Enquiry No: CC/IITK/09/2010
 ARCA SENA de PY
INDIAN INSTITUTE OF TECHNOLOGY KANPUR
CP HE
COMPUTER CENTRE
Prof. Ashish Dutta TATAY- HEHE. E .HJT-208016 (WTA)
Head
P.O.-1.1.T. KANPUR - 208 016 (India)
CC/IITK/09/ 216
February 3, 2015
Sealed quotations are invited for the following items.
Sr.
No.
Item Description Qty
1
5 KVA ONLINE UPS with two hour battery backup on full load. The detail technical 16
specification of the UPS is given in annexure I.
Make: Numeric/ GE/ Eaton/ Socomec/ Emerson/ APC/ Delta/ Uniline/ APLAB/ Hi-Rel
Battery VAH should be minimum 16000 VAH.
Make of battery should be Panasonic/ rocket/ Exide/ Amara Raja
After Sales Service:
|.
2
For providing after sales service for the UPS, the vendor should have proper service support
at Kanpur/ Lucknow with adequate service persons, spares & standby UPS facility.
Single point of contact for Support: Vendor has to provide details of single point of contact
viz. designation, address, email address, telephone /mobile No. Escalation matrix for
support should also be provided with full details .
Terms & Conditions:
Ь
2.
3:
5.
6.
7.
All quotations must reach undersigned by February 25, 2015, 5 P.M.
Quotation must be valid till 30/04/2015
Quotation shall be submitted in two parts.
e Part-I (Technical) should contain all technical details and specification of the offered
UPS along with technical compliance sheet, Battery details (like make, AH, total
number), warranty and applicable tax rate (like VAT etc.)
e Part-II (Financial) should contain the price of the offered UPS alongwith commercial
terms and conditions. The price should not be quoted in the technical bid.
Warranty: three years on UPS and battery.
The vendor (if not OEM) should have valid authorization for this tender enquiry from the
OEM company.
Quantity may increase or decrease.
Payment terms: 90% on delivery and 10% after satisfactory installation.
(Ashish Dutta)
Annexure I
Technical Specifications — ONLINE 5 KVA UPS
Feature Specification
Capacity 5 KVA Online
Technology IGBT Based Rectifier
Input Voltage Range 230V +20% AC, Single Phase
Input Frequency Range SOHZ +10%
Input Power factor >0.95
Output Voltage 230V AC +1%, Single Phase
Output Frequency 50Hz £0.5%
Output Power Factor 0.80 Lag
Output Waveform PWM Sine Wave
Protection Input and Output Over and Under Voltage, Output Overload,
Output Short Circuit, Battery Low Trip etc. If the UPS shuts
down after permissible or deep discharge, it should switch on
automatically after mains power restoration
Indications Mains On, Inverter On, Battery Low, Over Load etc.
Alarm Mains Failure, Battery Low, Trip conditions etc.
LCD Display Input Voltage, Output Voltage, Output Current, Battery Charge
etc.
Battery 12 V Lead Acid Sealed Maintenance Free Batteries
Backup 2 Hour Backup on Full Load. Battery VAH should be minimum
16000 VAH.
Bypass Automatic Static Bypass Switch
Remote Monitoring SNMP Support
Ambient Temperature 0 - 50 DegC
Enclosure M. S. Powder Coated with Caster Wheels for UPS and Batteries
Warranty 3 Years on UPS and Battery