HPRi Series Modular Inverter System 120 VDC Input 90 kVA to 180

HPRi Series Modular Inverter System 120 VDC Input 90 kVA to 180
HPRi Series Modular Inverter System
120 VDC Input 90 kVA to 180 kVA
277/480 VAC 3 Phase 4 Wire Output
The Philtek HPRi 3 Phase Modular Inverter System features expansion
and redundancy capabilities.
Maintenance Bypass
Switch & AC Breaker
AC-DC bus bars
and connections
shroud
Plug and Play
Inverter
Modules
Plug In Static Switch
and Controller Module
Inverter
Tray
AC Power Plant
Racks
90 KVA HPRi Inverter System c/o AC Power Plant, Controller and 9 x 10 KVA Inverter Modules
Inverter Modules “Plug and Play”
• 10 KVA output each
• High frequency PWM technology, quiet operation
• “Hot Pluggable”, allows installation or removal of modules
without de-energizing the system
• Output compatible with Active Power Factor Corrected AC
Loads
Static Bypass Switch and Controller
• Output power rating self configured, 2 mSec transfer time
• Microprocessor Controlled with LCD display and Industrial
style LED Mimic Diagram
• User configured to operate in the On-line ( Inverter preferred )
or the Off-line (AC line preferred ) mode
• Provides an additional level of redundancy when operated in
the On-line Mode
• Plug in modular construction, can be removed or installed with
no output interruption during Maintenance Bypass
• Optional RS-232 Communication Port available
AC Power Plant
• Constructed of heavy duty 23” racks
• Make Before Break Maintenance Bypass Switch provides
uninterrupted output during bypass
• AC line Circuit Breaker for overload protection during Static
Bypass
• Fully enclosed AC and DC power bus bars, pre-wired to
terminal blocks for external connections
• Inverter docking
trays provide easy plug in and removal of
Inverter Modules
• CSA
Certification pending
System Specifications (Subject to change without notice)
DC Input
Bypass AC Input
Nominal
Range
Current
120 V
105 to 145 V
See Table
Connection
Voltage
Current
See Table
4 wires (Y) + Gnd
277/480V 3 Phase 60 Hz
± 1%
Static Bypass Switch
Transfer Time
AC Output
Power
Connection
Voltage
Regulation
Dynamic Regulation:
100 % step load
Recovery
Efficiency
Distortion ( linear load )
Non Linear Load Capability
Active P.F. Corrected Loads
Load Power Factor ( PF )
Frequency Tolerance
Overload
Synchronization:
Range
Rate
± 4%
< 8 mSec
90 % to 92 %
< 1.0 % THD
Up to 100 %
Compatible
1.0
± 0.1 % free running
120 % for 10 minutes
± 1.5 Hz
1 Hz per Sec
4 wires (Y) + Gnd
277/480V 3 Phase 60 Hz
Same as output current
see Table
Voltage Tolerance
Frequency Tolerance
Overload:
2 mSec typical
4 mSec maximum
± 10 %
± 1.5 Hz
120 % for 10 Minutes
1000 % for 8 ms
Environmental
Temperature
Humidity
Cooling
0º C to 40º C
95 % RH
Forced Air with temperature
Controlled Fans
Inverter Modules
Output
Model #
10 kVA 277 Vac 1Φ
HPRi-INV-10K-120-E
Weight
320 Lbs
Inverter System 120 VDC input 277/480 VAC 60 Hz 3 Phase Output
Output VA @ 1.0 PF
90,000 VA
120,000 VA
150,000 VA
*AC Power Plant + Controller Model #
HPRi 180K-120-3E+3R3E
HPRi 180K-120-3E+4R3E
HPRi 180K-120-3E+5R3E
Inverter Modules Required
9 x 10 kVA
12 x 10 kVA
15 x 10 kVA
AC Output Current per Phase
109 Amp AC
145 Amp AC
189 Amp AC
DC Input Current @ 105 V
3 x 318 Amp DC
4 x 318 Amp DC
5 x 318 Amp DC
*AC Power Plant Racks
4
5
6
Overall Dim. W”xD”xH”
98 x 29 x 84
122.5 x 29 x 84
147 x 29 x 84
Total Weight ( Net )
4,205 Lbs.
5,460 Lbs.
6,715 Lbs.
Inverter System 120 VDC input 277/480 VAC 60 Hz 3 Phase Output
Output VA @ 1.0 PF
180,000 VA
180,000 VA N+1
*AC Power Plant + Controller Model #
HPRi 180K-120-3E+6R3E
HPRi 180K-120-3E+7R3E
Inverter Modules Required
18 x 10 kVA
21 x 10 kVA
AC Output Current per Phase
217 Amp AC
217 Amp AC
DC Input Current @ 105 V
6 x 318 Amp DC
**7 x 318 Amp DC
*AC Power Plant Racks
7
8
Overall Dim. W”xD”xH”
171.5 x 29 x 84
196 x 29 x 84
Total Weight ( Net )
7,970 Lbs.
9,225 Lbs.
* AC Power Plant shipped
disassembled
** The actual maximum total
input current is only
1,908 A DC
Ordering Information:
First determine your power requirement, then select the
appropriate AC Power Plant + Controller and quantity of
Inverter Modules from the above tables
For example:
180,000VA output with N+1 redundancy requires
Qty 1
Qty 21
HPRi 180K-120-3E+7R3E
HPRi-INV-10K-120-E
For More Information please Contact:
In Canada
In USA
Philtek Electronics Ltd. Philtek Power Corp.
Tel: (604) 270-4642
Tel: (360) 332-7252
Fax: (604) 270-8343
Fax: (360) 332-7253
Web Site: www.philtek.com
(Printed in Canada 1000)