Siemens SDR vacuum recloser Instruction manual
Below you will find brief information for vacuum recloser SDR. The SDR vacuum recloser is a three-phase, outdoor device designed for repeated opening and reclosing in case of a fault. It is comprised of two main components: the recloser switch unit and the control cubicle. The recloser switch unit is comprised of the poles, the operating mechanism and the operating mechanism housing. The control cubicle is equipped with integrated pole-mount brackets. It can be installed on the recloser pole or substation frame at an operating height as preferred by the user.
advertisement
Assistant Bot
Need help? Our chatbot has already read the manual and is ready to assist you. Feel free to ask any questions about the device, but providing details will make the conversation more productive.
Type SDR up to 27.6 kV vacuum recloser instruction manual
Installation operation maintenance E50001-F710-A249-X-A400
Answers for energy.
2
Hazardous voltages.
Will cause death, serious injury or property damage.
Always de-energize and ground the equipment before maintenance. Read and understand this instruction manual before using equipment. Maintenance should be performed only by qualified personnel. The use of unauthorized parts in the repair of the equipment or tampering by unqualified personnel will result in dangerous conditions which will cause death, severe injury or equipment damage. Follow all safety instructions contained herein.
Important
The information contained herein is general in nature and not intended for specific application purposes. It does not relieve the user of responsibility to use sound practices in application, installation, operation and maintenance of the equipment purchased. Siemens reserves the right to make changes in the specifications shown herein or to make improvements at any time without notice or obligation. Should a conflict arise between the general information contained in this publication and the contents of drawings or supplementary material or both, the latter shall take precedence.
Qualified person
For the purpose of this manual a qualified
person is one who is familiar with the installation, construction or operation of the equipment and the hazards involved.
In addition, this person has the following qualifications:
Is trained and authorized to de-energize, clear, ground and tag circuits and equipment in accordance with established safety procedures.
Is trained in the proper care and use of protective equipment, such as: rubber gloves, hard hat, safety glasses or face shields, flash clothing, etc., in accordance with established safety practices.
Is trained in rendering first aid.
Further, a qualified person shall also be familiar with the proper use of special precautionary techniques, personal protective equipment, insulation and shielding materials, and insulated tools and test equipment. Such persons are permitted to work within limited approach of exposed live parts operative at 50 volts or more shall, at a minimum, be additionally trained in all of the following:
The skills and techniques necessary to distinguish exposed energized parts from other parts of electric equipment
The skills and techniques necessary to determine the nominal voltage of exposed live parts
The approach distances specified in
NFPA 70E and the corresponding voltages to which the qualified person will be exposed
The decision-making process necessary to determine the degree and extent of the hazard and the personnel protective equipment and job planning necessary to perform the task safely.
Introduction
General description
Receiving, handling and storage
Installation and commissioning
Operation
Maintenance
Technical data
Appendix
Installation and commissioning report
Table of contents
32 - 33
34 - 41
42 - 48
49 - 55
4 - 5
6 - 15
16 - 17
18 - 27
28 - 31
Note:
These instructions do not purport to cover all details or variations in equipment, nor to provide for every possible contingency to be met in connection with installation, operation or maintenance. Should further information be desired or should particular problems arise that are not covered sufficiently for the purchaser’s purposes, the matter should be referred to the local sales office.
The contents of this instruction manual shall not become part of or modify any prior or existing agreement, commitment or relationship. The sales contract contains the entire obligation of Siemens Energy,
Inc. The warranty contained in the contract between the parties is the sole warranty of
Siemens Energy, Inc. Any statements contained herein do not create new warranties or modify the existing warranty.
3
4
Introduction
Introduction
These instructions apply to the vacuum recloser type SDR and are intended to familiarize personnel with the mechanical design and function of the recloser. These instructions also include notes on operation and information concerning installation and maintenance.
The purpose of this manual is to assist the user in developing safe and efficient procedures for the installation, maintenance and use of the equipment.
Personnel must familiarize themselves as early as possible with the instructions and other documents provided in order to gather any further relevant information on the recloser and its features.
Should further information be desired, or should particular problems arise that are not covered in the operating instructions, the matter should be referred to the local
Siemens sales office.
In written or verbal communications, please provide the serial number of the recloser (see Figure 41), the complete description from the operating instructions, and use only the designations and numbers for sub-parts used in this instruction manual.
Designated use
The recloser is deemed properly used when it is operated in accordance with the agreed terms and conditions of supply and technical data and also the equipment and special tools supplied are used exclusively for their intended purpose in accordance with the provisions of these operating instructions and applicable laws, codes, regulations and standards.
Any other use is forbidden, unless the consent of Siemens has been obtained.
If the above-mentioned conditions are not observed or the safety instructions are not followed, there can be danger from:
High voltage
Charged springs
Falling and/or tipping parts
Charged capacitors.
Responsibility of the operator
In order to avoid incidents, mis-operation or equipment damage, the party responsible for transportation, installation, operation, maintenance and disposal of the recloser or of parts thereof must ensure that only qualified and instructed personnel are assigned to work. Before starting work, regularly thereafter and following any unusual occurrences, personnel shall be instructed concerning the possible hazards and the safety measures required. Regulations and instructions for safety at work (together with instructions on action to be taken in the event of incidents and/or fire) shall be available to personnel. Equipment and facilities required for safe work and also the personal protective equipment, clothing, etc., necessary for certain procedures shall be available and used. Only spare parts, lubricants and auxiliary materials approved by Siemens shall be used.
Introduction
Hazardous voltages.
Will cause death, serious injury and property damage.
Do not contact energized conductors.
De-energize and ground high voltage conductors before working on or near them.
Signal words
The signal words "danger," "warning" and
"caution" used in this manual indicate the degree of hazard that may be encountered by the user. These words are defined as:
Danger - Indicates an imminently hazardous situation that, if not avoided,
will result in death or serious injury.
Warning - Indicates a potentially hazardous situation that, if not avoided,
could result in death or serious injury.
Caution - Indicates a potentially hazardous situation that, if not avoided, may result in minor or moderate injury.
Caution (without safety alert symbol) -
Indicates a potentially hazardous situation that, if not avoided, may result in property damage.
Hazardous procedures
In addition to other procedures described in this manual as dangerous, user personnel must adhere to the following:
1. Always work only on de-energized equipment. Always de-energize the equipment before performing any tests, maintenance or repair. The equipment should be isolated, grounded and have all control power removed before performing any tests, maintenance or repair.
2. Always perform maintenance on the control cabinet only after the capacitors are discharged (see page
14).
3. Check to be certain the indicator flag is green, indicating that the switch unit is in the open position (see Figure 7, page 9).
4. Always let an interlock device or safety mechanism perform its function without forcing or defeating the device.
Field service operation and warranty issues
Siemens can provide competent, welltrained field service representatives to provide technical guidance and advisory assistance for the installation, overhaul, repair and maintenance of Siemens equipment, processes and systems.
Contact regional service centers, sales offices or the factory for details, or telephone Siemens field service at
+1 (800) 347-6659 or +1 (919) 365-2200 outside the U.S.
For medium voltage customer service issues, contact Siemens at +1 (800) 347-
6659 or +1 (919) 365-2200 outside the
U.S.
5
6
General description
Recloser principle and design
Reclosers are used in distribution systems. Like circuit breakers, reclosers are used to make and break normal and fault currents. Reclosers are fully equipped with sensors and a controller to provide a means of protection and control. In case of a line fault, reclosers can break and make currents several times, thus avoiding longer network interruptions due to temporary faults.
Type SDR vacuum reclosers are outdoor devices designed for repeated opening and reclosing in case of a fault, as specified in ANSI/IEEE standard C37.60.
The vacuum recloser consists of two main components: the recloser switch and the control cubicle.
This instruction manual covers information related to the recloser switch unit and the control cubicle. The instruction manual does not cover the controller or related accessories (for example, modems).
For information pertinent to the controller, refer to the Siemens Protection
Devices Limited instruction manuals.
The manufacture, design and testing of the vacuum recloser is based on current regulations and standards and state-ofthe-art technology. The product conforms to the following standards:
ANSI/IEEE C37.60/IEC 62271-111
IEC 60255-11
IEC 60255-21-1 Class I
IEC 60255-21-2 Class I
IEC 60255-21-3 Class I
IEC 60255-22-1 Class III
IEC 60255-22-2 Class IV
IEC 60255-22-3 Class III
IEC 60255-22-4 Class IV
IEC 60255-22-5
IEC 60255-22-6
IEC 60255-25
IEC 60255-5
IEC 62271-1
Note: IEEE C37.60 and IEC 62271-111 are the same document (dual logo IEEE and
IEC).
General description
Recloser switch unit with encapsulated vacuum interrupter
The recloser switch unit is comprised of the poles, the operating mechanism and the operating mechanism housing. The side sections with the support feet form the base of the recloser switch unit. The switch unit can be secured to the pole mounting or substation frame.
C B A Upper terminal
(Usually line side)
Pole with integrated vacuum interrupter
Side section with support foot
Lower terminal
(Usually load side)
Operating mechanism housing
Figure 1: Recloser switch unit rear view
A B
Position indicator
(underneath)
Pole with integrated vacuum interrupter
C
Upper terminal
(usually line side)
Lower terminal
(usually load side)
Name plate
Connector for control cable
Connector for sensor cable (optional)
Figure 2: Recloser switch unit front view
Ground terminal M12
7
8
General description
Pole
The poles are molded using cycloaliphatic epoxy resin specially designed for outdoor use. The vacuum interrupters are encapsulated in the pole units. In addition, each pole contains a current transformer and may also contain an optional voltage sensor.
The sequence of the poles is C - B - A
(sequence left to right when viewed from the lower terminal side of the recloser switch unit - rear of recloser) (refer to
Figure 4). This is marked on the operating mechanism housing by identification indents (A = 1 indent, B = 2 indents and C
= 3 indents). This sequence identifies the currents IA, IB and IC of the controller.
Upper terminal 3/4” with terminal connector
Upper terminal
(Usually line side)
Integrated current transformer (CT), generally used as load side
Integrated voltage sensor
(optional), generally used as load side
Lower terminal
(Usually load side)
Lower terminal
3/4” with terminal connector
Figure 3: Pole with integrated vacuum interrupter
C B A
Phase identification indents
Figure 4: Pole sequence (C-B-A or 3-2-1 when viewed from rear)
Phase identification indent
Figure 5: Detail of pole identification indent
(phase C or 3)
General description
Current transformers (CTs)
The type SDR vacuum recloser is equipped with one integrated current transformer per pole. The current transformer is the conventional type (iron core magnetic) and has a ratio of 800 A:1 A. It is for protection purposes and optimized for operation with the controller (see control cubicle on page 13). The secondary signal is based on IEC 60044-1.
The secondary wires of the CT are connected to a varistor for each pole in the switch unit. This prevents the occurrence of high voltages (due to open-circuit CT secondary) if the control cable is removed while the switch unit is in operation. Do not disable the varistor circuit.
The signal transfer from the CTs to the controller is by the control cable. A separate cable is not required.
Voltage sensor (optional)
The SDR vacuum recloser can be equipped with integrated resistive voltage sensors
(optional). The integrated resistive voltage sensors have a high level of accuracy and are used both for measurement and protection purposes. The ratio is adapted to operation with the controller (see control cubicle on page 13) and provides a
110 V/√3 secondary signal with rated primary voltage applied to the recloser.
No other controller should be used for the voltage measurement as the sensor design and controller design are coordinated. An optional separate sensor cable equipped with special screening (shield) is used for the signal transfer from the voltage sensors to the controller. This results in a high level of accuracy and protection against disturbances. The sensor cable is connected at the back of the operating mechanism housing next to the control cable.
The secondary wires of the voltage sensors are connected to a varistor for each pole in the switch unit. This prevents the occurrence of high voltage on the sensor cable if the sensor cable is removed while the switch unit is in operation. Do not disable the varistor circuit.
Operating mechanism
The operating mechanism for the vacuum interrupters is located in a metal housing.
To meet the required fast reclosing cycles, a magnetic actuator with capacitors as energy storage drives the switch unit. A gang-operated mechanism connects the magnetic actuator with the vacuum interrupters.
The operating mechanism is equipped with anti-condensation space heaters. It is operated together with the heating in the control cubicle and controlled by a thermostat.
A mechanical position indicator is easily visible from the ground and shows the current switch position of the recloser
(open = green, closed = red). The colored display is reflective in the dark when using a flashlight.
Lockout handle
A lockout handle with ring protrudes from the operating mechanism housing. The ring is colored bright yellow and is therefore easily seen.
By pulling the lockout handle, the recloser opens and remains locked in this position.
The locking has a dual electrical effect; it locks out both the controller and the electronics. It also mechanically locks the magnetic actuator.
As long as the lockout handle is pulled out, it is not possible to close the switch unit electrically, whether locally or from a remote location. The interlocking is not reset until the lockout handle has been completely pushed in. After this, the switch unit can be closed electrically, either locally or from the control room.
The switching is described in the Operation section of this instruction manual (see page 28).
Note: The lockout handle must be fully pushed in or the interlocking will prevent closing of the recloser.
Recloser position
Closed
Open
Lockout handle
Color of position indicator
Table 1: Recloser position and indicator color
Position indicator
Operations counter
Figure 6: Operating mechanism (viewed from below)
Lockout handle
Red
Green
Position indicator
Figure 7: Operating mechanism with lockout handle pulled out
9
10
General description
Operations counter
Figure 8: Operations counter on the bottom of the switch unit
Operations counter
A mechanical operations counter is installed at the bottom of the recloser switch unit. It records the total number of switching operations independently of the electrical recording in the controller. The operations counter is used to keep track of the total number of operations of the switch unit in case the controller is replaced or the electronic counter is reset in the controller.
General description
Optional line-side external voltage sensors
Holes for king bolt
(not visible from this view)
Switch unit attachment points
Figure 9: Pole-mounting frame (design 1)
Lifting eyes
Optional line-side surge arresters
Optional load-side surge arresters
Holes for king bolt
(not visible from this view)
Switch unit attachment points
Optional load-side surge arresters
Figure 10: Pole-mounting frame (design 2)
Pole-mounting frames
A pole-mounting frame is used to install the recloser switch unit on an overhead line pole. The mounting frames can also optionally accommodate surge arresters and source side external voltage sensors.
The following pole-mounting frames are available:
Design 1 with provisions for line-side external voltage sensors and line- and load-side surge arresters (see Figure 9)
Design 2 with provisions for load-side surge arresters (see Figure 10).
It is recommended that at least two 0.75 inch bolts be used as king bolts to secure the pole-mounting frame to the pole.
For installing within substations, a special frame is available (see installing at the substation on page 23).
11
12
General description
Control cubicle
The control cubicle is equipped with integrated pole-mount brackets. It can be installed on the recloser pole or substation frame at an operating height as preferred by the user.
The control cubicle is equipped with a lockable door with provision for a padlock.
Behind the door is a swing frame, which contains the controller, miniature circuit breakers and a general power outlet (GPO) for a laptop. Behind the swing frame, there are printed circuit boards (PCB), rechargeable batteries and wiring connections.
The control cubicle is equipped with a thermostat-controlled anti-condensation heater (space heater). The thermostat also controls the space heater in the switch unit. Each heater consists of two resistors.
The heating is switched off above approximately 40° C.
PCB1: Power supply board: power supply unit for charging of batteries and capacitors, protected by CB1
PCB2: Switch unit driver (SUD): controls the magnetic actuator with monitoring of end positions, monitoring for broken cable and with discharge switch for the capacitors
PCB3: Capacitors for magnetic actuator
Door
Control cubicle
Miniature circuit breakers
CB1, CB2 and CB3
General power outlet
(GPO)
Figure 11: Control cubicle with door open
General description
Pole-mount bracket
Controller
(illustrated partially withdrawn)
Open pushbutton
Swing panel
Close pushbutton
PCB3
PCB2
PCB1
Controller
Swing panel
Footnote:
1 Arrangement of PCB1, PCB2 and
PCB3 may vary based on order-specific requirements. For actual arrangement, see order-specific drawings included with each control cabinet.
Figure 12: Control cubicle with swing panel open 1
PCB3 PCB2 PCB1
Space heater
Figure 13: Printed circuit boards inside control cubicle 1
Figure 14: Space heater
13
14
General description
Discharge switch for the capacitors
The discharge toggle switch on the switch unit driver (SUD) module/printed circuit board PCB2 serves to discharge the capacitors. In the "discharge capacitors" position (right position), the capacitor charging operation is turned off and the capacitor discharged via a resistor – discharge of the capacitors takes roughly one minute.
In the "operating" position (left position), as shown in Figure 15, the red discharge
LED next to the switch shows the voltage at the capacitor is more than 40 V (LED on). Work on the capacitor should only be performed once the LED no longer illuminates.
For normal operation, the switch must be brought into the "operating" position (left position) – however, the LED does not light up during operation.
Discharge
LED
Toggle switch for discharging capacitor
(operating position)
Figure 15: Printed circuit board PCB2 - toggle switch for discharging capacitor
Hazardous voltage.
Could result in serious injury or equipment malfunction.
For maintenance work, the toggle switch on PCB2 must be in the
"discharge capacitors" position (pointing right). Do not work on the capacitor circuits when the red discharge LED is lit.
For normal operation, the toggle switch on PCB2 must be in the
"operating" position (pointing left).
General description
Auxiliary power supply
The control cubicle works on an internal
48 Vdc bus, which is provided by rechargeable batteries as an element of an uninterruptible power supply. This internal bus is energized from PCB1, which charges the batteries and the capacitors. Charging of the batteries is automatically compensated for temperature.
PCB1 is supplied by auxiliary power provided on site, either through a usersupplied low-voltage supply or individual power transformer (optional). This supply needs to be connected to terminals on terminal block X1. PCB1 is then protected by the miniature circuit breaker CB1.
The same supply is used for the heaters and the general power outlet (GPO). They are protected by miniature circuit breaker
CB2.
Rechargeable batteries
Four-12 V batteries are supplied with the recloser. They are to be installed in series on site (see Installation and commissioning on page 22). The batteries are protected by the miniature circuit breaker CB3. The batteries ensure minimal stand-by operation for 48 hours at 20° C from a fully charged initial condition.
If miniature circuit breaker CB3 opens or trips, it disconnects the control power for the controller and the controller will neither operate the recloser nor protect the network. Control and protection functions restart automatically by closing
CB3.
If the batteries are not in use, they should be recharged after six months.
User interfaces
The following interfaces are available for purchaser use:
Three binary inputs (BI) and three binary outputs (BO) are provided on the terminal rail on the rear of the controller, as identified on the wiring diagrams. The binary inputs are switched to 48 V (wet contacts). The binary outputs are potential-free (dry contacts).
On the front of the controller is a USB interface for connecting a laptop computer to set parameters, download events and update firmware.
For connection to a remote terminal unit
(RTU) or supervisory control and data acquisition (SCADA):
RS/EIA-485 port at rear
Connection for IRIG-B signal at rear
(optional)
Optical ports (Rx/Tx) (optional)
RS/EIA-232 port at rear (optional).
Communication protocols DNP3, Modbus and IEC 60870-5-103 are supported through the communication interfaces.
An optional power supply can be provided for additional communication modules
(radio unit or modem). It is directly connected to the auxiliary power supply through CB2 and not connected to the uninterruptible power supply.
Additional BI/BO may be provided as an option.
Additional BI/BO for purchaser use
Rear communication interfaces
Figure 16: Controller rear interfaces
15
16
Receiving, handling and storage
Heavy weight.
Can result in death, serious injury or property damage.
Obtain the services of a qualified rigger prior to hoisting the recloser switch unit to assure adequate safety margins in the hoisting equipment and procedures to avoid damage.
Introduction
This portion of the manual covers the receiving, handling and storage instructions for type SDR vacuum reclosers.
This section of the manual is intended to help the user identify, inspect and protect the recloser prior to its installation.
Receiving procedure
Make a physical inspection of the shipping container before removing or unpacking the recloser. Check for shipment damage or indications of rough handling by the carrier. Check each item against the manifest to identify any shortages.
Shipping damage claims (when applicable)
Follow normal shipment damage procedures, which should include:
1. Check for visible damage upon arrival.
2. Visible damage must be noted on delivery receipt and acknowledged with driver‘s signature. Notation
"Possible internal damage, subject to inspection" must be on delivery receipt.
3. Notify the Siemens field service at
+1 (800) 347-6659 or +1 (919) 365-
2200 outside the U.S.
4. Arrange for carrier‘s inspection. Do not move the unit from its unloading point.
Receiving, handling and storage
Handling procedure
1. Carefully remove the packing material from the recloser. Keep the shipping pallet for later use if the recloser is to be stored prior to its installation.
2. Inspect for concealed damage.
Notification to carrier must take place within 15 days to assure prompt resolution of claims.
3. The recloser should be appropriately lifted to avoid damaging the recloser.
4. The palleted recloser can also be moved using a properly rated forklift vehicle. The pallets are designed for movement by a standard forklift.
Storage procedure
Whenever possible, store the recloser indoors. The storage environment must be clean, dry and free of such items as: construction dust, corrosive atmosphere, mechanical abuse and rapid temperature variations.
Space heating
Space heating for the control cubicle must be used for both indoor and outdoor storage to prevent condensation and corrosion. The control cubicle space heater should be connected to a 120 Vac auxiliary supply at terminals X-1, X1-2, and X1-5 as shown on Figures 42 and 45, and as discussed in the "Connecting the auxiliary voltage supply" on page 25 of this instruction manual. After these connections have been made, circuit breaker CB2, as shown on Figure 11, must be switched to the "on" position.
17
18
Installation and commissioning
This section provides information about the installation and commissioning with regard to the following:
Required documents
Personnel requirements
Tools, devices and expendable materials to be used
Safety
Recording/documentation.
Hazardous voltages.
Will cause death, serious injury or property damage.
To avoid electrical shock or burns, this equipment must be installed, operated and maintained only by qualified persons thoroughly familiar with the equipment, instruction manuals and drawings.
Heavy weight.
Can result in death, serious injury or property damage.
Obtain the services of a qualified rigger prior to hoisting the recloser switch unit to assure adequate safety margins in the hoisting equipment and procedures to avoid damage.
Installation and commissioning
Mechanical installation
The following documents are required for installation:
These operating instructions
Installation and commissioning report form (see page 49).
A responsible person (or supervisor) must be assigned to oversee the installation and commissioning work. This person must instruct personnel during installation and commissioning tasks, and check for compliance with the applicable safety procedures.
The installation and commissioning work must be performed by authorized personnel who must be qualified persons as described on page 2 of this instruction manual.
Suitable lifting apparatus in good working condition and transport vehicles with sufficient load-bearing capacity must be used for installation.
All safety regulations, including NFPA 70E and OSHA regulations, must be observed.
Installation and commissioning must be documented (see "Installation and commissioning report,“ page 49).
Torque requirements for all hardware are as follows:
.38 inch: (31 lbf-ft ± 5 lbf-ft)
.50 inch: (75 lbf-ft ± 9 lbf-ft)
.62 inch: (120 lbf-ft ± 20 lbf-ft)
.75 inch: (250 lbf-ft ± 40 lbf-ft).
Preparatory work
Both the installation and commissioning report (see page 49) and these installation instructions are based on the sequence of the work to be performed. The on-site conditions may result in deviations from the sequence shown.
The following preparatory work must be performed:
Instruct installation and maintenance personnel with regard to:
1. Safety
2. Cleanliness at installation site
3. Safety markings
4. Dealing with incidents or unexpected conditions
Check delivery documents for completeness
Check all shipping units for shipping damage
Inspect power pole ground conductor and install ground conductor, if necessary
If installation is on substation frame, check foundation for substation frame and install ground connection, if required.
Mounting the recloser on the pole
The recloser is mounted in several steps.
1. Pre-assembly of pole-mounting frame on the ground, including switch unit and including any accessories (such as arresters or voltage sensors).
2. Attachment of pole-mounting frame to the pole.
3. Attachment of control cubicle to the pole.
4. Connection of control cubicle to recloser switch unit.
19
20
Installation and commissioning
Pre-assembly of pole-mounting frame
Pre-assembly of the pole-mounting frame takes place as per the following exploded view drawings. Depending on which pole- mounting frame has been supplied, one of the following pre-assembly procedures must be performed.
Pre-assembly of the pole-mounting
frame - design 1 (see Figure 17)
The pole-mounting frame is made up of the following components:
One recloser switch unit
One pole-mounting frame (design 1)
One support for line-side external voltage sensors and surge arresters
One support for load-side surge arresters
Two leveling feet
Four-.38 inch bolts, washers, lockwashers and nuts
Eight-.50 inch bolts, washers, lockwashers and nuts
Four-.62 inch bolts, washers, lockwashers and nuts.
Figure 17: Assembly of pole- mounting frame (design 1)
Support for line- side external voltage sensors and surge arresters
Lifting eyes
Recloser switch unit
Holes for king bolts
Pole-mounting frame (design 1)
Support for load-side surge arresters
Leveling feet
Figure 18: Assembly of pole- mounting frame (design 2)
Holes for king bolts
Recloser switch unit
Pole-mounting frame (design 2)
Support for load-side surge arresters
Leveling feet
Installation and commissioning
Pre-assembly of the pole-mounting
frame - design 2 (see Figure 18)
The pole-mounting frame is made up of the following components:
One recloser switch unit
One pole-mounting frame (design 2)
One support for load-side surge arresters
Two leveling feet
Four-.38 inch bolts, washers, lockwashers and nuts
Four-.50 inch bolts, washers, lockwashers and nuts
Four-.62 inch bolts, washers, lockwashers and nuts.
Installation of switch unit on the pole
To attach the switch unit, the following components are required:
Pre-assembled pole-mounting frame, including switch unit and supports as shown in Figures 17 or 18
Two-.75 inch mounting bolts (length equal to pole diameter plus four inches)
Four-.75 inch washers, lockwashers and nuts.
Bolts, nuts and washers are not included in the scope of supply.
Figure 19: Lifting of the switch unit
Lifting eyes
Figure 20: Installation of polemounting frame (design 1)
Support for line- side external voltage sensors and surge arresters
Pole-mounting frame (design 1)
Recloser switch unit
Support for loadside surge arresters
Leveling feet
Figure 21: Installation of polemounting frame (design 2)
Lifting eyes (same as shown in Figure 19)
Pole-mounting frame (design 2)
Leveling feet
Recloser switch unit
Support for loadside surge arresters
21
22
Installation and commissioning
Four batteries
Lifting eyes
Polemounting brackets
Figure 22: Lifting of control cubicle
Temperature sensor
Figure 23: Installation of batteries
1. Insert both mounting bolts through the pole and install the washer without tightening (hole spacing
14.12 inches).
2. Lift completely assembled mounting frame using lifting points indicated in
Figures 20-21 (as appropriate), and lower mounting frame onto the king bolts. Tighten hardware to secure.
3. Check that all bolts of the polemounting frame are correctly secured.
Installation of the control cubicle on the pole
To attach the control cubicle the following components are required:
Two-0.50 inch mounting bolts with nuts and washers (length equal to pole diameter plus four inches; not included in scope of delivery)
Control cubicle
Batteries.
1. Insert upper mounting bolt through the pole (hole spacing 42.0 inches).
2. Lift control cubicle with two cables using the lifting eyes and fasten to the upper mounting bolt. Tighten nut by hand.
3. Align control cubicle and insert lower mounting bolt through the pole and fasten.
4. Tighten bolted connections and check stability.
5. Install the four batteries with terminals facing towards each other (per Figure
23) and secure with the velcro strips.
6. Place temperature sensor on the battery under a velcro strip and fasten with the velcro strip.
7. First connect the positive terminal, then connect the adjacent terminals of two batteries using the short connecting cables and finally connect the negative terminals to the control cubicle connection. Make sure the connections have the correct polarity
(compare with the labelling on the cables).
Note: Avoid incorrect polarity of batteries.
Connecting the rechargeable batteries with the wrong polarity will result in damage to the control electronics (PCB2) and also misoperation of the recloser.
Installation and commissioning
Installation at the substation
Assemble the substation frame and secure it to the prepared foundation. Fasten the switch unit and control cubicle in the positions in the substation frame provided.
Substation frame elevation is normally
115.0 inches to the bottom of the switch unit. The frame may be adjusted up to
20.0 inches higher or lower in 2.0 inch increments.
Attachment of the surge arrester
(optional)
The surge arresters must be fastened in the positions provided on the corresponding supports using the bolts supplied with surge arresters or by user.
Attachment of the source side external voltage sensors (optional)
The source side external voltage sensors must be fastened in the positions provided on the corresponding supports using the bolts supplied with voltage sensors or by user.
Electrical installation
The following must be carried out in order to establish the electrical connections:
establish the ground (earth) connection,
connect the recloser switch unit to the control cubicle,
connect the auxiliary voltage, and
establish the high-voltage connection.
Establishing the ground (earth) connection
Both the recloser switch unit and the control cubicle must be connected to the pole ground (earth) or ground (earth) in the substation. The lower pole mount of the control cubicle can be used as a grounding plate for all connections. If surge arresters are installed, these must also be securely grounded (earthed).
For correct grounding (earthing), the following must be observed:
The recloser (switch unit plus control cubicle) must be grounded (earthed) in accordance with local regulations and work practices.
The cable to be used must be suitable for grounding (earthing). This particularly applies for the cross section of the grounding (earthing) cable and connections.
Figure 24: Assembly of the substation frame
Connector for control cable
Connector for sensor cable
(optional)
Ground
(earth) terminal M12
Figure 26: Recloser switch unit connections - front view
Foundation bolt 4 x .38 x 16 in
2.0 (50)
13.8 (350)
2.0 (50)
13.8 (350)
60.2 (1,530)
70.9 (1,800)
Connector for sensor cable
(optional)
Cable gland for auxiliary supply and user interface cable
Connector for control cable
Figure 25: Foundation plan Figure 27: Control cubicle connections - bottom view
23
Surge arrester load-side (optional)
Ground connection for surge arrester
Control cable
Control cubicle
Ground terminal .5
(control cubicle)
Installation and commissioning
Switch unit
Ground terminal M12
(switch unit)
Ground wire
Ground level
Pole ground
Figure 28: Connection of cables and grounding (earthing) of recloser
For grounding (earthing) to be effective, the cables (control and optional sensor cable) must be installed as close together as possible with the ground (earth) conductor (see Figure 28). Ideally they should be bundled together.
Connect cables between recloser switch unit and control cubicle
1. Connect control cable to the recloser switch unit and control cubicle. The plug-in connection on the control cable is protected against polarity mismatch.
2. Secure plugs to prevent them from loosening using the locking clip.
3. Connect sensor cable (optional) to the recloser switch unit and control cubicle. The plug-in bolted joint on the sensor cable is protected against polarity mismatch.
4. Check plugs are inserted correctly and secured.
5. Fasten the control and sensor cable to the pole using appropriate means (for example, cable ties).
6. Loop and fasten excess lengths of cable in the area of the pole-mounting frame.
24
Installation and commissioning
Connecting the auxiliary voltage supply
The auxiliary voltage is supplied either by an external transformer or an external low-voltage power supply. In both cases, insert the connection cable through the cable gland (see Figure 27) into the control cubicle and attach to the corresponding terminals.
Phase to: X1-1
Neutral to:
Ground to:
X1-2
X1-5
Establishing high-voltage connection
The recloser switch unit is equipped with terminal connectors to fasten cables or with flat spade connectors, depending on the configuration specified by the purchaser.
Commissioning
The equipment must be commissioned as follows. The installation and commissioning report (see page 49) serves as documentation and a checklist.
Terminal connectors for purchaser use BI/BO
(terminal block X4)
X2
Figure 29: Terminal connectors
Terminal connectors for auxiliary supply
(terminal block X1)
X3 X4
Thermostat
X1
Hazardous voltages.
Will cause death, serious injury and property damage.
Do not contact energized conductors.
De-energize and ground the equipment before working on or near high voltage conductors.
25
Figure 30: Controller front panel
Installation and commissioning
Function tests
1. Switch on miniature circuit breakers
CB1 and CB3 (see Figure 11).
The start up of the controller is shown in the display.
The PROTECTION HEALTHY LED lights up green after approximately
30 s.
The status LED AuxPower OK lights up green.
The status LED Recloser OK lights up green.
The LED next to F1 lights up green.
Position indicator on the bottom of the recloser switch unit is green
(open).
2. Press Close pushbutton.
The recloser closes.
LED next to F1 goes out.
LED next to F2 lights up red.
During switching, the Recloser OK status LED goes out briefly
(capacitors are charged for the next switching operation). Within 1 s, the status LED lights up green again. A longer period indicates the charging level of the batteries is very low or CB3 is not switched on.
Position indicator on the bottom of the recloser switch unit is red.
3. Press Open pushbutton.
Recloser opens.
LED next to F2 goes out.
LED next to F1 lights up green.
Position indicator on the bottom of the recloser switch unit is green.
4. Press F2 key (close) on the controller and then press ENTER.
The recloser closes.
LED next to F1 goes out.
LED next to F2 lights up red.
During switching the LED status
Recloser OK extinguishes briefly.
Position indicator on the bottom of the recloser switch unit is red.
5. Press F1 key (open) on the controller and then press ENTER.
Recloser opens.
LED next to F2 goes out.
LED next to F1 lights up green.
Position indicator on the bottom of the recloser switch unit is green.
26
Installation and commissioning
6. Press Close pushbutton or F2 key
(close) on the controller and then press
ENTER.
The recloser closes.
LED next to F1 goes out.
LED next to F2 lights up red.
Position indicator on the bottom of the recloser switch unit is red.
7. Mechanically operate by pulling the lockout handle.
Recloser opens.
LED next to F2 goes out.
LED next to F1 lights up green.
Position indicator on the bottom of the recloser switch unit is green.
8. Press Close pushbutton.
No switching operation shall take place.
9. Activate F2 key (CLOSE) on the controller and then press ENTER.
No switching operation shall take place.
10. Push lockout handle back in completely.
11. Press Close pushbutton or F2 key
(CLOSE) on the controller and then press ENTER.
The recloser closes.
LED next to F1 goes out.
LED next to F2 lights up red.
Position indicator on the bottom of the recloser switch unit is red.
12. Switch on miniature circuit breaker
CB2.
At external temperatures of < 35° C, the heaters become warm after approximately one minute.
Final tasks
1. Adjust controller to the correct desired setting file.
The controller is default set in Group
1.
2. If necessary, select another group for a user-specific parameter set.
3. If applicable, check the voltage and current readings of the controller.
4. Check date and time on controller and correct if necessary.
5. Set trip counter to zero (at initial installation only).
6. Delete event memory (at initial installation only).
7. If necessary, download events for further documentation.
8. Close and latch swing panel.
9. Fit controller cover and fasten.
10. Close and secure control cubicle door.
Note: For further information and additional operating instructions for the controller, use the separate controller instruction manuals. These can be downloaded at http://www.reyrolleprotection.com/individual_product.
php?product_id=233 .
27
Operation
Control cubicle
Controller
Close pushbutton
Open pushbutton
Figure 31: Control cubicle with controller
Operation
The recloser is just one device in a distribution system. The user of the recloser must set the controller protection and control parameters to suit the user’s distribution system needs, and to provide reliable, safe and trouble-free operation of the recloser.
Safety instructions for operation
In addition to the local safety rules and work practices, special precaution must be taken:
The accessories required to operate the recloser must be stored in a clean location and must be checked regularly for completeness and good condition.
All keys must be accessible only to the authorized operating personnel.
No modifications should be made to the recloser. This includes, but is not limited, to removal of parts, opening the operating mechanism housing and any modification (including adjustment) of the drive system of the recloser.
The control cable and the optional sensor cable must not be removed during operation. Removing these cables would mean no further electrical operation could be performed and no measurement values or other signals could be sent from the recloser switch unit to the controller.
Switching
Switching comprises electrical switching
(remote and/or local operation) and mechanical switching (by means of the lockout handle).
Switching is carried out automatically by the controller to protect the network by remote control or manually on site.
Local operation
Local operation describes the manual electrical switching of the recloser on site.
Manual switching using the lockout handle is discussed in the Lockout operation section of this instruction manual on page
30.
These switching actions can be carried out from the control cubicle using the Close/
Open pushbuttons or using the function keys on the controller.
Hazardous voltages.
Will cause death, serious injury or property damage.
Always de-energize and ground the equipment and all terminals before performing any work near high-voltage conductors.
Work on the recloser switch unit or the control cubicle should be performed only by qualified personnel.
Do not open the inner panel of the control cubicle, as interior parts energized at voltages higher than 50 V are present.
Do not disconnect control or sensor cables while recloser is energized, as connectors contain energized parts.
28
Operation
Switching using Close/Open pushbuttons
Open/Trip the recloser
1. Press the Open pushbutton.
The recloser opens.
After switching, the green LED next to the function key F1 shows at the open position has been reached.
The red LED next to F2 is off.
The switch action is complete.
The mechanical position indicator on the bottom of the recloser switch unit shows green.
Closing the recloser
1. Press the Close pushbutton.
The recloser closes.
After switching, the red LED next to the function key F2 indicates the close position has been reached.
The green LED next to F1 is off.
The switch action is complete.
The mechanical position indicator on the bottom of the recloser switch unit shows red.
Switching via the controller
Opening the recloser
1. Press the function key F1.
2. Press the Enter key.
The recloser opens.
After switching, the green LED next to the function key F1 indicates the open position has been reached.
The red LED next to F2 is off.
The switch action is complete.
The mechanical position indicator on the bottom of the recloser switch unit shows green.
Closing the recloser
1. Press the function key F2.
2. Press the Enter key.
The recloser closes.
After switching, the red LED next to the function key F2 indicates the close position has been reached.
The green LED next to F1 is off.
The switch action is complete.
The mechanical position indicator on the bottom of the recloser switch unit shows red.
Figure 32: Controller
F1 function key Open
F2 function key Close
Enter key
29
30
Operation
Figure 33: Lockout handle with ring for manual operation (pushed in, normal operation)
Figure 34: Lockout handle with ring for manual operation (pulled out, recloser open and locked out)
Lockout operation
Lockout operation combines the mechanical tripping / opening of the recloser and the interlocking to inhibit subsequent closing of the recloser.
The lockout can also be operated when under load.
For three-pole recloser, all three poles will be operated simultaneously by the mechanical link of all poles.
Open the recloser
1. Using a hot stick or suitable rod from the ground, pull down the lockout handle until it reaches the end (lower) position.
The recloser opens. By operating the lockout mechanism, the recloser is opened mechanically and locked in this position.
The mechanical position indicator on the bottom of the recloser switch unit shows green.
The green LED next to the function key F1 in the controller indicates the switch unit has operated.
The switch action is completed.
As long as the lockout handle is pulled out, it is not possible to close the recloser electrically, whether locally or from a remote location.
Closing the recloser electrically from the controller
1. Using a hot stick or suitable rod from the ground, push the lockout handle back in completely.
2. Press the F2 key.
3. Press the Enter key.
The recloser closes.
After switching, the red LED next to the function key F2 indicates the switch position has been reached.
The green LED next to F2 is off.
The switch action is complete.
The mechanical position indicator on the bottom of the recloser switch unit shows red.
Closing the recloser electrically using the Close/Open pushbuttons
1. Using a hot stick or suitable rod from the ground, push the lockout handle back in completely.
2. Press the Close pushbutton.
The recloser closes.
After switching, the red LED next to the function key F2 indicates the switch position has been reached.
The green LED next to F2 is off.
The switch action is complete.
The mechanical position indicator on the bottom of the recloser switch unit shows red.
Note: The lockout handle needs to be pushed back completely. Otherwise, the interlocking still prevents closing.
Operation
Malfunction
Failure of the auxiliary power supply
"Aux power OK" does not light up
Heating and GPO socket do not work
Failure of batteries
Closing of the recloser is blocked
Incomplete recloser cycle > only switching off is possible
Remedy
The auxiliary power supply is protected by a miniature circuit breaker in the front plate of the swing frame
1. Check miniature circuit breaker CB1 and switch on if necessary.
2. Check the status of the external auxiliary power supply.
Check miniature circuit breaker CB2 and switch on if necessary.
The batteries are protected by a miniature circuit breaker
(behind the swing panel).
1. Check miniature circuit breaker CB1 and switch on if necessary.
2. Check the battery status via the controller menu and replace batteries if necessary.
Manual lockout handle is not fully returned to (pushed in) starting position.
1. Push manual lockout handle back in completely.
Auxiliary power supply may be inadequate or capacitors may be faulty. In this case, the controller’s self-monitoring function can block the full cycle.
1. Check fault messages from the controller.
Table 2: Troubleshooting
31
32
Maintenance
Hazardous voltages.
Will cause death, serious injury or property damage.
Always de-energize and ground the equipment and all terminals before performing any work near high-voltage conductors.
Work on the recloser switch unit or the control cubicle should be performed only by qualified personnel.
Do not open the inner panel of the control cubicle, as interior parts energized at voltages higher than 50 V are present.
Do not disconnect control or sensor cables while recloser is energized, as connectors contain energized parts.
General
The recloser switch unit of the SDR vacuum recloser is designed to require no maintenance for 10,000 operating cycles under ANSI/IEEE C37.60 "usual service conditions." Regular monitoring and, if need be, replacement of the batteries is necessary for the control cubicle. Regular maintenance is required for components in the control cubicle, primarily consisting of checks of cleanliness, tightness of connections, battery test and similar activities.
Maintenance plan
The following work should be carried out as part of regular inspections reflected in
Table 3.
Spare parts
Spare parts must be replaced only by instructed and certified personnel. Refer to list in Table 4.
Maintenance
Work to be performed
Visual inspections
1. Terminals clean and undamaged
2. No visible corrosion or damage to metal parts and cables
3. No loose parts (for example, bolts or connections)
4. Ground (earth) connections secure and undamaged
5. Labelling clearly legible
6. Control cubicle undamaged and correctly secured
Function tests
1. Controller indicates fault-free operation of the auxiliary power supply, batteries and capacitors (monitoring LEDs)
2. Fault-free operation of communication modules
3. Perform battery test or check result of last battery tests at the controller
Protection tests
1. Protection test using secondary injection equipment, in conjunction with recloser function test (see Function test in the Installation and commissioning section of this instruction manual)
2. Function test of lockout handle
Reset counter "Switching operations since last visit" (refer to controller instructions)
Recommended interval
12 months (adjust interval according to experience)
12 months (as part of visual inspection)
Four years (adjust interval according to experience)
Following every maintenance session
Table 3: Maintenance plan
Table 4: Spare parts
Accessory/spare part
Surge arresters (3EK7)
Auxiliary power supply (PCB1)
Switch unit driver (PCB2)
Capacitor board (PCB3)
External current transformer
External voltage transformer
Transformer 11 kV for auxiliary voltage supply
Transformer 12 kV for auxiliary voltage supply
Transformer 13.8 kV for auxiliary voltage supply
Current/voltage transformer pole-mount frame
Control cable
Sensor cable
Cover for position indicator
Bird guards
Set of terminal connectors (six pieces)
Set of batteries (four batteries, 12 Ah, 48 V)
Heaters
Type SDR up to 27.6 kV vacuum recloser instruction manual
Order number
On request
On request
On request
On request
On request
On request
On request
On request
On request
On request
On request
On request
On request
On request
On request
On request
On request
E50001-F710-A249-X-4A00
33
Technical data
Table 5: Main characteristic data
Characteristic
Rated maximum voltage U r
Unit kV
Rated continuous current I r
Rated lightning impulse withstand voltage U p
Power frequency insulation level withstand test voltage (one minute dry) U d
Rated symmetrical interrupting current I sc
Rated symmetrical making current
Mechanical life (operating cycles)
Permissible short-circuit operations
Ambient temperature range
A kV kV kA kA
ºC
Centerline spacing between phases
Flashover distance
Phase/phase (conductor/conductor) in (mm)
Unit in (mm)
Phase/ground (earth) (conductor/ground (earth)) in (mm)
Creepage distance Unit
Phase/ground (earth) (conductor/ground (earth)) in (mm)
Between line-side and load-side terminal in (mm)
Voltage class
15.5
27.6
400, 630, 800 400, 630, 800
110 125
50
12.5, 16
32.5, 42
10,000 up to 200
-30 to +55
14.8 (376)
60
12.5, 16
32.5, 42
10,000 up to 200
-30 to +55
14.8 (376)
12.3 (312)
11.3 (287)
31.9 (810)
46.2 (1,174)
12.3 (312)
11.3 (287
31.9 (810)
46.2 (1,174)
Table 6: Minimum trip currents
Protective function
Phase faults
Ground (earth) faults
Sensitive ground (earth) faults
Table 7: Operating times
Operation time
Closing time
Opening time
Arcing time
Interrupting time
34
Table 8: Dead times for recloser cycle (reclosing interval)
Deal time
Dead time after first open
Dead time after second and third open
Dead time after fourth open
Unit
A
A
A
Minimum trip current
40
40
4
40
40
4
Unit ms ms ms ms
Time
<60
<35
<15
<50
<60
< 5
<15
<50
Unit s s s
Time range
0.2 to 14,400 0.2 to 14,400
2 to 14,400 2 to 14,400
30 to 14,400 30 to 14,400
Technical data
Current transformer data
The current transformer has a ratio of
800 A:1 A.
Voltage sensor data (optional)
The ratio of the voltage sensors is adapted to operation with the controller and provides a 110 V/√3 secondary signal when the recloser is energized at rated maximum voltage.
Ambient conditions
The type SDR vacuum recloser is suitable for use under "usual service conditions" as given in IEEE standard C37.60/
IEC 62271-111, as follows:
Ambient temperature -30° C to 55° C
(standard)
Ambient temperature -40° C to 55° C
(optional)
Solar radiation <1,120 W/m 2
Altitude <1,000 m or less
Altitude correction factor
The insulating capability of insulation in air decreases as the altitude increases due to the reduced air density. The rated lightning impulse withstand voltage values (see
Table 5) are valid according to IEC 62271-1 and IEEE C37.60 up to an installation height of 1,000 m above sea level. Above a height of 1,000 m, the insulation level must be corrected in line with Figure 35.
Example: At 2,500 m altitude, a unit rated
110 kV BIL under "usual service conditions" will have a lightning impulse withstand capability of:
110
K
=
110 e m(h-1000)/8150
=
110
1.193
= 92.2 kV
Auxiliary system Unit
Auxiliary power requirement, controller
Auxiliary power requirements, heating
(control cubicle and switch unit)
Auxiliary power requirement, communication
(dependent on modem used)
External requirements (external user, for instance, laptop)
W
W
W
A
Power consumption
<20
Control cubicle = 80, switch unit = 50
<15 (typical)
10 (maximum value - restricted by power supply provided by user)
Table 9: Power consumption
1.5
1.4
1.3
1.2
1.1
1.0
1.0 1.5 2.0 2.5 3.0 3.5 4.0
Site altitude in thousands of meters
U ≥ U0 x K
U Rated withstand voltage U under standard reference atmospheric conditions
U0 Required rated withstand voltage for the installation location
K Altitude correction factor K = e m (h-1000)/8150
H Installation height in meters m 1.0 for alternating-current voltage, lightning impulse voltage (among the conductors, conductor-ground, longitudinal stress)
Figure 35: Altitude correction factor K
35
36
Technical data
Table 10: Switch unit dimensions and weights
Rated voltage U r
Dimensions: length x width x height in (mm)
Weight lbs (kg)
15 kV and 27.6 kV
46.2 (1,173) x 20.5 (521) x 37.9 (962)
309 (139)
Figure 36: Recloser switch unit dimensions in (mm)
37.9 (962)
24.2 (615)
18.1 (460)
20.5 (521)
14.8 (376)
23.5 (597)
9.8 (250)
14.4 (365)
0.88 (22) x 1.25 (32) slot
0.4 (10)
46.2 (1,173)
Technical data
Rated voltage U r
Dimensions: length x width x height
(without pole-mount brackets)
Weight (without batteries) in (mm) lbs (kg)
15 kV and 27.6 kV
18.0 (457) x 14.0 (356) x 36.0 (914)
150 (67)
Table 11: Control cubicle
Figure 37: Control cubicle dimensions in (mm)
14.0 (356)
36.0 (914)
18.0 (457)
37
38
Technical data
Table 12: Pole-mount frame
(design 1)
Rated voltage U r
Dimensions: length x width x height in (mm)
Weight lbs (kg)
15 kV and 27.6 kV
58.9 (1,496) x 46.2 (1,173) x 41.7 (1,060)
170 (76)
Figure 38: Pole-mount frame
(design 1) dimensions in (mm)
58.9 (1,496)
44.9 (1,141)
18.7 (475)
18.6 (473)
41.7 (1,060)
65.4 (1,662)
41.0 (1,041)
14.8
(376)
14.8
(376)
46.2 (1,173)
Technical data
Rated voltage U r
Dimensions: length x width x height in (mm)
Weight (without batteries) lbs (kg)
15 kV and 27.6 kV
32.7 (831) x 46.2 (1,174) x 39.4 (1,001)
120 (54)
Table 13: Pole-mount frame
(design 2)
Figure 39: Pole-mount frame
(design 2) dimensions in (mm)
32.7 (831)
18.7 (475)
16.2 (413)
39.4 (1,001)
46.2 (1,173)
14.8
(376)
14.8
(376)
46.2 (1,173)
39
40
Technical data
Table 14: Substation frame
Rated voltage U r
Dimensions: length x width x height in (mm)
Weight lbs (kg)
15 kV and 27.6 kV
64.0 (1,626) x 24.1 (612) x 115.0 (2,921)
298 (135)
Figure 40: Substation frame dimensions in (mm)
14.0 (356)
75.1 (1,907)
14.8 (376)
37.9 (962)
46.2 (1,173)
36.0 (914)
18.0
(457)
Box
115.0 (2,921)
29.5 (750)
64.0 (1,626)
60.9 (1,537)
7.9 (200)
13.8 (350)
24.1 (612)
0.38 x 15.0
(9.6 x 381)
2.0 (50)
14.0 (356)
70.9 (1,800)
The nameplate is located at the rear of the recloser switch unit. A copy of the nameplate is placed inside the control cubicle, which is normally shipped together with the recloser switch unit.
Technical data
Figure 41: Nameplate
Rated maximum voltage U r
Rated lightning impulse withstand voltage U p
Rated short-time withstand voltage (60s)
U d
Serial number Manufacturer
Type designation/ order number
Standard
Quality control stamp
Weight m
Design code
Date of manufacture
Rated continuous current I r
Rated symmetrical interrupting current I sc
41
Appendix
Figure 42: Circuit diagram of control cubicle (associated tables on pages 43 and 44)
2 1 e abl r c
5 1 7 8 nso Se e tag Vol t ren Cur
PE N
-9 X1 pen
-10 ose
X1
CCl
CO
-7
-8
-6 ck
X1
OEP
X1
X1
CEP
Lo
T t2 t1
Sta
Sta
Cap
-3
-4 X1 tT2 tT1
X1
Ba
X2 oad
X2
-1 ttP
-4
Ba
RL
Ba
X1
X1
X1
-5
-2
-3 le ab l c tro
C3 C5 C7
Con
42
Appendix
Table 15: Figure 42 signals for PCB1 - power supply
X3
X3
X3
X3
X3
X3
X3
X3
X1
X1
X2
X2
Signals for PCB1 - power supply
Termination Pin Signal
X1 5 PE
3
4
1
2
1
2
1
2
L
N
TE1
TE2
DCDCin
160VP
160VO
48 V
7
8
5
6
Ground
DCDCon
ExtPG
Tlow
Description
Ground/housing
Phase
Neutral
Temperature sensor
Temperature sensor
Operating voltage DC/DC-converter
+ voltage DC/DC-converter
- voltage DC/DC-converter
Charging voltage for batteries +54.5 V
(temperature compensated)
Ground
Control signal from SUD: DC/DC-converter on/off
Power good
Temperature low
43
44
Appendix
Table 16: Figure 42 signals for PCB2 - switch unit driver
X3
X3
X3
X3
X3
X2
X2
X3
X2
X2
X2
X2
X2
Signals for PCB2 - power supply
X1
X1
X1
X1
X2
X1
X1
X1
X1
Termination Pin
X1
X1
1
2
7
8
9
10
1
5
6
3
4
Signal
BatT1
Stat2
Stat1
BatT2
CapT
Lockout
CEP
OEP
COpen
CClose
48 V
4
5
6
2
3
7
8
1
4
5
2
3
6
Ground
RLoad
BattP
DCDCin
Tlow
ManOpen
DCDCon
160V0
160VP
UCapP
UCapN
MA1
MA2
Description
Battery test/stop charging (BO6)
BI2 (status 2) limited operation
BI3 (status 1) operation okay
Battery test/load (BO2)
Capacitor test (BO3)
Lockout (BI10)
Closed end position (BI7)
Open end position (BI6)
Command "open" from controller (BO4)
Command "close" from controller (BO5)
Controlled battery voltage +54.5 V (temperature compensated)
Ground
Load for battery test
Battery positive
Operating voltage for internal components
Temperature low
Manual open
On/off DC/DC-converter for capacitors
Reference voltage for 160 V capacitor voltage
(0V)
160 V capacitor voltage (positive) +160 V
Voltage capacitors positive, Cap+160 V
Voltage capacitors negative, CapGND
Magnetic actuator pin 1 (+)
Magnetic actuator pin 2 (-)
Appendix
Figure 43: Wiring diagram of controller
Analog
.................... ....................
Rear view arrangement of terminals and modules
Shows contacts internal to relay case assembly
Contacts close when the relay chassis is withdrawn from case
Legend
BI
BO
Binary input
Binary output
45
Appendix
Figure 44: Component arrangement of control cubicle
46
Legend:
PB1, PB2
CB1, CB2, CB3
7SR224
PCB1
PCB 2
PCB3
R1
GBAR
C14D6
GBAR
BTY1 - BTY4
R2
GCFI
R3
SE
RCPT
Pushbuttons
Miniature circuit breakers
Controller
Power supply board
Switch unit driver
Capacitors
Battery test resistor
Ground bar
Connector for control cable
Ground bar
Batteries
Battery temperature sensor
Ground fault circuit interrupter
Space heater
Thermostat
Duplex receptacle
(See Figure 45 for user connections.)
Appendix
Figure 45: Terminal block arrangement of control cubicle
Note: User and internal connections may vary depending on order specific requirements. For details and specific requirements, refer to order specific drawings.
47
48
Appendix
Installation and commissioning report
The installation and commissioning report on the following pages is intended for using and copying as a checklist.
Installation and commissioning report
User
Location
Contract number
Rated maximum voltage (kV)
Auxiliary voltage
Siemens SDR
Recloser type
Serial number
Rated continuous current (A)
Rated short-circuit current (kA)
SDR distribution recloser
Answers for energy.
49
50
Installation and commissioning report
Table 17: Preparatory tasks
A.02
A.03
A.04
A.05
A.06
A.07
A.01
A.08
Checklist
Installation and commissioning personnel have received instruction and meet the conditions for
"Qualified person" (see page 2):
Occupational safety
Safety markings
Transit damage.
The recloser (switch unit and control cubicle) is visually in good condition and undamaged.
Any paint damage occurring during transport and installation has been repaired.
All accessories and special equipment ordered are available/assembled at the installation site.
Pole or foundation is in suitable condition.
Grounding (earthing) is sufficient and in accordance with local regulations.
Compare the correct voltage of the recloser. (For example, compare the rated voltage of the recloser
(see Figure 41) with the system voltage. Contact
Siemens customer service if the voltage is incorrect at +1 (800) 347-6659 or +1 (919) 365-2200 outside the U.S..)
Determine the correct auxiliary voltage. Digit 11 of the order number indicates the auxiliary voltage required:
3 corresponds to 110 Vdc
4 corresponds to 220 Vdc
5 corresponds to 110 / 220 Vac
6 corresponds to 220 / 240 Vac
9 corresponds to 110 / 120 Vac with auxiliary transformer.
Contact Siemens customer service if the auxiliary voltage is incorrect at +1 (800) 347-6659 or
+1 (919) 365-2200 outside the U.S..
Notes
B.01
B.02
B.03
B.05
B.06
B.07
Installation and commissioning report
Table 18: Visual inspections after installation
Checklist
All bolted connections and other assembly elements are tight.
Batteries are installed correctly:
All four are connected in series
Contacts point to the back
Polarity labelling on the supply wires on the left and right correspond to actual connection of the batteries
Velco straps are over the batteries and fastened tightly.
Temperature sensor is in contact with a battery and secured (see Figure 23).
Cross-sectional area of the ground (earth) connection is adequate or the required ground current and connection to the switch unit is secure.
Auxiliary voltage is connected correctly:
Phase: X1 - 1
Neutral: X1 - 2
Protective (ground) conductor: X1 - 5.
Capacitor discharge switch is in operating position.
Switch must be to the left (see Figure 15).
Notes
51
52
Installation and commissioning report
Table 19: Function checks
C.01
C.02
C.03
C.04
C.05
Checklist
Switch on miniature circuit breakers: CB1 and CB3
(behind the panel):
Start-up of controller is shown on display.
"Protection healthy" LED lights green after approximately 30 seconds
Status LED "AuxPower OK" lights up green
Status LED "Recloser OK" lights up green
LED next to F1 lights up green
Position indicator on the bottom of the recloser switch unit is green (open).
Press Close pushbutton:
Recloser closes.
LED next to F1 is no longer lit
LED next to F2 lights up red
During switching, the "Recloser OK" status LED goes out briefly (capacitors are charged for the next switching operation). Within 1 s, the status
LED lights up green again. A longer period indicates the charging level of the batteries is very low or CB3 is not switched on.
Position indicator on the bottom of the recloser switch unit is red.
Press Open pushbutton:
Recloser opens
LED next to F2 is no longer lit
LED next to F1 lights up green
Position indicator on the bottom of the recloser switch unit is green (open).
Press F2 key (close) on the controller and then press
<Enter>:
Recloser closes
LED next to F1 is no longer lit
LED next to F2 lights up red
During switching, the "Recloser OK" status LED goes out briefly
Position indicator on the bottom of the recloser switch unit is red.
Press F1 key (open) at the controller and then press
<Enter>:
Recloser opens
LED next to F2 is no longer lit
LED next to F1 lights up green
Position indicator on the bottom of the recloser switch unit is green (open).
Notes
C.06
C.07
C.08
C.09
C.10
C.11
Installation and commissioning report
Table 20: Function checks
Checklist
Press Close pushbutton or F2 key (close) at the controller and then press <Enter>:
Recloser closes
LED next to F1 is no longer lit
LED next to F2 lights up red
Position indicator on the bottom of the recloser switch unit is red.
Mechanical operation of the recloser by pulling the lockout handle:
Recloser opens
LED next to F2 is no longer lit
LED next to F1 lights up red
Position indicator on the bottom of the recloser switch unit is green (open).
Press Close pushbutton:
No switching operation shall take place.
Activate F2 key (close) at the controller and then press <Enter>:
No switching operation shall take place.
Push lockout handle back in completely:
Press close pushbutton or F2 key (close) at the controller and then press <Enter>
Recloser closes
LED next to F1 is no longer lit
LED next to F2 lights up red
Position indicator on the bottom of the recloser switch unit is red.
Switch on miniature circuit breaker CB2:
At external temperatures of < 95º F (35º C) the heaters heat up after approximately one minute.
Notes
53
54
Installation and commissioning report
Table 21: Final tasks
D.02
D.03
D.04
D.05
D.01
D.06
D.07
D.08
Checklist
Adjust the controller to the desired setting file:
The controller shows default set in - Group 1
If necessary, select other group with user-specific parameter settings.
If applicable, check the voltage and current readings of the controller.
Check the date and the time on the controller and correct if necessary.
Set trip counter to zero (at initial installation only).
Delete event memory (at initial installation only):
If necessary, download events for further documentation.
Close and latch swing panel.
Install controller cover and fasten.
Close and secure control cubicle door.
Notes
Table 22 Other services
E.01
E.02
E.03
Checklist
Instruction manual available.
Routine test records available.
On-site instruction on recloser/controller.
Notes
Installation and commissioning report
Table 23: Remarks
Technician
Commissioning engineer
Owner
Supervisor
Instructed person
Name Department Date Signature
Table 24: Signatures
55
Published by and copyright © 2009:
Siemens AG
Energy Sector
Freyeslebenstrasse 1
91058 Erlangen, Germany
Siemens Energy, Inc.
7000 Siemens Road
Wendell, North Carolina 27591 USA
For more information, contact
+1 (800) 347-6659
Order No. E50001-F710-A249-X-A400
Printed in USA
All rights reserved.
Trademarks mentioned in this document are the property of Siemens AG, its affiliates or their respective owners.
Subject to change without prior notice.
The information in this document contains general descriptions of the technical options available, which may not apply in all cases.
The required technical options should therefore be specified in the contract.
www.usa.siemens.com/energy
advertisement
Key Features
- Repeated opening and reclosing
- Three-phase, outdoor device
- Control cubicle with integrated pole-mount brackets
- Recloser switch unit with poles, operating mechanism and operating mechanism housing
- Optional surge arresters and source side external voltage sensors
- Anti-condensation space heater
- Mechanical position indicator
- Mechanical operations counter
- Discharge toggle switch on the switch unit driver (SUD) module
- Uninterruptible power supply