KNX IP BAOS 772 database with building structure

KNX IP BAOS 772 database with building structure
KNX IP BAOS 772 database with building structure
Operating manual
IP -Configuration:
General
The structured database is a special database for the KNX IP
BAOS 772, in which the building structure is configured and
the corresponding parameters and communication objects are
created automatically.
ETS Database
With the ETS, following parameters can be set:
General:
IP-Address:
Enter the IP-Address of the KNX IP BAOS 772 here.
IP-Sub network:
Enter the sub network mask here. The mask helps the device
to discover, whether the communication partner is the local
network. If the partner is not in the local network, then the device sends the IP telegrams not directly to the partner but to
the gateway, which forwards the telegrams to the device.
Device name:
It’s possible to assign any name for the KNX IP BAOS 772.
The device name should be significant (e.g. Data points 1st
floor), because the name is used when searching for devices.
IP address assignment:
DHCP: The device can get its IP-address from a DHCP-server
automatically. There must be a DHCP-server in the LAN in
order to use this functionality (e.g. this can be a DSL-router
with a DHCP-server integrated).
Manually: In this case, the IP-address, the sub network and the
IP-address of the gateway have to be entered.
Sending of indications:
When this parameter is activated a client will receive asynchronous data point value indications
IP-Gateway-Address:
Enter the IP-Address of the gateway here.
Hint: Leave 0.0.0.0 there, if the KNX IP BAOS 772 ought to be
used only in the local LAN.
Example for IP-Address assignment:
Over a PC the KNX IP BAOS 772 shall be accessed.
IP-Address of the PC:
192.168.1.30
Sub network of the PC:
255.255.255.0
The KNX IP BAOS 772 is located in the same local LAN therefore it uses the same sub network mask. Because of the used
sub network the IP-address assignment is limited, only addresses with format 192.168.1.xx can be assigned the device,
xx stands for the range 1-255 (without 30, because already
assigned to PC). Be careful not to use one IP-address more
then once.
IP-address KNX IP BAOS:
192.168.1.31
Sub network KNX IP BAOS:
255.255.255.0
WEINZIERL ENGINEERING GmbH
2014-07-02
EN
Page 1/3
KNX IP BAOS 772 database with building structure
Function groups:
Here, the respective functional groups are activated and the
corresponding names have to be assigned. These names
should be descriptive (e.g. Kitchen). A special case is the
group "Common functions". This only can be activated or deactivated.
The information of the individual function groups are saved as
parameter bytes (byte 1 - 384), which can be read via ethernet.
For each function group there are 32 bytes available, which
are set as follows:
Byte 1:
Function group activated/ deactivated
Byte 2-31:
Name of function group
Byte 32:
Reserved for further use
Functions:
Functions:
The following function types with the associated communication objects can be selected:
Deactivated
Switch actuator
1. Switch on/off
Switch actuator with state
1. Switch on/off
2. Switch state
Dim actuator
1. Dim brighter/darker
2. Dim relative
3. Dim value
Dim actuator switch state
1. Dim brighter/darker
2. Dim relative
3. Dim value
4. Dim switch state
Dim actuator value state
1. Dim on/off
2. Dim relative
3. Dim value
4. Dim value state
Jalousie actuator
1. Jalousie up/down
2. Jalousie step/stop
Jalousie actuator with state 1. Jalousie up/down
2. Jalousie step/stop
3. Jalousie up/down-state
4. Jalousie step/stop-state
Shutter
1. Shutter up/down
2. Shutter stop
Shutter with state
1. Shutter up/down
2. Shutter stop
3. Shutter up/down-state
Temperature
1. Temperature state
Temperature with set point 1. Temperature state
2. Temperature set point
Scene
1. Scene switch
Presence
1. Presence state
Window contact
1. Window contact state
Door contact
1. Door contact state
Smoke alert
1. Smoke alert state
Water alert
1. Water alert state
The information of the individual functions are saved as parameter bytes (byte 385-6528), which can be read via Ethernet. For each function there are 32 bytes available, which are
set as follows:
Byte 1:
Function type
Byte 2-31:
Name of function
Byte 32:
Reserved for further use
Here the respective functions of the activated function groups
have to be selected and appropriate names have to be assigned (e.g., Light dining table). For each function 5 communication objects have been reserved, which are configured via
function type.
WEINZIERL ENGINEERING GmbH
2014-07-02
EN
Page 2/3
KNX IP BAOS 772 database with building structure
Common functions:
Here the common functions can be activated, for which you
don’t have to set any names. For each function, a communication object has been reserved. The following functions can be
activated:
Time
1. Time state
Date
1. Date state
HVAC mode
1. HVAC mode switch
Door bell
1. Door bell state
Door opener
1. Door opener switch
Burglary alert
1. Burglary alert state
Rain alert
1. Rain alert state
Wind alert
1. Wind alert state
Outdoor temperature
1. Outdoor temperature state
The information of the common functions are saved as parameter bytes (bytes 6529-6538), which can be read via
Ethernet. These functions only have 10 bytes available. These
are set as follows:
Byte 1:
Common functions activated/deactivated
Byte 2-10:
Single common function activated/deactivated
Weinzierl Engineering GmbH
DE-84508 Burgkirchen
E-Mail: info@weinzierl.de
Web: www.weinzierl.de
WEINZIERL ENGINEERING GmbH
2014-07-02
EN
Page 3/3