Technical data sheet BKN230-24LON

Technical data sheet BKN230-24LON
Technical data sheet
BKN230-24LON
Communication and power supply unit
for Top-Line fire protection actuators for
LONWORKS® applications.
•AC 230 V supply via Euro plug
•Supply and control are electrically
isolated
•Simple integration of a smoke detector
contact possible
•Suitable actuators
Top-Line fire protection actuators
BF(G)24TL-T-ST
Technical data
Electrical data
Safety
Dimensions / Weight
Nominal voltage
Nominal voltage range
Power consumption Operation
For wire sizing
Connections
AC 230 V, 50/60 Hz
AC 198 ... 264 V
9 W (incl. actuator)
10 VA (incl. actuator)
see «Connections» on page 2
Protection class
Degree of protection
EMC
Low-voltage directive
Mode of operation
Software Class
Transceiver
International certificate
Rated impulse voltage
Control pollution degree
Ambient temperature
Non-operating temperature
Moisture test
Maintenance
II Totally insulated
IP40
CE according to 2004/108/EC
CE according to 2006/95/EC
Type 1 (EN 60730-1)
A (EN 60730-1)
FTT-10A
CB in accordance with IEC 60730-1/-2-14
4 kV (EN 60730-1)
2 (EN 60730-1)
–30° ... +50°C
–40° ... +80°C
95% r.h., non-condensating (EN 60730-1)
Maintenance-free
Dimensions
Weight
See «Dimensions» on page 5
Approx. 680 g
Safety notes
!
• The device has been designed for use in stationary heating, ventilation and air-conditioning
systems and is not allowed to be used outside the specified field of application, especially in
aircraft or in any other airborne means of transport.
• Only authorised specialists may carry out installation.
All applicable legal or institutional installation regulations must be complied with during
installation.
• The device may not be opened by the user nor by anyone else other than a trained specialist.
It does not contain any parts that can be replaced or repaired by the user.
• The device contains electrical and electronic components and is not permitted to be
disposed of as household refuse. All locally valid regulations and requirements must be
observed.
Product features
Application
www.belimo.com
The BKN230-24LON is used as
– Power supply unit
– Connection socket
– LONWORKS® interfacing
with fire protection damper actuators of the Top-Line series (e.g. BF24TL-T-ST).
T3-BKN230-24LON • en • v1.0 • 02.2010 • Subject to changes
/5
Communication and power supply unit for Top-Line
fire protection actuators for LONWORKS® applications
BKN230-24LON
Product features
Mode of operation
Functional Profile as per LONMARK®
Properties
The BKN230-24LON unit adds extra functionality to the safe functions that are already an inegral
part of the actuator, converting the actuator‘s digital MP-Bus protocol to LONTALK® and vice
versa.
The BKN230-24LON unit is LONMARK® certified. All functions of Top-Line fire protection
actuators are made available to the LONWORKS® network in the form of standard network
variables (SNTV) conforming to LONMARK® requirements. The objects «Node», «FSDA» and
«Open Loop Sensor» are implemented.
– Built-in LED test function for checking the actuator and the BKN unit independently of the bus
network
– Terminal strip for additional local smoke detector with a floating contact
– Plug for Top-Line fire protection actuator
– Built-in «Watchdog» for triggering a safety function in the event of bus malfunction (must be
setting in the Functional Profile)
– Visual indicators for actuator position, status and maintenance
Accessories
Description
BELIMO PC-Tool (MFT-P) for diagnostics, service, OEM settings.
Communication between LONTALK® and actuator is interrupted while the PC-Tool is plugged in.
ZIP-USB-MP (interface set for the PC)
ZTH-GEN (Adjustment and diagnostic tool)
Electrical installation
Connections
1
Power supply: AC 230 V
2
Error (LED red)
3
Damper (actuator) open (LED green)
4
Damper (actuator) closed (LED yellow)
5
Plug for smoke detector contact
6
Plug for LONWORKS® network
7
Plug for BELIMO PC-Tool
8
Plug for Belimo Top-Line fire protection actuator
9
Cable entry for smoke detector contact
2
4 3
9
10
1
5
11
6
12
8
13
14
7
10 Cable entry (z.B. für LONWORKS® network)
11 Cable entry for BELIMO actuator
Please note!
• Pull out the AC 230V mains plug before
opening the housing cover!
12 Cable entry for BELIMO PC-Tool
!
13 Status (LED yellow) / Service-Pin (LONTALK®)
14 Test button and test LED (yellow)
Wiring diagram
LONWORKS
FTT10A
AC 230 V
2
1
1)
b
a
7
5
6
1
PC-Tool 2)
1)Factory-fitted
jumper. Can be removed if
necessary to be replaced by a smoke detector
(nc). The safety function will be triggered if
terminals 1 and 2 are not linked.
2)Plug-in contacts for connecting a PC via the
ZIP-USB-MP module.
8
BKN230-24LON
M
/5
Top-Line Antrieb
Tf1
Tf2
T3-BKN230-24LON • en • v1.0
• 02.2010
• Subject to changes
www.belimo.com
BKN230-24LON
Communication and power supply unit for Top-Line
fire protection actuators for LONWORKS® applications
Electrical installation
(Continued)
Signalling
Display
Colour
green
yellow
Error
Status LED
(LONTALK®)
yellow
Test
yellow
Status
Function
flashing
Damper OPENING
on
Damper OPEN
flashing
Damper CLOSING
on
Damper CLOSED
flashing
Existing fault
on
flashing
MP communication fault
No user software loaded
on
Not configured (factory setting)
off
Configured (normal operation)
Test in progress
on
Test function
Holding the test button depressed for at least 3 seconds will initiate a test sequence. The test
button is accessible through a hole and can be pressed with the aid of a thin tool.
Service
If the LONWORKS® node has not been configured the actuator can be opened and closed by
pressing the test button (< 3 s).
In the configured state, however, pressing the test button will always initiate a test sequence.
Flashing
The LED’s for error, damper open and damper closed flash for approximately 7 seconds when
necessary. Repeated flashing does not extend the flashing time.
Factory Settings
The BKN230-24LON unit is not configured before delivery.
The unit can be configured manually by applying mains power and pressing the service button
for 3 to 10 seconds.
Principle diagram
Top-Line actuators
AC 24 V
AC 24 V
BKN230-24LON
BKN230-24LON
AC 230 V
AC 230 V
LONWORKS® network
Note
For safety reasons, BELIMO recommends that
motorised fire protection dampers be operated only
on separate networks.
Topology
The FTT 10-A transceiver is suitable for all forms of topology (bus, star, ring, etc.).
Addressing
The bus node address (fixed) is stored in the BKN230-24LON unit. This means that no readdressing or system resetting is necessary when replacing a Top-Line actuator.
www.belimo.com
T3-BKN230-24LON • en • v1.0 • 02.2010 • Subject to changes
/5
Communication and power supply unit for Top-Line
fire protection actuators for LONWORKS® applications
BKN230-24LON
Functional Profile as per LONMARK®
The BKN230-24LON unit is LONMARK® certified. The following actuator functions are made available via the LONWORKS® network as
standardised network variables in accordance with LONMARK®: the Node Object #0, the Fire Smoke Damper Actuator Object #11001_10 and the
Open Loop Sensor Object #11003_01.
Node Object #0
Node Object
Implementing the two standard network variables Request and Status in the
node object is mandatory.
Mandatory
nviRequest
SNVT_obj_request
nvoStatus
SNVT_obj_status
nvoAlarm
SNVT_alarm
nvoStatus
nvoFileDirectory
SNVT_adress
SNVT_address
Output variable that shows information in the address range of the Neuron chip.
SCPTdevMajVer
SCPTdevMinVer
http://www.lonmark.org
Details see «Technical Ressources»
Fire Smoke Damper Actuator Object
(FSDA #11001_10)
FSDA
Mandatory
nvoAc tuPosn
SNVT_hvac_emerg
Implementing the two standard network variables ActuDrive and ActuPosn in
the FSDA object is mandatory.
nviActuDrive
SNVT_hvac_emerg
Controls actuator position.
Optional
nvoActuDriveFb
SNVT_hvac_emerg
Configuration Properties
SNVT_obj_status
Output variable indicating the actual status of the actuator.
nvoFileDirectory
Configuration Properties
nviActuDrive
SNVT_hvac_emerg
SNVT_obj_request
Input variable to request the status of the actuator.
Can also be used to initiate the test function. Testing is only possible if the
damper is in the open position (after the nviActuDrive command).
Optional
nviTimeSet
SNVT_time_stamp
nviRequest
nvoActuPosn
SNVT_hvac_emerg
Reflects the actuator position.
nciRcvrtHrtBt
SNVT_time_sec
Sets the maximum time that may expire before the actuator automatically goes
to the fail-safe position.
For safety reasons a time window of 60...300 s is recommended.
nciRcvrHrtBt
SNVT_time_sec
nciSafetyPosn
SNVT_state
nciDriveTime
SNVT_time_sec
Contains the motor drive time set in the actuator.
nciDriveTime
SNVT_time_sec
Mandatory
nciTurnOffTime
SNVT_elapsed_tm
Contains the turn-off time of the actuator.
nciTurnOffT
SNVT_elapsed_tm
nciZoneNum, nciInstallDate und nciMaintDate
Information can be stored in the BKN230-24LON unit (via the system
integrator).
nciZoneNum
unsigned long
nciOemLabel
nciActuLabel
SNVT_str_asc
nciLocation
nciOemLabel
SNVT_str_asc
Optional
nciLocation
SNVT_str_asc
nciInstallDate
SNVT_time_stamp
SNVT_str_asc
OEM string stored in the actuator (Contents: e.g. damper type, tripping
temperature, etc.).
nciMaxSendTime
SNVT_time_sec
SNVT_str_asc
Location string stored in the actuator (Contents: Location positi-on, fire zone,
etc.).
http://www.lonmark.org
Details see «Technical Ressources»
nciMaintDate
SNVT_time_stamp
/5
T3-BKN230-24LON • en • v1.0 • 02.2010 • Subject to changes
www.belimo.com
Communication and power supply unit for Top-Line
fire protection actuators for LONWORKS® applications
BKN230-24LON
Functional Profile as per LONMARK®
(Continued)
Open Loop Sensor Object (Fire, Smoke)
Open Loop Sensor
Mandatory
nvoFireAlm
SNVT_switch
nvoFireTrouble
SNVT_switch
Implementing the two standard network variables “FireAlm“ and
“FireTrouble“ in the OLS object is mandatory.
For each fire and smoke damper actuator the following 3 sensor values are
monitored:
– duct temperature
– duct exterior temperature
– status of additional sensor contact (e.g. smoke detector)
nvoFireAlm
Optional
nvoEmergMode
SNVT_hvac_emerg
nvoFireTrouble
SNVT_switch
Indicates any initiator failure condition that can be detected by the device
Configuration Properties
nvoEmergMode
nciMaxSendTime
SNVT_time_sec
SNVT_hvac_emerg
For direct control of a FSDA. OR function of the nvoFireAlm states.
Mandatory
nciMaxSendTime SNVT_time_sec
nciZoneNum
unsigned
Defines the maximum period of time in which the “nvoFireAlm” must be
sent.
For safety reasons a time window of 60...300 s is recommended.
nciOemLabel
SNVT_str_asc
NciZoneNum, nciInstallDate und nciMaintDate
Information can be stored in the BKN230-24LON unit (via the system
integrator).
nciLocation
SNVT_str_asc
nciInstallDate
SNVT_time_stamp
nciMaintDate
SNVT_time_stamp
SNVT_switch
Transmits the fire information of the 3 sensor values in case of a fire alarm
condition.
http://www.lonmark.org
Details see «Technical Ressources»
Optional
nciFireText 1
SNVT_str_asc
A detailed guideline for system integrators can be downloaded from
www.belimo.ch as PDF.
nciFireText 2
SNVT_str_asc
nciFireText 3
SNVT_str_asc
Dimensions [mm]
Dimensional drawings
5
54
153
140
43
88
4.5
45
130
www.belimo.com
T3-BKN230-24LON • en • v1.0 • 02.2010 • Subject to changes