Watts 420 Wiring Instructions

Watts 420 Wiring Instructions

advertisement

Assistant Bot

Need help? Our chatbot has already read the manual and is ready to assist you. Feel free to ask any questions about the device, but providing details will make the conversation more productive.

Manual
Watts 420 Wiring Instructions | Manualzz

- Data Brochure

Boiler Reset Module 420

1

Information

Brochure

Choose controls to match application

2

Application

Brochure

Design your mechanical applications

3

Rough-in

Wiring

Rough-in wiring instructions

D 420

08/07

4

Wiring

Brochure

Wiring and installation of specific control

5

Data

Brochure

Control settings and sequence of operation

6

Job

Record

Record settings & wiring details for future reference

Introduction

The Boiler Reset Module 420 provides outdoor reset to a hydronic heating system in order to maximize comfort and efficiency. The 420 can operate a single on / off boiler or a single modulating boiler. The 420 can override the outdoor reset water temperature to provide Domestic Hot Water or Setpoint operations.

Features:

Boiler DHW Setpoint

Demand Demand

51 52 53 54 55 56

C R

24 V (ac)

57 58

Output 1 VA

/

Boil On-Off / Mod

Off / tekmar Stager

Menu

Item

Test

DHW Valve:

24 V (ac) 8 VA

C Vlv + – Com Boil Out

DHW

59

Mod (dc)

60 61 62 63 64 65

Powered Do not apply power

Boiler Reset Module 420 tN4 tektra 991-01

Meets Class B: Canadian

ICES & FCC Part 15

Made in Canada

66

Pump

DHW

67

N

Demands: 20 - 260 V (ac)

Relay Rating: 115 V (ac) 5 A

10 A max.

68

Primary

69

Pump N

1 of 24 © 2007 D 420 - 08/07

Table of Contents

Table of Contents ...........................................................2

Display and DIP Switches ..............................................2

Dip Switch Settings ................................................2

Display and Symbols Description............................4

User Interface ........................................................5

Display Menus ................................................................6

Outdoor Reset ...................................................... 12

Boiler Temperature Control .................................. 14 tekmar Stager Operation ...................................... 17

Zone Load Shedding ............................................ 17

Domestic Hot Water Temperature Operation ....... 17

DHW with Low Temperature Boilers ..................... 19

Setpoint Temperature Operation ........................... 19

Testing the Control ....................................................... 10

Sequence of Operation ................................................. 12

tekmarNet ® 4 Communication ............................... 12

Error Messages ............................................................ 21

Troubleshooting ............................................................23

Warranty ....................................................................... 24

Display and DIP Switches

Dip Switch Settings

Set the DIP switch settings prior to making adjustments to the control through the user interface. Setting the DIP switches determines which menu items are displayed in the user interface.

If you change a DIP switch setting while the control is powered up, the LCD display returns to the View menu.

Lock / Unlock

Use the Lock / Unlock DIP switch to lock and unlock the Access

Level of the 420 and all connected tN4 devices, including tN4 thermostats. For details, see “Access Levels” viewed or changed.

segment representing a padlock is viewed in the bottom right hand corner of the display.

Unlock.

/

Boil On-Off / Mod

Off / tekmar Stager

Boiler

51 52

DHW

Demand

53 54 55

Setpoint

Demand

56

C R

24 V (ac)

57 58

Output 1 VA

/

Boil On-Off / Mod

Off / tekmar Stager

Menu

Item

Test

DHW Valve:

24 V (ac) 8 VA

C

59

Vlv

DHW

60

Powered

+ –

Mod (dc)

61

Com Boil Out

62 63 64 65

Do not apply power

Boiler Reset Module 420 tN4 tektra 991-01

Meets Class B: Canadian

ICES & FCC Part 15

Made in Canada

66

Pump

DHW

67

N

Demands: 20 - 260 V (ac)

Relay Rating: 115 V (ac) 5 A

10 A max.

68

Primary

69

Pump N

© 2007 D 420 - 08/07 2 of 24

Boil On-Off / Mod

The Boil On-Off / Mod DIP switch selects whether the control operates an On-Off boiler or the firing rate of a

Modulating boiler.

boiler.

tekmar Stager / Off

Use the tekmar Stager / Off DIP switch when a tekmar staging control is be connected to the 420 in order to operate multiple boilers. A tekmar stager may include Boiler

Controls 264, 265, and 268.

420 will then provide the stager with a target temperature via a 0-10 V (dc) signal. When the tekmar Stager / Off

DIP switch is set to tekmar Stager, the Boiler Sensor

DIP switch must be set to Sup.

Access Level

The Access Level restricts the number of Menus, Items, and Adjustments that can be accessed by the user. The

Access Level setting is found in the Miscellaneous (MISC) menu. Select the appropriate access level for the people who work with the control on a regular basis.

There are two Access Level settings: access level is sufficient for the normal set up of the control.

to the user.

In the following menu tables, the access level the item is visible in is shown in the access column.

3 of 24 © 2007 D 420 - 08/07

Item Field

Displays an abbreviated name of the selected item

Number Field

Displays the current value of the selected item

S

Menu Field

Displays the current menu

Status Field

Displays the current status of the control’s inputs, outputs and operation. Most symbols in the status field are only visible when the

VIEW Menu is selected

Symbols Description

PUMP

Displays when the primary or mixing pump is in operation.

BURNER

Displays when the burner contact is closed.

LOCK

Displays when the access levels are locked.

WARNING

Displays when an error exists.

COMMUNICATION BUS

Displays when tN4 thermostats are connected.

DHW PUMP

Displays when the DHW Pump is in operation.

°F, °C, %, HOURS, MINUTES

Units of measurement.

BOILER DEMAND

Displays when a boiler demand is present.

DHW DEMAND

Displays when a DHW demand is present.

SETPOINT DEMAND

Displays when a Setpoint demand is present.

DEVICE OUTPUT SCALE

Displays output of the modulating boiler.

© 2007 D 420 - 08/07 4 of 24

User Interface

Use the User Interface available on the Liquid Crystal Display

(LCD) to setup and monitor the operation of the system.

Use the four push buttons to the left of the LCD (Menu,

Item, Up, Down) to select settings. As you enter settings, record the settings in the Job Record J 420.

Menu

The menus display in the Menu Field at the top left side of the LCD. Three menus are available: View, Adjust, and

Miscellaneous.

Adjusting a Setting

To adjust a setting:

1. Select the appropriate menu using the Menu button.

2. Select the item using the Item button.

3. Use the Up or Down button to make the adjustment.

Default Item

item for more than five seconds.

After navigating menus, the display reverts back to the default item after 60 seconds of button inactivity.

Item

In each menu, a group of items can be selected. The abbreviated name of the selected item displays in the Item field of the LCD display.

Item button.

and press and release the Up button.

Continue to next Item

Continue to next Item

Continue to next Item

Back to View Menu

5 of 24 © 2007 D 420 - 08/07

Display Menus

View Menu (1 of 1)

The View menu items display the current operating temperatures and status information of the system.

Item Field Range

-76 to 149°F

(-60.0 to 65.0°C)

Access Description

InS

Ad

OUTDOOR SECTION B

Current outdoor air temperature as measured by the outdoor sensor.

-22 to 266°F

(-30.0 to 130.0°C)

InS

Ad

BOILER SUPPLY SECTION C

Current boiler supply water temperature as measured by the boiler sensor.

– – –, 35 to 230°F

(– – –, 1.5 to 110.0°C)

Ad

BOILER TARGET SECTION C

The boiler target is the temperature the control is currently trying to maintain at the boiler supply sensor. “– – –” is displayed when no heat is required for boiler zones.

0-100% Ad

BOILER MODULATION SECTION C

Current percent modulation of the boiler’s burner.

Note: This item is only available when the Boiler

On-Off / Mod DIP switch is set to Mod.

0 to 9999 hr

InS

Ad

BOILER RUN TIME

The total running time of the boiler since this item was last cleared. To clear this item, press the Up and Down buttons simultaneously while viewing this item.

After the last item, the control returns to the first item in the menu.

© 2007 D 420 - 08/07 6 of 24

Adjust Menu (1 of 3)

The Adjust Menu items are the programmable settings used to operate the mechanical equipment.

Item Field

Continued on next page.

Range

-60 to 45°F

(-51.0 to 7.0°C)

Default = 10°F

(-12.0°C)

1 HRF1

2 HRF2

3 Fancoil

4 Fin-tube Convector

5 Radiator

6 Baseboard

Default = 4

40 to 100°F

(4.5 to 38.0°C)

Default = 70°F

(21.0°C)

Access

InS

Ad

Description

OUTDOOR DESIGN SECTION B

The design outdoor air temperature used in the heat loss calculations for the heating system. Typically set to the temperature of the coldest day of the year.

InS

Ad

Ad

BOILER TERMINAL

BOILER INDOOR SECTION B

The design indoor air temperature used in the heat loss calculation for the boiler zones. Typically set to

70°F (21.0°C).

SECTION B

The type of heating terminal units that are being used in boiler zones.

70 to 220°F

(21.0 to 104.5°C)

Default = 180°F

(82.0°C)

InS

Ad

BOILER DESIGN SECTION B

The supply water temperature required for boiler zones on the typical coldest day of the year.

OFF, 80 to 180°F

(OFF, 26.5 to 82.0°C)

Default = 140°F

(60.0°C)

InS

Ad

BOILER MINIMUM SECTION C

The minimum allowed boiler target temperature and boiler return protection temperature. Check the boiler manufacturer’s manual for recommend supply water temperatures.

120 to 225°F, OFF

(49.0 to 107.0°C, OFF)

Default = 200°F

(93.5°C)

Ad

BOILER MAXIMUM SECTION C

The maximum allowed boiler target temperature.

0:00 to 3:00 min

Default = 0:10 min

Ad

FIRE DELAY SECTION C

The time delay the control can expect between the time that the relay contact closes to fire the boiler and when the burner actually fires.

7 of 24 © 2007 D 420 - 08/07

Adjust Menu (2 of 3)

Item Field Range

Au, 2 to 42°F

(Au, 1 to 23.5°C)

Default = Au

Access

Ad

Description

BOILER DIFFERENTIAL SECTION C

The temperature differential that the control is to use when it is operating the boiler.

10 to 230 seconds

Default = 30 seconds

0 to 50%

Default = 0%

50 to 100%

Default = 100%

Ad

Ad

Ad

BOILER MOTOR SECTION C

The amount of time required for the modulating actuating motor to fully open the gas valve or operate the fan speed from a stopped position to full speed on a modulating boiler.

Note: This item is only available when the Boiler

On-Off / Mod DIP switch is set to Mod and the tekmar

Stager DIP switch is set to OFF.

MINIMUM MODULATION SECTION C

The minimum percent modulation of the burner.

Note: This item is only available when the Boiler

On-Off / Mod DIP switch is set to Mod and the tekmar

Stager DIP switch is set to OFF.

MAXIMUM MODULATION SECTION C

The maximum percent modulation of the burner.

Note: This item is only available when the Boiler

On-Off / Mod DIP switch is set to Mod and the tekmar

Stager DIP switch is set to OFF.

Au, 5 to 30 min

Default = Au

Ad

CYCLE LENGTH

The cycle length to which all tN4 devices will synchronize.

OFF, Mb1, Mb2, Mb3,

Mb4

Default = OFF

Continued on next page.

OFF,

1 (parallel, no priority)

2 (parallel, priority)

3 (pri-sec, no priority)

4 (Pri-sec, priority)

Default = 1

InS

Ad

SCHEDULE

Selects which network setback schedule the control will follow.

InS

Ad

DHW MODE SECTION F

Selects the DHW mode of operation. This determines the operation of the primary pump in combination with the DHW pump and whether or not DHW priority is required.

© 2007 D 420 - 08/07 8 of 24

Adjust Menu (3 of 3)

Item Field Range

100 to 220°F

(38.0 to 104.5°C)

Default = 180°F

(82.0°C)

OFF, ON

Default = OFF

Access

Ad

Description

DHW EXCHANGE OCCUPIED SECTION F

The minimum boiler target temperature to the DHW heat exchanger during the Occupied period.

Note: This item is only available when DHW Mode is set 1 through 4.

Ad

DHW EXCHANGE UNOCCUPIED SECTION F

Selects whether the control should respond to DHW demands during the Unoccupied period. This item is only available when DHW Mode is set 1 through 4 and a network setback schedule is selected.

OFF,

1 (parallel, no priority)

2 (parallel, priority)

3 (pri-sec, no priority)

4 (Pri-sec, priority)

Default = 1

Ad

SETPOINT MODE SECTION H

Selects the Setpoint mode of operation. This determines the operation of the primary pump.

60 to 220°F

(15.5 to 104.5°C)

Default = 180°F

(82.0°C)

OFF, ON

Default = OFF

Ad

Ad

SETPOINT OCCUPIED SECTION H

The minimum boiler target temperature when a setpoint demand is present during the Occupied period.

Note: This item is only available when Setpoint Mode is set 1 through 4.

SETPOINT UNOCCUPIED SECTION H

Selects whether or not a Setpoint demand will be responded to during the UnOccupied period.

Note: This item is only available when Setpoint Mode is set 1 through 4 and a network setback schedule is selected.

40 to 100°F, OFF

(4.5 to 38.0°C, OFF)

Default = 70°F (21.0°C)

InS

Ad

WWSD OCCUPIED SECTION B

The system’s warm weather shut down temperature during the Wake and Occupied periods.

40 to 100°F, OFF

(4.5 to 38.0°C, OFF)

Default = 60°F (15.5°C)

Ad

WWSD UNOCCUPIED SECTION B

The system’s warm weather shut down temperature during the Sleep and Unoccupied period.

Note: This item is only available when the Schedule is not set to OFF.

After the last item, the control returns to the first item in the menu.

9 of 24 © 2007 D 420 - 08/07

Misc (Miscellaneous) Menu (1 of 1)

Item Field

The Miscellaneous Menu Items set control and display options such as access level and temperature units.

Range

InS (Installer)

Ad (Advanced)

°F, °C

Default = °F

Access

InS

Ad

Description

ACCESS LEVEL

The access level that is to be used by the control.

Note: This item is only available when the Lock / Unlock

DIP switch is set to Unlock.

InS

Ad

UNITS

Select temperature units between Fahrenheit and

Celsius.

0 to 24 Ad

BOILER BUS DEVICES

Displays the number of devices on the boiler bus.

OFF, SEL Ad

FACTORY DEFAULT

Loads the factory defaults when the Up and Down buttons are pressed.

420

InS

Ad

TYPE

Displays the type number of this product. The software version is displayed when the Up button is held.

After the last item, the control returns to the first item in the menu.

Testing the Control

The control has a built-in test routine that tests the main control functions. The control continually monitors the sensors and displays an error message whenever a fault is found. The individual outputs and relays are tested using a test sequence.

Test Sequence

Each step in the test sequence lasts 10 seconds.

again. To advance to the next step, press the Test button again.

the control exits the entire test routine.

release the Test button to display the appropriate device.

© 2007 D 420 - 08/07 10 of 24

HAZARD

Access to the Test button requires the removal of the front cover and exposes hazardous voltage while the control is powered. Only trained, qualified and competent personnel should operate the Test button.

Test Press and Hold for 1 second

Step 1 The primary pump turns on and remains on for the rest of the test sequence.

Step 2 The boiler contact is closed to fire an on-off boiler for 10 seconds or enable a modulating boiler.

IF the On-Off / Modulating DIP switch is set to Modulating or the tekmar Stager / Off DIP switch is set to tekmar

Stager:

Step 3 When a demand is present, the modulation output ramps up to 100%.

Step 4 When a demand is present, the modulation output ramps down to 0%.

The boiler contact is opened and the boiler is shut off.

Step 5 If DHW MODE is set to 1 or 2, the primary pump is shut off and the DHW Pump contact is closed.

If DHW MODE is set to 3 or 4, the primary pump stays on and the DHW Pump contact is closed.

The control exits the test sequence.

If a device fails to operate during the test sequence, refer to the W 420 Wiring Brochure to check the operation of the control. If the control works properly, refer to any troubleshooting information supplied by the equipment manufacturer.

Max Heat

The control has a function called Max Heat. In this mode, the control turns on and operates the system up to the maximum set temperatures as long as there is a demand for heat. tN4 thermostats operate to meet the occupied setting +5°F (3°C). The control operates in this mode for up to 24 hours or until the Test button is pressed. Use this mode to run the circulators during system start-up to purge air from the piping.

HAZARD

Access to the Test button requires the removal of the front cover and exposes hazardous voltage while the control is powered. Only trained, qualified and competent personnel should operate the Test button.

Test Press and Hold for 3 seconds

To enable Max Heat:

Press and hold the Test button for more than 3 seconds and less than 6 seconds.

If there is a demand for heat, the ‘TEST’ and ‘MAX’ segments are displayed on screen and the control will turn on all outputs for up to 24 hours.

If there is no demand for heat, the ‘TEST’ and ‘MAX’ segments are still displayed but no outputs are turned on until there is a demand for heat present.

To Cancel Max Heat:

Press the test button to cancel Max Heat manually or wait

24 hours and the control will automatically leave the Max

Heat mode.

Zone Test

In Zone Test mode, each tN4 device is individually turned on one at a time. The control tests each zone for up to 5 minutes of no button activity. Use this feature to purge air out of each zone and assist in troubleshooting.

HAZARD

Access to the Test button requires the removal of the front cover and exposes hazardous voltage while the control is powered. Only trained, qualified and competent personnel should operate the Test button.

Test Press and Hold for 6 seconds

To enable Zone Test:

1. Press and hold the Test button for more than 6 seconds.

The control displays ZN TEST OFF.

2. Press the Up button to change the display to ZN TEST

ON. After 3 seconds, the boiler, all pumps, and the mixing valves are shut off.

3. The control operates stage one of the tN4 device with the lowest address number. Device number one of the boiler bus (b:01) has the lowest address number and device

24 of bus 3 (3:24) has the highest address number. All other tN4 zones are shut off.

4. Pressing the Up button will turn off stage 1, and turn on stage 2 of the same device (if that device has a second stage) or turn on stage 1 of the device with the next lowest address. The Down button can be pressed to move to a device with a lower address number. The Up and Down buttons will only move through devices on the same bus.

5. Press the Item button to switch busses. The Up and

Down buttons can then be used to move through the devices and the heating stages of each device on the next bus.

6. To cancel the Zone Test, press the Test button. Once the Zone Test ends or is cancelled, the control resumes normal operation.

11 of 24 © 2007 D 420 - 08/07

Test

Hold for 6 seconds

Wait

3 seconds

Test

Sequence of Operation

tekmarNet

®

4 Communication

tekmarNet ® 4 (tN4) communicates between tN4 devices

(thermostats, Reset Module and Expansion Modules). Each tN4 device is connected to a tN4 communication bus using two wires. Each tN4 bus adjusts a single water temperature in the system using indoor temperature feedback. The Boiler

Reset Module 420 allows for one tN4 bus. This allows you to control a system with one water temperature.

A system that has more than one tN4 bus is referred to as a tN4 network.

Network

Bus 1 Bus 2

Section A

Outdoor Reset Module

The Boiler Reset Module 420 is the system control for a hydronic heating system. The 420 operates a single heat source such as a boiler, a domestic hot water tank, and responds to other heating requirements such as pool heating and snow melting. The 420 also coordinates and optimizes the operation of all the tN4 thermostats.

tN4 Thermostat

The tN4 thermostat operates heating, cooling, and or ventilation equipment for a zone. Several tN4 thermostats may work in a group when operating a cooling system. Up to 24 tN4 thermostats can connect to a single tN4 bus.

Test

Menu

Item

Do not apply power tN4 tN4

Power

Zone Group Pump A

Zone Group Pump B

Zone A1

Zone A2

Zone A3

Zone B1

Zone B2

Zone B3 tekmarNet ® 4

Thermostats tekmarNet ® 4

Thermostats

Outdoor Reset

In a heating system, the rate of heat supplied to the building must equal the rate of which heat is lost. If the two rates are not equal, the building will either cool off or over heat.

The rate of building heat loss depends mostly on the outdoor temperature. Outdoor Reset allows a hot water heating system to increase the water temperature, adding heat to the building, as the outdoor temperature drops. The rate at which the water temperature is changed is defined by the characterized heating curve.

Characterized Heating Curves

A characterized heating curve determines the amount the supply water temperature is raised for every 1° drop in outdoor air temperature. There is a characterized heating curve for each tN4 communication bus.

The characterized heating curve takes into account the type of terminal unit that the system is using. Since different types of heating terminal units transfer heat to a space using

© 2007 D 420 - 08/07

Section B different proportions of radiation, convection and conduction, the supply water temperature must be controlled differently.

Each tN4 bus is assigned a terminal unit setting that the control uses to vary the supply water temperature to suit to the terminal unit used. This improves the control of the air temperature in the building.

12 of 24

Indoor Temperature Feedback

Most buildings have internal heat gains due to people, passive solar heating and mechanical or electrical equipment.

Likewise, wind loads cause a building to lose heat faster than during design conditions. If only the outdoor temperature is measured, the control cannot compensate for these internal heat gains or loses and the building may over or under heat.

In order to maintain the most comfortable temperature, the control uses indoor temperature feedback from tN4 thermostats in order to adjust the water temperature on each tN4 bus on a continual basis.

Terminal Unit

There is a terminal unit setting for each tN4 bus. The Terminal

Unit setting is found in the Adjust menu.

Hydronic Radiant Floor (1)

Terminal type 1 is a heavy, or high mass, hydronic radiant floor system. This type of a hydronic radiant floor is embedded in either a thick concrete or gypsum pour. This heating system has a large thermal mass and is slow acting.

Radiator (5)

Terminal type 5 is a radiator terminal unit has a large heated surface that is exposed to the room. A radiator provides heat to the room through radiant heat transfer and natural convection.

Hydronic Radiant Floor (2)

Terminal type 2 is a light, or low mass, hydronic radiant floor system. Most commonly, this type of radiant heating system is either attached to the bottom of a wood sub floor, suspended in the joist space, or sandwiched between the subfloor and the surface. This type of radiant system has a relatively low thermal mass and responds faster than a high mass system.

Baseboard (6)

Terminal type 6 is a baseboard terminal unit is similar to a radiator, but has a low profile and is installed at the base of the wall. The proportion of heat transferred by radiation from a baseboard is greater than that from a fin-tube convector.

Fancoil (3)

Terminal type 3 is a fancoil terminal unit or air handling unit (AHU) consisting of a hydronic heating coil and either a fan or blower. Air is forced across the coil at a constant velocity by the fan or blower and is then delivered into the building space.

Outdoor Design Temperature

The outdoor design temperature is typically the coldest outdoor air temperature of the year. This temperature is used when doing the heat loss calculations for the building and is used to size the heating system equipment. If a cold outdoor design temperature is selected, the supply water temperature rises gradually as the outdoor temperature drops. If a warm outdoor design temperature is selected, the supply water temperature rises rapidly as the outdoor temperature drops.

The outdoor design setting is found in the Adjust menu.

Fin–tube Convector (4)

Terminal type 4 is a convector terminal unit is made up of a heating element with fins on it. This type of terminal unit relies on the natural convection of air across the heating element to deliver heated air into the space. The amount of natural convection is dependant on the supply water temperature to the heating element and the room air temperature.

13 of 24 © 2007 D 420 - 08/07

Warm Weather Shut Down (WWSD)

The Warm Weather Shut Down is the outdoor temperature at which hydronic heating is no longer required. The boiler operates only when a Domestic Hot Water (DHW) Demand or a Setpoint Demand is present.

The WWSD setting is found in the Adjust menu.

Boiler Terminal Unit Defaults

When a terminal unit is selected for boiler zones, the control loads default values for the boiler design, boiler maximum supply, and boiler minimum supply temperatures.

The factory defaults can be changed to better match the installed system. Locate the Boiler Terminal Unit setting in the Adjust menu.

Terminal Unit BOIL DSGN BOIL MAX

High Mass Radiant (1) 120°F (49°C) 140°F (60°C)

Low Mass Radiant (2) 140°F (60°C) 160°F (71°C)

BOIL MIN

OFF

OFF

Fancoil (3) 190°F (88°C) 210°F (99°C) 140°F (60°C)

Fin-Tube Convector (4) 180°F (82°C) 200°F (93°C) 140°F (60°C)

Radiator (5)

Baseboard (6)

160°F (71°C)

150°F (76°C)

180°F (82°C)

170°F (77°C)

140°F (60°C)

140°F (60°C)

Boiler Indoor Design

The boiler indoor design temperature is the indoor temperature the heating designer chose while calculating the heat loss for the boiler water heated zones. This temperature is typically

70°F (21.0°C). This setting establishes the beginning of the boiler characterized heating curve.

menu.

Boiler Design Temperature

The boiler design supply temperature is the boiler water temperature required to heat the zones on the typical coldest day of the year.

Boiler Characterized Heating Curve

Boiler

Design

Terminal Unit

Outdoor

Design

Boiler Temperature Control

The 420 is able to operate a single, hot water, on-off or modulating boiler as a heat source. For proper operation of the boiler, the 420 must be the only control that determines when the boiler is to fire.

*Important note: The boiler operator, also known as an aquastat, remains in the burner circuit and acts as a secondary upper limit on the boiler temperature. The boiler operator temperature setting must be adjusted above the

420’s Boiler Maximum setting in order to prevent short cycling of the boiler burner.

Boiler Target Temperature

The boiler target temperature is determined by connected tN4 devices or by a DHW or Setpoint demand received by the control. The tN4 devices determine the highest water temperature required and then, requests this temperature on the tN4 boiler bus. The temperature request creates a

Boiler Demand and this is indicated on the display. A DHW demand and a Setpoint demand have temperature settings to which the boilers are operated to meet and are able to override the tN4 bus temperature if required.

Boiler

Indoor

Decreasing Outdoor Temperatures

Section C

The control displays the temperature that it is currently trying to maintain as the boiler supply temperature in the View menu. If the control does not presently have a requirement for heat, it does not show a boiler target temperature.

Instead, “– – –” is displayed in the LCD.

Boiler Minimum

The boiler minimum is the lowest temperature that the control is allowed to use as a boiler target temperature.

During mild conditions, if the control calculates a boiler target temperature that is below the Boiler Minimum setting, the boiler target temperature is adjusted to at least the

Boiler Minimum setting. During this condition, if the boiler is operating, the minimum segment is turned on in the display when viewing either the boiler supply temperature or the boiler target temperature. Set the Boiler Minimum setting to the boiler manufacturer’s recommended temperature.

Boil MIN + 1/2 Boiler Differential l Wa t er Te

MIN segment on a t t

Boil MIN

Boil MIN – 1/2 Boiler Differential

© 2007 D 420 - 08/07 14 of 24

Boiler Maximum

The boiler maximum is the highest temperature that the control is allowed to use as a boiler target temperature. If the control does target the Boiler Maximum setting, and the boiler temperature is near the boiler maximum temperature, the maximum segment will be displayed in the LCD while either the boiler target temperature or the boiler temperature is being viewed. At no time does the control operate the boiler above 248°F (120.0°C).

Fixed Differential

If the user desires to have a fixed differential, this is set using the Boiler Differential setting in the Adjust menu.

Auto Differential

In order to decrease temperature swings and increase boiler efficiency, the Auto Differential feature automatically changes the on / off differential of the boiler based on the heating load. As the load increases, the differential will decrease to minimize temperature swings. As the load decreases, the differential will increase to prevent short cycling.

Boil MIN + 1/2 Boiler Differential

MAX segment on re re l l Wa te r r

Boil MAX

Boil MIN – 1/2 Boiler Differential

MAX segment on

Fire Delay

The Fire Delay is the time delay that occurs between the time that the control closes the boiler contact to fire the boiler and when the burner fires.

Off

Differential

Time

On

Boiler Contact Closed

Fire Delay

Burner On

Time

On-Off Boiler Operation

If the heat source is an On-Off Boiler, the Boil On-Off / Mod

DIP switch must be set to On-Off.

Differential

An on / off heat source must be operated with a differential in order to prevent short cycling. With the control, either a fixed or an auto differential may be selected. The boiler differential is divided around the boiler target temperature.

The boiler contact closes when the supply water temperature is 1/2 of the differential setting below the boiler target temperature. As the supply temperature reaches 1/2 of the differential above the boiler target temperature, the boiler is shut off.

Differential = 10°F (6°C)

165°F (74°C)

160°F (71°C)

155°F (68°C)

Boiler

On

Boiler

On

Target + 1/2 Differential

Target

Target – 1/2 Differential

Modulating Boiler Operation

The 420 can operate a single hot-water modulating boiler.

This requires the use of the Mod (dc) output on the 420.

To operate a modulating boiler, the Boil On-Off / Mod DIP switch must be set to Mod. The control operates the boiler by first switching the boiler contact to allow the modulating boiler to go through the ignition sequence (the boiler contact may not be required on all modulating boilers). A 0-10 V (dc) analog signal is used to modulate the boiler firing rate from the Minimum Modulation setting using Proportional,

Integral and Derivative (PID) logic in order to satisfy the boiler target temperature.

A modulating boiler requires all the same settings as an on-off boiler in addition to the settings below.

Modulating Boiler Differential

A modulating boiler must be operated with a differential while operating in low fire. The boiler differential is divided around the boiler target temperature. The boiler burner ignites at low fire when the supply water temperature is

1/2 of the Boiler Differential setting below the boiler target temperature. The boiler is shut off in low fire as the supply temperature reaches at least 1/2 of the differential above the boiler target temperature. With the control, either a fixed or an auto differential may be selected.

When the boiler is modulating above low fire, the differential does not apply. Instead, the modulation output signal is determined using Proportional, Integral and Derivative (PID) logic in order to satisfy the boiler target temperature.

15 of 24 © 2007 D 420 - 08/07

Boiler Motor Speed

The Boiler Motor Speed is the amount of time the boiler requires to go from 0% modulation to 100% modulation.

Gas valve actuating motors have a design time from fully closed to fully open which can be found in the manufacturer’s manual.

The Boiler Motor Speed should be set to this time.

The Boiler Motor Speed setting for a Variable Frequency

Drive (VFD) is the amount of time required to go from a stopped position to 100% fan speed. Since a VFD has a very quick response rate, it may be necessary to increase the Motor Speed setting in order to increase the stability of the boiler modulation.

0 Vdc

Control Rang

18%

Boiler Rang

10 V (dc)

1.8 V (dc)

Minimum Modulation

The minimum modulation defines the minimum output signal from the control to the boiler burner. It is based on a percentage of the control’s output signal range.

The Minimum Modulation default setting is 0%.

For boilers with electronic operators, the boiler’s input signal range may not match the output signal range of the 420 control. The Minimum Modulation setting limits the control output range in order to match the boiler’s input range.

Maximum Modulation

The maximum modulation defines the maximum output signal from the control to the boiler burner. It is based on a percentage of the control’s output signal range.

The Maximum Modulation default setting is 100%.

For boilers with electronic operators, the boiler’s input signal range may not match the output signal range of the 420 control. The Maximum Modulation setting limits the control output range in order to match the boiler’s input range.

menu.

To calculate the Maximum Modulation, use the following formula:

For 0-10 V (dc):

To calculate the Minimum Modulation, use the following formula:

For 0-10 V (dc):

Minimum Modulation =

0 V (dc) – Boiler’s Minimum Input Signal x 100%

Example:

A boiler requires a 1.8 V (dc) signal to fire the boiler at low fire. The boiler can be modulated to 10 V (dc) where it reaches high fire.

This means the boiler’s input signal range is 1.8 to

10 V (dc). The 420 control has an output signal range of

0-10 V (dc).

To make the two signal ranges the same, the Minimum

Modulation required is:

Minimum Modulation = 0 V-1.8 V x 100% = 18%

V-10

Maximum Modulation =

0 V (dc) – Boiler’s Maximum Input Signal x 100%

Example:

A boiler’s input signal range is 2-9 V (dc). The 420 control has an output signal range of 0-10 V (dc).

To make the two signal ranges the same, the Maximum

Modulation required is:

Maximum Modulation = 0 V-9 V x 100% = 90%

0 Vdc

90%

20%

10 V (dc)

2.0 V (dc)

0 V (dc)

tekmar Stager Operation

In some cases, multiple boilers may be required. In these cases, the 420 allows for a connection to a tekmar Boiler

Control 264, 265, or 268. The 420 uses the modulating output to provide a 0-10 V (dc) signal to the external input terminals on the Boiler Control. The 420 controls the Boiler

Section D

Control target temperature by changing the voltage signal.

The Boiler Control responds to the boiler target by staging the multiple boilers.

The following table can be used to convert a 0-10 V (dc) signal to a boiler target temperature:

Voltage (dc) 0 1 2 3 4 5 6 7 8 9 10

Boiler Target Off 50°F (10°C) 68°F (20°C) 86°F (30°C) 103°F (40°C) 121°F (50°C) 139°F (60°C) 157°F (70°C) 174°F (80°C) 192°F (90°C) 210°F (99°C)

© 2007 D 420 - 08/07 16 of 24

To use the tekmar Staging operation, the following DIP switch settings are required:

1. Set the 420 Off / tekmar Stager DIP switch to tekmar

Stager.

2. Set the 420 Boil On-Off / Mod DIP switch to Mod.

The 420 boiler sensor must be located on the supply pipe leading from the boilers. On the Boiler Control 264, 265, or 268, the External Input / Stand Alone DIP switch must be set to External Input. Any domestic hot water (DHW) demands or setpoint demands in the system must connect to the 420 in order to allow for DHW or setpoint priority.

Zone Load Shedding

If the boiler temperature approaches the boiler minimum setting, the control can turn off certain high temperature zones in order to reduce the load on the boiler. This is known as Zone Load Shedding. Zones are shed in the following order:

1. The second stage of any 2-stage thermostats which have “BOIL” selected as their heat source in order of decreasing priority. Priority is determined by the address number of the thermostat (b:01 is the highest priority,

3:24 is the lowest priority).

Section E

2. The first stage of any thermostats on the boiler bus, again, in order of decreasing priority. The first stage of the highest priority thermostat (lowest address number) will not be shed unless there is also a setpoint or DHW call.

When the boiler supply temperature goes above the minimum setting, the control begins restoring the load by turning first stages back on in the reverse order that they were shed, followed by second stages in the reverse order that they were shed.

Domestic Hot Water Temperature Operation

DHW Demand

A powered DHW Demand is required in order for the control to provide heat to the DHW system. A DHW aquastat or setpoint control is used as a switch in the DHW demand circuit. The control registers a DHW Demand when a voltage between 24 and 230 V (ac) is applied across the

DHW Demand terminals (53 and 54).

Once the control detects a DHW demand, the DHW Demand segment turns on in the LCD.

Boiler Target Temperature

The boiler target temperature is at least as hot as the DHW

Exchange setting. The DHW demand overrides the boiler reset target temperature, except when the boiler reset target is higher than the DHW exchange setting.

menu.

DHW During UnOccupied

The control has a DHW Exchange UnOccupied setting that allows the installer to select On or Off. When set to On, and the control receives a DHW Demand during an UnOccupied or Sleep period, the control continues operation of the DHW system as it would during the Occupied and Wake periods.

When set to Off, the control can ignore a DHW Demand for the duration of the UnOccupied and Sleep periods.

Section F

DHW Mode and Priority Operation

The control has four different settings available for DHW

Mode that affect pump operation. The required DHW Mode setting will depend on the piping arrangement of the DHW tank and whether or not priority for DHW is necessary. DHW

Priority stops or limits the delivery of heat to the building heating system while the DHW tank calls for heat. This allows for quick recovery of the DHW tank.

DHW MODE 1 - DHW in Parallel no Priority

When a DHW Demand is present, the DHW Pump contact closes. The primary pump (P1) does not turn on, but may operate based on either Boiler or Mixing requirements or a Setpoint Demand.

It is assumed that the DHW pump will provide adequate flow through the heat exchanger and the boiler.

Mode = 1

DHW

Pump

Primary

Pump

17 of 24 © 2007 D 420 - 08/07

DHW MODE 2 - DHW in Parallel with Priority

When a DHW Demand is present, the DHW Pump contact closes. The primary pump (P1) can operate when a boiler demand is present. If the boiler is unable to maintain the boiler target temperature, space heating zones are shut off sequentially using tN4 communication in order to provide priority to the DHW tank. This is known as zone load shedding.

It is assumed that the DHW pump will provide adequate flow through the heat exchanger and the boiler.

Mode = 2

OFF

DHW

Pump

Primary

Pump

DHW MODE 3 - DHW in Primary / Secondary no

Priority

When a DHW Demand is present, the DHW Pump contact is closed and the primary pump (P1) is operated.

Mode = 3

DHW

Pump

Primary

Pump

DHW MODE 4 - DHW in Primary / Secondary with

Priority

When a DHW Demand is present, the DHW Pump contact is closed and the primary pump (P1) is operated. Priority over space heating zones is achieved by shutting off the zone pumps or zone valves through tN4 communication.

This is known as zone load shedding.

Mode = 4

OFF

DHW

Pump

Primary

Pump that the control provides DHW priority is reduced. Once the allowed time for priority has elapsed, the control overrides the DHW priority and resumes space heating.

DHW Priority Override Time

Decreasing Outdoor Air Temperature

Conditional DHW Priority

If the boiler supply temperature is maintained at or above the required temperature during DHW generation, this indicates that the boiler has enough capacity for DHW and possibly heating as well. As long as the boiler supply temperature is maintained near the target, DHW and heating occurs simultaneously.

DHW Post Purge

After the DHW Demand is removed, the control performs a purge on the boiler. The control shuts off the boiler and continues to operate the DHW pump and the primary pump

(P1) if applicable. This purges the residual heat from the boiler into the DHW tank. The control continues this purge for a maximum of four minutes or until the boiler supply water temperature drops 20°F (-6.5°C) below the boiler target temperature during the DHW operation. The control also stops the purge if the boiler supply temperature drops below the current boiler target temperature.

DHW Mixing Purge

After DHW operation, the boiler is extremely hot. At the same time, the heating zones may have cooled off considerably after being off for a period of time. When restarting the heating system after a DHW demand with priority, the control shuts off the boiler and continues to operate the DHW pump while the primary pump is turned on. This allows some of the DHW return water to mix with the cool return water from the zones and temper the boiler return water.

DHW Priority Override

DHW Priority Override applies to DHW MODE 2 and 4.

To prevent the building from cooling off too much or the possibility of a potential freeze up during DHW priority, the control limits the amount of time for DHW priority. As the outdoor air temperature becomes colder, the length of time

© 2007 D 420 - 08/07 18 of 24

OFF

DHW

Pump

Primary

Pump

DHW with Low Temperature Boilers

If DHW heating is to be incorporated into a low temperature system such as a radiant floor heating system, a mixing device is often installed to isolate the high DHW supply temperature from the lower system temperature. If a mixing device is not installed, high temperature water could be supplied to the low temperature system while trying to satisfy the DHW demand. This may result in damage to the low temperature heating system.

The control is capable of providing DHW heating in such a system while minimizing the chance that the temperature in the heating system exceeds the design supply water temperature. In order to do this, the control must be set to DHW MODE 2 or DHW MODE 4 and Boil MIN must be set to OFF.

Section G

On a call for DHW, the control provides DHW priority by sending a message on the boiler temperature bus to the tN4 thermostats to shut off the heating zones for a period of time.

The length of time is based on the outdoor air temperature as described in the DHW Priority Override section. However, if the DHW Demand is not satisfied within the allotted time, the boiler shuts off and the heat of the boiler is purged into the

DHW tank. A DHW mixing purge occurs in order to reduce the boiler water temperature and once the boiler supply temperature is sufficiently reduced, the DHW Pump contact shuts off. The heating system zones are allowed to turn on for a period of time to prevent the building from cooling off.

After a period of heating, and if the DHW Demand is still present, the control shuts off the heating system and provides heat to the DHW tank once again.

Setpoint Temperature Operation

Setpoint

The control can operate to satisfy the requirements of a setpoint load in addition to a space heating load and a

DHW load. A setpoint load overrides the current outdoor reset temperature and WWSD setting in order to provide heat to the setpoint load.

Section H

Setpoint Mode 1 - Setpoint in Parallel

Whenever a setpoint demand is present, the boiler is operated to maintain the setpoint target. The primary pump

(P1) does not turn on, but may operate based on either a

Boiler, Mixing or a DHW Demand.

It is assumed that the Setpoint pump will provide adequate flow through the heat exchanger and the boiler.

Mode = 1

Setpoint

Setpoint Demand

A Setpoint Demand is required in order for the control to provide heat to a setpoint load.

The control registers a setpoint demand when a voltage between 24 and 230 V (ac) is applied across the Setpoint

Demand terminals (55 and 56). Once voltage is applied, the Setpoint Demand segment turns on in the LCD.

Primary

Pump

Boiler Target During Setpoint

The boiler target temperature during a Setpoint Demand is increased to at least the Setpoint setting. This temperature is maintained as long as the control has a setpoint demand.

Setpoint During UnOccupied

The control has a Setpoint UnOccupied setting that allows the installer to select On or Off. When set to On, and the control receives a Setpoint Demand during an UnOccupied or Sleep period, the control continues operation of the

Setpoint system as it would during Occupied and Wake periods. When set to Off, the control can ignore a Setpoint

Demand for the duration of the UnOccupied and Sleep periods.

Setpoint Modes

The Setpoint Mode determines the operation of the primary pump. The Setpoint Mode setting is found in the

Adjust menu.

19 of 24

Setpoint Mode 2 - Setpoint in Parallel with Priority

When a Setpoint Demand is present, the boiler is operated to maintain the setpoint target. The primary pump (P1) can operate when a boiler demand is present. If the boiler is unable to maintain the boiler target temperature, space heating zones are shut off sequentially using tN4 communication in order to provide priority for the setpoint load. This is known as zone load shedding.

It is assumed that the setpoint pump will provide adequate flow through the heat exchanger and the boiler.

Mode = 2

Setpoint

OFF

Primary

Pump

© 2007 D 420 - 08/07

Setpoint Mode 3 – Setpoint in Primary / Secondary

Whenever a setpoint demand is present, the primary pump

(P1) is turned on and the boiler is operated to maintain the setpoint target.

Mode = 3

Setpoint

Primary

Pump

Setpoint Mode 4 - Setpoint in Primary / Secondary with Priority

Whenever a Setpoint Demand is present, the primary pump

(P1) is turned on and the boiler is operated to maintain the setpoint target. Space heating zones will be shut off using zone load shedding if the boiler is unable to maintain the boiler target temperature.

Mode = 4

Setpoint

OFF

Setpoint Priority Override

Setpoint Priority Override applies to SETPOINT MODE

2 and MODE 4. To prevent the building from cooling off too much or the possibility of a potential freeze up during setpoint priority, the control limits the amount of time for setpoint priority. As the outdoor air temperature becomes colder, the length of time the control provides setpoint priority is reduced. Once the allowed time for priority has elapsed, the control overrides the setpoint priority and resumes space heating.

Conditional Setpoint Priority

If the boiler supply temperature is maintained at or above the required temperature during setpoint generation, this indicates that the boiler has enough capacity for setpoint and possibly heating as well. As long as the boiler target temperature is maintained, setpoint and heating occur at the same time.

Primary

Pump

Pump Operation

Primary Pump

The primary pump is switched on in the following situations: has H1 Pump set to On.

• There is a DHW Demand and the control is set to DHW

Mode 3 or 4.

Section I

DHW Valve

The DHW Valve operates whenever there is a DHW Demand and the control is not in DHW Priority Override.

Setpoint Mode 3 or Mode 4.

DHW Pump

The DHW Pump operates whenever there is a DHW Demand and the control is not in DHW Priority Override.

DHW

Pump

Primary

Pump

Pump Exercising

Section J

The system control will exercise all pumps, mixing valves and hydronic zones (zone valves and zone pumps) for 10 seconds every three days to prevent seizure.

© 2007 D 420 - 08/07 20 of 24

Error Messages

Local Errors and Device Errors

Error messages are used to indicate a problem somewhere in the system. There are two types of error messages: Local

Errors and Device Errors.

A Local Error indicates an error specific to a device. For example, a thermostat with a sensor short circuit will show a Sensor

Short Error on its display. No other devices will show this specific error (unless they also have a sensor short circuit).

A Device Error is used to indicate that there is a local error somewhere else on the system. For example, if a thermostat has a sensor short circuit, that thermostat will show a Local Error indicating specifically what the problem is. All other devices on the network will show Device Errors, indicating the address of the device with the Local Error. In other words,

Device Errors are nothing more than pointers, showing you that there is a local error somewhere on the system and where to find it.

Error Priority

Only one error can be shown on a particular device at a time. If there is more than one error on the system, the highest priority error will be the one that is shown. The table on pages 22 and 23 lists error messages in order of high priority to low priority.

How to Locate an Error Message

If the warning symbol (flashing circle with exclamation mark) is visible on screen, this indicates that there is an error somewhere on the system. To view the error message, you must first put the control into the Advanced or Installer access level (available in MISC menu). When an error message is present, it is available as an item in the VIEW menu.

While in the View Menu, press the item button until the error message is displayed. You may have to advance through several View Menu items before the message is displayed.

If the error message is a Device Error (if “DEV” or “DEV ERR” is shown on screen), read the address shown and go to the device with that address. That device will have a Local Error indicating specifically what the problem is. When the problem is corrected, the error message will automatically clear.

Access Levels

In some cases, it is not desirable to let day-to-day users view error messages. In these cases, by lowering the access level of the thermostat or setpoint device to ‘User’ or lower, error messages cannot be seen in the View menu and the warning symbol only appears if there is a local error or a device error caused by a critical error on another device. If there is an error message on the system that you cannot find on a particular thermostat, make sure that the access level on that thermostat is set to Installer or Advanced.

Sensor Temperature Errors

If a control is unable to display a temperature due to a sensor malfunction or communication problem, the word “Err” is displayed in place of the temperature. This usually indicates that there is an error somewhere on the system but is not the actual error message. Keep looking through the View menu to find the actual error message.

Device is attempting to show supply temperature but cannot because of sensor problem.

Keep pressing the Item button to find the actual error message

21 of 24

Once error is corrected, the temperature can be displayed

© 2007 D 420 - 08/07

Error Messages (1 of 2)

Error Message Description

ADJUST ERROR

The control failed to read the Adjust menu settings, and reloaded the factory default settings.

Operation stops until you check the Adjust menu settings.

Note: To clear the error, the access level must be set to Advanced and the settings in the

Adjust menu must be checked.

MISCELLANEOUS ERROR

The control failed to read the Miscellaneous menu settings, and reloaded the factory default settings. Operation stops until you check the Miscellaneous menu settings.

Note: To clear the error, the access level must be set to Advanced and the settings in the

Misc menu must be checked.

BOILER BUS ERROR

Communication has been lost on the boiler bus. Check the tN4, C and R wires for each tN4 device. Check the polarity of the C and R wires. Check for loose or broken wires.

BOILER BUS DEVICE LOST

Communication is lost to a tN4 device at address AA on the Boiler bus. The LCD on the lost device displays Bus Boil OPn. Ensure that there is power to the lost device. Trace the wires from the control to the lost device looking for loose or damaged wires.

Note: If you deliberately remove a tN4 device, hold the Up and Down buttons to clear the error.

MIX MODULE ERROR

A Mixing Module has been connected to the Boiler bus. Ensure that there is not a Mixing

Module on the Boiler bus.

BOILER SENSOR SHORT CIRCUIT

Due to a short circuit, the control failed to read the boiler sensor. When there is a call for heat, the control no longer controls the boiler(s). Instead, the control provides a boiler enable to the boiler’s aquastat or boiler control until the sensor is repaired. The control will not operate the boiler contact if the Boil Minimum setting is less than 100°F (38.0°C). Locate and repair the problem as described in the Data Brochure D 070.

BOILER SENSOR OPEN CIRCUIT

Due to an open circuit, the control failed to read the boiler sensor. The control no longer controls the boiler. Instead, the control provides a boiler enable to the boiler’s aquastat or boiler control until the sensor is repaired. The control will not operate the boiler contact if the Boil Minimum setting is less than 100°F (38.0°C). Locate and repair the problem as described in the Data

Brochure D 070. If you deliberately remove the boiler sensor, set the Boiler Sensor Return /

Supply DIP switch to Return. Power down for 10 seconds then restart the control.

OUTDOOR SENSOR SHORT CIRCUIT

Due to a short circuit, the control failed to read the outdoor sensor. As a result, the control assumes an outdoor temperature of 32°F (0.0°C) and continues operation. Locate and repair the problem as described in the Data Brochure D 070.

© 2007 D 420 - 08/07 22 of 24

Error Messages (2 of 2)

Error Message Description

OUTDOOR SENSOR OPEN CIRCUIT

Due to an open circuit, the control failed to read the outdoor sensor. As a result, the control assumes an outdoor temperature of 32°F (0.0°C) and continues operation. Locate and repair the problem as described in the Data Brochure D 070. Once the error is corrected, press any button to clear the error.

DEV SCHD

The selected system schedule is no longer available. Either the system schedule master is no longer connected to the network or the system schedule number has been changed on the schedule master.

DEVICE ERROR AT ADDRESS #:##

#:## is the address of the device with the error. The bus number displays before the colon, and the device number displays after. Go to the device with the address displayed.

Possible Addresses: b:01 to b:24 - Device Error on Boiler Bus

Troubleshooting

Symptom Possible Causes

No voltage present on demand terminals.

Boiler does not fire when there is a

DHW or Setpoint Demand

Control in Unoccupied and DHW

Unoccupied or Setpoint Unoccupied set to OFF.

Corrective Action

Test voltage across demand terminals using voltmeter.

Check which schedule the 420 is operating on.

Display is not on.

Boiler contact is not connected to boiler thermostat connection.

No voltage to control.

Plugs are not connected between the 420 to the Zone Manager.

Fuse is blown.

Trace wires from boiler contact to boiler thermostat connection. Use the Test sequence to check the boiler contact.

Check breaker panel or disconnect.

Check voltage using a voltmeter.

Ensure the plugs are secured to the

Zone Manager pins.

Check fuse on Zone Manager. Check total VA draw on all thermostats and zone valves connected to the Zone

Manager. This cannot exceed 40 VA.

23 of 24 © 2007 D 420 - 08/07

Limited Warranty and Product Return Procedure

Limited Warranty The liability of tekmar under this warranty is limited. The Purchaser, by taking receipt of any tekmar product (“Product”), acknowledges the terms of the Limited Warranty in effect at the time of such Product sale and acknowledges that it has read and understands same.

The tekmar Limited Warranty to the Purchaser on the

Products sold hereunder is a manufacturer’s passthrough warranty which the Purchaser is authorized to pass through to its customers. Under the Limited Warranty, each tekmar Product is warranted against defects in workmanship and materials if the Product is installed and used in compliance with tekmar’s instructions, ordinary wear and tear excepted. The pass-through warranty period is for a period of twenty-four (24) months from the production date if the Product is not installed during that period, or twelve (12) months from the documented date of installation if installed within twenty-four (24) months from the production date.

Any representations or warranties about the Products made by Purchaser to its customers which are different from or in excess of the tekmar Limited Warranty are the Purchaser’s sole responsibility and obligation. Purchaser shall indemnify and hold tekmar harmless from and against any and all claims, liabilities and damages of any kind or nature which arise out of or are related to any such representations or warranties by Purchaser to its customers.

The pass-through Limited Warranty does not apply if the returned Product has been damaged by negligence by persons other than tekmar, accident, fire, Act of God, abuse or misuse; or has been damaged by modifications, alterations or attachments made subsequent to purchase which have not been authorized by tekmar; or if the Product was not installed in compliance with tekmar’s instructions and

/ or the local codes and ordinances; or if due to defective installation of the Product; or if the Product was not used in compliance with tekmar’s instructions.

The liability of tekmar under the Limited Warranty shall be limited to, at tekmar’s sole discretion: the cost of parts and labor provided by tekmar to repair defects in materials and / or workmanship of the defective product; or to the exchange of the defective product for a warranty replacement product; or to the granting of credit limited to the original cost of the defective product, and such repair, exchange or credit shall be the sole remedy available from tekmar, and, without limiting the foregoing in any way, tekmar is not responsible, in contract, tort or strict product liability, for any other losses, costs, expenses, inconveniences, or damages, whether direct, indirect, special, secondary, incidental or consequential, arising from ownership or use of the product, or from defects in workmanship or materials, including any liability for fundamental breach of contract.

THIS WARRANTY IS IN LIEU OF ALL OTHER WARRAN-

TIES, EXPRESS OR IMPLIED, WHICH THE GOVERNING

LAW ALLOWS PARTIES TO CONTRACTUALLY EXCLUDE,

INCLUDING, WITHOUT LIMITATION, IMPLIED WARRAN-

TIES OF MERCHANTABILITY AND FITNESS FOR A PAR-

TICULAR PURPOSE, DURABILITY OR DESCRIPTION OF

THE PRODUCT, ITS NON-INFRINGEMENT OF ANY REL-

EVANT PATENTS OR TRADEMARKS, AND ITS COMPLI-

ANCE WITH OR NON-VIOLATION OF ANY APPLICABLE

ENVIRONMENTAL, HEALTH OR SAFETY LEGISLATION;

THE TERM OF ANY OTHER WARRANTY NOT HEREBY

CONTRACTUALLY EXCLUDED IS LIMITED SUCH THAT

IT SHALL NOT EXTEND BEYOND TWENTY-FOUR (24)

MONTHS FROM THE PRODUCTION DATE, TO THE

EXTENT THAT SUCH LIMITATION IS ALLOWED BY THE

GOVERNING LAW.

The pass-through Limited Warranty applies only to those defective Products returned to tekmar during the warranty period. This Limited Warranty does not cover the cost of the parts or labor to remove or transport the defective Product, or to reinstall the repaired or replacement Product, all such costs and expenses being subject to Purchaser’s agreement and warranty with its customers.

Product Warranty Return Procedure All Products that are believed to have defects in workmanship or materials must be returned, together with a written description of the defect, to the tekmar Representative assigned to the territory in which such Product is located. If tekmar receives an inquiry from someone other than a tekmar Representative, including an inquiry from Purchaser (if not a tekmar Representative) or Purchaser’s customers, regarding a potential warranty claim, tekmar’s sole obligation shall be to provide the address and other contact information regarding the appropriate Representative.

tekmar Control Systems Ltd., Canada tekmar Control Systems, Inc., U.S.A.

Head Office: 5100 Silver Star Road

Vernon, B.C. Canada V1B 3K4

(250) 545-7749 Fax. (250) 545-0650

Web Site: www.tekmarcontrols.com

Product design, software and literature are Copyright © 2007 by: tekmar Control Systems Ltd. and tekmar Control Systems, Inc.

24 of 24

All specifications are subject to change without notice.

Printed in Canada. D 420 - 08/07.

advertisement