Fixed Gas Detector Operation Manual

Fixed Gas Detector Operation Manual
BS03
Fixed Gas Detector Operation Manual
BS03 Fixed Gas Detector Operation Manual
BS03 Fixed Gas Detector Operation Manual
Problem
Safety Information
Before using the device, please first carefully read and follow the
following information to operate the device:
z
Please don't use the defective detector. Before using, please
z
It displays FAUL
connection, wire
Re-connect the wire
broken, or sensor
or replace the sensor
damaged
contact the seller.
No response to the
Sensor damaged
Replace the sensor
In order to keep the accuracy, please calibrate it once before the
gas
Circuit Fault
Contact the seller
first time using.
Wrong connection
Wire connection fault
Check the connection
Working voltage of the detector is DC18V to DC30V and
to the controller
Electric circuit fault
Contact the seller
recommended voltage is DC24V. The voltage exceeding DC30V
will damage the detector.
z
Before using, please make sure the housing is fixed.
z
There should be no speedy gas flow on the installation place.
Otherwise, it will influence the detection result.
z
Solution
Wrong wire
check if there is crack or spare part missing. If yes, please
z
Possible reason
Please don't expose the device to the gas which concentration is
exceeding the range. Otherwise, it will influence the accuracy
and shorten the sensor life.
z
Please don't paint the sensor parts or detector.
z
Only sensor spare parts which are specified for BS03 are
allowed to be used.
z
It's suggested calibrate the sensor once every 6 months.
z
In order to avoid damage human beings, please operate it when
power off. Before opening the cover, make sure there is no
mixture gas of combustible gas and air. Otherwise, it will
possibly cause fire or explosion.
z
Please avoid water or dust to come into the housing.
z
Please
z
Please don't expose the device to the environment which has
electric shock, strong magnetic field or serious continuous
mechanic shocking.
BS03 Fixed Gas Detector Operation Manual
BS03 Fixed Gas Detector Operation Manual
z
When no using, please take out the battery from the remote
controller.
z
Installation must abide by the national and local regulations.
z
It's forbidden to disassembly, adjust or repair the device without
permission.
z
All the operation inside the device must be carried by
professional persons.
7.1 Take off the calibration cover in counter-clockwise.
7.2 Pull out the decoration part downwards.
7.3 Screw off the jackscrew from the sensor protection cover.
7.4 Take off the protection cover in counter-clockwise.
7.5 Take out the old sensor.
7.6 Put the new sensor into the sensor cover.
Note: Please put the new sensor into the correct fixing holes. It's
forbidden to rotate the sensor.
7.7 Then install in turns protection cover, jackscrew, decoration part
and calibration cover. The replacement is completed.
7.8 Electrify the detector and calibrate the detector.
8. Normal problem and solution
BS03 Fixed Gas Detector Operation Manual
BS03 Fixed Gas Detector Operation Manual
1. Brief introduction
Note: Zero calibration must be carried in the clean air. It's forbidden
BS03 fixed gas detector, adopting high-quality catalytic gas sensor
to calibrate zero when the target gas exists in the working place.
and SMD arts and crafts, has advantages of good reproducibility,
6.6Single point calibration
disturbing-proof against temperature and humidity, long life-span and
6.6.1 After using for some time, the result of the detection may be not
easy operation.
so correct because of the sensor drift. Consider of the convenience
The signal output is standard 4-20mA. It is widely used in refineries,
of the user, the device is designed with the function of single point
chemical plant, LPG station, gas boiler, and Spray-Paints etc where
calibration.
gas leakage easily.
6.6.2 Procedure: Put the device into the calibration gas with known
concentration (Suggested inputting half of the detection range gas for
2-3 minutes). In normal status, press “Setup” four times and it
2. Technical data
Gas
Range
Resolution
L-alarm
H-alarm
displays “F-4”. Then press “Confirm” and it displays “50”(The pre-set
LEL
0-100%LEL
1%LEL
20%LEL
50%LEL
calibration level). This figure can be changed by pressing “+” or “-”.
LEL Vapor
0-100%LEL
1%LEL
20%LEL
50%LEL
And then press “Confirm” to remember this figure. Then it displays
CO
0-1000PPM
1PPM
35PPM
200PPM
“XXXX” (The A/D of the present environment). When the figure on
H2S
0-100PPM
1PPM
10PPM
15PPM
the screen is steady, press “Confirm” to remember this figure and
NH3
0-100PPM
1PPM
25PPM
50PPM
calibrate it. It will go to effect after exiting from this mode. The screen
CL2
0-20PPM
0.1PPM
5PPM
10PPM
O2
0-30%VOL
0.1%VOL
19.5%VOL
23.5%VOL
SO2
0-500PPM
1PPM
10PPM
50PPM
CO2
0-6000PPM
1PPM
1500PPM
2000PPM
NO
0-100PPM
1PPM
25PPM
50PPM
NO2
0-20PPM
0.1PPM
5PPM
10PPM
HCN
0-100PPM
1PPM
5PPM
10PPM
displays “F-4”. The user can press “Confirm” to make the other
setting or press “Cancel” to return to the normal status.
Note: Please don't carry the above calibration when the detector is
working or there is no calibration gas.
7. Sensor replacement
In normal working environment, the life of catalytic sensor is 3 years
and electrochemical sensor is 2 years. When the sensor life is
overdue, the detection result may be not accurate. Please contact the
Sensor type: Catalytic or electrochemical gas sensor
seller for replacing the sensor.
Gas sampling: Natural diffusion
Before replacing the sensor, please first cut off the power supply and
Power supply: DC24V±25%
follow the following steps to replace it:
Power consumption: ≤3W
Working method: Continuous monitoring
Error rate: ≤±5%F.S.
BS03 Fixed Gas Detector Operation Manual
BS03 Fixed Gas Detector Operation Manual
High alarm setting: “F--2”
Indication method: 4-digit LED light
Zero calibration: “F--3”
Condition display: 3 LED lights indicate fault alarm, L-alarm level
Single point calibration: “F--4”
alarm and H-alarm level
Factory setting: “F--5”(Unavailable to the customers).
Operation: Infrared remote control
6.3 Low alarm setting
Response time: ≤30s (LEL) / ≤60s (toxic gas)
In normal status, press “Setup” once and it displays “F-1”. Press
Working temperature: -40℃ ~ 70℃ (LEL) / -20℃ ~ 50℃ (toxic)
“Confirm”, it displays “50”(The pre-set first level alarm). This figure
Working humidity: <93%RH
can be adjusted by pressing “+” or “-”. After setting completed, press
Explosion-proof: Ex dⅡCT6
“Confirm” to save the result. The device exits to the normal status.
Protection: IP55
The setting will affect. The screen displays “F-2”. The user can press
Pressure Limit: 86-106kPa
“Confirm” to make the other setting or press “Cancel” to return to the
Signal output: 4~20mA
normal status.
2 relay output
6.4 High alarm setting
Install screw thread: G3/4"
In normal status, press “Setup” twice and it displays “F-2”. Then
Cable dimension: ≥1.5mm2×3
press “Confirm”, it displays “20”(The pre-set first level alarm). This
Transmit distance: ≤1000m
figure can be adjusted by pressing “+” or “-”. After setting completed,
Dimensions and weight: l×b×h, mm 210×200×105
press “Confirm” to save the result. The device exits to the normal
status. The setting will affect. The screen displays “F-1”. The user
can press “Confirm” to make the other setting or press “Cancel” to
return to the normal status.
6.5 Zero calibration
After the detector work normally for more than 10 minutes, put the
device into the clean air. (For O2 / N2 gas detector, the device should
be put into pure N2 gas environment). In normal status, please press
“Setup” three times, it displays “F-3”. Then press “Confirm”, it
displays “XXXX” (The A/D of the present environment). When the
figure on the screen is steady, press “Confirm” to remember this
figure and calibrate it. It will go to effect after exiting from this mode.
The screen displays “F-3”. The user can press “Confirm” to make the
other setting or press “Cancel” to return to the normal status.
3. Construction illustration
about 2100g
BS03 Fixed Gas Detector Operation Manual
No.
Name
No.
Name
1
Calibration cap
9
Pipe connector
2
Decoration
10
Display screen
3
Lower cover
11
Wire connection hole
4
Upper cover
12
H-alarm LED
5
Wire connection hole
13
L-alarm LED
6
Pipe connector
14
Fault / Power LED
15
Ground nut
7
8
Remote receiver
window
BS03 Fixed Gas Detector Operation Manual
Fixing hole
6. Operation instruction
6.1 On the remote controller, there are totally fives buttons as follows:
“Setup”, “Confirm”, “Cancel”, “+” and “-”. On the spot, it's forbidden to
replace the batteries.
Note: “Setup”, “Confirm” and “Cancel” are single-spring buttons.
These buttons can only be springed once even if you press them
continuously, and the interval between two springs should not be less
than 1 second. “+” and “-” are continuous-spring buttons and can be
4.
springed by continuous pressing. Setting can only be affected after
pressing “Confirm”. After setting, press “Cancel” to return to the
normal mode. Effective setting can be kept till the next setup, even if
without power.
6.2 Illustration of display:
Normal: gas concentration
Sensor fault: FAUL; yellow LED is on (only for LEL)
High concentration protection: FAUL; 3 LED are on (only for LEL)
Low alarm: gas concentration; red low alarm LED on
High alarm: gas concentration; red low and high alarm LED on
Installation
Low alarm setting: “F--1”
BS03 Fixed Gas Detector Operation Manual
BS03 Fixed Gas Detector Operation Manual
the enclosure through the pipe connector, compaction circle, air-proof
4.1 Installation position
closing plug and the wire connection hole. According to the
4.1.1 For petrol gas, oil gas and alcohol gas etc. which is heavier
explosion-proof
than the air, the position is 0.3m-0.6m higher than the ground.
requirement,
please
don't
take
out
the
explosion-proof closing plug from the unused wire connection holes.
4.1.2 For natural gas, CH4 etc which is lighter than the air, the
Please don't throw away any part inside the enclosure or the PCB.
position is 0.5m-2m higher than the gas source.
5.3 All the wires should be connected to the terminals. The terminal
Note: Gas density more than 0.97kg/CBM, then it's heavier.
instruction is as follows:
Gas density less than 0.97kg/CBM, then it's lighter.
4.1.3 The position should be far away from shocking, shattering,
strong electromagnetic interference. Around the position, there
should be at least 0.3m empty place.
Icon
Name
Function
Specifications
24V
Anode of power
Power input
DC24V±25%
GND
Cathode of
power
Power input
DC24V±25%
Iout
Current output
Current output
4~20mA
H.S
High alarm
High alarm output
Switch relay
L.S
Low alarm
Low alarm output
Switch relay
5.4 After the correct wire connection, take out the useless wire from
the enclosure. Then tighten the compaction circle, rubber air-proof
circle and wire. Explosion-proof soft tube can also be connected with
the device directly.
Note: The size of the wire between the controller and detector should
be not less than 6mm, and the distance should be note more than
1000m.
5.5 After checking all the connection well, install the display PCB and
the front cover. Make sure O-type circle is put on and connected with
the cover tightly.
4.1.4 The position should be within 1m around the possible gas
leakage area, such as valve, pipe connection point, gas outlet place.
Please try to install it nearer to the above places, but avoid
influencing the working of the other equipments. Please avoid the
environment of high temperature and humidity. Also please keep it
from water swashing, oil and mechanical damage. Please also
consider the convenience of maintenance and calibration.
4.1.5 For large scale detection, we suggest install 1pc every 10-12
square meters, so as to get the best detection result.
4.2 Dimensions
BS03 Fixed Gas Detector Operation Manual
BS03 Fixed Gas Detector Operation Manual
4.3 Installation methods
Note: Fix the detector with sensor head downwards. According to the
installation place, fix the detector onto the wall or gas pipes. Details
as follows:
Method 3: If there is 1" to 2″ (diameter) pipe, the user can use 2
Method 1: If there are transverse or vertical siphon with G3/4 Screw
U-type bolts to fix the hanging plate on the pipe, and then fix the
thread in installed places, please connect the two terminals of the
detector onto the plate. Or, the user can first fix the detector onto the
detector to the gas pipes. Then connect and screw down the pipe
plate and then fix the plate on the pipe.
screw thread nut and fix it tightly.
Method 2: If the user needs to
install the detector on the wall, please choose an appropriate metope
according to the detector dimensions. Then fix the detector by using
5.
Wire
3 pieces of M6×70
bulge bolts in the
connection
corresponding
Note: Wire connection must be carried when power off.
installed orifice.
5.1 Screw down the cover in counter-clockwise way. Then use a
cross-type screw to screw down the 3 bolts and take off the display
PCB.
5.2 Screw down the pipe connector in counter-clockwise way. Take
out the explosion-proof pad. In turns, put 3-line wire to the internal of