KNX module for smoke alarm devices Dual/VdS -

KNX module for smoke alarm devices Dual/VdS -
Product definition
KNX module for smoke alarm devices Dual/VdS and
Q-Label
(Order no 2343 00)
Art. no 2343 00
Page 1 of 22
Product definition
Table of contents
1
Product definition .............................................................................................................. 3
1.1
1.2
1.3
2
Product catalogue .............................................................................................................. 3
Accessories ........................................................................................................................ 3
Application ......................................................................................................................... 3
Installation, electrical connection and operation ................................................................. 4
2.1
2.2
2.3
2.4
Safety notes ....................................................................................................................... 4
Device design ..................................................................................................................... 5
Mounting and electrical connection ................................................................................... 6
Start-up .............................................................................................................................. 7
3
Technical data .................................................................................................................... 8
4
Software description .......................................................................................................... 9
4.1 Software specification ........................................................................................................ 9
4.2 Software KNX module for smoke alarm device Dual/VdS ................................................ 10
4.2.1 Range of functions .................................................................................................... 10
4.2.2 Information on the software ...................................................................................... 11
4.2.3 Object table ............................................................................................................... 12
4.2.4 Functional description ............................................................................................... 18
4.2.5 State of delivery ......................................................................................................... 19
4.2.6 Parameters ................................................................................................................ 20
Art. no 2343 00
Page 2 of 22
Product definition
1 Product definition
1.1 Product catalogue
Product name: Gira KNX smoke alarm device module
Application:
KNX connection of smoke alarm device Dual/VdS
Design:
Installation
Order No.:
2343 00
1.2 Accessories
Smoke alarm device Dual/VdS
Order No.: 2330 02
1.3 Application
The Gira KNX smoke alarm device module connects a smoke alarm device Dual/VdS to Instabus
KNX lines.
It allows several smoke detectors Dual/VdS which are equipped with the Gira KNX smoke alarm
device module to be networked.
The module enables local alarms to be sent to the KNX bus and alarms to be received via the KNX
bus.
Alarms which the smoke alarm device receives via the 2-wire bus can be forwarded to the KNX
bus via the module and received again and processed by alarm devices networked via KNX.
Differentiating between local and remote alarms is possible but not necessarily required, a joint
message is performed depending on the parameterisation. Configuring the alarm transmission
interval is possible.
The Gira KNX smoke alarm device module also enables monitoring the connected smoke alarm
device. For this purpose, various pieces of state information from the smoke alarm device are
made available via the KNX bus, for example the state of the battery. In addition, a general fault
object is provided which can send to the KNX bus in configurable intervals and/or in case of a
fault.
The Gira KNX smoke alarm device module can also query the values recorded by the smoke alarm
device as a temperature sensor and make them available on the KNX bus. For this, the ambient
temperature is sent cyclically per day.
Using the module, the connected smoke alarm device can be used as a signal transmitter.
A signal tone can be triggered by a received KNX telegram. It can then be deactivated again after
a defined period of time or by another KNX telegram.
Art. no 2343 00
Page 3 of 22
Installation, electrical connection and operation
2 Installation, electrical connection and operation
2.1 Safety notes
Electrical devices may only be installed and mounted by a qualified electrician.
In doing so, the applicable accident prevention regulations must be observed.
Failure to observe the installation instructions can result in damage to the device, fire or
other dangers.
The Gira smoke alarm device should only be planned, mounted and serviced by a "Certified
expert for smoke alarm devices in accordance with DIN EN 14676".
Smoke alarm devices which are planned, mounted or serviced improperly represent a risk
because ideal smoke detection may not be able to be guaranteed.
For this purpose, Gira offers the "Certified expert for smoke alarm devices in accordance with
DIN 14676" online course, complete with certificate.
It can be viewed online by clicking on the following link: http://akademie.gira.de
Please see the operating instructions enclosed with the device for more information.
Art. no 2343 00
Page 4 of 22
Installation, electrical connection and operation
2.2 Device design
1 KNX connection
2 Programming LED (red)
3 Programming button
4 Latch
Art. no 2343 00
Page 5 of 22
Installation, electrical connection and operation
2.3 Mounting and electrical connection
Module
1. Connect the KNX bus to the KNX connection of the Gira KNX smoke alarm device module
via the connection terminal (1).
2. Connect the 9 V monoblock battery to the battery connection and insert the battery into the
battery compartment. The smoke alarm device cannot be latched into the mounting plate
or 230 V base when no battery is inserted.
3. Insert the Gira KNX module into the module interface of the smake alarm device.
The insert pins must lock.
4. Fasten the smoke alarm device to the mounting plate or the 230 V base for smoke alarm
devices.
5. Perform a function test.
Art. no 2343 00
Page 6 of 22
Installation, electrical connection and operation
2.4 Start-up
The device can be started up after mounting the device and connecting the bus line. (The module
can also be started up when not inserted).
The following physical address is factory preset
15.15.255
This address has to be reprogrammed in order to be able to use the device.
Programming the physical address of the module
Programming is done in the programming environment of the ETS (3.0f, 4.0 or higher). An
additional KNX data interface is required for programming.
• Make sure that the bus voltage is switched on.
• Press the programming button (3).
Programming LED (2) lights up red
• Program the physical address using the ETS.
Programming LED goes out after a successful programming process.
• Make note of the physical address on the device
Programming the application programme and configuration data
After programming the physical addresses, the application program must be imported to the
device.
• Make sure that the bus voltage is switched on.
• Parameterise the device accordingly in the ETS
• Import the software to the device
• Start-up is complete
Art. no 2343 00
Page 7 of 22
Technical data
3 Technical data
KNX medium
Start-up mode
KNX connection
TP
S mode (ETS)
Bus connection terminal
Power consumption
typ. 0.5 W
Ambient temperature
Storage temperature
Installation width
Installation height
Installation depth
-10 °C to +65 °C
-20 °C to +65 °C
38 mm
82 mm
30 mm
Protection type
protection class
IP20 (compliant with EN60529)
III (compliant with IEC 61140)
Test marks
KNX, CE
Art. no 2343 00
Page 8 of 22
Software specification
4 Software description
4.1 Software specification
ETS search paths:
Security / smoke alarm devices
Configuration:
S-mode standard
Applications:
No Brief description
.
1
Gira KNX smoke alarm device
Art. no 2343 00
Name
Version
KNX module for smoke alarm
device Dual/VdS
1.0
Page 9 of 22
Software KNX module for smoke alarm device Dual/VdS
Range of functions
4.2 Software KNX module for smoke alarm device Dual/VdS
4.2.1 Range of functions
•
•
Networking smoke alarm devices
Monitoring the state of smoke alarm devices
Art. no 2343 00
Page 2 of 22
Software KNX module for smoke alarm device Dual/VdS
Information on the software
4.2.2 Information on the software
•
•
The Gira KNX smoke alarm device module can be parameterised for ETS 3.0f or higher.
The Gira KNX smoke alarm device module is protected against importing an invalid
application version.
Art. no 2343 00
Page 3 of 22
Software KNX module for smoke alarm device Dual/VdS
Object table
4.2.3 Object table
Number of communication objects: 19
Number of addresses (max):
36
Number of assignments (max):
36
Dynamic table management:
no
Maximum table length:
36
Function:
Alarm function
Combine local and wired alarm = yes
Send message cyclically
Send alarm
Object
0
Description:
Function:
Function
Send
Name
Alarm
Type
1-bit
DP type
ETS4
1,002
Flag*
C, R, T
1-bit object for signalling an alarm. Only visible when the "Combine local and
wired alarm" parameter is set to "yes". This is triggered by a local heat alarm, a
local smoke alarm and an alarm received via the networking terminal. A "1" is sent
when the alarm has been triggered. Sent cyclically when "Alarm repetition" is
activated.
Alarm function
Parameter: Combine local and wired alarm = no
Object
0
Description:
Function
Send
Name
Local alarm
Type
1-bit
DP type
ETS4
1,005
Flag*
C, R, T
1-bit object for signalling a local alarm. Only visible when the "Combine local and
wired alarm" parameter is set to "no". This is triggered by a local heat alarm, a
local smoke alarm, and a local test alarm. A "1" is sent when the alarm has been
triggered. Sent cyclically when "Alarm repetition" is activated.
Art. no 2343 00
Page 4 of 22
Software KNX module for smoke alarm device Dual/VdS
Object table
Function:
Alarm function
Parameter: Send message cyclically
Send alarm
Combine local and wired alarm = no
Object
1
Description:
Function:
Function
Name
Type
Send
Wired alarm
1-bit
DP type
Flag*
ETS4
1,005
C, R, T
1-bit object for signalling an alarm which was signalled via a 2-wire line. A "1" is
sent when the alarm has been triggered. Sent cyclically when "Alarm repetition" is
activated.
Alarm function status output
Object
2
Description:
Function:
Function
Name
Type
DP type
Flag*
Send
Smoke alarm status
1-bit
1,002
C, R, T
1-bit object for signalling a local smoke alarm. A "true" is sent when the alarm has
been triggered.
Alarm function status output
Object
3
Description:
Function:
Function
Name
Type
DP type
Flag*
Send
Heat alarm status
1-bit
1,002
C, R, T
1-bit object for signalling a local heat alarm. A "1" is sent when the alarm has
been triggered.
Alarm function status output
Object
4
Description:
Function:
Function
Send
Name
Status alarm via
wire
Type
1-bit
DP type
1,002
Flag*
C, R, W
1-bit object for signalling an alarm which was signalled via a 2-wire line.
A "1" is sent when the alarm has been triggered.
Alarm function input
Object
5
Description:
Function
Name
Type
DP type
Flag*
Receive
Auxiliary unit alarm
1-bit
1,003
C, R, W, A
1-bit object for activating an alarm. When a "1" is assigned to the object, the
smoke detector emits an alarm. Simultaneously the state is transferred to the
communication object 5 "Status alarm via KNX". This only works when the smoke
detector is inserted.
Smoke alarm devices are networked with one another via KNX using this
communication object. Depending on the object value, the alarm is also activated
via the 2-wire bus.
Art. no 2343 00
Page 5 of 22
Software KNX module for smoke alarm device Dual/VdS
Object table
Function:
Alarm function status output
Object
6
Description:
Function:
Function
Name
Type
DP type
Flag*
Send
Status of alarm via
KNX
1-bit
1,002
C, R, T
1-bit object for signalling an alarm which was signalled via the auxiliary units
communication object. A "1" is sent when the alarm has been triggered.
Alarm function input
Object
7
Description:
Function:
Function
Receive
Name
Test alarm
Type
1-bit
DP type
1,003
Flag*
C, R, W, A
1-bit object for activating a test alarm. When a "1" is assigned to the object, the
smoke detector emits a test alarm. Simultaneously the state is transferred to the
communication object 7 "Status test alarm". This only works when the smoke
detector is inserted.
Alarm function status output
Object
8
Description:
Function:
Function
Name
Type
DP type
Flag*
Send
Status test alarm
1-bit
1,002
C, R, T
1-bit object for signalling a test alarm which was signalled via the test alarm
communication object. A "1" is sent when the test alarm has been triggered.
Signal transmitter function input / output
Parameter: Switch-on duration signal tone
Object
9
Description:
Function
Name
Type
DP type
Flag*
Signal transmitters
Receive
1-bit
1,001
C, R, W, T
1-bit object to activate the signal transmitter. When a "1" is assigned to the object,
the signal transmitter is activated. An assigned "0" deactivates the signal
transmitter. It is automatically deactivated after the duration set in the "Switch-on
duration signal tone" parameter and sends a "0" in this case. If the switch-on time
is parameterised to "unlimited", the signal can only be deactivated by a telegram.
The alarm signal (test alarm) of the smoke alarm device is used as the signalling
tone.
Art. no 2343 00
Page 6 of 22
Software KNX module for smoke alarm device Dual/VdS
Object table
Function:
Temperature function
Parameter: Send temperature cyclically
Object
11
Description:
Function:
Function
Name
Type
DP type
Flag*
Send
Temperature
2-byte
9,001
C, R, T
2-byte object which provides the temperature measured by the smoke alarm
device. The "Send temperature cyclically" parameter can be used to define a
transmission interval or transmission condition. If the condition "per day" is set,
the temperature is send once a day. The function is deactivated when "Send
temperature cyclically" is parameterised to "no".
Error monitoring
Parameter: Send message cyclically
Send fault
Object
12
Description:
Function
Name
Type
DP type
Flag*
Send
Fault
1-bit
1,002
C, R, T
1-bit object for signalling a fault. If a "true" is sent, there is a fault on the smoke
alarm device. This object is activated in case of the following faults:
•
Defective smoke chamber
•
Defective temperature sensor
•
Weak battery
•
230 V error (if parameterised accordingly)
•
Dirty smoke chamber
•
Smoke chamber difference signal too low
•
Smoke chamber electricity too high
•
Smoke chamber has too many compensation pulses
•
Smoke chamber loading time too high
•
Temperature sensor 1 too warm
•
Temperature sensor 1 too cold
•
Temperature sensor 2 too warm
•
Temperature sensor 2 too cold
The value can be sent cyclically. The "Send message cyclically" and "Send fault"
parameters are used to set this. Sending the message is deactivated when the
fault is eliminated and "Fault acknowledgement" has been received.
A "0" is sent in this case.
Art. no 2343 00
Page 7 of 22
Software KNX module for smoke alarm device Dual/VdS
Object table
Function:
Object
13
Description:
Function:
Object
14
Description:
Function:
Error monitoring
Function
Name
Type
Receive
Fault
acknowledgement
1-bit
DP type
ETS4
1,016
Flag*
C, A
1-bit object for acknowledging a fault. Communication objects 11 and 14 to17
maintain their "1" value as long as the error is cleared and in addition this
communication object is assigned a "1".
Error monitoring
Function
Send
Name
Battery fault
Type
1-bit
DP type
1,002
Flag*
C, R, T
1-bit object for signalling a battery fault. The message is triggered when the
smoke alarm device signals "Weak battery". A "1" is sent if there is a fault. When
the fault has been eliminated and a "1" is received on the " Fault
acknowledgement" communication object, the object is set to "0".
Error monitoring
Parameter: Report 230 V fault = Yes
Object
15
Description:
Function:
Object
16
Description:
Function
Name
Type
DP type
Flag*
Send
230 V fault
1-bit
1,002
C, R, T
1-bit object for signalling a fault on the 230 V connection. The object is only visible
when the "Report 230 V fault" parameter is parameterised to "yes". The message
is triggered when the smoke alarm device signals a 230 V error (failure). A "1" is
sent if there is a fault. When the fault has been eliminated and a "1" is received on
the "Fault acknowledgement" communication object, the object is set to "0".
Error monitoring
Function
Name
Type
DP type
Flag*
Send
Smoke chamber
fault
1-bit
1,002
C, R, T
1-bit object for signalling a smoke chamber fault. The message is triggered when
the smoke alarm device signals a smoke chamber defect. A "1" is sent if there is a
fault. When the fault has been eliminated and a "1" is received on the "Fault
acknowledgement" communication object, the object is set to "0".
Art. no 2343 00
Page 8 of 22
Software KNX module for smoke alarm device Dual/VdS
Object table
Function:
Object
17
Description:
Function:
Object
19
Description:
Error monitoring
Function
Name
Type
DP type
Flag*
Send
Temperature sensor
fault
1-bit
1,002
C, R, T
1-bit object for signalling a fault of the temperature sensor. The message is
triggered when the smoke alarm device signals a temperature sensor defect. A "1"
is sent if there is a fault. When the fault has been eliminated and a "1" is received
on the "Fault acknowledgement" communication object, the object is set to "0".
Error monitoring
Function
Send
Name
Alarm device fault
Type
1-bit
DP type
1,002
Flag*
C, R, T
1-bit object for signalling a communication fault between the KNX module and the
smoke alarm device. A "1" is sent when there is a communication fault (even if
the module is not inserted in a smoke alarm device). When the fault has been
eliminated and a "1" is received on the "Fault acknowledgement" communication
object, the object is set to "0".
*The default values are specified.
Art. no 2343 00
Page 9 of 22
Software KNX module for smoke alarm device Dual/VdS
Functional description
4.2.4 Functional description
Alarms
The module enables alarms to be sent and received using a KNX-TP connection. In this context, it
is possible to differentiate between local and remote alarms or report them via a joint
communication object. Settings are made using the "Merge local and wired alarm" parameter.
Alarms can be sent in cyclical, configurable intervals. The corresponding settings can be made
using the "Send report cyclically" and "Send alarm" parameters.
State monitoring
The state of the smoke alarm device can be monitored via the module. A general fault
communication object is available for this purpose, as well as various communication objects for
individual faults such as "Weak battery". The general "Fault" communication object for faults can
be set to cyclical transmission. The "Send message cyclically" and "Send fault" parameters are
used for this purpose.
Temperature measurement
The module can query the temperatures measured by the smoke alarm device and make them
available on the KNX bus. Vie the "Send temperature cyclically" parameter the condition “per day”
can be set (temperature is send once a day). The specific send time depends to the initialization of
the KNX module.
Signal tone
The module enables a smoke alarm device to be used as a signal transmitter. A signal tone on the
smoke alarm device can be activated and deactivated using a communication object. In addition,
it is possible to have the signal tone deactivated automatically after the time period defined via the
"Switch-on duration signal tone" parameter.
Important: Due to the external triggering (e. g. test alarm) of the signal tone the battery lifetime
of the smoke alarm device is drained faster.
Art. no 2343 00
Page 10 of 22
Software KNX module for smoke alarm device Dual/VdS
State of delivery
4.2.5 State of delivery
Physical address
Device name
Art. no 2343 00
15.15.255
Gira KNX smoke alarm device
Page 11 of 22
Software KNX module for smoke alarm device Dual/VdS
Parameters
4.2.6 Parameters
Description:
Values:
Comments:
Gira KNX smoke alarm device
Merge local and
wired alarm
Yes
No
Send message
cyclically
No
Per minute
Per hour
Per day
Art. no 2343 00
This parameter determines whether there
is a joint communication object for the
signalling of alarms triggered locally and
via wire, or whether there are two
individual objects.
Local and wired alarms are combined via
the "Alarm" communication object. The
"Local alarm" and "Wired alarm"
communication objects become invisible.
The "Local alarm" and "Wired alarm"
communication objects become visible.
The "Alarm" communication object
becomes invisible.
This parameter defines the transmission
cycle for faults and alarms. For both
types of messages, a separate parameter
can be used to set whether cyclical
transmission or event-controlled
transmission should be used.
Messages are sent only in case of
change. In this case, the "Send alarm"
and "Sent fault" parameters cannot be
changed.
The messages are sent at a preset
interval as long as the "cyclical" setting
has been selected in the "Send alarm" or
"Send fault" parameter. In addition, the
messages are sent immediately in case of
change.
The messages are sent at a preset
interval as long as the "cyclical" setting
has been selected in the "Send alarm" or
"Send fault" parameter. In addition, the
messages are sent immediately in case of
change.
The messages are sent at a preset
interval as long as the "cyclical" setting
has been selected in the "Send alarm" or
"Send fault" parameter. In addition, the
messages are sent immediately in case of
change.
Page 12 of 22
Software KNX module for smoke alarm device Dual/VdS
Parameters
Send alarm
Only in case of change
Cyclical
Send fault
Only in case of change
Cyclical
Report 230 V fault
No
Yes
Art. no 2343 00
This parameter determines whether
alarm messages should only be sent in
case of change or cyclically.
Alarm messages are sent only in case of
change.
Alarm messages are sent at the interval
set with the "Send message cyclically"
parameter and in case of change. Only
available when the "Send message
cyclically" parameter is not set to "no".
This parameter determines whether fault
messages should only be sent in case of
change or cyclically.
Fault messages are sent only in case of
change.
Fault messages are sent at the interval
set with the "Send message cyclically"
parameter and in case of change. Only
available when the "Send message
cyclically" parameter is not set to "no".
The message of a 230 V fault can be
activated or deactivated using this
parameter. Activation is only advisable
when a 230 V base is used.
A 230 V fault is not sent and the 230 V
fault is not evaluated by the "Fault"
communication object.
A 230 V fault is sent and evaluated by the
"Fault" communication object.
Page 13 of 22
Software KNX module for smoke alarm device Dual/VdS
Parameters
Send temperature
cyclically
No
Per day
Compare internal
temperature sensors
+0.0 °C
-10.0 °C to +10 °C
(In steps of 0.5)
Switch-on duration
signal tone
Unlimited
1 s to 24 s
Art. no 2343 00
This parameter determines whether the
temperature is sent to the KNX bus and
when transmission should occur.
The temperature is not sent to the KNX
bus.
The temperature is sent at the set
interval. The specific send time depends
to the initialization of the KNX module.
If the temperature measured by the
module consistently deviates from the
actual value, it is possible to compensate
this deviation using this parameter.
The measured temperature is corrected
by the configured value.
This parameter defines the maximum
switch-on duration of the signal tone.
The signal tone can only be deactivated
by a telegram.
The maximum switch-on duration of the
signal tone corresponds to the
configured value.
Page 14 of 22