E3METERTM Intelligent Power Strip RN1231

E3METERTM Intelligent Power Strip RN1231
E3METERTM Intelligent Power Strip
RN1231 Datasheet
General Description
Features
E3METER® intelligent power distribution
strips (IPS) are the core element of our
innovative monitoring system. They provide
valuable data for both data center operators
and clients: accurate energy consumption
logging enables operators to offer usage
based energy billing. A bright local display
gives real-time feedback on power
consumption which simplifies for example
load balancing during commissioning
of new equipment. Alarms make early
detection of overload and other abnormal
situations possible which helps to prevent
power outages.
•Non-Intrusive voltage, current and
frequency measurement through current
transformer
Data transfers between E3METER® IPS
and a central E3METER® Concentrator
use
reliable
narrowband
powerline
communication (PLC) technology which
avoids the need for extra cabling. All
measured values can be accessed via
standard SNMP.
Two dedicated extension ports can be
used to measure temperature and humidity
through E3METER® remote sensors.
•Energy and power measurements (active,
reactive, apparent, power factor) per
phase
•Neutral current measurement
•1% accuracy
•Factory calibrated
•Alarms
•Internal temperature sensor
•2x
extension
ports
for
temperature/humidity sensors
external
•Data logging in E3METER® Concentrator
•Data access by 3rd-Party Tools via SNMP
(through E3METER® Data Concentrator)
•Reliable
Powerline
Communication
(Cenelec B, FCC or ARIB)
•10/100 Mbps Fast Ethernet (HTTP, SNMP,
Telnet, NTP)
•36x C13, 6x C19 outlets
(other combinations on request)
Actual looks and features are subject to change without notice. © 8/2009 - 01/2014 (v5). All rights reserved.
Riedo Networks Ltd, Switzerland, www.riedonetworks.com, info@riedonetworks.com
E3METERTM Intelligent Power Strip
RN1231 Datasheet
Physical
Length
Width
Depth
Weight
1670 mm (three phase)
44 mm (1U)
51 mm
3 kg
AC Input
Nominal Input Voltage
Max. Input Current
Input Frequency
Input Cable/Plug
230 / 400 V rms
16 A rms per phase
50 - 60 Hz
2.5m (other lengths on request) CEE 16A 5p 6h
AC Output
Nominal Output Voltage
Max. Output Current
Output Connections
Integrated Filter/Switch
230 / 400 V rms
16 A rms per phase
36 x C13 & 6 x C19
No (optional on request)
Communication
Reliable narrowband Powerline Communication
(Cenelec B, FCC or ARIB)
10/100 Mbps Fast Ethernet, RJ-45 connector
(HTTP, SNMP, Telnet, NTP)
Console on left RJ12 connector, 115’200 bps, 8n1
Powerline
Ethernet
Serial
Display
Technology
Refresh Rate
Screen Saver
TFT full graphic color display, 320x240
1 Hz
Display turned-off automatically after 15 minutes
Sensors
Internal
External
Temperature
2 extension ports for temperature and humidity sensors
Measurements / Alarms
Accuracy
P
Q
S
Ep
Eq(C)
Eq(L)
Urms
Irms
Upk
f
PF
[%]
[W]
[VAR]
[VA]
[kWh]
[kVARh]
[kVARh]
[V]
[A]
[V]
[Hz]
N/A
Ti, T1, T2
[°C]
H1, H2
[%]
Alarm
Alarm
Alarm
Alarm
1% (IEC 1036 Class 1)
Real power per phase & total
Reactive power per phase & total
Apparent power per phase & total
Real energy per phase & total
Reactive energy (Capacitive) per phase & total
Reactive energy (Inductive) per phase & total
Line voltage per phase
Output current per phase, Neutral, total
Peak line voltage per phase
Line frequency per phase
Power factor per phase
Internal temperature and values from external
temperature sensors
Humidity values from external sensors
Actual looks and features are subject to change without notice. © 8/2009 - 01/2014 (v5). All rights reserved.
Riedo Networks Ltd, Switzerland, www.riedonetworks.com, info@riedonetworks.com
Was this manual useful for you? yes no
Thank you for your participation!

* Your assessment is very important for improving the work of artificial intelligence, which forms the content of this project

Download PDF

advertising