Chatter data logger datasheet
DATA LOGGER WITH INTEGRATED MODEM
General
Chatter™ Data Logger is designed for monitoring drinking water and
waste water installations. Chatter™ Data Logger has a built-in multichannel data logger, a GSM / GPRS modem and a battery ensuring up to
5 - 10 years of continuous operation.
The embedded software activates the required digital and analog inputs,
and time-stamped data are stored at selectable intervals. Three different
types of call can be selected; Data for standard SQL-database, SCADA
system or as e-mail or SMS, and the calls can be scheduled to user controlled
intervals, transferred using the GSM/GPRS net.
Installation and configuration of data logging are very simple with the MJK
user software. Data from the SQL database can be transferred to larger
SCADA systems using Chatter CNS plug-in.
Chatter™ Data Logger is available in two different versions: one for pipe
mounting and one for wall mount.
Features
• Transmits data and alarms to standard SQL database using GSM/GPRS network
• Transmits data and alarms to SCADA systems using Modbus® RTU protocol over GSM/GPRS network
• Data transmission by e-mail to up to four e-mail addresses:
• Data directly in the mail body
• Data as attached CSV file in the mail.
• Data file can be displayed by Chatter Link PC software
• Transmits live data and alarms as SMS message to up to four recipients
• Alarms can be sent alone or along with other communication as SMS.
Application
• Measuring levels, pressure, temparature, flow and more paramateres in
wells, boreholes, sewers and rivers or lakes
• Ground water level monitoring. Chatter™ Data Logger is especially useful in places without main power supply, as it is developed for having a very long lifespan on the built-in battery.
• Storm flow logging, activated by level-trigger or analog limit.
Logging of amount, durance and time of storm flows.
DATASHEET
EN 6.10 CHATTER DATASHEET 1506
6.10
Chatter™
Chatter™ Data Logger
Four-In-One
Chatter™ Data Logger measures and stores data in the data logger and can transmit in 4 different modes:
Sends data to a SQL database, where measurements and alarms
can be transferred to e.g. a Scada system
• Data transmission by e-mail to up to four different e-mail addresses.
• Data directly in the mail body.
• Data as attached CSV file in the mail. Data file can be displayed by Chatter Link PC software
• Both live data and alarms can be sent as SMS message.
• Sends SMS messages to up to four different recipients.
•Alarms can be sent as SMS message alone or together with other communication.
Chatter™ Data Logger can send alarms and status of the
measurements as SMS messages
Specifications
Chatter™ Data Logger
Power supply
Built-in 3,6 VDC, 19 Ah lithium battery
Performance
Better than 5 years@1 measurement/day and 1 call/day
Clock
Real-time clock, 24-hour clock
Memory storage
DB Version: > 100.000 measured values (date- and time-stamped)
RTU and E-mail version: 90.000 measured values (date- and timestamped)
Log intervals
1, 2, 5 10 min, 1, 2, 4, 8, 12 or 24 hours
Event Log intervals
1, 2, 5 10 min, 1, 2, 4, 8, 12 or 24 hours
Call intervals
1, 2, 4, 8, 12 or 24 hours, and 10, 25, 50 100, 250, 500 or 1000 Logs
Communication
Build-in GSM/GPRS quad-band 850/900/1800/1900 MHz modem w/ on-board SIM- card holder
External Communication
Protocol
MJK Proprietary protokol for DB Version,
Modbus® RTU-mode, Modbus® TCP or COMLI® for RTU version
1 pcs. RS485 for Serial Data input
1 pcs. USB 1,1 type mini B, female
1 pcs. MMCX, female, for antenna
Interface
Antenna
Pipe: Built-in GSM/GPRS Antenna - Dual band, Amplification 0 dB, Frequency 900/1800 MHz
Mounting
In Pipe with inner diameter Ø 63 - Ø106 mm or on a wall
Enclosure
IP 67
Materials
Pipe: PC-ASA (top) and aluminium (base)
Wall: Glas-reinforced PC (polycarbonate)
Temperature range
- 20 … 60 °C
Air humidity
Max. 95% relative
Weight
Pipe mounting: 1,8 kg
Wall mounting: 0,7 kg
CE approvals
EN61000-6-1:2007, EN61000-6-3:2007
Input and Output 4AI/4DI/1RS485
Digital inputs
4 pcs. 2 - 5 VDC (min. time for state 1 second)
Analog inputs
4 pcs. 0 - 2,5 VDC
Serial Data input
Power supply for I/O
1 pcs. RS-485 Modbus® com port for max. 4 units Modbus® RTU-mode, 9600 baud, 2-wire RS-485,
Master mode, Function 3, Read only
1 pcs. 3,6 VDC
1 pcs. 3,6 VDC ON/OFF-controlled
1 pcs. 5 VDC ON/OFF-controlled, option +10 or +15 VDC.
Accuracy
AI: Better than ± 1% FS
Resolution
AI: 10 bit, input impedance: min. 10 K ohm
Database Server
Server requirements
Microsoft Server 2008 R2, IIS v.7 (Internet Information Services)
Microsoft SQL Database 2008 R2 Express Edition
Network requirements.
MPLS/APN (Multi-Protocol Label Switching) or internet access
As our products are developed continously, we reserve the rigth to make any changes without prior notice.
Chatter™ Data Logger
Electrical Connections
ANT.1
ON OFF
Wall mounting, small: Item#
204110
204122
Dimensions
156
83
GND
GND
B
RS485
A
GND
SIM card
GND
3V6-B
3V6-A
GND
USB
+5/ 10/ 15V
AI 4
GND
AI 3
AI 1
AI 2
DI 4
GND
DI 3
DI 1
DI 2
Battery
190
mm
190
79
150
mm
150
Ø20
144
Pipe mounting:
Item# 204105
249
101
mm
101
144
Wall mounting, wide:
Item# 204125
Accessories
Chatter Link™
Designed for for setup, configuration and
viewing online data through USB connection.
Expert Digital Hydrostatic Level transmitters.
•
•
•
•
•
Hydrostatic Piezo-resistive relative measuring
principle.
RS485 digital output, Modbus, level and
Temperature signals.
Measuring range: 0–3 m …300 m
(0-10ft ..1000 ft)
Supply voltage: 3,5 - 12V DC
Accuracy, better than ± 0.25 % FS @ +10 to 30 °C
Indre rørdiameter
Inner
Pipe dia.
Ø 63 - 106 mm
Ø 63 - Ø106
Chatter™ Data Logger
Order Numbers
Chatter™ Data Logger
2041051
Chatter™ Data Logger GSM/GPRS for tube mounting
2041102
Chatter™ Data Logger GSM/GPRS for wall mounting
204122
Chatter™ Data Logger GSM/GPRS for wall mounting, 10-30VDC (3,7 V Li-Ion)
2041253
Chatter™ Data Logger GSM/GPRS for wall mounting, 230VAC/12VDC
2
Accessories
840134
Chatter™ System Software DVD
840400
Chatter Link™
840128
Chatter™ Data Logger Notification System. Must run on the same server as Chatter DB System
840135
Chatter™ Data Logger Setup Tool
521751
Mounting wedge kit for tube Ø63-92mm, 3 x 3 pcs. Metal, wedge sizes: 1, 2, 3 and 4
521752
Mounting wedge kit for tube Ø84-106mm, 3 x 3 pcs. Metal, wedge sizes: 4, 5 and 6
521755
Wedge screws, kit with 3 pcs.
521757
Padlock bracket, Ø 8mm
521760
Gasket for Chatter™ Data Logger base/tube
521761
Gasket for Chatter™ Data Logger top/base
521762
Gasket for Chatter™ Data Logger cover plate
550246
Battery 3.6 V, 19 Ah Lithium
550246-1
Battery 3.6 V, 35 Ah Lithium
550246-2
Battery 3.6 V, 65 Ah Lithium
569108
Screw, self-tapping, KB50x14
569123
Screw, self-tapping, KB35x7
571055
Rubber band, 60mm, folded
691095
USB Cable, Mini /USB
691098
USB plug, mini to mini for panel mounting, IP67
Antennas
See data sheet: EN 6.26 GSM-GPRS Antennas Datasheet
Expert Hydrostatic
Level Transmitters
See data sheet: EN 2.75 Expert Datasheet
1) Battery 550246 is used for this device
2) Battery 550246-1 can be used alternatively
3) Battery 550246-1 or 550246-2 can be used alternatively
MJK Automation
Byageren 7
DK-2850 Nærum
Denmark
Tel +45 45 56 06 56
Fax +45 45 56 06 46
www.mjk.com
Connect, MµConnect, Chatter, MagFlux, Oxix, pHix compact, Shuttle and SuSix are
registrered trademarks of MJK Automation. © 2014 Xylem, Inc.