1. Application:
Panel of four fans with integrated digital thermostat in a RACK 19" enclosure with a 1U height. Forces air
circulation between active devices generating heat inside RACK cabinets. It is fitted with a detachable temperature
sensor with a 2m length and with a 230VAC detachable power cord with a 2m length.
2. Technical parameters
Power supply
Current consumption
Power consumption
Mounting dimensions:
External dimensions :
Net/gross weight:
Finish:
Application:
Notes:
Declarations, warranty
230 VAC / 50Hz
0,32A
76W
W=19", H=1U
W=482, H=44, D=314 [mm, +/-2]
4,90 / 5,09 [kg]
- steel plate 1.2 mm, color black (RAL 9004)
- Four 230VAC fans, air flow: 4 x 50÷110CBM/H
- temperature sensor
Indoor
- Four-point butt mounting to RACK profiles
- the set includes 4 M6 screws + cage nuts + plastic washer
- the panel is fitted with a 230VAC LZ=2m detachable cord
- the panel is fitted with a detachable temperature sensor with a
LT=2m power cord
O
O
- setting switch ON and OFF temperatures 0 C ÷ +50 C
- Digital display of the current temperature
- power switch on the front panel
CE, RoHS, 2 years from the production date
19"
1U
44mm
482mm
314mm
3. RAWP-1R mounting:
4. Connection
Connect the temperature sensor to the "Sensor" socket located at rear of the unit and plug 230VAC power cord
into the "Power" socket. Turn the device using the power switch located on the front panel. After switching on
the device, the current temperature measured by the sensor will be displayed.
5. Checking the preset operating parameters:
After pressing the [˄] fan activation temperature will be displayed.
After pressing the [˄] button fan shutdown temperature will be displayed.
After pressing the [Set] button, F4=0 will be displayed
After pressing the [Set] button, the alarm temperature will be displayed
During fan operation, the Cool LED is on.
6. Setting the operation parameters:
Press and hold the [Set] button for 3 seconds, the unit will enter the programming mode. The Set LED will light
up and one of the F1 ÷ F6 programs will be displayed; use [˄] or [˅] buttons to select the desired program
number.
After pressing the [Set] button, the set value will be displayed.
To change the program values, press and hold the [Set] button and use [˄] and [˅] buttons to set the desired
value. Press [Rst] to save and exit.
Caution - disconnect the 230V power supply using the power switch each time after exiting the
programming mode
Available programs:
F1 – program to set the fan activation temperature
F2 – program to set the fan shutdown temperature
F3 – program for adjusting the temperature sensor
F4 – turn off - set to „0”
F5 – program for setting an acoustic indication – exceeding the preset F1 and F2 temperatures by a predefined
F5 value (F5=0 – no alarm)
F6 – program to set the fan activation temperature
2
Program
F1
F2
F3
F4
F5
F6
Function
Fan activation temperature
Fan shutdown temperature
Calibration of the temperature sensor
Turn off - - set to "0"
Alarm - exceeding the preset F1 and F2
temperatures
Delay of alarm activation after exceeding the preset
temperature
Range
F2 ÷ +50
-40 ÷ F1
-5 ÷ +5
-
Units
O
C
O
C
O
C
-
0 ÷ 50 („0” alarm off)
0 ÷ 99
7. Errors:
When the display shows:
E1 – accompanied by acoustic indication – memory error
E2 – accompanied by acoustic indication – temperature sensor error
HH – exceeding the operating temperature of the controller
WARRANTY
Pulsar (manufacturer) grants a two-year quality warranty for the equipment, starting from the production date.
PRODUCENT
Pulsar
Siedlec 150,
32-744 Łapczyca
Tel. (+48) 14-610-19-40, Fax. ( +48) 14-610-19-50
e-mail: biuro@pulsar.pl, sales@pulsar.pl
http:// www.pulsar.pl, www.zasilacze.pl
3
O
C
min
Was this manual useful for you? yes no
Thank you for your participation!

* Your assessment is very important for improving the work of artificial intelligence, which forms the content of this project

Download PDF

advertising