Elite XT - VES Fire Detection Systems
Elite XT
Releasing
Fire Control Panels
Standard Features
Product Overview
UL 864 and FM approved
Designed and manufactured to the highest
standards in a quality controlled environment
and with UL and FM approvals, the Elite XT
releasing panel offers outstanding value and
performance for all small to medium fixed
firefighting installations.
Three detection zones as standard
Any single zone or any combinations
of zones can be configured to release
Configurable first stage NAC delays
Configurable detection delays
Zero time delay upon manual release
option
Non-latching zone input option to
receive signals from other systems
such as aspirating equipment
Configurable releasing delays up to
60 seconds in 5 second steps
Configurable releasing duration up to
5 minutes in 5 second steps
APPROVED
Manufactured by Kentec Electronics Ltd.
Dartford, DA11JQ, United Kingdom
Programable
Functions
Access Level 2
Test Zones 1 to 3
Disable Zones 1 to 3
Disable 1st Stage Alarms
Disable Pre-activated 1st Stage Relay
Disable Pre-activated 2nd Stage Relay
Disable Extract Fan Output
Disable Manual Release Input
Disable Releasing Sub System
Activate Extract Fan Output
Activate Alarm Delays
Countdown timer shows time
remaining until release
Supports up to seven, four wire status
indicators
With three detection zones as standard, release
can be configured to activate from any
combination of detection zone inputs to allow
(among other combinations) any two from three
type activations such as would be required for
detection in ceiling void, room and floor void
applications.
The extensive configuration options of the Elite
XT allow the functionality of the system to be
extensively modified.
The panel contains a large LED display to enable
easy configuration and control which also
displays the time remaining until release for
added user safety.
Built in Extract Fan control
Compatible with conventional
detectors from Apollo, Hochiki
America and System Sensor
The countdown timer is duplicated on up to
seven remote status units to provide local
indication of the system status.
With all of the electronics mounted on a single,
easily removable, steel plate Elite XT panels are
both robust and easy to install.
Elite XT is supplied in an enclosure that matches
the design and color of the Elite CP range and is
available in standard red or optional gray.
Access Level 3
Sounder Delay
Coincidence Detection
Disable Panel Features
Zone Alarm Delays (Detectors)
Zone Alarm Delay (Call stations)
Configure Zone for I.S Barrier Use
Zone Short Circuit Alarm
Zone Non Latching
Zone Inputs Delay
Extinguishant Release Time Delay
Extinguishant Release Duration Timer
Extinguishant Reset Delay Timer
VES Fire Detection Systems,
Tel (US): 800.270.3066 (Toll free) Tel (non US): (001) 610.992.3378 E-mail: info@ves-network.com
620 Allendale Road, King of Prussia, PA. 19406
Fax: 610.992.3380
Web: www.ves-network.com
Technical Specifications
Mains supply: 115V AC or 230V AC
Terminal capacity: 12 AWG
Mains supply fuse: 3.15 Amp (F3.15A L250V)
No. of detectors per zone: Dependent on type (maximum 32)
Finish: Epoxy powder coated
Detection circuit end of line: 6K8 5% ½ Watt resistor
Color: Red (optional gray)
Supervised input end of line: 6K8 5% ½ Watt resistor
Power supply rating: 3 Amps total including battery charge 28V +/- 2V
Sounder circuit end of line: 10K 5% ¼ Watt resistor
Maximum ripple voltage: 200 millivolts
Extinguishant output EOL: 1N4004 Diode
Battery type: Two 12 Volt 7Ah sealed lead acid in series
No. of detection circuits: 3
Battery charge voltage: 27.6VDC nominal (temperature compensated) No. of sounder circuits: 2 x 1st Stage, 1 x 2nd Stage
Battery charge current: 0.7A maximum
Extinguishant release output: Rated at 1 Amp
Battery fuse: 20mm, 3.15A glass Sloblow
Extinguishant release delay: Adjustable 0 to 60 seconds (in 5 second steps)
Maximum current draw from batteries: 3 Amps
Extinguishant release duration: Adjustable 60 to 300 seconds (in 5 second steps)
Quiescent current of panel in mains fall: 0.095A
Normal Zone Impedance (EOL): 6.8K
Aux 24V output: Fused at 500mA with electronic fuse
Detector Alarm Impedance: 470 Ohm
NAC outputs: 24V Fused at 500mA with electronic fuse
Pull Station Alarm Impedance: 270 Ohm
Trouble relay contact rating: 30VDC 1A Amp maximum
Short circuit threshold: Short circuit Impedance 99 Ohms
Fire relay contact rating: 30VDC 1A Amp maximum
Supervised Inputs Normal Impedance (EOL): 6.8K
Local fire relay contact rating: 30VDC 1A Amp maximum
Supervised Inputs Alarm Impedance: 470 Ohm
First stage contact rating: 30VDC 1A Amp maximum
Supervised inputs Short circuit threshold: 99 Ohms
Second stage contact rating: 30VDC 1A Amp maximum
Status unit/Ancillary board connection: Two wire RS485 connection
Extract contact rating: 30VDC 1A Amp maximum
Status unit power output: Rated at 500mA with electronic fuse
Zone quiescent current: 2mA maximum
S
O
L
Extract Fan Power
Extinguishant Low
Pressure Switch
470R
6K8
Releasing Solenoid
DIODE
Extinguishant Released
Pressure Switch
Remote Abort Switch
470R
Remote Manual
Release Switch
470R
470R
470R
6K8
S
6K8
S
S
6K8
S
S
Shutdown Power
S
Stop Air Conditioning
6K8
S
6K8
Peripheral
Detectors
10K
6K8
To Status
Units
E
10K
Releasing
Detectors
Disablement Switch
10K
2nd Stage
Notification
Appliances
6K8
1st Stage
Notification
Appliances
Remote Auto/Manual
Select Switch
Ordering Codes
Part number
Description
VF1810-10
Elite XT - Red 115V
VF1810-11
Elite XT - Red 230V
VF1810-40
Elite XT - Gray 115V
VF1810-41
Elite XT - Gray 230V
Auxiliary Signalling Relays
S
R0V SIL AL FLT RST
NO C NC C NO NC C NO NC C NO
NC C NO NC C NO
AUX
REMOTE
DATA POWER NAC 1 NAC 2 ZONE 1 ZONE 2 ZONE 3 2ND
1ST
2ND
MODE MAN. ABORT REL EXTING. LOW EXTRACT TROUBLE
LOCAL
FIRE
24V
CONTROL
SOUNDER STAGE
STAGE SELECT RELEASE
PRESS.
PRES.
RELAY
FIRE
RELAY
STATUS UNITS
SWITCH
SWITCH
Elite XT PCB
VES Fire Detection Systems,
Tel (US): 800.270.3066 (Toll free) Tel (non US): (001) 610.992.3378 E-mail: info@ves-network.com
620 Allendale Road, King of Prussia, PA. 19406
Fax: 610.992.3380
Web: www.ves-network.com