C:\Documents and Settings\bsubrama\Desktop\Symmetra MW
 Symmetra MW 1000kW, Single Mains Bottom Entry 1 MOD UPS with 1MW External Bypass SSW Drawing guide
Sheet No.| Component /Detail Description
1 Draw ing Guide Symmetra MW 1000kW Single mains Bottom entry 1 MOD w ith External Bypass Static Switch Draw ing guide
2-5 Solution Symmetra MW 1000kW Single mains Bottom entry 1 MOD w ith External Bypass Static Switch Solution
6-8 UPS Symmetra MW 1000kW Single mains Bottom entry 1 MOD w ith External Bypass Static Switch
9 1 MW EBS Symmetra MW 1000kW Single mains Bottom entry 1 MOD External Bypass Static Switch
10 System One Line Diagram |Symmetra MW 1000kW Single mains Bottom entry 1 MOD w ith External Bypass Static Switch System one line diagram
11 Site Planning data Symmetra MW 1000kW Single mains Bottom entry 1 MOD w ith External Bypass Static Switch Site Planning data
12 System Wiring Diagram Symmetra MW 1000kW Single mains Bottom entry 1 MOD w ith External Bypass Static Switch System wiring diagram.
13 System Control Wiring Diagram | Symmetra MW 1000kW Single mains Bottom entry 1 MOD w ith External Bypass Static Switch System Control wiring diagram.
LEGEND
SYMBOL DESCRIPTION SYMBOL DESCRIPTION SYMBOL DESCRIPTION
Cx CIRCUIT BREAKER
EE NORMALLY OPEN CONTACT ~
_ CONVERTER
— SWITCH DISCONNECT
— NORMALLY CLOSED CONTACT
— SWITCH FUSE DISCONNECT
——— BUS BAR LINK — BATTERY MODULE
Е FUSE —
— РР — STATIC SWITCH
A TERMINAL
« INVERTER
e PROTECTIVE EARTHING x LAMP =
SCHNEDER ВЕСТ О ЗНА NOT BE COPED, REPRODUCED OR , nr a Matet ans 1 © SYMF1000KBH1C1EBS 0
OR SALE OF ITEMS WITHOUT WRITTEN PERAISSION FROM. SCHNEIDER Sch neider oo 1400 nor Re WB EPS sTAC sMICHL DRAM: MAHARUDRAYYA | 07-JUN-12 ANGLE
ELECTRIC. THIS DRAWING IS BASED UPON LATEST AVAILABLE 7 Electric DRAWING GUIDE ENGINEER: B.H.NIELSEN/S.WAGH| 07-JUN-12 | PROJECTION
INFORMATION AND IS SUBJECT TO CHANGE WITHOUT NOTICE PROJECT: DRAWINGS SHEET 1 0F13| APPROVED: —C.LARSEN/S.WAGH — 07-JUN-12 N/A
X
7 7 77/7
ISOMETRIC VIEW LEFT CONFIGURATION
NOTES:
1. INSTALLATION SHALL COMPLY WITH ALL APPLICABLE NATIONAL, STATE AND LOCAL ELECTRICAL REGULATIONS.
2. PLEASE REFER TO PRODUCT MANUALS FOR ADDITIONAL DETAILS PRIOR TO INSTALLATION AND
SITE PREPARATION WORK.
3. CABLE ENTRY IS FROM BOTTOM OF THE UNIT.
4. FRONT AND REAR SERVICE ACCESS IS REQUIRED.
INPUT 400 AC 3PH SINGLE MAINS SYMF 1 000KBH1 (1 EBS
OUTPUT 400V AC 3PH
1000KW 1MOD BOTTOM ENTRY W/ EXT. BYPASS STATIC SWITCH MAHARUDRAYYA | 07-JUN-12
SOLUTION ISOMETRIC—LEFT CONFIGURATION B.H.NIELSEN/S.WAGH | 07-JUN-12
DRAWINGS 2 0F13 C.LARSEN/S.WAGH| 07-JUN—12
0
FIRST
ANGLE
PROJECTION
0
/ |
F /
0
J
у
ОХ
"RON,
\
ISOMETRIC VIEW RIGHT CONFIGURATION
NOTES:
1. INSTALLATION SHALL COMPLY WITH ALL APPLICABLE NATIONAL, STATE AND LOCAL ELECTRICAL REGULATIONS.
2. PLEASE REFER TO PRODUCT MANUALS FOR ADDITIONAL DETAILS PRIOR TO INSTALLATION AND SYMMETRA MW UPS
SITE PREPARATION WORK. INPUT 400V AC 3PH SINGLE MAINS SYMF1 000KBH1 C1 EBS 0
3. CABLE ENTRY IS FROM BOTTOM OF THE UNIT. ‚ооо VOD BOTTOM ENTRY Y EXT. PASS STA SMTCH MAHARUDRAYYA | 07-JUN-12 FIRST
4. FRONT AND REAR SERVICE ACCESS IS REQUIRED. SOLUTION ISOMETRIC—RIGHT CONFIGURATION B.H.NIELSEN/S.WAGH| 07-JUN-12 ANGLE
DRAWINGS 3 0F13 C.LARSEN/S.WAGH 07—JUN—12 PROJECTION
5154
UPS sd
/ ^^ \ CLEARANCE 1067
TOUCH SCREEN FOR 1067
INVERTER SECTION CONTROL SECTION | USER INTERFACE INPUT/OUTPUT SECTION EXTERNAL BYPASS STATIC SWITCH VENTLA TION
os IIIT TIT qr MIR MIR 1 Ir 1 FRONT DOOR IS a © о
y PERFORATED | HL I HL Hil | I FORTE TOUCH SCREEN
ee | AEO | | NIN UN osea vo WEE
0000 o O,
I SHEED I I I | | I I | | | I | | I I SEED L {
I d000 | I I | | I I | | | I | | I I 0000
SL ONE LL Le 6665 1000
ГОДЕ ЕДЕ ARRE Г ДЕ TT Г a
SN 1 E =
Lee 3 Le о + FRONT
UT TU FT EE 2032
Le ee I] Le Lo i
nto owe we mye! JE ||
ENE EE ME SR В
Le ee HI I] Le
8 8 8 818 8 518 8
[Ne] 1013 1013 1016 1027
FRONT VIEW=LEFT CONFIGURATION SIDE VIEW
SHIPPING SPUT— SHIPPING SPLIT 25— 540 —368—{ [—25
e e -. . e e e . e . e le | of le e e e e |!e e|||e e CENTER OF GRAVITY DETAILS
| COOLING SLOTS | | COOLING SLOTS | | COOLING SLOTS | | COOLING SLOTS | | COOLING SLOTS | coc vers Y cone vans Y 245 UPS ASSEMBLY/INVERTER SECTION/CONTROL SECTION/1/0 CABINET/EBS
(REFER TO BELOW COG TABLE)
DC connection DC connection
| COOLING SLOTS | | COOLING SLOTS | | COOLING SLOTS | | COOLING SLOTS | | COOLING SLOTS | COOLING SLOTS RECOMMENDED KNOCKOUT AREA pr 394
—— FRONT
COOLING SLOTS 1015
COOLING SLOTS COOLING SLOTS COOLING SLOTS COOLING SLOTS COOLING SLOTS COM CONNECTION AREA ]
| | | | | AC connegtion AC connection COG
E SNTE > | AR <
АСЕ! yd COM CONNECTION Y distance
e . e e e e | eo e e e e o e oo e |o 1 e | e . . e
+ COG i COG
A COM CONNECTION FOR CABLE ENTRY X—distance 7_ distance
SEE SHEET 7
TOP VIEW FRONT VIEW SIDE VIEW
NOTES:
1. INSTALLATION SHALL COMPLY WITH ALL APPLICABLE NATIONAL, STATE AND LOCAL ELECTRICAL REGULATIONS. COG TABLE
9. PLEASE REFER TO PRODUCT MANUALS FOR ADDITIONAL DETAILS PRIOR TO INSTALLATION AND SITE PREPARATION WORK. — ER — TUS ASSEMBLII — INVERTER SEGINON — TCONTROL SECIIONIINPUTOUTPUT CABINEN —EBE—
3. ALL DIMENSIONS ARE IN MILLIMETERS OF FULLY
4. WEIGHT WITH PMs WITHOUT PMs GRAVITY popuLATED |UNPOPULATED
INVERTER SECTION 3959kg 3107kg
IN/OUT SECTION 480kg 480kg Х - DISTANCE| 1539mm 1069mm | 1048mm 553mm 529mm 508mm
CONTROL SECTION 610kg 610kg
1MW EBS 460kg 460kg Y - DISTANCE 841mm 775mm 615mm 1052mm 1017mm 939mm
TOTAL WEIGHT 5509kg 4657kg Z-DISTANCE| 54mm | s32mm | 565mm 553mm 500mm 426mm
5. CABLE ENTRY IS FROM BOTTOM OF UNIT.
6. ENCLOSURE PROTECTION CLASS : IP20.
SYMMETRA MW UPS
7. FRONT SERVICE CLEARANCE AND TOP VENTILATION CLEARANCE REQUIRED AS SHOWN. INPUT 400V AC 3PH SINGLE MANS SYMFT1000KBH1C1EBS 0
. ° OUTPUT 400V AC 3PH
о СА © TEMPERATURE ; dat os 1000KW 1MOD BOTTOM ENTRY W/ EXT. BYPASS STATIC SWITCH ан a Tn ANGLE
/A10. THIS INFORMATION PROVIDED CONSERVATIVE CENTER OF GRAVITY CALCULATION. SOLUTION GENERAL ARRANGEMENT-LEFT CONFIG т /S.
DRAWINGS 4 0F13 C.LARSEN/S.WAGH 07—JUN—12 | PROJECTION
5153
TOUCH SCREEN
USER INTERFACE UPS
|
IN 500
/ TOUCH SCREEN ` CLEARANCE 1067
EXTERNAL BYPASS STATIC SWITCH INPUT/OUTPUT SECTION CONTROL SECTION / USER INTERFACE INVERTER SECTION VENTILATION pes
/ 7 \ / \ / \// мо —
== E I AN ewe mem
PERFORATED |
MATERIAL | FOR AR FLOW | | | | | | | | | | | | 1 | |
8 ES | ¿ERES I | I | I | _ | | | I | | I I I |
НО ¿dado E |
ELA I NAN В
== == == == == == == == MINIMUM _
SERVICE
CIE Met eee cnc
| | | | | | [| | | | | | | | 1 | |
| ' 2032
I-II MM ни
1 7 |
1048 nio , 420 1027
FRONT VIEW-RIGHT CONFIGURATION
25— 540 -—368— -—25 SHIPPING SPLIT SHIPPING SPLIT
CENTER OF GRAVITY DETAILS
245 7 NY — ° * ® | ee 2 2 2 2 2 ® UPS ASSEMBLY/INVERTER SECTION/CONTROL SECTION/1/0 CABINET/EBS
| coe sr II cons as Il conne ss II comme sos || comme ss | (REFER TO BELOW COG TABLE)
DC connection DC connection
394 or re COOLING SLOTS | COOLING SLOTS JI COOLING SLOTS ]| COOLING SLOTS Ii COOLING SLOTS || COOLING SLOTS | FRONT
~~
1015 COOLING SLOTS 1015
AC connettion AC connection
ie A LL |=] COG
N 7 ; | | | JE! distance
COM CONNECTION
COM CONNECTION METRO А, COG соб
FRONT VIEW SIDE VIEW
NOTES:
1. INSTALLATION SHALL COMPLY WITH ALL APPLICABLE NATIONAL, STATE AND LOCAL ELECTRICAL REGULATIONS. COG TABLE
3. ALL DIMENSIONS ARE IN MILLIMETERS OF FULLY
4. WEIGHT WITH PMs WITHOUT PMs GRAVITY POPULATED|UNPOPULATED
INVERTER SECTION 3959kg 3107kg
IN/OUT SECTION 480kg 480kg X - DISTANCE| 1539mm 1069mm | 1048mm 553mm 529mm 508mm
CONTROL SECTION 610kg 610kg
1MW EBS 460kg 460kg Y - DISTANCE 841mm 775mm 615mm 1052mm 1017mm 939mm
TOTAL WEIGHT 5509kg 4657kg - 54 553 500 426
5. CABLE ENTRY IS FROM BOTTOM OF UNIT. Z- DISTANCE mm | 53mm | S6Smm mm mm mm
6. ENCLOSURE PROTECTION CLASS : IP20.
SYMMETRA MW UPS
7. FRONT SERVICE CLEARANCE AND TOP VENTILATION CLEARANCE REQUIRED AS SHOWN. INPUT 400V AC 3PH SINGLE MANS SYMF1000KBH1CTEBS O
о СА © TEMPERATURE -—: dat oe 10008 10D BOTON ENTRY № т, B PAS STATIC SWITCH MAHARUDRAYYA | 07-JUN-12 FIRST
; í - SOLUTION GENERAL ARRANGEMENT-RIGHT CONFIG. B.H.NIELSEN/S.WAGH 07-JUN-12 ANGLE
ZA10. THIS INFORMATION PROVIDED CONSERVATIVE CENTER OF GRAVITY CALCULATION. DRAWINGS 5 0F13 C.LARSEN/S.WAGH 07-JUN-12 PROJECTION
LN Ye” UA een” Y NIC NY | = |
|
55
65
[TYP]
5 | 620 | 635 || 902
FRONT VIEW DETAIL 110 || _
(FRONT PANELS REMOVED) [TYP]
615
24 120 TYP
[TYP] 7 80 HOLES
1012
Ш | Г”
Y Y
POWER MODULES CONTROL SECTION
UPS
FLOOR ANCHORING DETAIL
1012 1013
Y Y
INPUT/OUTPUT CABINET EXTERNAL BYPASS STATIC SWITCH
LEFT CONFIGURATION
NOTES:
[TYP FRONT VIEW DETAIL
(FRONT PANELS REMOVED)
615
12 31 TYP 24
MP] [TYP] 7, / 80 HOLES TYP]
1012 1012 101
1 \ 7 \ y A “
Y Y Y
EXTERNAL BYPASS STATIC SWITCH INPUT/OUTPUT CABINET CONTROL SECTION
\
UPS
FLOOR ANCHORING DETAIL
1. INSTALLATION SHALL COMPLY WITH ALL APPLICABLE NATIONAL, STATE AND LOCAL ELECTRICAL REGULATIONS.
2. PLEASE REFER TO PRODUCT MANUALS FOR ADDITIONAL DETAILS PRIOR TO INSTALLATION AND
SITE PREPARATION WORK.
3. ALL DIMENSIONS ARE IN MILLIMETERS.
Y
POWER MODULES
RIGHT CONFIGURATION
SYMMETRA MW UPS
INPUT 400V AC 3PH SINGLE MAINS
OUTPUT 400V AC 3PH
1000KW 1MOD BOTTOM ENTRY W/ EXT. BYPASS STATIC SWITCH
UPS—FLOOR ANCHORING
DRAWINGS 6 0F13
SYMF1000KBH1C1EBS
B.H.NIELSEN/S.WAGH
C.LARSEN/S.WAGH 07-JUN-12
0
FIRST
ANGLE
PROJECTION
Input to
Control section
Dim.: 75 x 12
REFER
VIEW-—A
REFER
VIEW-B
DC BAT 1+
In N
L
(REFER SHEET 8)
FRONT VIEW (REFER SHEET 8)
MIDPOINT
BAT 1-
BAT 2+
External
Connections
Dim.: 60 x 15
OUTPUT
L3
INPUK L2
|
Î 108
FRONT
TOP VIEW
NOTES:
1. INSTALLATION SHALL COMPLY WITH ALL APPLICABLE NATIONAL, STATE AND LOCAL ELECTRICAL REGULATIONS.
2. PLEASE REFER TO PRODUCT MANUALS FOR ADDITIONAL DETAILS PRIOR TO INSTALLATION AND
SITE PREPARATION WORK.
3. SOME STRUCTURAL DETAILS HAVE BEEN OMITTED FOR THE PURPOSE OF CLARITY.
4. ALL DIMENSIONS ARE IN MILLIMETERS.
REFER BAR
(BOTH SIDES) 8 15
TYP.
Output L1 to
Control section M12 SOS
Dim.: 75 x 12 ' 45 75
Output L2 to J О | |
Control section
Dim.: 75 x 12 VIEW A (ENLARGED
INPUT /OUTPUT, PE BUS DETAIL
Output L3 to
Control section
Dim.: 75 x 12 TT Un
an 15
M12 BOLTS
0 INV GROUND TYP. NÓ
Control DC MIDPOINT 30 o
Dim.: 60 x 15 BAT 1-. BAT 2+ N
18 |----
VIEW B (ENLARGED
DC BUS DETAIL
SIDE VIEW 1010—— — —
170 -—271— -283—— -—137
CABLE CABLE
397 ENTRY ENTRY
FOR FOR
DC DC 1015
e |CABLE CABLE
[TYP] ENTRY FOR ENTRY FOR
i | |AC IN AC OUT
© . . e e . . ©
| 441 420
TOP VIEW
TOP AND BOTTOM CABLE ENTRY
DETAILS TYPICAL)
SYMMETRA MW UPS
INPUT 400V AC 3PH SINGLE MAINS
OUTPUT 400V AC 3PH
1000kW MOD BOTTOM ENTRY W/ EXT. BYPASS STATIC SWITCH
UPS—INTERNAL VIEW INPUT/OUTPUT CABINET
DRAWINGS 7 0F13
SYMF1000KBH1C1EBS 0
MAHARUDRAYYA = 07-JUN-12 FIRST
B.H.NIELSEN/S.WAGH 07-JUN-12 ANGLE
C.LARSEN/S.WAGH 07—JUN—12 | PROJECTION
443
FRONT —
1221
SECTION L=L
NOTES:
1.
2.
3.
4.
5. SOME STRUCTURAL DETAILS HAVE BEEN OMITTED FOR THE PURPOSE OF CLARITY.
INSTALLATION SHALL COMPLY WITH ALL APPLICABLE NATIONAL, STATE AND LOCAL ELECTRICAL REGULATIONS.
PLEASE REFER TO PRODUCT MANUALS FOR ADDITIONAL DETAILS PRIOR TO INSTALLATION AND
SITE PREPARATION WORK.
ALL DIMENSIONS ARE IN MILLIMETERS
INPUT FUSE RATING: 2100A (SEMICONDUCTOR TYPE)
«=== FRONT
Out L2
Out LS
1201
SECTION R—R
INPUT «т № Зе СНЕ MAINS SYMF 1000KBH1CTEBS 0
1000KW 1MOD BOTTOM ENTRY W/ EXT. BYPASS STATIC SWITCH MAHARUDRAYYA — 07-JUN-12 FIRST
UPS-INTERNAL SECTIONS-INPUT OUTPUT CABINET B.H.NIELSEN/S.WACH | 07-—JUN-12 ANGLE
DRAWINGS 8 0F13 C.LARSEN/S.WAGH 07—JUN—12 | PROJECTION
GROUND
BUS BAR
493
- 902 |
FRONT VIEW (PANELS REMOVED)
NOTES:
1.
2.
INSTALLATION SHALL COMPLY WITH ALL APPLICABLE NATIONAL, STATE AND LOCAL ELECTRICAL REGULATIONS.
PLEASE REFER TO PRODUCT MANUALS FOR ADDITIONAL DETAILS PRIOR TO INSTALLATION AND
SITE PREPARATION WORK.
3. ALL DIMENSIONS ARE IN MILLIMETERS, UNLESS OTHERWISE SPECIFIED.
4.
SOME MECHANICAL COMPONENTS HAVE BEEN OMITTED FOR THE PURPOSE OF CLARITY.
IN OUTPUT L1 INPUT L2 OUTPUT L2
INPUT L3
OUTPUT L3
/
D
Jol | ©
№ ° \№
\ |
NE
(UT
A
o
t 1 “TH
o >
|
№ 1 +
Т Т
7
015 mm
,— HOLES FOR EXTERNAL
CONNECTIONS [TYP]
ANN
Nu
| L— GROUND BUS BAR
E
Ee
=
ET ET
REAR
SECTION A—A
BOTTOM CABLE ENTRY DETAIL
3 PLACES 144 5 Puces Г“
| + $ Y +4 + +
y e. + + 5% + i + +
-—107 e] Ne
552
INPUT_BUS DETAILS
Thickness—10mm
615
24 PLACES
[TYP]
GROUND BUSBAR DETAIL
Thickness—12mm
OUTPUT BUS BAR DETAIL
Thickness—10mm
45
SYMMETRA MW UPS
INPUT 400V AC 3PH SINGLE MAINS
OUTPUT 400V AC 3PH
1000kW 1MOD BOTTOM ENTRY W/ EXT. BYPASS STATIC SWITCH
EXTERNAL BYPASS SWITCH-INTERNAL VIEW
DRAWINGS
9 0F13
SYMFTO000KBH1CTEBS 0
MAHARUDRAYYA | 07-JUN-12 FIRST
B.H.NIELSEN/S.WAGH| 07-JUN-12 | ANGLE
C.LARSEN/S.WAGH| 07-JUN-12 | PROJECTION
MAINTENANCE BYPASS PANEL (MBP) ZA SYMMETRA MW_UPS
o ou a Comput Cr —_— à |
2000A : | - Mains - -
/N | 3P | | ca PE © ruse | SSW | |
ANS = L1.L2,L3.N.PE [Tuas 2100 | [27H | BATTERY BREAKER BATTERY AN
PROVIDED BY OTHERS и ТГ лы | — | —\ a
3x400/230V, 50Hz ~~ TTT E. Q5 | © | | | Ш Ope | OPE © |
TN-S | 1600A I. | | | | do E® + e] | | | | |
| < a —— | | | O PE | + | 7 |
; . | | | | + |— — | . .
2A, 1P, Moo | | 0-0 — x—0-——— — |
| C—Characteristic | | | | | [ | | @а7 | |...
| 1 NX Y TO MBP CAN | | | | ———
| 1/0 BOARDS | оной | | | | 16004 Г o a
Q3 to -—-— LT er ily
| 1600A | | | | | | _ | T | |! |
4P L1,L2,L3,N loo N | 2— ——— 0
| — — SE ПЕЙ 1112,13 | | © ot © eo __ — |
Q2 I ` У < ` - ` . o
| 16004 | OL E. One | OR SEO |
sp | - = 1 E LE.
| | | EXTERNAL BYPASS STATIC SWITCH | BATTERY BREAKER AN BATTERY AN
or mm al CABINET 2 CABINET 2
| 2s | | | Bypass © Peo ——
eo " FUSE |
| 1 SO0A Q6 | | | | Litas 21004 PH L1,L2,L3 |
ap 1600A — 7 PE © — a] |
> | Bypass |
| | | | SSW
| | Bypass 1MW |
| | | Output :
No lias |
L_ о о, | LEGEND:
LLLZLSNPE ess AC CABLE — PROVIDED BY OTHERS.
ects — oA I zz DC CABLE — PROVIDED BY OTHERS.
| UPS SYSTEM OUTPUT
еее ее — — | 1000kW, 3x400/230V
TN-S
NOTES:
1. INSTALLATION SHALL COMPLY WITH ALL APPLICABLE NATIONAL,STATE AND LOCAL
ELECTRICAL REGULATIONS.
2. PLEASE REFER TO PRODUCT MANUALS FOR ADDITIONAL DETAILS PRIOR TO
INSTALLATION AND SITE PREPARATION WORK.
3. DRAWING DEPICTS POWER SYSTEM CONNECTIONS AND IS NOT REPRESENTATIVE OF
PHYSICAL LAYOUT.PLEASE REFER TO MECHANICAL DRAWINGS FOR PHYSICAL LAYOUT.
4. MAINS 3x400/230V TN-S (PROVIDED BY OTHERS). FOR OTHER(TN—C,TN-C-S, TT, IT)
EARTHING PRINCIPLES CONTACT Schneider Electric.
5. ALL AC POWER CABLING IS L1,L2,L3,N,PE.
A6. RECOMMEND PROTECTION. UPS HAS NO BUILT IN DISCONNECT DEVICES TO SWITCH
OFF EXTERNAL AC (Q1 AND Q5) AND DC (Q7 AND Q8) INPUT POWER.
7. Q1, Q2, Q3,04,05 AND Q6 WITH 2NO/2NC AUXILIARY CONTACTS.
8. Q7, Q8 DC RATED THERMAL MAGNETIC TRIP MOLDED CASE CIRCUIT BREAKER WITH
24VOLT DC UNDERVOLTAGE RELEASE (UVR) AND 2NO/2NC AUXILIARY CONTACTS.
9. PLEASE REFER TO THE INSTALLATION MANUAL FOR THE BREAKER SETTINGS OF Q1 AND Qs.
UPS INPUT AND OUTPUT CONDUCTORS MUST BE IN SEPARATE CABLE RUNS.
UPS AND STATIC BYPASS WITHSTAND RATING, lcw = 200kA
DC CABLING SHOULD BE SEGREGATED FROM AC CABLING
POWER WIRING AND CONTROL WIRING SHOULD BE SEGREGATED.
10.
11.
12.
13.
A4,
THIRD PARTY PRODUCT PROVIDED BY Schneider Electric,NOT PART OF THIS SOLUTION.
SYMMETRA MW UPS
INPUT 400V AC SEM SINGLE MAINS
1000kW 1MOD BOTTOM ENTRY W/ EXT. BYPASS STATIC SWITCH
SYSTEM ONE LINE DIAGRAM
DRAWINGS 100713
SYMF1000KBH1C1EBS
MAHARUDRAYYA | 07—JUN-12
S.ANDERSEN | 07-JUN-12
C.LARSEN| 07-JUN-12
0
ANGLE
PROJECTION
N/A
Symmetra MW 1000kW Single Mains Site Planning Data for 1 Module Capacity
Manual
UPS Voltage Mains AC Input - Bypass ‚ AC Output (UOB) UPS Mechanical Data (Inverter Section EBS Mechanical Data
Rating (VAC) (UIB) (MBB) External Battery System +Control Section +10 Section only)
Current (A)
1 Module Floor Floor
OCPD Nominal Max. OCPD* | Nominal | OCPD UPS Weight |Loading| Heat EBS Loading Heat
Full OCPD*| Recom. | Nominal | Discharging | Discharging | Recom. | Current | Recom. | Dimension '* [per UPS| Data |Dissipation| Dimension Weight per Data | Dissipation
kW | kVA | Input | Output | Load | Max.“ | (A) (A) | VDC (V) | Current (A) | current (A) (A) (A) (A) |HxWxD (mm)| (kg) '? |(kg/sqgm)| — (kw)'* | HxWxD (mm) EBS (kg) (kg/sqm) (kW)
1000 | 1000 | 400 400 1494 1623 2000 1600 2x384 1356 1595 1600 1443 1600 2032x4138x1067 5049 1143 30.92 2032x1016x1067 460 424.33 30.92
Symmetra MW®
Notes.
1. Nominal Input current based on nominal mains voltage + batteries fully charged at 100% ohmic load.
2. Maximum Input current based on fully battery recharge + nominal mains voltage at 100% ohmic load.
3. Suggested input overcurrent protection based on continuous full load.
4. Nominal battery voltage assumed to be 2.0 volts/ cell (lead technology)
5. Voltage range is 340 - 460V, for 400V 50Hz system.
6. At 380V, nominal output is reduced from 200kW to 180kW in each power module section.
7. AC input to be L1,L2 L3.N PE and output to be L1,L2,L3,N,PE
8. Overcurrent protective devices (OCPD) may be either gL fuse type or MCCB rated at 20kA fault rating
9. DC cabling should be sized to give < 1% wltage drop at the nominal battery discharge current
using four-wire separate conductors in positive, centre-taps and negative poles
10. Cable entry is bottom of the UPS.
11. Control wiring to be run separately using screened conductors away from power cabling preferably in a separate containment or cable tray
12. Weights and dimensions are for fully populated power frames.
13. Heat loss refers to max loading and fully charged batteries
14. Input THDI = 5% at Full Load
15. Output: THDU =3% Linear Load, =5% Non linear load
Efficiency Details
UPS % of load
Rating
in kW | 25% | 50% | 75% | 100%
1000 | 95.00 | 97.00 | 97.50 | 97.60
THIS DRAWING AND SPECIFICATIONS HEREIN ARE THE PROPERTY OF TITLE: SYMMETRA MW UPS DWG NO: REV.
SCHNEIDER ELECTRIC AND SHALL NOT BE COPIED, REPRODUCED OR e INPUT 400V AC 3PH SINGLE MAINS SYMF 1 000KBH1 C1 EBS 0
NT me Schneider ¡on ne son Bis of ae swe so 711 MAMARUDRANA | 07-JUN-12 | ANGLE
ELECTRIC. THIS DRAWING IS BASED UPON LATEST AVAILABLE & Electric SITE PLANNING DATA ENGINEER: B.H.NIELSEN/S.WAGH | 07-JUN-12 | PROJECTION:
INFORMATION AND IS SUBJECT TO CHANGE WITHOUT NOTICE. PROJECT: DRAWINGS SHEET11 0513) APPROVED: — C.LARSEN/S.WAGH” 07-JUN-12 N/A
MAINTENANCE BYPASS PANEL (MBP)/N EXTERNAL BYPASS STATIC SWITCH
— DI EN o А = ° EL [me a |
‚ output Е = —— PARALLEL BUS2 —| Tormi mate]
— xn — с Te ABUS op MBP ABUS |
Я ЧЕ Ci Se |
3 3 TR a MP ABUS о — out
| + oe X174 Extemal X131 ABS Fs fae]
' 5 5 B EPO External
as 7 e | ЦЕ E CONTACT EPO |
04 Г 7 L518 A x130 |
5 He § MBP CAN | (vo |
95 Г — pes 1/0 BOARD 2 022 || TAL |
ЕТ Ц 0P4533B Be — : . Era ES Al .
os [7 г | Ha] e 1 | e
| — | | t ru | | TH & CONNECTION |
[¥172 RELAY OUTPUT х176 ЕРо от | —PLANE 0P0957|
TP] ee] EEE] BANANA! | [=r = BATTERY BREAKER CABINET 1/N
. | ALA —-——- 12 | 8) . во =. =. =. ©
H2 & CE Ш + EE +| - RX ®
| es = Ш | 5. |8 | | |
= 16 ———— — ——— .
: 7 | В RE] PE] нете
’ не @ = [16 | ' | + HH
+ 7 | X182 X183 TEMP. To
H5 @ _ пан | 180 MCCB STAT MCCB IND SENSOR En BATTERY
4
pe Eu | 5) emom Bottery CAN At .
= 22 2 | 0 board, р 0/N
. External Lamp 23 . | 1
supply Vac or V DC _ F— _ | y, meeB | 3
Max. 250Vac, 5A 24 2 TRIG
25 —
Q5 ST eN | | !
27 | | .
Q6 ST EA | | _J
С a |
Shunt trip for | | |
| ut od A , | UPS | e EE
elay ‘erminator] — | — — = о о — — —
output ON-0765 | — Г 7]
Jol Je]. , {128 — РАвлия. BUS1 — ones al | | | |
al 1 Г 1 | X173 [+]2]s]+] [+]2]s]+] H | /N — e 1278] ~—PARALLEL BUS2 —|x127A [ome] | | | ol star 85 ec ND | |
| : | : x178 X175 X170 0 “№ DAT | Ha wep ABUS | | | | [+] |
T ABUS .
92 Г ran re CAP CHG M_OK ID JUMP ‘OUT X177 — _L — — — — — — — — Г т Тео ба | | | EC Battery CAN | .
Er 18 то Га — #2 | | | a 1/0 board ID 1 хм |
IN : | £ |] X185
az ECN lé | Extemal 1 x131 PO Out ——L_J EEE 0P4512B woos | 3]
| [= = X174 EPO |“ | вета Г | | я X185 TRIG |] |
“Г ка Eme ar ame 1] | He À |
| ——T—X130
e | E MBP CAN ul 2 EMO | A . X186 FUSE MONITOR
Q5 Г” e | +1 | TZ | | 1 | (Display) BAT = fia .
: Le | gi 1/O BOARD 1 | — . Ta, es saus Ou |
11 11 gu 12] | 1 | ag
Q6 Г” EN LE OP4533B Se x128 = | 2 iE 4 | ‚
рт RELAY OUTPUT x176 evo our HE IH SE CONNECTON |
Tels [se [Te [so [oo] Tell oe] | |2) — РАКЕ 0P0957; | BATTERY BREAKER CABINET 2/\
. EEN ST rT — — — — == РТ
| «TT
15
16
17
18
19
20
21
22
. 23 .
E
25
| Q1 ST En |
27
Q2 ST en
С
Shunt trip for
back feed
NOTES: we |
1.
2.
A 3.
Ad,
AS.
A 6.
AT.
8.
INSTALLATION SHALL COMPLY WITH ALL APPLICABLE NATIONAL,STATE AND LOCAL ELECTRICAL REGULATIONS.
PLEASE REFER TO PRODUCT MANUALS FOR ADDITIONAL DETAILS PRIOR TO INSTALLATION AND SITE PREPARATION WORK..
THE CAPACITORS ARE ENERGY STORAGE FOR EPO WHEN NO OTHER SOURCE IS AVAILABLE LEGEND:
C1 = B41456-B7339-M = 33000uF (202-0333), C2 = B41456-B7339-M = 33000uF (202-0333).
15 CONDUCTOR IS SHIELDED TWISTED PAIR PROVIDED BY Schneider Electric.
EPO WIRING OPTIONAL
FOR LATEST BOARD PART NUMBER, REFER LATEST REVISION/CONTACT Schneider Electric.
IF BATTERY CABINET FUSES ARE NOT PRESENT, THE TERMINALS WILL HAVE TO BE FITTED WITH
JUMPERS.
THIRD PARTY PRODUCT PROVIDED BY Schneider Electric,NOT PART OF THIS SOLUTION. SYMMETRA MW UPS
INPUT 400V AC 3PH SINGLE MAINS
. . _ OUTPUT 400V AC 3PH
ABUS CABLE, Schneider Electric SUPPLIED, IS BELDEN 8108 — 8 PAIR, 24 AWG, W/SHIELD. CABLE 1000 1400 BOTTOM ENTRY W/ EXT. BYPASS STATE SWICH
SHALL BE TERMINATED WITH AMP HDP-20 DB15F—M CONN. SYSTEM WIRING DIAGRAM
DRAWINGS 12 0F13
SYMF1000KBHTCTEBS
MAHARUDRAYYA | 07-JUN-12
S ANDERSEN | 07-JUN-12
C LARSEN/S WAGH 07-JUN-12
0
ANGLE
PROJECTION
N/A
UPS (RELAY CARDS)
CONTROL SECTION BACKBLANE
7 76 7 7 7 7 7 7
Eo ERRE ERRE E XOOBA
(112131 [11213] (11213) (112131 [1/2/3) [1/2/31 [11213] [11213] 1
UPS RELAY BOARD A | 9210 1 | 4220 | | J230 | | 2240 | | 4250 | | 9260 | 1 2270 | | J270 | |
ОР4620 10-1 Generator Battery Room DC Ground + Reserved — PlantClock Power Tie |
Active Vent Fault Fault Sync Detection < hol |
Oo |—|—!
O aja — —
= >
LL æ |---
Eg 35 „a 5% 35 385 38 Е ë 8 E. sas
2 x 3 ———
55 ES 45 qa 88 gE 16 El 88 38 as BE ва #8 Е 22066 |
NN EN LN RE RE NR EN RR EN ER
| J401 | J402 | J403 | J404 | | J405 | J406 | J407 | J408 | | J409 | J410 | J411 | J412 | | J413 | J414 | J415 | J416 | |
[112131112 1311121131112 13| [1/2/3/1/2/3/1/2/3/1/2/53/ [11213111213 1112131112131 |112 1311121311213 1112131 |
A A A A A A m
[11213] [11213] (11213) [112131 [1/2/3) [1/2/31 [11213] [1[2[3] |
UPS RELAY BOARD ZN | J210 | | 4220 | | 4230 | ! J240 | | 4250 | | J260 | | 4270 | | 1270 |
ОР4620 10—2 | |
so
: : 7 § § ЗВ
5 be 38 Ec Ex En + а 3 eg 3 ЗЕЕ
= : 5 © | со) со! - =
£5 ES 55 ES 33 8% 88 27 82 828 38 2 358 |
NONE ONE NONE ONE EN ONO NANO |
| J401 | J402 | J403 | J404 | | J405 | J406 | J407 | J408 | | J409 | J410 | 411 | 2412 | | 1413 | 1414 | J415 | J416 |
[112131112 1311121131112 13| I112|3|1|2131]2I3|1|2|3| (1/2/3/1/2/3/1/2/3/1/2/31 [112/3/1/2/3/1/2/3/1/213) |
TO FAN
The relay board can accept wetted input on pins 2 and 3, the voltage range has to be min. 12Vac/dc and CAN XOOBA
max. 42.2Vac/60Vdc.
LEGEND:
ABUS CABLE — SUPPLIED BY Schneider Electric. SEE NOTE 8
NOTES
SEE SHEET 12
THIS DRAWING AND SPECIFICATIONS HEREIN ARE THE PROPERTY OF
SCHNEIDER ELECTRIC AND SHALL NOT BE COPIED, REPRODUCED OR
USED IN WHOLE OR IN PART, AS THE BASIS FOR THE MANUFACTURE
OR SALE OF ITEMS WITHOUT WRITTEN PERMISSION FROM SCHNEIDER
ELECTRIC. THIS DRAWING IS BASED UPON LATEST AVAILABLE
INFORMATION AND IS SUBJECT TO CHANGE WITHOUT NOTICE.
TE: SYMMETRA MW UPS
INPUT 400V AC 3PH SINGLE MAINS
761% SYMF1000KBH1C1EBS “O
©
OUTPUT 400V AC 3PH . — —
Schneider ной 14400 BOHOM. ENTRY W/ EXT. ins; Sn: Sw], DRAM MAHARUDRAYYA | 07-JUN-12
ectric SYSTEM CONTROL WIRING DIAGRAM ENGINEER: S ANDERSEN! 07-JUN-12
PROJECT: DRAWINGS | SHEET 13 OF 13| APPROVED: C LARSEN/S WACH! 07-JUN-12
ANGLE