
for Division 2. The specifics differ between the three classes
(I, II and III). Equipment suitable for Division 1 is also suitable
for Division 2 locations.
Hazardous Location
Devices
Typical Class II Hazardous Areas
• Flour mills
• Feed mills
• Grain elevators and grain handling facilities
• Aluminum manufacturing and storage areas
• Magnesium manufacturing and storage areas
• Coal preparation and handling facilities
• Starch manufacturing and storage areas
• Confectionery plants
• Pulverizer sugar and cocoa manufacturing, and storage plants
• Spice grinding and storage plants
Divisions
Group F. Atmospheres containing combustible carbonaceous dusts, including carbon black, charcoal, coal, or dusts
that have been sensitized by other materials so that they
present an explosion hazard.
Group G. Atmospheres containing combustible dusts not
included in Group E or F, including flour, grain, wood, plastic,
and chemicals.
45
EST3X
Hazardous Location Devices
EST3XX
Head End
SUBMIT

Initiating Devices
Rate Compensation Heat Detectors
Series 302 heat detectors are designed for use in normal environments as well as environments
where the detectors are subject to weather, moisture (internal condensation), and explosive
atmospheres. They are normally-open devices designed to close an electrical circuit upon
activation. All models feature rate compensation and are available with either 135 °F (57.2 °C)
or 194 °F (90 °C) ratings. They are self restoring, hermetically sealed, shock and corrosion
resistant, and are tamperproof.
Initiating
Devices
Surface
Mount
Notification
Appliances
Box
mount
Sensor’s Rated
Temperature
Minimum Ambient
Air Temperature
Maximum Ceiling
Temperature
135 °F (57.2 °C)
194 °F (90 °C)
-40 °F (-40 °C)
-40 °F (-40 °C)
100 °F (38 °C)
150 °F (66 °C)
The sensor's aluminum tube acts as a heat collector when sources of heat radiate directly
on the tube. Install these sensors out of direct sunlight and away from radiating heat sources
including the direct flow from heaters and heat ducts.
302-AW-135 All-weather Heat Detector - Vertical Mounting FM & UL, 135 °F (57.2 °C)
Data Sheet E85001-0589
Data Sheet E85001-0589
302-AW-194 All-weather Heat Detector - Vertical Mounting FM & UL, 194°F (90 °C)
302-ET-135 All-weather Heat Detector - Vertical, Box Mount (½" NPT), FM & UL, 135 °F (57.2 °C)
Data Sheet E85001-0589
302-ET-194
All-weather Heat Detector - Vertical, Box Mount (½" NPT), FM & UL, 194°F (90 °C)
Data Sheet E85001-0589
302-EPM-135 Heat Detector - Explosionproof Mounting UL (Not FM approved), 135 °F (57.2 °C)
Data Sheet E85001-0589
302-EPM-194 Heat Detector - Explosionproof Mounting UL (not FM approved), 194°F (90 °C)
Data Sheet E85001-0589
AP-P
Adaptor plate for mounting 302 and 302-AW to any 3" box or 4" octagon outlet box Data Sheet E85001-0589
JALX11
Explosion proof outlet body with cover - Killark Data Sheet E85001-0589
Hazardous Location
Devices
.
Explosionproof/weatherproof Manual Stations
MPSR Series explosionproof/weatherproof manual pull stations are noncoded fire alarm
stations solidly constructed of die-cast material. They are rated for Class I Group B (hydrogen) C & D, Class II Groups E. F, G, Class III environments, and are rated NEMA 4X for
outdoor use. Key and screw reset models feature terminal connections and come complete
with backbox.
Hex Screw Reset
Cat 45 Key Reset
MPSR1-DHTWX-GE
MPSR1-D45WX-GE
Explosionproof Single-action, SPST with backbox.
MPSR1-SHTW-GE
MPSR1-S45W-GE
Weatherproof Single-action, SPST with backbox.
MPSR1-DHTW-GE
MPSR1-D45W-GE
Weatherproof Single-action, DPDT with backbox.
MPSR2-SHTW-GE
MPSR2-S45W-GE
Weatherproof Double-action, SPST with backbox.
MPSR2-DHTW-GE
MPSR2-D45W-GE
Weatherproof Double-action, DPDT with backbox.
MPSR2-SHTW-GE-NYW
MPSR2-S45W-GE-NYW Weatherproof Double-action, SPST with backbox, NYC white stripe.
Manual Stations
Data Sheet E85001-0588
For French markings add -F to the suffix of the model number. For bilinguial French/English markings add -B to the suffix of the model number.
MPSR-LP
Double action cover for explosionproof manual stations
MPSRGR10
Replacement glass rods for MPSR stations (10 pack).
276-K1
Cat 45 Key (each)
46
EST3X
Hazardous Location Devices
SUBMIT

Explosionproof Smoke Detector
Model 30-3013 detectors are high performance smoke detectors built for use in hazardous
locations. They are corrosion-resistant and feature a non-conducting aluminum alloy retaining
ring that protects the detector sensor against the effects of explosions and other catastrophic
events. The retaining ring mounts securely to a companion junction box, which offers several
common port configurations for conduit connection. Together, the ring and box provide a
sturdy protective shell for the detector head.
30-3013A1N12F
Data Sheet E85001-0645
Explosionproof Smoke Detector
Notification Appliances
Hazardous Location Strobes
• Class I, II, or III locations
116DEGEX-FJ hazardous location strobes are life safety signaling appliances designed for installation in
hazardous environments. State-of-the-art technology provide for high visual output and low maintenance.
The 116DEGEX-FJ has negligible in-rush current. When pendant, wall or ceiling mounted, the 116DEGEXFJ meets or exceeds the requirements of UL 1971 Signaling Appliance for the Hearing Impaired.
116DEGEX-FJ
Explosionproof Strobe, Diode Polarized
Data Sheet E85001-0624
116EX-B
Wall bracket mounting elbow
Data Sheet E85001-0624
116EX-C
Ceiling/wall mounting module
Data Sheet E85001-0624
116EX-P
Pendant mounting module - 3/4” (19 mm) NPT
Data Sheet E85001-0624
116-GRD
Lens Guard
Data Sheet E85001-0624
Hazardous Location
Devices
Hazardous Location Bells
• Class I groups B, C and D locations
• Class II groups E, F and G locations
• Class III hazardous locations, for Divisions 1 and 2
430D series of hazardous location bells are diode-polarized, heavy duty fire bells for use in life safety applications
where a diode supervised signal is required. They can be mounted to any solid surface using two 3/8 inch (10 mm)
bolts and the supplied mounting brackets or to a rigid conduit. The integral explosion-proof housing is mechanically
terminated to accept a standard 3/4 inch -14 National Pipe Taper (NPT) nipple.
439DEX-6AW (6”)
439DEX-8AW (8”)
439DEX-10AW (10”)
Bell – 24 Vdc
Catalog Sheet: 85001-0399
438DEX-6N5 (6")
438DEX-8N5 (8")
438DEX-10N5 (10")
Bell – 120 Vac
Catalog Sheet: 85001-0399
• Class I groups B, C and D locations
• Class II groups E, F and G locations
Door Holders
& Relays
Hazardous Location Horns
• Class III hazardous locations, for Divisions 1 and 2
888D and 889D hazardous location horns are diode-polarized, heavy duty, high decibel vibrating horns intended for
use in life safety systems in hazardous (classified) locations. These horns may be mounted to any solid surface using
two bolts. Each unit is supplied with a sealing fitting for a 3/4 inch -14 National Pipe Taper (NPT) nipple, and wire leads
for the electrical connection to the life safety system notification appliance circuit.
888D-N5 (120 Vac)
889D-AW (24 Vdc)
Horn – 120 Vac
Catalog Sheet: 85001-0397
47
EST3X
Door Holders & Relays

Hazardous Location
Devices
Door Holders
Electromagnetic Door Holders
24 Vdc
120 Vac 60 Hz
1501-AQN5 (Single Door)
1502-AQN5 (Double Door)
Floor Mounted
Data Sheet E85001-0421
1504-AQN5 (Long Catch Plate)
1505-AQN5 (Short Catch Plate)
Flush Wall Mounted
Data Sheet E85001-0421
1508-AQN5 (Surface)
1505-AQN9 (Completely flush)
Wall Mounted
Data Sheet E85001-0421
1500-1 (1.5” Extension)
1500-2 (2.5” Extension)
Catch Plate
Data Sheet E85001-0421
1500-7 (5.25 to 7.5” Extension)
1500-12 (7.5 to 12” Extension)
Catch Plate
Data Sheet E85001-0421
CS2595-5 (short)
CS2598-5 (long)
Replacement Armature
Data Sheet E85001-0421
Relays
Four-Voltage SPDT/DPDT Control Relays
MR Series multi-voltage control relays are ideal for applications where local contacts are
required for system status, remote contacts, or for control of electrical loads and general purpose switching. They are suitable for use with HVAC temperature control, fire alarm, security,
energy management, and lighting control systems. Relays provide 10-Amp contacts, which
may be operated by one of four input control voltages. Each relay position contains a red
LED that indicates the relay coil is energized. Relays may be snapped apart from a standard
four-module assembly and used independently.
MR-101/T (with mounting hardware)
MR-101/C (in metal enclosure)
Single SPDT relay
MR-104/T (with mounting hardware)
MR-104/C (in metal enclosure)
4-position SPDT relay Data Sheet E85300-02762
MR-201/T (with mounting hardware)
MR-201/C (in metal enclosure)
Single DPDT relay
MR-204/T (with mounting hardware)
MR-204/C (in metal enclosure)
4-position DPDT relay Data Sheet E85300-02762
Door Holders
& Relays
Electromagnetic door holders keep doors open until signaled by the fire alarm
system, a heat detector, a smoke detector, or an electrical switch. Door holders
should be installed wherever doors may be effectively used to confine smoke
and fire, or where the release of a self-closing door from a remote location
is required. Fail-safe operation is an inherent feature of these door holders. If
power fails, doors are released automatically, but may be opened or closed
manually at any time. All units are free of moving parts, are self-contained, and
require no maintenance. Door holders have a holding force of approximately
15-25 Lbf (66-111N).
24 Vac 60 Hz
Notification
Appliances
Initiating
Devices
EST3XX
Head End
SUBMIT
Data Sheet E85300-02762
Data Sheet E85300-02762
Heavy Duty DPDT Power Relays
MR-199 heavy duty power relays are designed for control applications where 30-Amp DPDT
contacts are required. Two models are available: a 115Vac coil and a 24Vdc coil, each of
which may be mounted in a rugged steel enclosure.
MR-199X-13 (relay only)
MR-199X-13/C (in metal enclosure)
Power Relay — 24 VDC Data Sheet E85300-02765
MR-199AX-14 (relay only)
MR-199AX-14/C (in metal enclosure)
Power Relay — 120 VDC Data Sheet E85300-02765
48
EST3X
Door Holders & Relays
SUBMIT

SPDT Relays
Single-pull/double-throw relays are ideal for applications where local or remote contacts are required for control of electrical loads. They are suitable for use with HVAC,
temperature control, fire alarm, security, energy management, and lighting control
systems. Each relay position contains a high-intensity LED which, when illuminated,
indicates the relay coil is energized. Individual relay circuits may be snapped apart
from standard four- or eight-position modules, and are also available in a single-circuit
configuration. The common power to each relay position is bussed on the printed
wiring board, which permits power to be connected only once per multi-position
module.
Single-Voltage Manual Override Relays
MR-600 series relays provide SPDT, 10-Amp contacts with manual override capability by means of an ON-AUTO-OFF
switch. The relay requires a 24Vac or 24Vdc power source supplied by the controlling system. With the switch in the ON
position the power relay is energized. With the switch in the AUTO position the relay is allowed to operate as signaled
by the controlling system. With the switch in the OFF position the relay cannot be energized.
MR-601/T (with mounting track)
MR-601/S (with mounting spacers) Single SPDT relay
Data Sheet E85300-02761
MR-604/T (with mounting track)
MR-604/S (with mounting spacers) 4-position SPDT relay Data Sheet E85300-02761
MR-608/T (with mounting track)
MR-608/S (with mounting spacers) 8-position SPDT relay Data Sheet E85300-02761
Three-Voltage Control Relays
MR-800 Series relays provide SPDT 10-Amp contacts that may be operated by one of three input control voltages:
24Vdc, 24Vac or 115Vac.
MR-801/T (with mounting track)
MR-801/S (with mounting spacers) Single SPDT relay
MR-804/T (with mounting track)
MR-804/S (with mounting spacers) 4-position SPDT relay Data Sheet E85300-02763
Data Sheet E85300-02763
MR-808/T (with mounting track)
MR-808/S (with mounting spacers) 8-position SPDT relay Data Sheet E85300-02763
Four-Voltage Control Relays
MR-700 Series relays provide SPDT 10-Amp contacts that may be operated by one of four input control voltages:
12Vdc, 12Vac, 24Vdc, or 24Vac.
MR-701/T (with mounting track)
MR-701/S (with mounting spacers) Single SPDT relay
MR-704/T (with mounting track)
MR-704/S (with mounting spacers) 4-position SPDT relay Data Sheet E85300-02764
MR-708/T (with mounting track)
MR-708/S (with mounting spacers) 8-position SPDT relay
Data Sheet E85300-02764
Door Holders
& Relays
Data Sheet E85300-02764
Three-Voltage Encapsulated Control Relays
PAM-1 relays provide 10-Amp Form C contacts. The relay may be energized by one of three
input voltages: 24Vac, 24Vdc, or 115Vac. The PAM-1 may be mounted with double-sided
adhesive tape, a self-tapping screw, or loosely placed in a backbox.
PAM-1
Encapsulated SPDT relay Data Sheet E85300-02766
49
Proven leadership.
Proud heritage.
Shared vision.
In 1872 when Robert Edwards
exceptional sensitivity to the needs
installed an electrically-operated
of our customers. Now we have
gas lamp igniter in a New York
access to the resources, talent, and
City church, he began a tradition
experience that is already setting
of innovation that would chart
a coordinated plan for excellence
the course of building safety and
into action. The result is a unique
security for the next 140 years.
synergy sustained by a strong
Today the company that bears his
organization with a well-defined
name draws on this rich legacy of
vision of the future.
inventiveness, and benefits from
fresh new alliances established
is why EDWARDS is among the
with one underlying goal:
fastest growing building systems
uncompromised excellence.
providers today. It’s also why, with
more than a century of solid growth
Today EDWARDS meets this
goal with quality products and an
That vision of excellence
behind us, you can put your trust in
EDWARDS.
See what’s possible now.
EDWARDS Strategic Partners:
Innovation, leadership,
and a rich tradition of excellence...
Whether EDWARDS life safety systems are protecting the lives and livelihoods
of the people who make businesses run, or the lives entrusted to the care of
public institutions; whether they’re charged with protecting the guests of the
world’s finest hotels, or preserving irreplaceable artifacts that bring history to life;
EDWARDS stands alone as the brand closely associated with some of the most
important and far-reaching developments in the life safety industry today.
Our strength is in our Strategic Partners — the people and organizations
we entrust with the technology that has charted the course of life safety protection for decades. Strategic Partners are not middlemen or go-betweens. They
are independent contractors who add value to the EDWARDS life safety solution.
As insiders, they enjoy exclusive access to products, custom design innovations,
and factory training. Yet as successful independent contractors, they are adept
at ensuring that each submittal is strong and competitive, and that each bid is
locally relevant to your installation. As local businesses they not only have to earn
your trust — they have to keep it.
Together these strengths set EDWARDS installations apart, and have
earned this brand a special place among life safety and security solutions available today. Perhaps that’s why many of the world’s most cherished landmarks
are protected by EDWARDS products. From the Bibliotheca Alexandrina Museum in Egypt, to the modern-day sphinx at the Luxor Hotel in Las Vegas, professionals who design, own and occupy the world’s most impressive structures
have chosen the EDWARDS solution.
See what’s possible now...
Contact your EDWARDS Strategic Partner today!
L I F E S A F E TY & I NCI DE NT M AN AGEM EN T
Contact us...
Email:edwards.fire@fs.utc.com
Web:
EDWARDS-fire.com
EDWARDS is a UTC brand.
1016 Corporate Park Drive
Mebane, NC 27302
E85005-0134
10-15-16
© 2016 United Technologies Corporation.
All rights reserved.
Was this manual useful for you? yes no
Thank you for your participation!

* Your assessment is very important for improving the work of artificial intelligence, which forms the content of this project