BS03
Fixed Gas Detector Operation Manual
BS03 Fixed Gas Detector Operation Manual
Safety Information
Before using the device, please first carefully read and follow the following information to operate the device: z Please don't use the defective detector. Before using, please check if there is crack or spare part missing. If yes, please contact the seller. z In order to keep the accuracy, please calibrate it once before the first time using. z Working voltage of the detector is DC18V to DC30V and recommended voltage is DC24V. The voltage exceeding DC30V will damage the detector. z Before using, please make sure the housing is fixed. z There should be no speedy gas flow on the installation place.
Otherwise, it will influence the detection result. z Please don't expose the device to the gas which concentration is exceeding the range. Otherwise, it will influence the accuracy and shorten the sensor life. z Please don't paint the sensor parts or detector. z Only sensor spare parts which are specified for BS03 are allowed to be used. z It's suggested calibrate the sensor once every 6 months. z In order to avoid damage human beings, please operate it when power off. Before opening the cover, make sure there is no mixture gas of combustible gas and air. Otherwise, it will possibly cause fire or explosion. z Please avoid water or dust to come into the housing. z Please z Please don't expose the device to the environment which has electric shock, strong magnetic field or serious continuous mechanic shocking.
BS03 Fixed Gas Detector Operation Manual
It displays FAUL
No response to the gas
Wrong connection to the controller
Wrong wire connection, wire broken, or sensor damaged
Sensor damaged
Circuit Fault
Re-connect the wire or replace the sensor
Replace the sensor
Contact the seller
Wire connection fault Check the connection
Electric circuit fault Contact the seller
BS03 Fixed Gas Detector Operation Manual
7.1 Take off the calibration cover in counter-clockwise.
7.2 Pull out the decoration part downwards.
7.3 Screw off the jackscrew from the sensor protection cover.
7.4 Take off the protection cover in counter-clockwise.
7.5 Take out the old sensor.
7.6 Put the new sensor into the sensor cover.
Note: Please put the new sensor into the correct fixing holes. It's forbidden to rotate the sensor.
7.7 Then install in turns protection cover, jackscrew, decoration part and calibration cover. The replacement is completed.
7.8 Electrify the detector and calibrate the detector.
8. Normal problem and solution
BS03 Fixed Gas Detector Operation Manual z When no using, please take out the battery from the remote controller. z Installation must abide by the national and local regulations. z It's forbidden to disassembly, adjust or repair the device without permission. z All the operation inside the device must be carried by professional persons.
BS03 Fixed Gas Detector Operation Manual
1. Brief introduction
BS03 fixed gas detector, adopting high-quality catalytic gas sensor and SMD arts and crafts, has advantages of good reproducibility, disturbing-proof against temperature and humidity, long life-span and easy operation.
The signal output is standard 4-20mA. It is widely used in refineries, chemical plant, LPG station, gas boiler, and Spray-Paints etc where gas leakage easily.
2. Technical data
Gas Range
LEL 0-100%LEL
LEL Vapor 0-100%LEL
CO 0-1000PPM
Resolution
1%LEL
L-alarm
20%LEL
H-alarm
50%LEL
H
2
S 0-100PPM 1PPM 10PPM 15PPM
NH
3
0-100PPM 1PPM 25PPM 50PPM
CL
2
O
2
0.1%VOL 23.5%VOL
SO
2
0-500PPM 1PPM 10PPM 50PPM
CO2 0-6000PPM 1PPM 1500PPM 2000PPM
NO 0-100PPM
HCN 0-100PPM 1PPM 5PPM 10PPM
Sensor type: Catalytic or electrochemical gas sensor
Gas sampling: Natural diffusion
Power supply: DC24V±25%
Power consumption: ≤3W
Working method: Continuous monitoring
Error rate: ≤±5%F.S.
BS03 Fixed Gas Detector Operation Manual
Note : Zero calibration must be carried in the clean air. It's forbidden to calibrate zero when the target gas exists in the working place.
6.6Single point calibration
6.6.1 After using for some time, the result of the detection may be not so correct because of the sensor drift. Consider of the convenience of the user, the device is designed with the function of single point calibration.
6.6.2 Procedure: Put the device into the calibration gas with known concentration (Suggested inputting half of the detection range gas for
2-3 minutes). In normal status, press “Setup” four times and it displays “F-4”. Then press “Confirm” and it displays “50”(The pre-set calibration level). This figure can be changed by pressing “+” or “-”.
And then press “Confirm” to remember this figure. Then it displays
“XXXX” (The A/D of the present environment). When the figure on the screen is steady, press “Confirm” to remember this figure and calibrate it. It will go to effect after exiting from this mode. The screen displays “F-4”. The user can press “Confirm” to make the other setting or press “Cancel” to return to the normal status.
Note : Please don't carry the above calibration when the detector is working or there is no calibration gas.
7. Sensor replacement
In normal working environment, the life of catalytic sensor is 3 years and electrochemical sensor is 2 years. When the sensor life is overdue, the detection result may be not accurate. Please contact the seller for replacing the sensor.
Before replacing the sensor, please first cut off the power supply and follow the following steps to replace it:
BS03 Fixed Gas Detector Operation Manual
High alarm setting: “F--2”
Zero calibration: “F--3”
Single point calibration: “F--4”
Factory setting: “F--5”(Unavailable to the customers).
6.3 Low alarm setting
In normal status, press “Setup” once and it displays “F-1”. Press
“Confirm”, it displays “50”(The pre-set first level alarm). This figure can be adjusted by pressing “+” or “-”. After setting completed, press
“Confirm” to save the result. The device exits to the normal status.
The setting will affect. The screen displays “F-2”. The user can press
“Confirm” to make the other setting or press “Cancel” to return to the normal status.
6.4 High alarm setting
In normal status, press “Setup” twice and it displays “F-2”. Then press “Confirm”, it displays “20”(The pre-set first level alarm). This figure can be adjusted by pressing “+” or “-”. After setting completed, press “Confirm” to save the result. The device exits to the normal status. The setting will affect. The screen displays “F-1”. The user can press “Confirm” to make the other setting or press “Cancel” to return to the normal status.
6.5 Zero calibration
After the detector work normally for more than 10 minutes, put the device into the clean air. (For O2 / N2 gas detector, the device should be put into pure N2 gas environment). In normal status, please press
“Setup” three times, it displays “F-3”. Then press “Confirm”, it displays “XXXX” (The A/D of the present environment). When the figure on the screen is steady, press “Confirm” to remember this figure and calibrate it. It will go to effect after exiting from this mode.
The screen displays “F-3”. The user can press “Confirm” to make the other setting or press “Cancel” to return to the normal status.
BS03 Fixed Gas Detector Operation Manual
Indication method: 4-digit LED light
Condition display: 3 LED lights indicate fault alarm, L-alarm level alarm and H-alarm level
Operation: Infrared remote control
Response time: ≤30s (LEL) / ≤60s (toxic gas)
Working temperature: -40℃ ~ 70℃ (LEL) / -20℃ ~ 50℃ (toxic)
Working humidity: <93%RH
Explosion-proof: Ex d CT6
Protection: IP55
Pressure Limit: 86-106kPa
Signal output: 4~20mA
2 relay output
Install screw thread: G3/4"
Cable dimension: ≥1.5mm
2
×3
Transmit distance: ≤1000m
Dimensions and weight: l×b×h, mm 210×200×105 about 2100g
3. Construction illustration
BS03 Fixed Gas Detector Operation Manual
No. Name No. Name
4.
3
4
5
6
7
Lower cover
Upper cover
Wire connection hole
Pipe connector
Remote receiver window
11
12
13
14
Wire connection hole
H-alarm LED
L-alarm LED
Fault / Power LED
Installation
BS03 Fixed Gas Detector Operation Manual
6. Operation instruction
6.1 On the remote controller, there are totally fives buttons as follows:
“Setup”, “Confirm”, “Cancel”, “+” and “-”. On the spot, it's forbidden to replace the batteries.
Note : “Setup”, “Confirm” and “Cancel” are single-spring buttons.
These buttons can only be springed once even if you press them continuously, and the interval between two springs should not be less than 1 second. “+” and “-” are continuous-spring buttons and can be springed by continuous pressing. Setting can only be affected after pressing “Confirm”. After setting, press “Cancel” to return to the normal mode. Effective setting can be kept till the next setup, even if without power.
6.2 Illustration of display:
Normal: gas concentration
Sensor fault: FAUL; yellow LED is on (only for LEL)
High concentration protection: FAUL; 3 LED are on (only for LEL)
Low alarm: gas concentration; red low alarm LED on
High alarm: gas concentration; red low and high alarm LED on
Low alarm setting: “F--1”
BS03 Fixed Gas Detector Operation Manual the enclosure through the pipe connector, compaction circle, air-proof closing plug and the wire connection hole. According to the explosion-proof requirement, please don't take out the explosion-proof closing plug from the unused wire connection holes.
Please don't throw away any part inside the enclosure or the PCB.
5.3 All the wires should be connected to the terminals. The terminal instruction is as follows:
Icon Name
24V Anode of power
GND
Iout
H.S
Cathode of power
Current output
High alarm
Function
Power input
Power input
Current output
High alarm output
Specifications
DC24V±25%
DC24V±25%
4~20mA
Switch relay
L.S Low alarm Low alarm output Switch relay
5.4 After the correct wire connection, take out the useless wire from the enclosure. Then tighten the compaction circle, rubber air-proof circle and wire. Explosion-proof soft tube can also be connected with the device directly.
Note : The size of the wire between the controller and detector should be not less than 6mm, and the distance should be note more than
1000m.
5.5 After checking all the connection well, install the display PCB and the front cover. Make sure O-type circle is put on and connected with the cover tightly.
BS03 Fixed Gas Detector Operation Manual
4.1 Installation position
4.1.1 For petrol gas, oil gas and alcohol gas etc. which is heavier than the air, the position is 0.3m-0.6m higher than the ground.
4.1.2 For natural gas, CH4 etc which is lighter than the air, the position is 0.5m-2m higher than the gas source.
Note : Gas density more than 0.97kg/CBM, then it's heavier.
Gas density less than 0.97kg/CBM, then it's lighter.
4.1.3 The position should be far away from shocking, shattering, strong electromagnetic interference. Around the position, there should be at least 0.3m empty place.
4.1.4 The position should be within 1m around the possible gas leakage area, such as valve, pipe connection point, gas outlet place.
Please try to install it nearer to the above places, but avoid influencing the working of the other equipments. Please avoid the environment of high temperature and humidity. Also please keep it from water swashing, oil and mechanical damage. Please also consider the convenience of maintenance and calibration.
4.1.5 For large scale detection, we suggest install 1pc every 10-12 square meters, so as to get the best detection result.
4.2 Dimensions