IDP-Relay-6 Module Data Sheet
Addressable Relay Module
IDP-Relay-6
Agency Listings
MEA
386-02-E Vol. 2
The IDP-Relay-6 is an addressable relay module for use with
Silent Knight IFP-series fire alarm control panels (FACPs). The
IDP-Relay-6 has six Form C relays. It allows a Silent Knight
FACP to switch discrete contacts by code command. If
needed, you can disable a maximum of three unused modules
on the IDP-Relay-6 board. No supervision is provided for the
notification appliance circuit.
The IDP-Relay-6 contacts can be used for virtually any
normally open or normally closed application. Each IDP-Relay6 is programmed with a unique signaling line circuit (SLC) loop
address. When an event occurs that controls the IDP-Relay-6,
the relay is triggered by the FACP.
Features
• Six Form C contacts
• Removable 12 to 18 AWG plug-in terminal blocks
• Relay programming is completely flexible–can be mapped to
zone conditions
• Individual LED for each relay contact
• Two module mounting in the IDP-ACB cabinet
• Up to three unused modules can be disabled
• Rotary address switches for fast installation
• Mounting hardware included
• UL Listed
Installation
The IDP-Relay-6 mounts in the Silent Knight IDP-ACB cabinet
(PN IDP-ACB). The IDP-ACB has a built-in chassis that will
accommodate one or two IDP-Relay-6 modules.
Compatibility
IDP-Relay-6
The IDP-Relay-6 is compatible with the
following FACPs:
• IFP-2000 / RPS-2000 Intelligent Fire
Panel
• IFP-2000ECS Emergency Communication
System with Fire Panel
• IFP-1000 / ECS Intelligent Fire Panel
• IFP-100 / ECS Intelligent Fire Panel
• IFP-50 Intelligent Fire Panel
Ordering Information
IDP-Relay-6
Accessories
IDP-ACB
Six Relay Control
Module.
IDP Module Cabinet.
Cabinet holds two
IDP-Relays.
P/N 350291 Rev F
Copyright © 2015 Honeywell International Inc
Specifications
Relay Contact Ratings
Physical
IDP-Relay-6
Height: 6.8” (17.3 cm)
Width: 5.8” (14.7 cm)
Depth: 1” (2.5 cm)
Shipping Weight: 6.3 oz (196 g)
Environmental
IDP-ACB
15.25” (38.7 cm)
12.5” (31.8 cm)
3” (7.6 cm)
6.5 lbs (2.8 kg)
Operating Temperature: 32ºF – 120ºF (0ºC – 49ºC)
Humidity: 10% – 93% non-condensing
Electrical
Wire Gauge: 12 – 18 AWG
Operating Voltage: 15 – 32 VDC
Standby and Alarm Current: 1.45 mA max
SLC Loop Resistance: 40W max
Current Rating
Max Voltage
Load
Description
Application
2A
30 VDC
Resistive
Coded
3A
30 VDC
0.9A
110 VDC*
0.5A
30 VDC
0.9A
1A
125 VAC*
30 VDC
0.3A
125 VAC*
0.7A
70.7 VAC*
1.5A
2A
* UL only
25 VAC
25 VAC*
Resistive
Resistive
Resistive
Inductive
(L/R = 5 ms)
Inductive
(L/R = 2 ms)
Inductive
(PF = 0.35)
Inductive
(PF = 0.35)
Inductive
(PF = 0.35)
Inductive
(PF = 0.35)
Noncoded
Noncoded
Noncoded
Coded
Coded
Noncoded
Noncoded
Noncoded
Noncoded
This document is not intended to be used for installation purposes. We try to keep our product information
up-to-date and accurate. We cannot cover all specific applications or anticipate all requirements. All
specifications are subject to change without notice. For more information, contact Silent Knight 12
Clintonville Road, Northford, CT 06472-1610 Phone: (800) 328-0103, Fax: (203) 484-7118.