DT8012F4 / DT8012F5 DUAL TEC® Motion Sensor - TLC

DT8012F4 / DT8012F5 DUAL TEC® Motion Sensor - TLC
DT8012F4 / DT8012F5 DUAL TEC® Motion Sensor – Installation Instructions
QUICK LINKS
Mounting Location Guidelines
Open the Sensor
Mount the Sensor
Sensor Components and Settings
Wire the Sensor
Walk Test the Sensor
Detection Patterns
Relay Operation
Troubleshooting
Sensor Specifications
Accessories
Approval Listings
Mounting location guidelines:
•
•
•
•
•
The optimal range is obtained at a mounting height of 2.3 m (7’ 6”).
[EN] = approved installation.
Allow a clear line-of-sight to all areas to protect.
Do not directly face windows.
Avoid close proximity to moving machinery, fluorescent lights and heating/cooling sources.
For use in applications with pets up to 45 kilograms (100 pounds).
1. Turn the arrow to point to the Unlock symbol.
2. Press firmly on housing latch.
3. Gently separate the front and rear housing.
-2-
LED
Power
Up
Walk Test
Normal
Trouble
Red
Slow
Blink
ON
Alarm
ON
Alarm
Fast
Blink
Yellow
OFF
Green
OFF
1. Close the sensor and apply power to the sensor. Initialization is complete
when the LED stops flashing slowly (about 30 seconds).
2. Walk through the detection area and observe the LED.
3. Adjust the microwave range as necessary to meet installation requirements.
ON
ON
Microwave Microwave
ON
PIR
ON
PIR
Walk test mode is active for 10 minutes, then automatically exits test mode, disables the LED and enters normal
operation mode. For an additional 10 minute walk test, enable walk test mode again with the flashlight feature:
Note: During power up and walk test modes the LED is active regardless of the LED Enable/Disable DIP switch setting.
Flashlight Feature:
1. Use a flashlight with a bright light beam, and stand within 1.2 m (4’) of the sensor.
2. Swing the light beam past the sensor lens 3-5 times, holding the beam on the lens
for 0.5 second each pass.
The flashlight feature is only available for the first 24 hours after the first power up.
Zones
2 Look-down
18 Lower
C 46 Intermediate
D 36 Long
A
B
-3-
OFF
OFF
RELAY OPERATION
Normal
Closed
Alarm Relay
1
ACCESSORIES*
SENSOR STATUS
Intrusion
Trouble1
Open
Open
For information on Trouble conditions, see the Troubleshooting section.
TROUBLESHOOTING
Alarm Relay
Red LED
NORMAL
Closed
Off
TROUBLE*
Self-Test Failure1
Open
Flashing
*TROUBLE CONDITIONS:
1
Self-Test Failure conditions:
• Microwave supervision failure: The sensor is operating in PIR mode only.
• PIR self-test failure: The sensor is disabled.
• Temperature compensation failure: The temperature compensation is
disabled.
Depending on the Trouble condition, take the following corrective actions:
• Verify the power supply is sufficient (at least 9V at the sensor).
• Cycle power to the sensor.
• Walk test the sensor.
If the Trouble condition does not clear, replace the sensor.
SPECIFICATIONS
Range: 12 m x 17 m
Power: 9.0 - 15 VDC; 9 mA typical, 14 mA maximum, 12 VDC;
AC Ripple: 3 V peak-to-peak at nominal 12 VDC
Alarm Relay: Energized Form A; 30 mA, 25 VDC, 22 Ohms
resistance maximum. Alarm Relay Duration: 3 seconds
Tamper: Cover; (NC with cover installed) Form A; 30 mA, 25 VDC;
Magnetic field
Microwave Frequencies: DT8012F4 – 10.525 GHz
DT8012F5 – 10.587 GHz
SMB-10
(P/N 0-000-110-01)
Swivel Mount Bracket
SMB-10C
(P/N 0-000-111-01)
Swivel Mount Ceiling Bracket
SMB-10T
(P/N 0-000-155-01)
Swivel Mount Bracket w/Tamper
* Accessories are not covered by certifications.
APPROVAL LISTINGS
EN50131-2-4:2008, Security Grade 2,
Environmental Class II.
Suitable for connection to an EN 60950 Class II
Limited Power Source.
Note: In EN 50131-2-4 compliant installations, mount the sensor at 2.3m,
disable look down, enable pet immunity, set the microwave sensitivity
to maximum and lock the sensor housing with the cover lock (see
“[EN]” where noted in Steps 1-4).
IMPORTANT: The sensor should be tested at least once each year.
NF&A2P 2 boucliers (référentiel NF324-H58)
et conforme aux normes EN50131-2-4 et
RTC50131-2-4; IP30 IK04
DT8012F4 – N° de certificat: 2821420019
DT8012F5 – N° de certificat: 2821420019
Organisme de certification:
CNPP Cert. : www.cnpp.com et
AFNOR Cert.: www.marque-nf.com
Honeywell Security Group - BP1219
1198 avenue du docteur Maurice Donat
Sophia Antipolis
06254 Mougins Cedex.
TEL: +33.4.92.94.29.50
FAX: +33.4.92.94.29.60
DT8012F5
PD6662:2010
Corrente norminale: 12 =
Corrente massima
assorbita: 14 mA
RFI Immunity: 20V/m 10-1000MHz, 15V/m 1000-2700MHz
PIR White Light Immunity: 10,000 Lux typical
Fluorescent light filter: 50 Hz / 60 Hz.
DT8012F4
INCERT B-893-0014
LARMKLASS 2
Operating Temperature: -10° to 55° C / 14° to 131° F
Relative Humidity: 5 to 95%; non-condensing
Temperature Compensation: Advanced Dual Slope
Dimensions: 9.8 cm H x 5.7 cm W x 4.35 cm D /
4.57” H x 2.76” W x 1.69” D
Weight: 96 g / 3.38 oz (net weight)
For any additional information, please refer to our Website:
http://www.honeywell.com/security/emea/hscdownload
Or contact:
Honeywell Security Group
Newhouse Industrial Estate
Motherwell
Lanarkshire ML1 5SB
United Kingdom
Tel: +44(0)1698 738200
Email: UK64Sales@Honeywell.com
Please contact your local authorised Honeywell representative for product warranty information
 2014 Honeywell International Inc. Honeywell and DUAL TEC are registered trademarks of Honeywell International Inc.
All other trademarks are the properties of their respective owners. All rights reserved.
P/N 800-16784 Rev A