MONITI Analogue Addressable Fire Alarm Panel

MONITI Analogue Addressable Fire Alarm Panel
MONITI
Analogue Addressable
Fire Alarm Panel
Alarm System Limitations
An automatic fire alarm system–typically made up of smoke detectors, heat
detectors, manual Call Points, audible warning devices, and a fire alarm control with
remote notification capability–can provide early warning of a developing fire. Such a
system, however, does not assure protection against property damage or loss of life
resulting from a fire. The Manufacturer recommends that smoke and/or heat detectors
be located throughout a protected premise following the recommendations of the
current edition of the National Fire Protection Association Standard 72 (NFPA 72),
manufacturer's recommendations, State and local codes, and the recommendations
contained in the Guide for Proper Use of System Smoke Detectors, which is made
available at no charge to all installing dealers. A study by the Federal Emergency
Management Agency (an agency of the United States government) indicated that
smoke detectors may not go off in as many as 35% of all fires. While fire alarm systems
are designed to provide early warning against fire, they do not guarantee warning or
protection against fire. A fire alarm system may not provide timely or adequate
warning, or simply may not function, for a variety of reasons:
Smoke detectors may not sense fire where smoke cannot reach the detectors such as
in chimneys, in or behind walls, on roofs, or on the other side of closed doors. Smoke
detectors also may not sense a fire on another level or floor of a building. A secondfloor detector, for example, may not sense a first-floor or basement fire.
Particles of combustion or "smoke" from a developing fire may not reach the sensing
chambers of smoke detectors because:




Barriers such as closed or partially closed doors, walls, or chimneys may inhibit
particle or smoke flow.
Smoke particles may become "cold," stratify, and not reach the celing or upper
walls where detectors are located.
Smoke particles may be blown away from detectors by air outlets.
Smoke particles may be drawn into air returns before reaching the detectors.
The amount of "smoke" present may be insufficient to alarm smoke detectors. Smoke
detectors are designed to alarm at various levels of smoke density. If such density
levels are not created by a developing fire at the location of detectors, the detectors
will not go into alarm.
Smoke detectors, even when working properly, have sensing limitations. Detectors that
have photoelectronic sensing chambers tend to detect smoldering fires better than
flaming fires, which have little visible smoke. Detectors that have ionizing-type sensing
chambers tend to detect fast-flaming fires better than smoldering fires. Because fires
develop in different ways and are often unpredictable in their growth, neither type of
detector is necessarily best and a given type of detector may not provide adequate
warning of a fire.
1
RE / DD / UM / MONITI V 1.0- 01
While a fire alarm system may lower insurance rates, it is not a substitute
for fire insurance!
Heat detectors do not sense particles of combustion and alarm only when heat on
their sensors increases at a predetermined rate or reaches a predetermined level.
Rate-of-rise heat detectors may be subject to reduced sensitivity over time. For this
reason, the rate-of-rise feature of each detector should be tested at least once per
year by a qualified fire protection specialist. Heat detectors are designed to protect
property, not life.
IMPORTANT! Smoke detectors must be installed in the same room as the control panel
and in rooms used by the system for the connection of alarm transmission wiring,
communications, signaling, and/or power. If detectors are not so located, a
developing fire may damage the alarm system, crippling its ability to report a fire.
Audible warning devices such as bells may not alert people if these devices are
located on the other side of closed or partly open doors or are located on another
floor of a building. Any warning device may fail to alert people with a disability or
those who have recently consumed drugs, alcohol or medication.
Please note that:



Strobes can, under certain circumstances, cause seizures in people with
conditions such as epilepsy.
Studies have shown that certain people, even when they hear a fire alarm
signal, do not respond or comprehend the meaning of the signal. It is the
property owner's responsibility to conduct fire drills and other training exercise to
make people aware of fire alarm signals and instruct them on the proper
reaction to alarm signals.
In rare instances, the sounding of a warning device can cause temporary or
permanent hearing loss.
A fire alarm system will not operate without any electrical power. If AC power fails, the
system will operate from standby batteries only for a specified time and only if the
batteries have been properly maintained and replaced regularly.
Equipment used in the system may not be technically compatible with the control. It is
essential to use only equipment listed for service with your control panel.
The most common cause of fire alarm malfunction is inadequate maintenance. To
keep the entire fire alarm system in excellent working order, ongoing maintenance is
required per the manufacturer's recommendations, IS, UL and NFPA standards. At a
minimum, the requirements of NFPA 72 shall be followed. Environments with large
amounts of dust, dirt or high air velocity require more frequent maintenance. A
maintenance agreement should be arranged through the local manufacturer's
2
RE / DD / UM / MONITI V 1.0- 01
representative. Maintenance should be scheduled monthly or as required by National
and/or local fire codes and should be performed by authorized professional fire alarm
installers only. Adequate written records of all inspections should be kept.
WARNING – Several different sources of power can be connected to the fire alarm
control panel. Disconnect all sources of power before servicing. Control unit and
associated equipment may be damaged by removing and / or inserting cards,
modules, or interconnecting cables while the unit is energized. Do not attempt to
install, service, or operate this unit this manual is read and under stood.
CAUTION – System Reacceptance Test after software changes. To ensure proper
system operation, this product must be tested in accordance with NFPA 72 after any
programming operation or change in site-specific software. Re-acceptance testing is
required after any change, addition or deletion of the system components or after any
modification, repair or adjustment to system hardware or wiring.
All components, circuits, system operations, or software functions known to be
affected by a change must be 100% tested. In addition, to ensure that other
operations are not inadvertently affected, at least 10% of initiating device that are not
directly affected by the change, upto maximum of 50 devices, must also be tested
and proper system operation verified.
This system meets NFPA requirements for indoor dry operation at 0-49° C/32-120° F
and at a relative humidity of 93 ±2% RH (non-condensing) at 32 ±2° C/90 ±3° F.
However, the useful life of the system's standby batteries and the electronic
components may be adversely affected by extreme temperature ranges and
humidity. Therefore, it is recommended that this system and all peripherals be
installed in an environment with a nominal room temperature of 15-27° C/60-80° F.
Verify that wire sizes are adequate for all initiating and indicating device loops. Refer
to manual Specifications section for maximum allowable I.R. drop from the specified
device voltage.
Like all solid state electronic devices, this system may operate erratically or can be
damaged when subjected to lightning-induced transients. Although no system is
completely immune from lightning transients and interferences,
proper grounding will reduce susceptibility. Overhead or outside aerial wiring is not
recommended, due to an increased susceptibility to nearby lightning strikes. Consult
with the Technical Services Department if any problems are anticipated or
encountered.
Disconnect AC power and batteries prior to removing or inserting circuit boards.
Failure to do so can damage circuits.
Remove all electronic assemblies prior to any drilling, filing, reaming, or punching of
the enclosure. When possible, make all cable entries from the sides or rear. Before
making modifications, verify that they will not interfere with battery, transformer, and
printed circuit board location.
3
RE / DD / UM / MONITI V 1.0- 01
Do not tighten screw terminals more than 9 in-lbs.Over-tightening may damage
threads, resulting in reduced terminal contact pressure and difficulty with screw
terminal removal.
This system contains static-sensitive components.
Always ground yourself with a proper wrist strap before handling any circuits so that
static charges are removed from the body. Use static-suppressive packaging to
protect electronic assemblies removed from the unit.
Follow the instructions in the installation, operating, and programming manuals. These
instructions must be followed to avoid damage to the control panel and associated
equipment. FACP operation and reliability depend upon proper installation by
authorized personnel.
Cautions and Warnings
READ AND SAVE THESE INSTRUCTIONS. Follow the instructions in this installation
manual. These instructions must be followed to avoid damage to this product and associated
equipment. Product operation and reliability depends upon proper installation.
DO NOT INSTALL ANY PRODUCT THAT APPEARS DAMAGED. Upon unpacking your
equipment, inspect the contents of the carton for shipping damage. If damage is apparent,
immediately file a claim with the carrier.
ELECTRICAL HAZARD - Disconnect electrical field power when making any internal
adjustments or repairs. Servicing should be performed by qualified personnel.
follows:
Ground yourself before opening or installing components
Prior to installation, keep components wrapped in anti-static material at all times.
STATIC HAZARD - Static electricity can damage components. Therefore, handle as
•
•
RADIO FREQUENCY ENERGY - This equipment generates, uses, and can radiate radio frequency
energy and if not installed and used in accordance with the instruction manual, may cause
interference to radio communications. It has been tested and found to comply with the limits
for a Class A computing device pursuant to Subpart J of Part 15 of FCC Rules, which are
designed to provide reasonable protection against such interference when operated in a
commercial environment. Operation of this equipment in a residential area may cause
interference in which case the user at his own expense will be required to take whatever
measures may be required to correct the interference.
SYSTEM REACCEPTANCE TEST AFTER SOFTWARE CHANGES - To ensure proper
system operation, this product must be tested in accordance with NFPA72-1996, Chapter 7
after any programming operation or change in site-specific software. Reacceptance testing is
required after any change, addition or deletion of system components, or after any
modification, repair or adjustment to system hardware or wiring.
All components, circuits, system operations, or software functions known to be affected by a
change must be 100% tested. In addition, to ensure that other operations are not
inadvertently affected, at least 10% of initiating devices that are not directly affected by the
change, up to a maximum of 50 devices, must also be tested and proper system operation
verified.
4
RE / DD / UM / MONITI V 1.0- 01
Table of Contents
Chapter 1: Product Description..................................................................7
1.1: Feature ..............................................................................................8
1.2: Specification ………………………………………………………10
1.3: Control and Indication …………………………………………….11
1.3.1: Controls …………………………………………………………11
1.3.2: Indication ………………………………………………………..12
1.3.2.1: LED Indication ………………………………………………..12
1.3.2.2: LCD Indication ………………………………………………..13
1.3.2.3: Local Buzzer …………………………………………………..13
1.4: Circuits …………………………………………………………….13
1.4.1: Main Circuit Board ………………………………………………13
1.4.2: Input Circuits (SLC) ……………………………………………..13
1.4.3: Output Circuit ……………………………………………………14
1.4.4: Relays ……………………………………………………………14
1.5: Components ………………………………………………………..14
1.6: Mechanical Construction ………………………………………….16
Chapter 2: Installation ……………………………………………………19
2.1: Installation Precaution ……………………………………………..19
2.2: Panel Mounting …………………………………………………….21
2.3: Panel Wiring ……………………………………………………….22
2.4: Relays ………………………………………………………………25
2.5: NAC …………………………………………………………….... 26
2.6: Signaling Line Circuit (SLC) ………………………………………26
2.7: UL Power-Limited wiring requirement …..………………………..30
Chapter 3: Programming …………………………………………………30
3.1: Programming Concept ……………………………………………..30
3.1.1: General Comment ………………………………………………..30
3.1.2: User Programming ……………………………………………….31
3.1.3: Initial Power up ………………………………………………….32
3.1.4: Programming Description ……………………………………….32
3.1.5: Programming Password …………………………………………32
3.2: Programming Instruction ………………………………………….33
3.2.1: Menu Key Flow Diagram ……………………………………….33
3.2.2: Main Menu ………………………………………………………40
3.2.2.1: View …………………………………………………………...40
3.2.2.1.1: Suppressed Events ..………………………………………….40
3.2.2.1.2: History ….……………………………………………………40
3.2.2.1.3: Loop Card ……………………………………………………41
3.2.2.2: Program ………………………………………………………..42
3.2.2.2.1: System ……………………………………………………….42
3.2.2.2.1.1: Settings……………………………………………………..42
3.2.2.2.1.1.1: Date & Time.……………………………………………..43
3.2.2.2.1.1.2: Caption ………………………………………………….43
3.2.2.2.1.1.3: Password ……. ………………………………………….43
3.2.2.2.1.1.4: Night Mode……………………………………………….44
3.2.2.2.1.2: Relay O/P …………………………………………………46
3.2.2.2.1.3: Advanced …………………………………………………..46
3.2.2.2.2: Loop Card ……………………………………………………47
5
RE / DD / UM / MONITI V 1.0- 01
3.2.2.2.2.1: Auto Learn …………………………………………………48
3.2.2.2.2.2: Status ………………………………………………………48
3.2.2.2.2.3: Style ………………………………………………………. 49
3.2.2.2.2.4: Device ……………………………………………………..49
3.2.2.2.2.4.1: Detector Programming ………………………………….49
3.2.2.2.2.4.2: Module Program ………………………………………...50
3.2.2.2.3: Grouping …………………………………………………….51
3.2.2.2.4: Features ……………………………………………………...55
3.2.2.3: Test ... ………………………………………………………….57
3.2.2.4: About …………………………………………………………. 58
Chapter 4: Operating Instruction ………………………………………..59
4.1: Panel Operation ……………………………………………………59
4.2: Initial Power up condition …………………………………………59
4.3: Inputs ………………………………………………………………59
4.4: Indications …………………………………………………………59
4.5: Buzzer ……………………………………………………………..60
4.6: Operating Keys ……………………………………………………61
4.7: Normal Monitoring Mode …………………………………………62
4.8: Alarm Condition …………………………………………………...62
4.9: Supervisory Condition ……………………………………………..63
4.10: Fault Condition ……………………………………………………64
4.11: Test Condition …….………………………………………………65
4.12: Disable Condition …………………………………………………65
Chapter 5: Servicing ………………………………………………………66
5.1: Installation / Replacement of PCB ………………………………...66
5.2: Lamp Test …………………………………………………………69
5.3: System Power ……………………………………………………..69
5.4: Trouble Shooting ………………………………………………….69
Chapter 6: Battery Calculation ………………………………………….70
Chapter 7: Wiring Requirements ……………………………………….73
Chapter 8: Compatible Devices ………………………………………….73
Chapter 9: Abbreviations ……….……………………………………….74
6
RE / DD / UM / MONITI V 1.0- 01
Chapter 1: Product Description
The MONITI is a compact, cost effective, intelligent addressable control panel
has an extensive list of powerful features. The power supply, master control and
indicating boards housed in a FR-ABS Plastic cabinet, providing a complete fire control
system for most applications. The panel has maximum capable for Single loop, which is
incorporated with the main circuit board. It has the ability to detect total number of
detectors and modules connected in a loop. It allows remote and local programming
of the control panel using the MonitI-CS upload/download utility. Any personal
computer with windows 7 or greater and compatible modem with a speed of 14.4
kbps or faster and Ravel upload/download graphic software kit (MonitI-CS). This allows
download of the entire program or upload of the entire program, history file, test data,
and current status.
7
RE / DD / UM / MONITI V 1.0- 01
1.1
Features.

32 bit processor - Arm Cortex M3.

Operates on 120 to 220V AC, 60 / 50 Hz.

Battery Backup 24V DC with Built in charger.

40 x 4 Characters LCD display.

Touch key pad for user friendly operation.

Loop cards with Class A or B wiring.

Maximum 147 devices.

Upto 192 Grouping Facility.

Auto learning facility.

Device / Detector wise Configuration facility.

Auto device type verification.

2000 Event storage with Real Time Clock.

USB 2.0 Interface for PC connectivity.

Two Programmable Form C relay for Fire, Fault and supervisory.

One Form C Potential Free relay for Fault

24V DC output.

One Supervised Notification Appliance Circuit.(NAC)
Off Line Programming: Create the entire program in any computer using intelligent
ravel software. Upload / download system programming locally.
8
RE / DD / UM / MONITI V 1.0- 01
RS 485
Communication
Port
Power Limited
Programmable Relay
1 & 2 and Fault Relay
NC NO C
Non-supervised
Power Limited
Power Limited
Resettable
24V DC O/P
Power Limited
24V NAC
Output
Power Limited
SLC Loop Terminals
C2
RS 485 I/P
A
B
FAULT-RLY3
NC
NO
C
PROG-RLY2
NC
NO
C
PROG-RLY1
NC
NO
C
DC O/P
_
_
E
LOOP
NAC O/P
+
_
+
IN
+
_
OUT
N
P
120 / 220 VAC
+
USB 2.0
Power Limited
USB 2.0 Port
F1
L1
Br1
F3
L3
U1
F3
U7
U7
U6
C28
+
Q1
U5
Q2
U6
CN 3
F3
12V 7Ah
Battery
CN 2
C13
C11
C10
12V 7Ah
Battery
Figure - 1
9
RE / DD / UM / MONITI V 1.0- 01
1.2
Specifications.
Primary Power
120 / 220VAC + 10% -15%, 60 / 50 Hz.
Standby Power
24V D.C (2 Nos of 12v, 7Ah) Sealed Lead acid battery.
Operating Condition
Operating Temperature : 0 - 49° C/32-120° F.
Relative Humidity : 93 ± 2% RH (non-condensing) at 32 ±2° C/96 ±3° F.
Charging Circuit
Charging Voltage – 28V, ± 0.2V Nominal
Charging Current – 0.5A (Max.).
Signaling Line Circuits
Class A or B loop card: 1 No.
No. of Device: 147 No’s.
Loop resistance: 40 ohms (Max.(Without Loop Sounder)).
20 ohms (Max.(With Loop Sounder & Maximum Load)).
Loop capacitance: 0.6 µf (Max.).
Loop Current: 300mA (Max.).
Notification Appliance Circuit
Class B, Style - Y wiring
Operating Nominal Voltage: 24 VDC Nominal
Current for NACs: 1.0Amps
Line Drop: 2.4V
End-Of-Line Resistor: 4K7, ½ watt
D.C. Output – Special Application
24VDC, 300mA Max.
Common Three Form – C Relays
Relay Contact Rating: 2Amps @ 30 VDC, 0.5Amps @ 125VAC.
Power Factor: 1.0
10
RE / DD / UM / MONITI V 1.0- 01
1.3
Control and Indications
ANALOGUE ADDRESSABLE
FIRE ALARM CONTROL PANEL
FAULT
FIRE
SILENCE
RESET
1
ABC
2
DEF
3
GHI
4
JKL
5
MNO
6
PQR
7
STU
8
VWX
9
YZ
*
0
SYSTEM ON
MAINS ON
MENU
BATTERY ON
EVACUATE
ENTER
PRE ALARM
NIGHT MODE
TEST

CHARGER FAULT
ACK.
Control
Keys
SUPERVISORY

SYSTEM FAULT
EARTH FAULT
NAC FAULT
DISABLED
TEST
SILENCED
Figure – 2
1.3.1.
Controls:
ACK. Key:
 To mute local buzzer in alarm condition.
 To mute local buzzer in Supervisory or fault condition.
 User or Admin password protected.
SILENCE Key:
 To silence the external NACs in Fire Condition.
 User or Admin password protected.
RESET Key:
 To reset the particular zones in Fire alarm or Latched Supervisory condition.
 User or Admin password protected.
 Possible to access only after silence in alarm condition.
EVACUATE:
 To activate External NACs Manually.
 User or Admin password protected.
11
RE / DD / UM / MONITI V 1.0- 01
CURSOR KEYS:
 To move the curse point in the LCD as required.
ENTER Key:
 To accept the programmed or edited menu, mode or value in the LCD.
MENU Key:
 To enter into the Main Menu in the LCD.
TEST Key:
 To enter into the Lamp Test mode.
 To enter into the self test for individual Device.
ALPHANUMERIC KEYS:
 These keys are used for entering the names etc. and numbers.
 ‘*’ Key is used to go back the previous screen in programming mode.
 ‘#’ is used for the Back Space / Delete the content.
1.3.2.
1.3.2.1
Indications:
LED indication
System On – Green
Fire – Red
Fault – Yellow
Supervisory – Yellow
Mains On – Green
Battery On – Green
Charger Fault – Yellow
Earth Fault – Yellow
System Fault – Yellow
Silenced – Yellow
Pre Alarm - Yellow
NAC Fault – Yellow
Test – Yellow
Night – Yellow
Disable – Yellow
12
RE / DD / UM / MONITI V 1.0- 01
1.3.2.2
LCD Indication
The 40X4 Character LCD is used for the programming the panel functions. It also
indicates all events along with the LED indications except system on and system
fault. Programmed zone wise location details can be viewed.
1.3.2.3
Local Buzzer
A piezo buzzer provides separate and distinct sounds for alarm, trouble and
supervisory conditions:



1.4
Alarm – Continuous
Fault – pulse 0.5sec ON and 5sec OFF
Supervisory / PreAlarm – pulse 0.25sec ON and 0.25sec OFF
Circuits
The main circuit board provides system control and visual indication control and
contains the system microcontroller, programming part (USB-2.0), non-volatile memory
for system events storages. The main circuit board is used for the critical functions like
programmable logic and timing functions and non critical functions, like customer
area location and device messages.
The visual display board consists of a series LED’s for common indication of
power, alarm, fault and supervisory. The display board has 40 X 4 characters LCD,
which describes for the system information with real time clock and it helps the user to
program the system options easily. It also contains matrix touch key pad, which helps
the user for friendly access.
1.4.1
Main Circuit Board
The main circuit board controls the display board, SLC loop card, output ports
like USB 2.0. The main circuit board contains relay outputs, NAC output etc.,
1.4.2
Input Circuits (SLC)
There is a Single SLC loop is provided with standard on the FACP main
circuit board. This SLC loop is configurable for class A style 4, 5 or 7 or class
B style B or C. It provides communication to addressable detectors,
monitor (initiating device) and controls (output device) modules. These
loop cards have redundancy, that is it give fire and alarm outputs like a
conventional FACP during the CPU is failed condition.
13
RE / DD / UM / MONITI V 1.0- 01
1.4.3
Output Circuit
The following outputs are available with this FACP:
 24V DC output for having capacity of 300 mA.
 24VDC Battery charger up to 40 Ah max.
 One Class B Style Y NACs, 1 Amp each.
1.4.4
Relays
Two programmable and one standard fault Form-C dry contact relays are
provided. These two programmable relays are factory default programmed for alarm,
prealarm and supervisory. Contacts are 2 Amps @ 30 VDC or 0.5 Amps @ 125VAC.
1.5
Components
The main circuit board contains the system CPU, other primary components
wiring interface terminal outputs and inbuilt SLC loop cards in main circuit boards. The
inbuilt SLC Loop Card gets the information’s from the detectors and modules and
provides it into the control panel. This allows the control panel to monitor and process
the information to the determine the status (alarm, fault, maintenance or normal) of
each detectors and modules. The maximum 127 Devices (Detectors & Modules) and
20 Loop powered sounder shall be connected in this loop card.
RS 485 I/P
A
B
FAULT-RLY3
NC
NO
C
PROG-RLY2
NC
NO
C
PROG-RLY1
NC
NO
C
DC O/P
_
+
LOOP
NAC O/P
_
_
+
IN
+
_
OUT
+
USB 2.0
F3
F3
U6
U7
+
Figure - 3
The display board contains the LED display for common indications and touch
key pad.
14
RE / DD / UM / MONITI V 1.0- 01
The power supply gives the power for the main circuit board and for SLC loop
cards. It is SMPS type power supply, gives the output for 2 amps max.
135.00 mm
C2
E
N
P
120 / 220 VAC
F1
L1
Br1
U1
L3
145.00 mm
U7
C28
Q1
U5
Q2
U6
CN 3
F3
CN 2
C13
C11
C10
Figure - 4
15
RE / DD / UM / MONITI V 1.0- 01
1.6
Mechanical Construction
The enclosure of the Panel is constructed by FRABS Plastic. The 19mm 14 no’s
of knockouts are given for cable entry at the top of the cabinet. The lockable hinged
door is provided to access the inside the cabinet. The panel also has sufficient space
to accommodate 2 Nos. of 12v, 7Ah batteries. For higher capacity batteries like 26Ah,
40Ah etc use separate enclosure should be used and installed with conduit in the
same room or near the panel.
295.00 mm
275.00 mm
375.00 mm
390.00 mm
Figure - 5
16
RE / DD / UM / MONITI V 1.0- 01
TOP VIEW
375.00 mm
LS VIEW
FRONT VIEW
280.00 mm
295.00 mm
285.00 mm
390.00 mm
RS VIEW
385.00 mm
BOTTOM VIEW
Figure – 6
17
RE / DD / UM / MONITI V 1.0- 01
NON POWER LIMITED
CABLE ENTRY
C2
E
RS 485 I/P
A
B
FAULT-RLY3
NC
NO
C
PROG-RLY2
NC
NO
C
PROG -RLY1
NC
NO
C
DC O/P
_
+
_
N
P
LOOP
NAC O/P
_
+
IN
+
_
120 / 220 VAC
OUT
+
USB 2.0
F1
L1
Br1
F3
L3
U1
F3
U7
U6
U7
C28
+
Q1
U5
Q2
U6
CN 3
F3
12V 7Ah
Battery
CN 2
C13
C11
C10
12V 7Ah
Battery
Figure - 7
18
RE / DD / UM / MONITI V 1.0- 01
Chapter 2: Installation
2.1
Installation Precaution
Installation Precautions
WARNING - Several different sources of power can be
connected to the fire alarm control panel. Disconnect all
sources of power before servicing. Control unit and associated
equipment may be damaged by removing and/or inserting
cards, modules, or interconnecting cables while the unit is
energized. Do not attempt to install, service, or operate this unit
until this manual is read and understood.
CAUTION - System Reacceptance Test after Software Changes.
To ensure proper system operation, this product must be tested
in accordance with NFPA 72 after any programming operation
or change in site-specific software. Reacceptance testing is
required after any change, addition or deletion of system
components, or after any modification, repair or adjustment to
system hardware or wiring. All components, circuits, system
operations, or software functions known to be affected by a
change must be 100% tested. In addition, to ensure that other
operations are not inadvertently affected, at least 10% of
initiating devices that are not directly affected by the change,
up to a maximum of 50 devices, must also be tested and
proper system operation verified.
This system meets NFPA requirements for indoor dry operation
at 0-49° C/32-120° F and at a relative humidity of 93 ±2% RH
(non-condensing) at 35 ±2° C/77 ±3° F. However, the useful life
of the system's standby batteries and the electronic
components may be adversely affected by extreme
temperature ranges and humidity. Therefore, it is
recommended that this system and all peripherals be installed
in an environment with a nominal room temperature of 15-49°
C/60-120° F.
Verify that wire sizes are adequate for all IDC’s loops. Most devices cannot tolerate
more than a 10% I.R. drop from the specified device voltage. Adherence to the
following will aid in problem-free installation with long-term reliability:
Like all solid-state electronic devices, this system may operate erratically or can be
damaged when subjected to lightning-induced transients. Although no system is
completely immune from lightning transients and interferences, proper grounding will
reduce susceptibility. Overhead or outside aerial wiring is not recommended, due to
an increased susceptibility to nearby lightning strikes. Consult with the Technical
Services Department if any problems are anticipated or encountered.
RE / DD / UM / MONITI V 1.0- 01
19
Disconnect AC power and batteries prior to removing or inserting circuit boards. Failure
to do so can damage circuits.
Remove all electronic assemblies prior to any drilling, filing, reaming, or punching of
the enclosure. When possible, make all cable entries from the sides or rear. Before
making modifications, verify that they will not interfere with battery, transformer, and
printed circuit board location.
Do not tighten screw terminals more than 1.0168 N-m. Over-tightening may damage
threads, resulting in reduced terminal contact pressure and difficulty with screw
terminal removal.
Though designed to last many years, system components can fail at any time. This
system contains static-sensitive components. Always ground yourself with a proper
wrist strap before handling any circuits so that static charges are removed from the
body. Use static-suppressive packaging to protect electronic assemblies removed
from the unit.
Follow the instructions in the installation, operating, and programming manuals. These
instructions must be followed to avoid damage to the control panel and associated
equipment. FACP operation and reliability depend upon proper installation by
authorized personnel.
20
RE / DD / UM / MONITI V 1.0- 01
2.2
Panel Mounting
390.00 mm
17.00 mm
280.00 mm
295.00 mm
295.00 mm
17.00 mm
55.95 mm
345.00 mm
375.00 mm
Figure – 8
Remove all the Boards before placing the panel in its mounting position. Place
the panel in its mounting position and fix the panel to the wall using the slots of the
screws. Ensure the enclosure and the inner parts of the panel are given sufficient
protection during installation. Fix the all boards in its position (Refer Figure 18, 19 & 20).
All external cables are to be entered via 14 Numbers of 19mm preformed knockouts
located at top of the panel.
When the installation of all the cables has been completed, clean the interior of
the enclosure ensuring all masonry debris and drilling swords are removed.
2.3
Panel Wiring
21
RE / DD / UM / MONITI V 1.0- 01
Warning: Several different sources of power can be connected to this panel.
Disconnect all sources of power before servicing. The panel and associated
equipment may be damaged by removing and / or inserting cards, modules or
inter connecting while this unit is energized.
Primary Power source (AC) and Earth Ground Connections
AC Power connections are made inside the control panel cabinet. The Primary
source for the MONITI is 120/220 VAC, 60/50Hz, 2 Amps. Run a pair of wires with
Earth conductor from the protected premises main breaker box to connector (AC
Terminal) of the power supply board. As per National Electrical Code, use 14 AWG
(2.00 mm2, 1.6mm O.D) or heavier gauge wire with 600V insulation. No other
equipment may be connected to this circuit. In addition, this circuit must be
provided with over current protection and may not contain any power disconnect
devices. A separate Earth Ground connection must be made to ensure the proper
panel operation and lighting and transient protection. Connect the Earth Ground
wire (Min. 14AWG / 2.00 mm2) to the connector CN1.
Standby Power Source (Batteries)
Observe polarity when connecting the battery. Connect the battery cable to
connector CN2 on the Power Supply board (RE – MON – PS-R1) using the connector
and cable provided. The battery charger is current – limited and capable of
recharging sealed lead acid type batteries up to 40Ah.
During alarm condition, the charger section is disconnected from the battery hence
there will not be any charging at that time.
22
RE / DD / UM / MONITI V 1.0- 01
Power Supply Circuit Board (RAVEL RE – MON – PS-R1)
Primary Source
120/220 VAC
60/50 Hz
C2
E
N
P
120 / 220 VAC
F1
L1
Br1
U1
L3
U7
C28
Q1
U5
Q2
U6
CN 3
F3
CN 2
C11
C13
C10
Secondary Source
24 VDC
Figure – 9
23
RE / DD / UM / MONITI V 1.0- 01
32 pin FRC Cable
to Display Board
Power Limited
USB 2.0 Port
RS 485
Communication
Port
Power Limited
USB 2.0
A
B
RS 485 I/P
NC
U6
NO
C
FAULT- RLY3
Programmable Relay
1 & 2 and Fault Relay
NC NO C
Non-supervised
Power Limited
NC
U7
NO
C
PROG-RLY2
NC
NO
+
C
PROG-RLY1
_
+
DC O/P
Power Limited
24V DC O/P
F3
_
+
NAC O/P
F3
_
IN
+
_
LOOP
OU T
Power Limited
24V NAC
Output
+
20 pin FRC Cable
from PS Board
Power Limited
SLC Loop Terminals
Master Board (RAVEL RE - MON – MB-R1)
Figure – 10
24
RE / DD / UM / MONITI V 1.0- 01
Field Wiring Diagram
A
RS 485
B
NC
Fault
Relay
NO
2 Programmable Potential Free Relays
For Fire, Fault, Supervisory Power
1 Fault Potential Free Relay
Limited outputs.
Contact Rating:
2.0A @ 30VDC
0.5A @ 125VAC
Power Factor: 1.0
C0
NC
Program.
Relay 2 NO
C0
NC
Program.
Relay 1 NO
C0
DC 24V
Output
(300mA)
NAC O/P
(1A)
Note:
All the field wiring circuits are
supervised
All the field wiring circuits are Power
limited except 120-220v A.C and
Battery.
_
+
_
EOL
+
Loop Card
_
IN
+
_
OUT
+
E
Signaling Line Circuit
Class A Style 5, 6 or 7 wiring
120 - 220V
N
AC Input
P
Figure – 11
2.4
Relays
The 2 Form – C programmable relays and 1 Fault Relay are provided in this FACP with
the contact rating for 2 Amps @ 30 VDC or 0.5 Amps @ 125 VAC (Resistive Only). The
default options for the Programmable Relay 1 as Fire and Relay 2 as Supervisory.
Fault Prog Prog
Rly Rly 2 Rly 1
Fault Prog Prog
Rly Rly 2 Rly 1
NC
NC
NO
CO
NC
NO
CO
NC
NO
CO
NO
CO
NC
NO
CO
NC
NO
CO
Relay contacts shown with power applied to
the panel active Fire or Fault or Supervisory
If the relay is configured as fault, then it will reverse
Relay contacts shown with power applied to
the panel no active Fire or Fault or Supervisory
If the relay is configured as fault, then it will reverse
Figure - 12
Note: The relay connections may be power limited or non – power limited, provided
that 0.25” spacing is maintained between conductors of power limited and non –
power limited circuits.
25
RE / DD / UM / MONITI V 1.0- 01
2.5
NACs
The one Class B Style Y, supervised NAC’s are provided with the current rating of 1
Amps. It gives the steady output for NACs (Notification Appliance Circuit) and
synchronizing module should be used for strobes.
EOL
+
_
Bell
+
Sounder
+
Sounder
+
NAC
Retain E.O.L Resistor 4K7 Ohms
for unused circuits
Figure – 13
NOTE:
For Synchronized ANSI Pattern Output External Synchronizing Module
to be used. Refer Chapter 8 for Compatible Devices.
2.6
Signaling Line Circuit (SLC)
No. of Loop Card
:
1
Type
:
Class A or Class B
Wire Size
:
2.5 sq. mm Max.
Loop Resistance
:
20 Ω Max.
Total No. of Devices
:
127 + 20 (Loop Sounders) Devices
Compatible Devices
:
Refer Chapter 8.
The SLC loop configurable for NFPA class A or Class B, provides with communication
to addressable detectors, monitor and control modules.
26
RE / DD / UM / MONITI V 1.0- 01
Class B SLC wiring
SLC wiring without Isolator
Figure - 14
27
RE / DD / UM / MONITI V 1.0- 01
1
2
3
4
RE-737MI
1
2
3
4
RE-737MI
1
2
3
4
RE-737MI
SLC wiring with Isolator
Two wire Addressable Detector
Addressable Modules
SLC Loops
FACP
Figure - 15
Class A SLC wiring
SLC wiring without Isolator
Figure - 16
28
RE / DD / UM / MONITI V 1.0- 01
SLC wiring with Isolator
IN
+
_
SLC Loops
FACP
Addressable Modules
+
OUT _
Figure - 17
29
RE / DD / UM / MONITI V 1.0- 01
2.7
Power-limited wiring requirements
The power limited and non-power limited circuit wiring must remain separated in
the cabinet. All power limited circuit wiring must remain at least 0.25” (6.35mm) away
from any other non- power limited circuit wiring and non-power limited circuit wiring
must enter and exit the cabinet through different knockouts and/or conduits as shown
in the figure - 7.
Chapter 3: Programming
3.1
programming Concept
Warnings: Before Programming
1.
2.
3.
4.
3.1.1
All applicable codes and standards should be considered when the programming
the control unit.
The Control Unit continues to monitor inputs circuits and devices and acts according
to the current program settings if and alarm is received while it is being
programmed.
Loading a new database erases the current database before loading the new
database. If the new database is not loaded after the erase, the panel will not
operate.
The Database must be completely loaded for it to be considered valid. The
program keeps track if the last database load was valid/complete or not. An invalid
database load disables the panel until a valid database load is done.
General Comments
Programming can be accomplished using the MONITI keypad or by connecting
an optional standard computer keyboard. The keyboard can be connected to the
USB 2.0 connector on the control panel main circuit board. The information presented
in this section refers to programming the MONITI via the onboard keypad.
3.1.2
User Programming
The MONITI is completely field programmable and requires no special software
skill. While programming the MONITI, the fire protection capabilities of the control
panel are enabled.
Site specific programming may be accomplished in following ways.


Auto programming Feature – This is a convenient method for the quickly
bringing the FACP addressable SLC devices online without the necessity of
programming each device individually. Refer to “Auto Learn” on the Page 19 for
a detailed description of Auto programming.
Manual Programming or editing, using the FACP keypad or a PC keypad
30
RE / DD / UM / MONITI V 1.0- 01

Off line programming and Editing feature allows creation and editing of site
specific custom programs using a windows based computer. For programs
requiring a large amount of data entry, this method may be preferred. AVANIRGS programming kit can be ordered for this purpose.
The system all normal screen will be displayed in a programmed system with no
active alarms, troubles or supervisory, as illustrated below.
To access the programming or view the status & history, press menu key, which is
shown in LCD as below.
DD/MM/YY
1. View
2. Program
3. About
<Panel Status>
HH:MM
[Main]
From this menu screen by pressing ‘1’, the panel enters into status/history view
mode. It allows user to view the event and program setting of the control panel. The
password is not required for this feature.
From this menu screen by pressing ‘2’, the panel enters into programming mode
which only can access by the authorized persons. After pressing ‘2’, LCD screen will be
in password prompt. After pressing correct password and by pressing enter key, user
can select the programming options to change it.
From this menu screen by pressing ‘3’, the panel shows the about the version
and revision levels.
Exit from view & Program Mode
The programmer can exit from the view / Program mode by pressing ‘*’key
repeatedly until the “System Healthy” screen.
3.1.3
Initial Power up
Here the initial programming procedure for a new system is described. The same
procedure is used for modify the programming settings in existing system.
After completing the wiring of the addressable devices to the SLC, apply power
to the control panel. If the addressable devices are not programmed in the Fire Alarm
Panel, the following trouble message will be displayed.
31
RE / DD / UM / MONITI V 1.0- 01
3.1.4
Programming Description
By pressing menu key, the view and program options have multiple functions or
features which may be chosen. To view all of the choices, it is necessary that the
programmer scroll through a number of the additional screen and cursor keys. Refer
“Programming Instruction”, for additional information of the various screens.
The title of the main option screen will always be displayed at bottom right of the subscreens. To select the one of the choices in a screen, the programmer presses the
keypad numerical key corresponding to the desired choice.
Note: That sub-screen may also have multiple options which require viewing more
than one screen. The same process, as detailed in the previous paragraph is followed
to view all options.
3.1.5
Programming Password
There is a factory set password which will access the programming screens as
indicated in the following examples. From either of the screens, access to specific
system and device feature or programming may be obtained. All user programming
and entries are stored in the nonvolatile memory. The factory set password can be
changed by user. Refer “Password Change” for additional information.
32
RE / DD / UM / MONITI V 1.0- 01
Programming Instruction
3.1.6
Menu Key Flow Diagram
33
RE / DD / UM / MONITI V 1.0- 01
MENU KEY - FLOW DIAGRAM
DEFAULT PASSWORD
ME NU
2
1
VIEW
2
3
HH:MM
[View ]
DD/MM/YY
<Panel Status>
HH:MM
1. PreAlarm
2. Supervisor y
3. Faults
[Suppress ed Events ]
DD/MM/YY
1. A ll
2. A larm
3. Delete
<Panel Status>
HH:MM
DD/MM/YY
1. System
2. LoopCard
3. Grouping
3
HH:MM
About
<Panel Status>
4. Features
DD/MM/Y Y
1. Settings
2. Relay O/P
3. Advanced
1
HH:MM
3
<Panel Status>
<Panel Status>
HH:MM
Addres sable Fire Alarm Control Panel
Ravel, MonitI 1.0
[About]
HH:MM
A
[Sys tem]
DD/MM/YY
<Panel Status>
1. Zone
2. Logic Input
3. Logic Output
[LC1]
DD/MM/YY
[Program]
DD/MM/YY
<Panel Status>
0. AutoLaearn
3. Devic es
1. Status : Enabled
2. Style : Class B
2
[History]
DD/MM/YY
<Panel Status>
Status: Enabled
Style : Class B
1. Devices
ADM IN
PASSW ORD R EQUIRED
(De fa ult: 5432 1)
PRO GRAM
DD/MM/YY
<Panel Status>
1. Suppress ed Events 4. Grouping
2. HISTORY
3. Loop Card
1
USER - 1234
ADM IN - 54321
Insta l l er - 65432 1
HH:MM
B
[LC]
Us e
Ke y to ch ange the
Opti ons , Enable d & Dis ab le d
HH:MM
C
[Grouping]
DD/MM/YY
<Panel Status>
HH:MM
AC Loss Delay
Disabled
[Featur es1]
4
Us e
4
DD/MM/YY
1. Zone
2. Logic Input
3. Logic Output
Fault [ XX]
HH:MM
[Grouping]
DD/MM/YY
Ke y to go the
Fe ature
<Panel Status>
HH:MM
DD/MM/YY
EVENT
[Suppressed Condition]
MCP MZ MM MC MX OP ML HT MR LS
0
0
0
0
0
0 0 0 0 0
NOD : X/147 Disabled :Y
1. Device Program
[LC1]
DD/MM/YY
<Panel Status>
Ev t No: XXX/ZZZ
Ev ents : Event
Date: dd/mm/yy Time: hh:mm:ss
DD/MM/YY
<Panel Status>
HH:MM
Status: Enabled
Sense : Medi
Type : Sw itch
Mode : Day
Blink : Enabled
1. Location [LC1 DXXX]
HH:MM
<Panel Status>
Trouble Remainder
Disabled
DD/MM/YY
[History ]
DD/MM/YY
DD/MM/Y Y
HH:MM
[Features2]
<Panel Status>
HH:MM
Auto Silence
Disabled
[Featur es3]
<Panel Status>
HH:MM
Silence Inhibit
Disabled
[Features4]
<Panel Status >
HH:MM
Earth Fault Detection
Disabled
[Features5]
34
RE / DD / UM / MONITI V 1.0- 01
MENU KEY - FLOW DIAGRAM
A
1
DD/MM/YY
<Panel Status>
1. Date & Time
4. Night Mode
2. Caption
3. Passw or d
HH:MM
DD/MM/YY
1. Daily D/N
2. WeekEnd
3. Holiday
HH:MM
F
[Night Mode]
4
[Settings]
2
1
DD/MM/YY
<Panel Status>
HH:MM
Date : DD / MM / YY
Time : HH : MM : SS
2
<Panel Status>
(#.Edit)
[RTC]
DD/MM/YY
<Panel Status>
1. Relay 1 : Fire
2. Relay 2 : Supervis ory
HH:MM
3
DD/MM/YY
<Panel Status>
Caption:
Ravel Elec tronics
DD/MM/YY
1
HH:MM
DD/MM/YY
1. User 1
2. User 2
3. User 3
(#.Edit)
[Caption]
<Panel Status>
<Panel Status>
4. User 4
5. User 5
6. Admin
HH:MM
[Pas sw ord]
HH:MM
Us e
Ke y to change th e
Opt ions , Fire ,
Supe rvis ory, Pre -A larm
Type : << Fire>>
[Relay O/P1]
[Relay O/P]
DD/MM/YY
<Panel Status>
HH:MM
Type : << Supervisory>>
[Relay O/P2]
2
DD/MM/YY
<Panel Status>
HH:MM
Old Passw ord ?
[Chg Us er X Pass]
3
DD/MM/YY
<Panel Status>
HH:MM
Passw ord?
[Passw ord]
DD/MM/YY
<Panel Status>
HH:MM
1. Slav e Config
4. Soft Addres s
2. Change AdvPass
3. Fac toryDefault
[Settings]
G
User X / Chg AdmPass
DD/MM/YY
<Panel Status>
HH:MM
New Pas sw ord Updated
[Chg User X Pass]
DD/MM/YY
<Panel Status>
HH:MM
Re-New Pass w ord ?
[Chg User X Pass]
DD/MM/YY
<Panel Status>
HH:MM
New Pas sw ord ?
[Chg User X Pass]
X=1-5
35
RE / DD / UM / MONITI V 1.0- 01
MENU KEY - FLOW DIAGRAM
F
1
DD/MM/YY
< Panel Stat us>
1. Sta tus
: D isabled
2. Start Time : HH:MM
3. End Time : HH:M M
HH:M M
3
<Panel Status>
[Day/Night]
2
<Panel Status>
HH:MM
DD/MM/YY
<Panel Status>
[Day /Night]
[Day/Night]
DD/MM/YY
1. Sta tus
2. Day 1
3. Day 2
<Panel Status>
HH:M M
3
: D isabled
DD/MM/YY
[WeekEnd]
2
<Panel Status>
HH:MM
DD/MM/YY
<Panel Status>
<Panel Status>
: Disabled
HH:MM
Day 1 : << Friday >>
[WeekEnd]
3
HH:MM
[W eekEnd]
Status : << Disabled>>
DD/MM/YY
1. Status
2. List
<Panel Status>
Day 2 : << Sunday>>
: XXX
: XXX
1
DD/MM/Y Y
HH:MM
Start HR ?
Status : << Disabled>>
2
HH:MM
End HR ?
[Day/ Night]
1
DD/MM/YY
DD/MM/YY
HH:MM
[WeekEnd]
2
DD/MM/YY
<Panel Status>
HH:MM
[0.Add]
[HD List]
[Holiday]
1
DD/MM/Y Y
<Panel Status>
HH:MM
Status : << Disabled>>
[Holiday]
36
RE / DD / UM / MONITI V 1.0- 01
MENU KEY - FLOW DIAGRAM
G
DD/MM/YY
DD/MM/YY
P. No: 1 2
Stat : D D
HH:MM
N/W A ddr?
1
1
<Panel Status>
2
[N/W Addr]
<Panel Status>
3 4
5
6
D D
D
D
3
3
DD/MM/Y Y
<Panel Status >
HH:MM
1. N/W A ddr : X X
4. Master Evacuate
2. Netw ork Status
5. Netw ork Sync
3. Master Silence
6. N/W O/P Config [N/W]
HH:MM
7
8
D
D
[N/W PNL]
DD/MM/YY
<Panel Status>
1. Send : Disable
2. Accept : Disable
HH:MM
[MstSil]
4
DD/MM/YY
<Panel Status>
1. Send : Disable
2. A ccept : Disable
HH:MM
[MstEvac ]
DD/MM/YY
5
2
Same as done in User and Admin passw ord
Change
3
DD/MM/Y Y
<Panel Status >
HH:MM
Warning !
All Configuration Changes get lost
(
. Continue)
(#. Canc el)
HH:MM
Netw ork Sync hronized
[NetSync ]
DD/MM/YY
<Panel Status>
HH:MM
1. Fire O/P : Disabled 4. NAC's : Disabled
2. Fault O/P : Disabled
3. Suprv O/P : Disabled
[N/W O/P]
6
Fac tory Default
Recover ing .....
<Panel Status>
DD/MM/YY
<Panel Status>
1. Read A ddress
2. Write A ddress
3. LED ON/OFF
1
DD/MM/YY
HH:MM
[Soft Addr]
<Panel Status>
HH:MM
Reading....
DD/MM/YY
4
DD/MM/Y Y
<Panel Status >
<Panel Status>
HH:MM
Dev ice Address: XXX
HH:MM
Compatible : << RAVEL >>
[Active LCs]
2
DD/MM/Y Y
<Panel Status>
HH:MM
Enter Address ?
Wait .....
[Enter Addr]
DD/MM/YY
5
DD/MM/YY
<Panel Status>
HH:MM
Warning! Connect One Device at a Time!
Ensure A ddressing Device Only Connec ted!
(
. Y es)
(#. No)
<Panel Status>
HH:MM
Enter Address? XXX
[Enter A ddr]
3
37
RE / DD / UM / MONITI V 1.0- 01
MENU KEY - FLOW DIAGRAM
B
DD/MM/YY
<Panel Status>
HH:MM
0. A uto Learn
3. Devices
1. Status : Enabled
2. Style : ClassB
[LC X]
MCP MZ MM MC MX OP ML HT MR LS
A
B
C
D
E F G H I
J
0
Auto Learning .....
Total Devic es : XXX
1
DD/MM/YY
<Panel Status>
[AutoLearn]
HH:MM
Us e
Ke y to chang e the
Options , Enable d & Dis able d
Status : << Enabled >>
[LC X]
DD/MM/YY
<Panel Status>
HH:MM
2
Us e
Ke y to change t he
Option s , Clas s B & Clas s A
Style : << Class B >>
[LC X]
3
MCP MZ MM MC MX OP ML HT MR LS
A
B
C
D
E
F G H I
J
NOD : XXX / 147 Disabled : YYY
1. Devices Program
[LC 1]
DD/MM/YY
<Panel Status>
HH:MM
1. Status : Enabled 4. Sense : Medi [0.jmp]
2. Type : aaaaaa
5. Mode : Day
[#.Del]
3. Location
[LC X DY YY]
DD/MM/YY
<Panel Status>
Empty
HH:MM
[0.jmp]
[#.Add]
[LC X DYYY ]
aaaaaa - Type of devices ; X - Loop card Number ; YY Y - Address of dev ices
1
DD/MM/YY
<Panel Status>
HH:MM
Status : << Enabled >>
[LC X DYYY*]
2
DD/MM/YY
<Panel Status>
HH:MM
Type : aaaaaa
[LC X DYYY]
3
DD/MM/YY
Location :
<Panel Status>
4
Us e
Ke y to c hange th e
Op tions , Ena ble d & Dis able d
DD/MM/YY
<Panel Status>
HH:MM
Sense :<< Medi >>
[LC X DYY Y]
Us e
Ke y to c hange th e
Opt ions for t ype s of
the de vi ce s
5
DD/MM/YY
<Panel Status>
Us e
Ke y to c hange th e
Options , Low , M e dium & High
HH:MM
Us e
Ke y to c hange th e
Opt ions , Day & Night
Mode :<< Day >>
[LC X DYY Y]
HH:MM
(#. Edit)
[LC X DYYY]
38
RE / DD / UM / MONITI V 1.0- 01
MENU KEY - FLOW DIAGRAM
C
1
DD/MM/Y Y
HH:MM
[0.jmp]
[ #.Add]
[ZGX]
Empty
#
DD/MM/YY
DD/MM/YY
<Panel Status>
DD/MM/YY
<Panel Status>
1. Devices
2. Active Count: CC
1
HH:MM
DD/MM/YY
<Panel St atus>
2
HH:MM
<Panel St atus>
DD/MM/YY
HH:MM
[0.jmp]
[#.Add]
[OGX]
HH:MM
<Panel Status>
HH:MM
<Panel Status>
Us e
#
DD/MM/YY
<Panel Status>
1. Devices
4. OG Act: Fire
2. Logic: LL
5. Delay: 000(Sec)
3. Stat: Enabled
1
DD/MM/YY
HH:MM
Empty
2
DD/MM/YY
[#.Edit]
[ OGX* Devs ]
HH:MM
Logic : LL
[OGX* Logic]
Us e
#
HH:MM
<Panel Status>
CC
[LGX* ActCnt ]
Ke y t o change the
Coun t 0 - 16
3
<Panel Status >
HH:MM
[0.jmp]
[#.Del]
[OGX*]
<Panel Status>
[#.Edit ]
[LGX* Devs ]
Activ e Count :
DD/MM/Y Y
1. Add
2. Delete
DD/MM/YY
1. Devices
<Panel Status>
Empty
HH:MM
[0.jmp]
[#.Del]
[LGX*]
Empt y
[Z GX* Devs]
1
DD/MM/YY
<Panel Status>
[#.Edit]
[Z GX* Devs]
PreAlarm : << Disabled>>
[PreAlarm]
DD/MM/YY
1. A dd
2. Delete
HH:MM
[0.jmp]
[#. Add]
[LGX]
Empty
HH:MM
[0.jmp]
[#.Del]
[ZGX]
<Panel Status>
Empty
2
DD/MM/YY
X - Gr o up Num b e r
DD/MM/YY
<Panel Status>
1.Devices
2. PreAlarm: Disabled
1
3
2
<Panel Status >
DD/ MM/YY
HH:MM
Ke y to change the
Logic 0 - 6 4
<Panel Status>
HH:MM
Status : << Enabled >>
[OGX* Status]
[LGX* Devs]
HH:MM
4
[ZGX* Add]
1
1
DD/MM/YY
1. Devices
2. Logic
<Panel Stat us>
DD/MM/YY
HH:MM
<Panel Status>
HH:MM
Output Group A ct : << Fire>>
[OGX* Act]
[LGX* Add]
DD/MM/YY
<Panel Status>
HH:MM
1
LC
Device
: AA
: DBBB
[
. Add]
[ZGX* Dev s]
DD/MM/YY
LC
Devic e
2
DD/MM/YY
1. Devices
<Panel Status>
DD/MM/Y Y
<Panel Status>
: AA
: DBBB
DD/MM/YY
<Panel Status>
<Panel Status >
HH:MM
2
DD/MM/Y Y
1. Add
2. Delete
[
. Add]
[LGX* Devs]
<Panel Status>
[
. Del]
[ZGX* Dev s]
2
DD/MM/YY
1. Devices
2. Logic
<Panel Stat us>
[LGX* Devs]
HH:MM
1
DD/MM/Y Y
1. Devices
<Panel Status>
<Panel Status>
: AA
: DBBB
HH:MM
[OGX* Add]
1
2
LC
Devic e
HH:MM
HH:MM
[LGX* Del]
DD/MM/YY
HH:MM
OG Delay: 000 (Sec)
[OGX* Delay]
[
. Add]
[LGX* Devs]
Logic
No :LDD
1
LC
Device
: AA
: DBBB
5
HH:MM
HH:MM
[ZGX* Del]
DD/MM/YY
<Panel Stat us>
HH:MM
[
. Del]
[LGX* Devs]
DD/MM/YY
<Panel Status>
Logic
No :LDD
DD/MM/YY
LC
Device
DD/MM/Y Y
HH:MM
LC
Device
[
. Del]
[ LGX* Devs ]
<Panel Status>
: AA
: DBBB
HH:MM
[
. Del]
[ OGX* Dev s]
39
2
<Panel Status >
: AA
: DBBB
DD/MM/Y Y
1. Devices
<Panel Status>
HH:MM
[
. Add]
[OGX* Devs]
HH:MM
[OGX* Del]
RE / DD / UM / MONITI V 1.0- 01
E
MENU KEY - FLOW DIAGRAM
DD/MM/YY
<Panel Status>
1. Lamp Test
4. Input Test
2. Output Test
5. Zone Test
3. Device Tes t
2
1
HH:MM
Al l LED W i ll
Glow
[Test]
DD/MM/YY
HH:MM
Outp ut Group XX Activated
O /P Grou p No?
ADM IN
PASSW ORD REQ UIRED
(Defa ul t: 54321)
3
DD/MM/YY
HH:MM
Device XX Test Activated
Device No?
4
5
DD/MM/YY
<Panel Status>
HH:MM
Total I/P Devices(s) Tested: XX
Test Pas s : PP
Tes t Fail : FF
0. Fail List
[Tes t]
Input Device
Auto Testing...
DD/MM/YY
HH:MM
Zone Group X
Auto Testing
Zone Group No?
DD/MM/YY
<Panel Status>
HH:MM
Total Devices (s) Tested: XX
Test Pas s : PP
Tes t Fail : FF
0. Fail List
[Tes t]
40
RE / DD / UM / MONITI V 1.0- 01
3.1.7
Main Menu
The MENU key navigates the user to view & Edit Loop Card specific
settings, Device specific settings, etc. It also possesses help menu for About and
Functional details. By Selecting Menu key the display shows the options as like
below,
DD/MM/YY
<Panel Status>
HH:MM
1. View
2. Program
3. About
3.1.7.1
[Main]
View
View Option can be accessible by User. By this option user can view
the past history and exiting configuration, however they cannot change
preserved settings. By selecting ‘1’ when in Main menu, the system enters
into View mode and shows the viewing category options as like below,
DD/MM/YY
<Panel Status>
1. Suppressed Events
4. Grouping
2. History
3. LoopCard
3.1.7.1.1
HH:MM
[View]
Suppressed Events
Suppressed Events option is used to view the suppressed events
during Fire condition. The suppressed events like Prealarm, Supervisory and
faults events can be viewed from this menu using corresponding number
keys. By selecting ‘1’ from view menu brings the suppressed events and
shows the suppressed events category options as like below.
DD/MM/YY
1. PreAlarm
2. Supervisory
3. Faults
3.1.7.1.2
<Panel Status>
HH:MM
[Suppressed Events]
History
History option is used to view the past panel event logs such
as Alarm, Supervisory, Fault, Silence Reset and etc., with Real Time
Clock. By pressing the key ‘2’ from View menu brings the History
mode. The history mode provides the following event filtering
option,
41
RE / DD / UM / MONITI V 1.0- 01
DD/MM/YY
1. All
2. Alarm
3. Delete
<Panel Status>
HH:MM
[View]
By selecting a number from the list in the history menu,
respected subject relevant logs alone displayed in the screen as like
below,
DD/MM/YY
<Panel Status>
Evt No: abcd / ABCD
Event : Type of Event
Date: dd/mm/yy
Time: hh:mm:ss
3.1.7.1.3
HH:MM
[View]
Loop Card
In order to view the loop card specific settings (such as wiring
style, no. of devices, status) the user need to press ‘3’ from the
View Menu. The loop card details can be viewed by pressing
corresponding loop card number and screen as shown
below.
DD/MM/YY
Status : Enabled
Style : ClassB
1. Devices
<Panel Status>
HH:MM
[LC1]
It also possesses the options to view Device Specific Settings.
By selecting a number from the list in the Loop card menu,
respected subject relevant configuration alone displayed in
the screen as like below,
MCP MZ MM MC MX OP ML HT MR LS
0
0
0
0
0
0
0
0 0
0
NOD : 0/147 Disabled : 0
1. View Devices
42
RE / DD / UM / MONITI V 1.0- 01
3.1.7.1.4
Grouping
By selecting number 4 from view menu, user can view the all
types of grouping and grouped devices in each groups. The
grouping menu screen is as shown below.
DD/MM/YY
1. Zone
2. Logic Input
3. Logic Output
3.1.7.2
Fault [ XX]
HH:MM
[Grouping]
Program
By selecting the number 2 from the main menu screen, the system
enters into program mode. This mode is protected by password and it
requires admin password (Default – 54321). In this mode, the panel loop
card configuration, RTC & password settings, to alter the optional features
and to reset the panel for factory default setting. After entering into the
view mode, screen will be as below.
DD/MM/YY
1. System
2. LoopCard
3. Grouping
<Panel Status>
4. Features
HH:MM
[program]
3.1.7.2.1
System
By selecting the number 1 from the program screen, the system
enters into panel’s configuration mode. In this mode, panel settings (RTC,
Caption, Password), relay output configuration and advanced Feature
configuration will be done. After entering into this mode, screen will be as
below.
DD/MM/YY
1. Settings
2. Relay O/P
3. Advanced
<Panel Status>
HH:MM
[System]
43
RE / DD / UM / MONITI V 1.0- 01
3.1.7.2.1.1
Settings
By selecting the number 1 from the System screen, the system
enters into panel settings mode. In this mode, Date & Time, caption,
Password and night mode are changed by entering into the
corresponding menu. After entering into this mode, screen will be as
below.
DD/MM/YY
1. Date&Time
2. Caption
3. Password
<Panel Status>
4. Night Mode
HH:MM
[Settings]
By selecting a number from the list in the system menu,
respected subject relevant configuration alone displayed.
3.1.7.2.1.1.1 Date & Time
By selecting the number 1 from the setting screen, the system
enters into RTC settings mode. In this mode, time and date settings
are changed by using ‘#’ key. After entering into this mode, screen
will be as below.
DD/MM/YY
<Panel Status>
Date : DD/MM/YY
Time : HH/MM/SS
HH:MM
[System]
3.1.7.2.1.1.2 Caption
By selecting the number 2 from the setting screen, the system
enters into Caption editing mode. In this mode, caption is changed
by using ‘#’ key, maximum 20 characters can entered which will be
display in front screen in system healthy mode. After entering into
this mode, screen will be as below.
DD/MM/YY
Caption:
Ravel Electronics
<Panel Status>
HH:MM
(#.Edit)
[Caption]
44
RE / DD / UM / MONITI V 1.0- 01
3.1.7.2.1.1.3 Password
By selecting the number 3 from the setting screen, the system
enters into password change mode. In this mode, the user 1 to 5
and admin password can be changed by selecting corresponding
number, after entering into this mode, screen will be as below.
DD/MM/YY
1. U ser 1
2. U ser 2
3. User 3
<Panel Status>
4. User 4
5. User 5
6. Admin
HH:MM
[Chg Pass]
After selecting corresponding number, password changing
screen as follows:
DD/MM/YY
<Panel Status>
Old Password?
HH:MM
[Chg XXX Pass]
XXX – User 1/2/3/4/5/admin
DD/MM/YY
<Panel Status>
New Password?
DD/MM/YY
[Chg XXX Pass]
<Panel Status>
Re-New Password?
DD/MM/YY
HH:MM
<Panel Status>
HH:MM
[Chg XXX Pass]
HH:MM
New Password Updated
[Chg XXX Pass]
45
RE / DD / UM / MONITI V 1.0- 01
3.1.7.2.1.1.4 Night Mode
By selecting the number 4 from the setting screen, the system enters
into night mode configuration. In this mode, the daily day/night time,
week end day and holidays list can be configured, after entering into this
mode, screen will be as below.
DD/MM/YY
1. Daily D/N
2. WeekEnd
3. Holiday
<Panel Status>
HH:MM
[NightMode]
3.1.7.2.1.1.4.1
Daily D/N
By selecting the number 1 from the night mode screen, the
system enters into Daily Day /night time and status configuration mode.
In this mode, the daily day/night time and status can be configured,
after entering into this mode, screen will be as below.
DD/MM/YY
<Panel Status>
1. Status
: Disabled
2. Start Time : HH:MM
3. End Time : HH:MM
HH:MM
[Day/Night]
The status can be changed by using appropriate number from
keypad and by using up & down cursor keys. Similarly the day / night
start and end time can be changed by selecting number 2 &3 from
the DayNight mode.
3.1.7.2.1.1.4.2
WeekEnd
By selecting the number 2 from the night mode screen, the
system enters into week end day and status configuration mode. In this
mode, the week end day and status can be configured, after entering
into this mode, screen will be as below.
DD/MM/YY
<Panel Status>
1. Status
: Disabled
2. Day 1
: FRI
3. Day 1
: SAT
46
HH:MM
[WeekEnd]
RE / DD / UM / MONITI V 1.0- 01
3.1.7.2.1.1.4.3
Holiday
By selecting the number 3 from the night mode screen, the
system enters into Holiday list and status configuration mode. In this
mode, the holiday list and status can be configured, after entering into
this mode, screen will be as below.
DD/MM/YY
<Panel Status>
1. Status
: Disabled
2. List
HH:MM
[Holiday]
Dates of holidays can be listed by selecting 2 from the Holiday
screen. These lists can be enabled / disabled by selecting 1 from the
holiday screen using up & down cursor keys.
3.1.7.2.1.2 Relay OP
By selecting the number ‘2’ from the system screen, the system
enters into the programmable relay output configuration mode. In this
mode, by choosing corresponding number to the corresponding relay
output can be configured as Fire, Supervisory and PreAlarm. After
entering into this mode, screen will be as below.
DD/MM/YY
<Panel Status>
1. Relay 1 : Fire
2. Relay 2 : Supervisory
HH:MM
[Relay OP]
By selecting corresponding number, the relay output options can
be changed using the up & down ‘▲▼’ cursor keys.
3.1.7.2.1.3
Advanced
By selecting the number ‘3’ from the system screen, the
system enters into advanced settings mode. It required the
Configuration (Advanced) password. In this mode, the system up
gradation like adding network Configuration for Repeater,
changing the configuration password, factory resetting and Soft
Addressing can be done. The default Configuration password is
“654321”. After entering into this mode, screen will be as below.
47
RE / DD / UM / MONITI V 1.0- 01
DD/MM/YY
<Panel Status>
HH:MM:SS
1. Network
4. Compatible : RAVEL
2. Change AdvPass 5. Soft Address
3. FactoryDefault
[Advanced]
3.1.7.2.1.3.1
Network:
By selecting the number 1 from the advanced menu screen,
the system enters into the slave configuration mode. In this mode
the slave address configuration and its status shall be viewed. After
entering into this mode, screen will be as below.
DD/MM/YY
<Panel Status>
HH:MM:SS
1. N/W Addr : X X
4. Master Evacuate
2. Network Status
5. Network Sync
3. Master Silence
6. N/W O/P Config [N/W]
3.1.7.2.1.3.2
Changing Advanced Password:
By selecting the number 2 from the advanced screen, the
system enters into the advanced password change mode. The
procedure for changing the password is similar to the user/admin
password changing method. After entering into this mode, screen
will be as below.
DD/MM/YY
<Panel Status>
Old Password ?
3.1.7.2.1.3.3
HH:MM
[ChgAdvPass]
Factory Default:
By selecting the number 3 from the advanced screen, the system
enters into the factory default setting mode. In this mode, it gives the
warning screen before changing configuration. After entering into this
mode, screen will be as below.
DD/MM/YY
<Panel Status>
HH:MM
Warning!
All Configuration Changes get lost
( . Continue)
(#. Cancel)
48
RE / DD / UM / MONITI V 1.0- 01
3.1.7.2.1.3.4
Soft Addressing:
By selecting the number 4 from the advanced menu /
screen, the system enters into the device soft addressing mode.
From this menu address of the initiating devices & output devices
shall be programmed. Only one device has to connect with the
SLC loop for addressing that device and after address written on
the device, device ID will be automatically incremented to next
address. From this menu you can read / write the address of the
connected device and LED on/off control shall be done. After
entering into this menu, screen will be as below.
DD/MM/YY
1. Read Address
2. Write Address
3. LED ON/OFF
3.1.7.2.2
<Panel Status>
HH:MM
[Soft Addr]
Loop Card
By selecting the number 2 from the program screen, the
system enters into loop card settings mode. After entering into this
mode, screen will be as below.
DD/MM/YY
0. AutoLearn
1. Status : Enabled
2. Style : ClassB
<Panel Status>
3. Devices
HH:MM
[LC]
To view and change loop card configurations can
configured from this menu. Auto Learning, configuration like style,
enabled/disabled and devices is done. Also the devices can be
added manually through the devices menu.
From this menu, required field is configured by pressing
corresponding number from the key pad.
49
RE / DD / UM / MONITI V 1.0- 01
3.1.7.2.2.1
Auto Learn
Auto Learning is done pressing the key ‘0’ from the selected
loop card screen. Auto learn is used to learn type of all the
devices connected in the loop card and gives the details about
devices and total number of devices connected in the loop card.
Ravel Protocol - After scanning the LCD Screen shown as
below.
MCP MZ MM MC MX OP ML HT MR LS
A
B
C
D
E
F
G H I
J
NOD : XXX / 147 Disabled : YYY
1. Devices Program
[LC 1]
Where XXX – Total number of device;
YYY – Total number of disabled devices;
A – Total number of Manual Call Point;
B – Total number of Zone module;
C – Total number of Switch monitor module
D – Total number of Control Module;
E – Total number of Input-Output Module;
F – Total number of Optical Detectors;
G – Total number of Multipoint Detectors;
H – Total number of Heat Detectors;
I – Total number of Relay Module;
J – Total number of Loop powered Sounder;
3.1.7.2.2.2
Status
The status is nothing but the loop card disabled / enabled.
The status of the loop card is change is done by selecting the
number ‘1’ from the loop card menu list. After entering into the
change mode, up & down cursor key is used to change the
options and press the enter key to accept the changes. The ‘n’
represents nth loop card.
DD/MM/YY
<Panel Status>
Status : << Enabled >>
3.1.7.2.2.3
HH:MM
[LC'n']
Style
By selecting the number 2 from the loop card screen, the
system enters into loop card style configuration mode. Type of
50
RE / DD / UM / MONITI V 1.0- 01
style Class A or Class B can select by using the up & down cursor
keys. After selecting the required style press ‘enter’ key to conform
the selection.
DD/MM/YY
<Panel Status>
Style : << ClassB >>
3.1.7.2.2.4
HH:MM
[LC'n']
Device
By selecting the number 3 from the loop card screen, the
system shows the number of detectors and modules are
connected in the system. Also from this menu detector and
module programming can done by pressing corresponding
number.
Ravel Screen:
MCP MZ MM MC MX OP ML HT MR LS
A
B
C
D
E
F G
H I
J
NOD : XXX / 147 Disabled : YYY
1. Devices Program
[LC 1]
3.1.7.2.2.4.1
Detector Program
From this menu, if the auto learning is not done then, the
individual detectors status, type, sense, mode and location can
be configured manually by selecting the corresponding number
form the numerical keypad. Detector address is shown at right
bottom of the screen and detector address is selected by using
the left/Right cursor keys. The options are changed by using the
up/down cursor keys.
DD/MM/YY
1. Status : Enabled
2. Type : Optical
3. Locations
<Panel Status>
4. Sense : Low
5. Mode : Day
HH:MM
[#. Del]
[LC1 D001*]
Options are:
1.
2.
3.
4.
Status : Enabled / Disabled
Type : Optical / Multi / Heat
Location – Detector Location
Sense : Low / Medium / High (Detector Sensitivity)
51
RE / DD / UM / MONITI V 1.0- 01
5. Mode : Day / Night
3.1.7.2.2.4.2
Module Program
From this menu, if the auto learning is not done then, the
individual modules status, type, category and location can be
configured manually by selecting the corresponding number form
the numerical keypad. Module address with loop card number is
shown at right bottom of the screen and module address is
selected by using the left/Right cursor keys. The options are
changed by using the up/down cursor keys.
DD/MM/YY
1. Status : Enabled
2. Type : MM
3. Location
<Panel Status>
4. IP
: Alrm
HH:MM
[#. Del]
[LC1 M001*]
Options are:
1.
2.
3.
4.
5.
6.
3.1.7.2.3
Status : Enabled / Disabled
Type : IP_M / OP_M / IO_M
Location – Module Location
IP: Alarm / Supervisory
Cat : Control / Relay / Others (Module Category)
DeAct: Rst (Reset) / Sil (Silence). (Selection
Deactivation of the device during silence / reset)
for
Grouping
By selecting the number 3 from the program screen, the
system enters into Group Setting mode. This mode is used to
combine the number of devices as a zone / Logic / Output group.
After entering into this mode, screen will be as below.
DD/MM/YY
1. Zone
2. Logic Input
3. Logic Output
<Panel Status>
HH:MM:SS
[Grouping]
52
RE / DD / UM / MONITI V 1.0- 01
Zone Grouping
By selecting the number 1 from the grouping screen, the
system enters into the zone grouping mode. In this grouping
maximum 64 zone can group with maximum 16 devices can add in
each zone group. After entering into this mode, screen will be as
below.
DD/MM/YY
<Panel Status>
Empty
HH:MM
[#.Add]
[ZG1]
After adding the zone group screen shows as below and
device can added by selecting number 1 from Zone group 1
screen.
DD/MM/YY
<Panel Status>
1. Devices
2. PreAlarm : Disabled
HH:MM
[0.Jmp]
[#.Del]
[ZG1]
In zone grouping the pre-alarm is enabled. Then first detector
is sensed fire, panel will not trigger NAC’s and on second detector is
sensed fire then panel will trigger the NAC’s and shows as alarm.
Logic Input Grouping
By selecting the number 2 from the grouping screen, the
system enters into the logic grouping mode. This mode is used to
give the output to the output device through the output grouping.
After entering into this mode, screen will be as below.
DD/MM/YY
<Panel Status>
Empty
HH:MM
[0. Jmp]
[#.Add]
[LG1]
After adding the logic group, screen shows as. Devices shall
be added using the sub menu ‘1’. Depending upon the active
counter the logic gives the output.
53
RE / DD / UM / MONITI V 1.0- 01
DD/MM/YY
1. Devices
2. Active Count: 1
<Panel Status>
HH:MM
[0. Jmp]
[#.Del]
[LG1]
For example, the 10 devices are added in the devices and
logic count is entered as ‘4’, then 4 out of 10 devices gets fire then
only the logic gives the output.
DD/MM/YY
<Panel Status>
Empty
HH:MM
[#.Edit]
[LG1* Devs]
By Pressing ‘#’ key it enters into add / delete menu. In device
sub menu, the adding devices and deleting devices shall be done.
Device shall add using the sub menu ‘1’ and delete by ‘2’. After
entering into the add/ delete menu devices will be shown in last line
by pressing ‘Enter’ key, the devices shall be add/delete.
DD/MM/YY
1. Add
2. Delete
<Panel Status>
HH:MM
[#.Del]
[LG1 Devs]
If there is no devices in the loop, it shows in display as “No
More I/P Device” otherwise as shown below.
DD/MM/YY
<Panel Status>
LC
: NN
Devices : DXX
HH:MM
[0. Mdle]
[
.Add]
[LG1* Devs]
NN – Loop card number; DXX – Detector address; MXX – Module
Address. Similarly for deleting the devices.
Logic Output Grouping
By selecting the number 3 from the grouping screen, the
system enters into the output grouping mode. This mode is used to
turn on the output devices with respect to the logic. After entering
into this mode, screen will be as below.
54
RE / DD / UM / MONITI V 1.0- 01
DD/MM/YY
<Panel Status>
Empty
HH:MM
[0. Jmp]
[#.Add]
[OG1]
After adding the output group, screen shows as below.
Devices shall be added using the sub menu ‘1’. Depending upon
the Logic number the output devices which are all grouped gets
on.
For example, the 10 devices are added in the devices and
Logic is entered as ‘4’, then the devices added in the group will turn
on for the logic 4 only.
DD/MM/YY
1. Devices
2. Logic: 0
<Panel Status>
HH:MM
[0. Jmp]
[#.Del]
[OG1*]
By pressing the ‘1’ the screen shown as below.
DD/MM/YY
<Panel Status>
Empty
HH:MM
[#.Edit]
[OG1* Devs]
By Pressing ‘#’ key it enters into the add / delete menu. In
device sub menu, the adding devices and deleting devices shall be
done. Device shall add using the sub menu ‘1’ and delete by ‘2’.
After entering into the add/ delete menu devices will be shown in
last line by pressing ‘Enter’ key, the devices shall be add/delete.
DD/MM/YY
1. Add
2. Delete
<Panel Status>
HH:MM
[#.Del]
[OG1 Devs]
If there is no devices in the loop, it shows in display as “No
More O/P Device” otherwise as shown below.
55
RE / DD / UM / MONITI V 1.0- 01
DD/MM/YY
<Panel Status>
LC
: NN
Devices : MXX
HH:MM
[
.Add]
[OG1* Devs]
NN – Loop card number; MXX – Module Address.
Similarly to delete the devices (Modules) in group.
3.1.7.2.4
Features
By selecting the number ‘4’ from program menu screen, the system
enters into panel feature configuration mode. In this mode, the various
options in each feature of this panel shall be configurable. The following
table shows the features and their options. After entering into this menu,
the screen will be as below
DD/MM/YY
<Panel Status>
HH:MM
Auto Silence
Disabled
[Feature X]
X – represents feature number
The features can be sequentially viewed by using right / left arrow
keys and the corresponding available options can be changed by using
Up & down arrow key.
Table 1:
yy
Feature Programming:
Options
Features
1
2
1
AC Loss Delay
Disabled
Enabled: 1 – 999 Min
2
Trouble Reminder
Disabled
Enabled: 1 – 999 Min
3
Auto silence
Disabled
Enabled: 1 - 999Secs
4
Silence Inhibit
Disabled
Enabled: 1 - 999Secs
5
Earth Fault
Disable
Enable
Note: Option 1 – Default Factory Setting.
56
RE / DD / UM / MONITI V 1.0- 01
AC Loss Delay:
When AC power is lost, the control panel trouble relay will activate.
The factory default option for this feature is Enabled, the trouble relay
activation on AC loss after the time delay setting. Relay activation may be
delayed by selected as shown in LCD screen display. Press up & down
keys to toggle between enabled / disabled option. The AC Loss Delay
timing can set 001 to 999min. After setting the required time press Enter
key to accept the time. When you enter into this mode the screen will be
as below.
DD/MM/YY
<Panel Status>
Auto Silence
Disabled
HH:MM
[Feature X]
Trouble Reminder:
The Trouble Reminder feature provides an audible reminder that a
fire/supervisory/Fault still exists on the panel after the control panel has
been silenced. The factory default for this feature is 'Enabled'. When this
feature is 'enabled', the control panel buzzer will give a beep tone for
every set time during a trouble condition, after the Signal Acknowledge
switch is pressed. The buzzer tone will continue to sound at these rates until
the trouble condition is cleared. Press up & down keys to toggle between
enabled / disabled option. The Trouble Reminder timing can set 1 to
999mins. After setting the required time press Enter key to accept the time.
When you enter into this mode the screen will be as below.
DD/MM/YY
<Panel Status>
HH:MM
Trouble Remainder
Enabled : 720 Min
[#.Edit]
[Feature 2]
Auto Silence:
Auto-silence is the program feature that will automatically silence
the Notification Appliance Circuits, if they are programmed as silenceable
circuits, after a programmed time interval. The factory default setting is
auto-silence disabled. Press up & down key to toggle between enabled /
disabled option.
The Auto silence timing can be set from 001 to 999 seconds. After
setting the required time press Enter key to accept the time. When you
enter into this mode the screen will be as below.
57
RE / DD / UM / MONITI V 1.0- 01
DD/MM/YY
<Panel Status>
HH:MM
Auto Silence
Enabled : 120 Sec
[#.Edit]
[Feature 3]
Silence Inhibit:
The Silence Inhibit feature prevents the silencing of Notification
Appliance Circuits, using the Silence switch or Reset switch, for the
amount of time corresponding to the selected option, after the NAC’s are
activated. The factory default for this feature is 'disabled'. Press up & down
key to toggle between enabled / disabled option. The Silence inhibit
timing can set 1 to 999 seconds. After setting the required time press Enter
key to accept the time. When you enter into this mode the screen will be
as below.
DD/MM/YY
<Panel Status>
HH:MM
Silence Inhibit
Enabled : 060 Sec
[#.Edit]
[Feature 4]
Earth Fault Detection:
The Earth Fault Detection feature prevents the earth fault sense of
all the field terminals, using this option user can enable or disable the
earth fault detection. The factory default for this feature is 'disabled'. Press
up & down key to toggle between enabled / disabled option. When you
enter into this mode the screen will be as below.
DD/MM/YY
<Panel Status>
Earth Fault Detection
Disabled
58
HH:MM
[#.Edit]
[Feature 5]
RE / DD / UM / MONITI V 1.0- 01
3.1.7.3
About
It shows the details of the panel by pressing number 3 from the menu
screen. The LCD will show as below. In this screen the model and software
version has shown.
DD/MM/YY
<Panel Status>
HH:MM
Addressable Fire Alarm Control Panel
Ravel, MonitI V1.0
[About]
3.1.7.4
Test
By using the Test key from the keypad, the system entered into device testing
mode connected in the loop cards and lamp test mode. After entering into this mode,
the screen shows as below.
DD/MM/YY
1. Lamp Test
2. Output Test
3. Device Test
<Panel Status>
4. Input Test
5. Zone Test
HH:MM
[Test]
By pressing the ‘1’ from this menu, the lamp test function would be activated to
glow all the LED in the panel for 3 seconds.
By selecting the ‘2’ from this menu, it enter into output test mode, system
requires the admin password (“Default - 54321”). After entering into this mode, by
giving the output group number that particular output grouped devices are activated
for 3 seconds and then deactivated.
By selecting the ‘3’ from this menu, it enters into the device test mode, system
requires the admin password (“Default - 54321”). After entering into this mode, by
giving the device number that particular device is activated for 3 seconds and then
deactivated.
By selecting the ‘4’ from this menu, it enters into the Input test mode, system
requires the admin password (“Default - 54321”). After entering into this mode, It will
test for all the input devices connected in the loop automatically and gives result in a
separate screen.
By selecting the ‘5’ from this menu, it enters into the zone group test mode,
system requires the admin password (“Default - 54321”). After entering into this mode,
by giving the zone group number that particular zone grouped devices are activated
for 3 seconds and then deactivated.
59
RE / DD / UM / MONITI V 1.0- 01
Chapter 4 Operating Instruction
4.1
Panel Operation
The operation of the panel is described in this manual. In this manual the
following details are described in detail, like inputs / outputs, indications, control
keys, alarm, fault supervisory conditions etc.,
4.2
Initial Power up Condition
When the power is applied to the panel, the LCD will first display “System
Initializing” and the panel will not respond to any key presses or to zone activity.
Once this step is done the panel will shows “System Healthy” in LCD display and
System On, Mains On and Battery On LED will glow.
4.3
SLC Loop Inputs
This type of input is the normal inputs to the system from smoke detectors,
heat detectors, Manual Call points, modules etc. They are required to activate
the NAC’s like bell and or strobes as well as an LED. They can operate the relays
and control modules in the network. It display as “ALARM” in the LCD and stores
the events in Alarm list.
4.4
Indications
SYSTEM ON: This LED will glow when the panel is energized by primary and standby
power. This is the only LED glowing in the normal monitoring condition. The LCD Display
as shown below.
DD/MM/YY
HH:MM
System Healthy
Ravel Electronics
MAINS ON: It indicates that panel is operated through the mains supply (120 /
220VAC). Whenever the Main Supply (220v A.C) fails, the Mains ON LED will goes to off
condition and it also indicated in LCD with toggle Buzzer tone.
BATTERY ON: It indicates that the battery is connected with the panels and it under
charging. Whenever the backup battery fails, the battery ON LED will goes to off
condition and it also indicated in LCD with toggle Buzzer tone. Similarly the same LED
will blink when the battery voltage goes down below the 21.6v (Battery Low).
CHARGER FAULT: It indicates that the battery is connected with the panels and but the
charger circuit is fail / battery is deep discharged. Whenever the backup battery
60
RE / DD / UM / MONITI V 1.0- 01
charger fails, the charger fault LED will be illuminated and it also indicated in LCD with
toggle Buzzer tone.
EARTH(Ground) FAULT: Whenever the Signaling Device circuits (SLCs), Notification
Alarm Circuits (NACs), Remote Inputs and DC output are gets contact with the Earth or
Body of the cabinet, the earth fault LED and common fault LED will be illuminated and
it also indicated in LCD earth fault with toggle Buzzer tone. The Earth fault can be
created through 0 Ohms resistor.
SYSTEM FAULT: Glowing of this LED indicates the failure of the CPU.
SILENCED: This LED will glow when the silence key is pressed in fire condition only.
NAC FAULT: Whenever there is any fault in Notification Appliances Circuits like NAC
loop Open / Short / Earth fault, it will be identified by COMMON NAC FAULT LED.
TEST: The test LED will glow whenever the Devices are under test mode.
FIRE: This twin fire LED will glow when any one or more of the devices are in fire
condition.
SUPERVISORY: This supervisory LED will glow when any one or more of the zones are
in supervisory condition.
FAULT: This fault LED will glow when any one or more of the zones are in fault
condition.
ZONE FIRE: This fire LED will glow when the zones are fire condition. The first fired
zone continuously in blink and other zone fire LED will glow steadily in fire condition.
The fired zone is displayed in the LCD, first fire zone and total no. of zone is
displayed separately.
DISABLE: This disable LED glows steadily in any input / output is in disabled condition.
NIGHT MODE: This day/night LED glows, panels is in night mode
PRE ALARM: This pre alarm LED glows when the first zone grouped (PreAlarm is
enabled) device goes to alarm.
4.5
Buzzer
A piezo buzzer provides separate and distinct sounds for alarm, trouble and
supervisory conditions:



4.6
Alarm – Continuous
Fault – pulse 0.5sec ON and 5sec OFF
Supervisory – pulse 0.25sec ON and 0.25sec OFF
Operating Keys
61
RE / DD / UM / MONITI V 1.0- 01
The control keys are located at center of the front sticker and these keys are
touch pad. They are as follows:
SILENCE Key: When the silence key is pressed, after entering the user or admin
password the following will occur:
 The silenceable Notification Appliance Circuits will be turned OFF
 The Silence LED will be turned ON
Upon the occurrence of a subsequent fire event, Signal Silence is overridden and
the control panel will respond to the new event.
RESET Key: When the Reset key is pressed, after entering user or admin password,
the control panel will show the menu as below.
DD/MM/YY
1. System
HH:MM
2. Alarm
[Reset]
From the above menu entire system can reset or only alarm can
reset by selecting appropriate number. By selecting number ‘2’ from this
menu, the system enters into reset the alarm from loop card or remote
input. When you enter into this mode the screen will be as below.
DD/MM/YY
1. Loopcard
2. Remote Input
HH:MM
[Alarm Reset]
To reset the only loop card, select ‘1’ from this menu and enter the
particular loop card number then press ‘enter’ key. Similarly to reset the
remote input, select ‘2’ from this menu and enter the particular input
number then press ‘enter’ key. Then the following actions will done.





Clear the status LED’s.
Bring back the LCD display to the healthy condition.
Turn off the Notification Appliance Circuits.
Reset fire zones by temporarily removing power.
Restore all system relays to normal.
The Reset key is accessible only after silencing in alarm condition.
Any alarm, supervisory or trouble condition that exists after a system reset, will
resound the system, reactivating normal system activity.
62
RE / DD / UM / MONITI V 1.0- 01
ACK. Key: This key is used to acknowledge the buzzer tone during the fault and fire
condition. This key can be operated with user or admin password.
EVACUATE Key: This key is used to energize the all-external NAC’s without actual
fire, It will operate at user or admin level. Using the silence key NAC output can be
silenced.
ENTER KEY: This key is used to accept the password during silence, reset in Fire
Condition And also used for the Evacuate and wherever requires.
CURSOR KEYS: The cursor keys (Right / Left arrows) are used to move the cursor
point wherever required.
ALPHANUMERIC KEYS: These keys are used for entering the names etc. and
numbers. ‘*’ Key is used to go back the previous screen in programming mode.
MENU KEYS: The menu key is used to get into the program menu to change the
required configurations. It requires password to change the configurations.
TEST KEYS: The help key is used to test the lamps and SLC devices in individual loops.
4.7
Normal Monitoring Mode
Normal Mode is the standard mode of operation. In this mode, the panel
continuously monitors system status. When no fire or supervisory or trouble
conditions exist, all LEDs will be off except the System On, Mains On and Battery On
LED. The Notification Appliance Circuits will be off, all relays are in their normal state
and the onboard buzzer will be off. When the system is in normal condition the LCD
screen will be as “System Healthy”.
4.8
Alarm Condition
When the control panel detects Fire via the Detector / MCP, the panel will
cause the following:




The common twin Fire LEDs will glow.
Turn on the NAC’s.
Turn on the panel buzzer with continuous tone.
Turn on the fire relay.
In case of multiple zone fire, the origin zone fire LED will be blinking and
subsequent zone fire LED will glow steadily.
To change the other indexed fire event zones which are suppressed use right / left
arrow keys.
63
RE / DD / UM / MONITI V 1.0- 01
Restoral: Silence the NAC’s by appropriate user or admin password. after silencing
the panel will perform the following;
 Turn off the Internal Buzzer.
 Turn off the External NAC’s.
 Turn on the silenced LED.
When the Fire condition is cleared and Reset key has been pressed after
entering the user or admin password. The Reset is accessed only after silencing the
panel in alarm condition. The panel will perform the following after clearing fire and
resetting:
 Turn off the common twin Fire LEDs.
 Turn off the Fire relay.
The LCD screen will be as below.
DD/MM/YY
HH:MM
System Healthy
Ravel Electronics
4.9
Supervisory Condition
When the control panel detects supervisory signal via the any normally open
contact devices, the panel will cause the following:
 The common supervisory LED will glow.
 Turn on the panel buzzer with intermittent buzzer tone (pulse 0.25sec ON
and 0.25sec OFF).
 Turn on the supervisory relay.
In case of multiple zone supervisory, the origin zone and recent zone
supervisory LED will be viewed in LCD screen.
To change the other indexed supervisory event zones which are suppressed use
right / left arrow keys.
Restoral: When the supervisory condition is cleared and Reset key has been pressed
after entering the user or admin password if the zones are programmed for
latching, the panel will perform the following:
 Turn off the supervisory LEDs.
 Turn off the supervisory relay.
The LCD screen will be as below.
DD/MM/YY
64
System Healthy
Ravel Electronics
RE / HH:MM
DD / UM / MONITI V 1.0- 01
Note:
If the supervisory mode is selected as resettable, the resetting the zone is not
required. The zone is retrieved automatically after clearing the supervisory
condition.
4.10
Fault Condition
The fault may any one of the following Zone fault / disable / earth fault, NAC
fault and power section fault. When there is one or more fault condition, the fire
alarm control panel performs the following:
 Turn on the common fault LED.
 Turn on the NAC fault / power fault LED.
 Turn on the panel buzzer tone with intermittent buzzer tone (pulse 0.5ec
ON and 5sec OFF).
 Activate the fault relay.
Restoral: When the fault condition is cleared, the panel will perform the following
automatically:
 Turn off the fault LEDs.
 Turn off the NAC fault / power fault LED.
 Turns off the buzzer tone.
 Deactivate the fault relay.
The LCD screen will be as below.
DD/MM/YY
HH:MM
System Healthy
Ravel Electronics
Note: The Fault occurred will not affect the other normal functions of
the panel
65
RE / DD / UM / MONITI V 1.0- 01
4.11
Test Condition
The panel LED’s and devices connected with the panel can be tested
through the menu from the Test key. By pressing the ‘Test key’, the system enters
into the test mode and in this there are three test modes like lamp test, Output
Test and Device test. After entering into this mode, the LCD screen will as shown
below.
DD/MM/YY
HH:MM
1. Lamp Test
2. Output Test
3. Device Test
4. Input Test
5. Zone Test
[Test]
4.11.1
Lamp Test
By entering into this menu using the number ‘1’ key, the LED in the panel will
turn on. The LED status shall be checked by using this menu.
4.11.2
Output Test
By pressing the number ‘2’ from the key pad, the system enters into the
output test mode. The devices connected in the output group can be tested by
group wise selecting corresponding number. Test LED is illuminates continuously
identifies the SLC/System, which is under test. The device turns on for 3 seconds
and turns off automatically. During test mode, the NAC outputs will not be
activated.
4.11.3
Device Test
By pressing the number ‘3’ from the key pad, the system enters into the
Device test mode. The devices connected in the SLC loop can be tested by
loop card wise for each device by selecting corresponding number. Test LED is
illuminates continuously identifies the SLC/System, which is under test. The device
turns on for 3 seconds and turns off automatically. During test mode, the NAC
outputs will not be activated.
4.12
Disable Condition
Disable: The any device/loop card can be Disabled / Enabled through the
programming. The ON status of disabled LED and common fault LED indicates, the
Device/loop card is disabled and the OFF status of the LED indicates the enabled.
Chapter 5: Servicing:
66
RE / DD / UM / MONITI V 1.0- 01
5.1 Installation/Replacement of PCB:
Remove the screws of PCB, which has to be change and remove the PCB
from the mounting position and place the new PCB in that same position
as shown below.
Mounting position for Main Circuit board (RAVEL RE - ADR – MB):
C2
E
N
P
120 / 220 VAC
F1
L1
Br1
U1
L3
U7
C28
Master
Board Fixing
Q1
U5
Q2
U6
CN 3
F3
RS 485 I/P
A
B
FAULT-RLY3
NC
NO
C
PROG-RLY2
NC
NO
C
PROG-RLY1
NC
NO
C
DC O/P
_
+
C13
C11
C10
LOOP
NAC O/P
_
CN 2
_
+
IN
+
_
OUT
+
USB 2.0
F3
F3
U6
U7
12V 7Ah
Battery
12V 7Ah
Battery
+
Figure – 18
Mounting position for Display board (RAVEL RE – ADR –DISP):
67
RE / DD / UM / MONITI V 1.0- 01
Display Board
Mounting Hole
RAVEL RE-ADR-DISP
RAVEL RE-ADR-DISP
Figure – 19
Mounting position for Power supply unit (RAVEL RE – ADR – PS):
68
RE / DD / UM / MONITI V 1.0- 01
RS 485 I/P
A
B
FAULT-RLY3
NC
NO
C
PRO G-RLY2
NC
NO
C
PRO G-RLY1
NC
NO
C
DC O/P
_
+
LOOP
NAC O/P
_
_
+
IN
+
_
OUT
+
USB 2.0
F3
F3
U6
U7
Power Supply
Board Fixing
+
C2
E
N
P
120 / 220 VAC
F1
12V 7Ah
Battery
U1
L3
Br1
U7
12V 7Ah
Battery
L1
C28
Q1
U5
Q2
U6
CN 3
F3
CN 2
C13
C11
C10
Figure – 20
5.2 Lamp Test
69
RE / DD / UM / MONITI V 1.0- 01
The lamp test function done through the sub menu by pressing
‘Test’ key, system (Panel) is in normal condition. In this mode, all the LED’s
are checked for good condition by glowing all LED’s.
5.3 System Power
Power
Max.
AH Derating
Capacity
Factor
Max.
standby
current
Max.
Alarm
current
Max.
standby
time
Max.
alarm
duration
Primary
(power
supply)
N/A
N/A
0.1A
0.5A
N/A
N/A
Secondary
(back up)
7Ah
10%
0.4A
1.8A
24 Hrs.
5 Min.
5.4 Trouble Shooting
Condition
Root Cause
Remedy
There is no
indication on
The panel
No power to the
Panel
Check Primary (AC)
power and Standby
power.
During Mains fail
condition Battery
fault LED is glowing
May be battery low
(<21.6V) or the
battery reaches the
de-rated (<19.5V)
Voltage.
Check the Battery voltage
and charge the battery or
replace the battery.
The Battery fault
and charger fail
shown in LCD.
The Battery
connected in
reverse.
Connect the battery
properly.
Chapter 6: Battery Calculation
70
RE / DD / UM / MONITI V 1.0- 01
Use Table 6-1 to calculate the total standby and alarm load in ampere hours (AH).
This total load determines the battery size (in AH), required to support the control
panel under the fail of the AC Power Supply. Complete the table 6-1 as follows:
1. Enter the NFPA standby and alarm times (refer to NFPA requirements below).
2. Calculate the ampere-hours for standby and Alarm, and then sum the standby
and alarm ampere-hours.
3. Multiply the sum by the derating factor of 1.2 to calculate the proper battery
size (in AH).
4. Write the ampere hour requirements on the protected premises lable located
inside the cabinet door.
71
RE / DD / UM / MONITI V 1.0- 01
Table 6-1: Total Secondary Power Requirements at 24 VDC
MONITI Battery Calculation
Secondary Power Source Requirements
Device Type
Main Circuit Board
Loop Card
Qty
1
0
Standby Current (amps)
Current Draw
Total
x
0.120000
=
0.12000
x
0.040000
=
Qty
1
0
Secondary Alarm Current (amps)
Current Draw
Total
x
0.170000
=
0.17000
x
0.085000
=
DC Output Power
4-wire Detector Heads
Addressable Devices
0
x
0.000000
RE-337-SH
RE-337-S
RE-337-H
RE-737MC
RE-737MM
RE-737MR
RE-737MZ
RE-737MX
RE-737M
RE-24ES
RE-374BS
RE-716BI
0
0
0
0
0
0
0
0
0
0
0
0
0
0
x
x
x
x
x
x
x
x
x
x
x
x
x
x
0.000500
0.000500
0.000500
0.000500
0.000500
0.000500
0.000500
0.000500
0.000500
0.000500
0.000500
0.000030
0.000000
0.000000
RE-24ES
RE-374BS
Miscellaneous Device 3
Miscellaneous Device 4
Miscellaneous Device 5
NAC #1
0
0
0
0
0
x
x
x
x
x
0.000000
0.000000
0.000000
0.000000
0.000000
=
x
0.000000
=
=
=
=
=
=
=
=
=
=
=
=
=
=
=
Maximum alarm draw for Addressable devices (SLC)
=
0
x
0.007000
=
=
0
x
0.007000
=
=
0
x
0.000000
=
=
0
x
0.000000
=
=
0
x
0.000000
=
0
x
0.000000
=
Current Draw from TB3 (non-alarm)
0.000000
Sum each column for totals
Total Standby Current
72
0
=
0.000000
0.12000
0.00000
=
Total Alarm Current
RE / DD / UM / MONITI V 1.0- 01
0.17000
MONITI Battery Calculation
Note: You can edit all current draws and are fully responsible for verifying these calculations. Only enter values in
yellow cells.
Standby Load Current (Amps)
0.120 A
Alarm Load Current (Amps)
0.170 A
Required Standby Time in Hours
24 Hours
x
24
=
2.880 AH
Required Alarm Time in Hours
5 Minutes
x
0.084
=
0.014 AH
Standby and Alarm Load Subtotal
Derating Factor
=
=
2.894 AH
x 1.2
Total Ampere Hours Required
=
3.473 AH
Recommended Batteries:
7AH Batteries
Battery Check
The batteries can be charged by the MONITI Charger.
The batteries can be housed in the MONITI Cabinet.
Current Draw Check
NAC#1 current is within the limitations of the circuit.
NAC#2 current is within the limitations of the circuit.
The standby current is within the limitations of the panel.
The alarm current is within output limitations of the panel.
73
RE / DD / UM / MONITI V 1.0- 01
Chapter 7: Wire Requirements
Connecting external system accessories to the MONITI main circuits
must be carefully considered to ensure proper operation. It is important to
use the correct type of wire, wire gauge and wire run length per each
MONITI circuit. Reference the chart below to specify wire requirements and
limitations for each MONITI.
TABLE 7-1: Wire Requirements
CIRCUIT
FUNCTION
CIRCUIT TYPE
WIRE TYPE AND
LIMITATIONS
RECOMMENDED
MAX. DISTANCE
Feet (meters)
WIRE GUAGE
10,000 (3,000 m)
8,000 (2,400 m)
4,875 (1,480 m)
3,225 (975 m)
12 AWG (3.25 mm2) Belden 9583
WPW999
14 AWG (2.00 mm2) Belden 9581
WPW995
16 AWG (1.30 mm2) Belden 9575
WPW991
18 AWG (0.75 mm2) Belden 9574
WPW975
Untwisted,
Initiating Device
Circuit
Connects to
Initiating Devices
unshielded wire
(Do not exceed 100
ohms)
24 VDC resettable,
nonresettable
Connects to
annunciators and
other accessories
No more than 1.2
volt drop
allowed from supply
source
to end of any
branch
Distance limitation set
by 1.2 volt maximum
line drop
12 AWG (3.25 mm2) - 18 AWG
(0.75 mm2)
Chapter 8: Compatible Devices
The compatible devices which are connected with this panel are given below:
Total Compatible Addressable Devices: 127 + 20 (LS) No’s Max.
Ravel Detectors:
RE-337-S
: The intelligent Photoelectric Smoke detector.
RE-337-H
: The intelligent Thermal detector.
RE-337D-SH
: The intelligent Multi Photoelectric & Thermal detector.
Ravel Modules:
RE-737MC
RE-737MM
RE-737MR
RE-737MI
RE-737MZ
RE-737MX
RE-737M
: The Control Module.
: The Monitor Module.
: The Relay Module
: The Isolator Module
: The Zone Module
: The Input Output Module
: The Manual Call Point
74
RE / DD / UM / MONITI V 1.0- 01
Compatible NAC’s:
1.
2.
3.
4.
RE-24CS
RE-24SS
RE-24ES
RE-34BS
: Mini Horn
: Sounder Cum Strobe
: Loop powered Sounder
: Loop powered Sounder Base
End Of Line Devices:
1. RE4K7 for External Inputs, Zone, and NACs.
Chapter 9: Abbreviations
NFPA
AC
FACP
LCD
SLC
Evt
NOD
NOM
DD
MM
YY
LC
RTC
OPTI
MULT
IP_M
OP_M
IO_M
Cat
Del
–
–
–
–
–
–
–
–
–
–
–
–
–
–
–
–
–
–
–
–
National Fire Protection Association
Alternate Current
Fire Alarm control Panel
Liquid Crystal Display
Signaling Line Circuit
Event
Number Of Device
Number Of Modules
Date
Month
Year
Loop Card
Real Time Clock
Optical Detector
Multiple Detector
Input Module
Output Module
Input / Output Module
Category
Delete
75
RE / DD / UM / MONITI V 1.0- 01
RAVEL ELECTRONICS PVT LTD
150A, 1st Main Road, Electronic Industrial Estate,
Perungudi, Chennai, Tamil Nadu.
Email : marketing@ravelfire.com; Web : www. ravelfire.com
DATE:
TEST CERTIFICATE
We hereby certify that the items details hereon have been manufactured,
inspected and electrically tested to ensure the compliance with ravel products
and process specification.
Model No.:
MONITI
Serial No.:
No. of Loops:
For RAVEL ELECTRONICS PVT LTD,
Q.C. – Engineer
Tested By
76
RE / DD / UM / MONITI V 1.0- 01
RAVEL ELECTRONICS PVT LTD
150A, 1st Main Road, Electronic Industrial Estate,
Perungudi, Chennai, Tamil Nadu..
Email : marketing@ravelfire.com; Web : www. ravelfire.com
WARRANTY CERTIFICATE
Model No.:
MONITI
Serial No.:
Ravel Electronics warrants each product to be free from defects in material and workmanship.
This obligation is limited to servicing or part returned to the company for that purpose and making good
any parts thereof which shall be within warranty period, returned to the company under a written
intimation and which to the company’s satisfaction to be found defective. The company reserves the
right to decide the workplace for the repair work. The freight for defective material will have to be borne
by the purchaser, and the transit risk for such material will rest with the purchaser.
This warranty will last for a period of 12 months from the date of Invoice of the product from
the factory. The warranty is applicable only if the product is used within its specifications. The warranty
for the replaced components will lapse along with that of the main product.
THIS WARRANTY IS VALID UP TO: 12 months from the date of invoice
Authorised Signatory
77
RE / DD / UM / MONITI V 1.0- 01
Ravel Electronics Pvt Ltd.,
150A, 1st Main Road,
Electronic Industrial Estate,
Perungudi, Chennai, Tamil Nadu.
Web: www.ravelfire.com
Email: marketing@ravelfire.com
78
RE / DD / UM / MONITI V 1.0- 01
Was this manual useful for you? yes no
Thank you for your participation!

* Your assessment is very important for improving the work of artificial intelligence, which forms the content of this project

Download PDF

advertising