key features - Elecon Systems Ltd
INDUSTRIAL Diesel Generator
MODEL:EDG-350
Specification & Application Data
Rating Range – 60Hz Operation
Standby
kW
kVA
336-354
420-442
Prime
kW
kVA
320-321
400-402
KEY FEATURES
ELECON industrial generators are efficient,
Reliable and versatile source of power for Standby
or Prime Power Applications. All generator sets and
components are factory built, and productions tested.
The Genset features a heavy-duty John Deere 4- cycle
Diesel engine certified by the Environmental Protection
Agency (EPA) to conform to Tier 3 non-road emission
Regulations, an AC high capability alternator regulated
by a precise Automatic Voltage Regulator. Heavy- duty
Constructed chassis supports the complete set.
The generator is protected by a best-in-class sound
Attenuated enclosure designed for prime or standby
applications.
• Engine – generating set tested to ISO 8528-5.
• The Genset engine is certified by the Environmental
Protection Agency (EPA) Tier 3 non-road emission regulations
• The brushless, single bearing, 4 poles, 12-wire generator end,
with automatic voltage regulator has broad range reconnect ability.
• The Genset is CSA certified.
• Integral vibration isolation rubbers eliminate the need of vibration
spring isolators.
• Global product support.
• Operations and maintenance manuals.
• One Year Warranty Standard, Extended warranties are also available.
• Heavy duty construction that is designed for use in prime or standby
applications.
• Assembled in Canada.
GENSET RATINGS
GENSET
Model
EDG-350
ENGINE
Model
ALTERNATOR
Model
HCI 444 E
HCI 444 E
VOLTAGE
N-L | L-L
120/208
120/240
277/480
347/600
Ph
3
3
3
3
Hz
60
60
60
60
150°C RISE
STANDBY RATING
kW kVA Amps
336
420
1166
336
420
1010
354
442
532
354
442
425
kW
320
320
321
321
125°C RISE
PRIME RATING
kVA Amps
400
1110
400
962
402
483
402
386
Ratings: Standby ratings are continuous for the duration of any power outage. No overload capacity is specified at this rating. Prime ratings are
continuous per BS5514, DIN 6271, IDO-3046, and IEC34-1 with 10% overload capacity one hour in twelve hours. Larger alternators may be used to meet
special application requirements. Elecon reserves the right to change the design or specifications without notice and without any obligation or liability
whatsoever.
GENERAL GUIDELINES FOR DERATION: ALTITUDE: Derate 1.5% per 1000ft. (305 m) elevation above 3300ft (1003 m) TEMPERATURE:
Derate 0.5% per 10°F (5.5°C) temperature above 77°F (25°C)
Elecon Systems Ltd. – 6212 Davies Road, Edmonton AB, T6E 4M9 – Tel: 780-472-8858
Fax: 780-426-4296 • www.eleconpower.ca
INDUSTRIAL Diesel Generator
MODEL:EDG-350
Specification & Application Data
Engine Specification
GENERAL DATA
Manufacturer
Engine model
EPA Certification for:
Rated
Nominal Power (PRIME)
Nominal Power (STANDBY)
Engine type
Injection type
Aspiration type
Cylinder arrangement
Bore and stroke
Displacement
Cooling system
Governor type
Air cleaner type
Compression ratio
Stage
RPM
kW – HP
kW – HP
(mm) – In
L – in3
JOHN DEERE
6135HF485
Tier 3
1800
365
489
401
538
Diesel 4 stroke
UNIT INJECTION
TURBOCHARGED
6–L
(132 x 165) 5,20 x 6,50
13.5
824
Liquid (Cool Guard II)
Electronic
Medium duty w/double cartridge
16.0 : 1
Application data
EXHAUST SYSTEM
Exhaust manifold type
Exhaust outlet diameter
Max. Exhaust temp. at full load
Exhaust Gas Flow
Maximum allowed back pressure
PRIME
Dry
mm – In
°C
°F
kg/h – Lb/h
(m3/min) – ft3/min
(mm/H2O) – inH2O
STANDBY
Dry
160 – 6.304
417
446
783
835
1638 – 3611.16
1890 – 4166.73
(65) - 2295
(75) – 2649
1016 – 40
COOLING SYSTEM
Engine cooling air flow
m3/s – ft3/s
Generator cooling air flow
m3/min – ft3/min
Total cooling air flow (engine + generator + combustion)
Open Skid version
m3/min – ft3/min
Sound Attenuated version
m3/min – ft3/min
Total cooling capacity
l – gal
Antifreeze recommended
l – gal
13.7 – 483.6
59.4 – 2,097.7
1,829.0 – 64,590.5
2,377.0 – 83,943.0
65.0 – 17.2
32.5 – 8.6
Elecon Systems Ltd. – 6212 Davies Road, Edmonton AB, T6E 4M9 – Tel: 780-472-8858
Fax: 780-426-4296 • www.eleconpower.ca
INDUSTRIAL Diesel Generator
MODEL:EDG-350
Specification & Application Data
LUBRICATION SYSTEM
Oil Filter: quantity. Type
Oil pan capacity
Oil pan capacity with filter
Oil cooler
Recommended oil
Specific oil consumption full load
Oil Press
% fuel
(psi) – kPa
1 x Cartridge
50 – 13.2
40 – 10.56
Water Cooled
15W-40 or API CI-4 PLUS o CI-4
<0.1% <0.1%
42 – 287
m3/h – ft3/h
1980 – 69900
m3/h – ft3/h
-¯-
kW – btu/min
kW – btu/min
194 – 11042
4.4 – 250.40
l – gal
l – gal
VENTILATION REQUIREMENTS
Air requirement for combustion at
100% load/rated speed
Cooling airflow
Heat rejected to ambient:
From engine
From alternator
ELECTRICAL SYSTEMS
Ground (negative/positive)
Volts (DC)
Ampere rating
Starter motor rated voltage (DC)
Starter motor rated
Battery recommendations
Min. Cold Cranking Amps
12V
24V
Negative
12
90
12
2.03 / 2.76
V
Amp
V
kW / HP
Amp
Negative
24
65
24
2.03 / 2.76
1900
1900
FUEL SYSTEMS
Recommended fuel
Fuel supply line. min. ID
Fuel return line. min. ID
Fuel pump Type
Secondary filter
Secondary Water Separator
mm – in
mm – in
FUEL CONSUPTION
100% Load
75% Load
50% Load
25% Load
#2 Diesel
13 0.5
10 0.38
Engine Driven
2µm
Included
PRIME rating
l/h
gal/h
l/h – gal/h
l/h – gal/h
l/h – gal/h
l/h – gal/h
88.0
65.9
47.4
27.1
23.2
17.4
12.5
7.1
STANDBY rating
l/h
gal/h
100.0
72.9
51.8
30.6
26.4
19.3
13.7
8.1
Elecon Systems Ltd. – 6212 Davies Road, Edmonton AB, T6E 4M9 – Tel: 780-472-8858
Fax: 780-426-4296 • www.eleconpower.ca
INDUSTRIAL Diesel Generator
MODEL:EDG-350
Specification & Application Data
Alternator Specifications
GENERAL DATA
Manufacturer
Stamford
Model (480V)
HCI 444 E
Alternator Type
4 poles, rotating field
Exciter Type
Brushless, self-excited
PMG (optional)
Leads: quantity, type
12, reconnectable
Stator Pitch
2/3
Insulation system
Material
Class H
Temperature rise
150 °C Standby
125 °C Prime
Bearing: quantity, type
Single bearing sealed
Coupling
Flexible disc
Automatic Voltage regulator
STD regulator
SX440
PMG regulator or EBS
Opt MX341, Opt MX321
Voltage regulation, no load to full load
STD regulator
+/-1.5%
PMG regulator load acceptance
+/-1%, +/-0.5%
SOUND ATTENUATED MODEL
STANDARD SIZE
(Length x Width x Height)
(Size W/Extended
mm
4,500 x 1,800 x 2,342
Capacity, Tank)
in
177.2 x 70.9 x 92.2
Dry weight (with std.
accessories)
Fuel Tank Capacity
Run Time (Hr)
Prime Power
Standby Power
Noise level
kg Lb
L Gal
100 %
30.5
27.9
7m
5,500
12,125
740
195.4
75% 50% 25%
11.2 15.6 27.4
10.1 14.3 24.2
79 dBa
OPEN SKID MODEL
Overall size (L x W x H)
Dry weight (with std.
accessories)
Fuel Tank Capacity
(Length x Width x Height)
mm
3,175 x 1,575 x 2185
in
kg Lb
125 x 62 x 86
3,310
7,295
Optional
Elecon Systems Ltd. – 6212 Davies Road, Edmonton AB, T6E 4M9 – Tel: 780-472-8858
Fax: 780-426-4296 • www.eleconpower.ca