MR-2608 Fire Alarm Control Unit
MODUL-R™
MR-2608
FIRE ALARM CONTROL UNIT
GENERAL DESCRIPTION
FEATURES
The MR-2608 is a microprocessor based fire alarm control unit with
8 zones for conventional fire detection devices.
• UL, ULC, CSFM, and MEA Listed
• 5 year warranty
• Conventional input circuits 8-Style B (Class B) or 4-Style D (Class A)
Front Panel
• Input circuits programmable for N.O. or N.C. contacts
The front panel consists of 4 system LEDs, 8x2 zone LEDs, and
6 function keys. The four system LEDs provide common indication of
alarm, trouble, supervisory, and AC power. LEDs will flash with a
new condition and will remain on steady after acknowledgement.
The zone LEDs consist of a red alarm LED and a yellow trouble LED
for each input circuit. LEDs will flash with a new condition and will
remain on steady after acknowledgement. Amber alarm LEDs are
available by special order for use with supervisory zones.
• Style Y (Class B) notification appliance (bell) circuits
• System alarm and trouble relays
• Alarm and trouble LEDs for each zone
• Custom labels per zone
• Alarm verification by zone
• Ground fault indication by input circuit
• Programmable input circuits
Function keys provide the following functions : acknowledge, signal
silence, system reset, ground fault, lamp test, and city disconnect.
Each function key has an LED to indicate when it is available.
• Two stage alarm capability
The yellow zone LEDs are also used to indicate common troubles.
This function is activated by pressing the Ground Fault function key.
• Optional remote annunciator
• Field programmable via service terminal
• 'Hot Key' system controls
• Signal silence inhibit
Input Circuits
• Signal time limit cut-out
Input circuits are individually software definable for contact devices
only, smoke detectors only, or combination of smoke detectors and
contact devices. Circuits defined for smoke detector and contact
devices are able to differentiate between smoke detector operation
and contact device operation which permits combining contact and
smoke detectors on one common circuit when the alarm verification
feature is used. The circuits are further definable for alarm or supervisory. If there are any supervisory zones defined, the function relay
becomes the supervisory relay. Input circuits programmed for contact
devices can be further defined for use with N.O. or N.C. contacts.
Circuits can support Style B (Class B) or Style D (Class A) wiring.
When Style D wiring is used, two circuits are required for each
Style D circuit.
Ground fault conditions occurring on the input circuits are
indicated as to the circuit of origin of the ground fault.
MODUL-R
• Totally software driven
MR-2608
Output Circuits
The MR-2608 provides 2 supervised polarity reversing notification
appliance (bell) circuits, 1 general purpose Form C relay, and
2 system operated Form C relays for alarm and trouble indication.
Ground faults are indicated by notification appliance (bell) circuit.
The general purpose Form C relay operation is program defined. If
there are any supervisory type input circuits, the general purpose
relay becomes the supervisory relay.
The system Form C relays are for alarm and trouble indication. The
trouble relay is normally energized to allow for indication of both AC
power and battery power loss.
Fire Alarm
Control
Unit
MODUL-R™ FIRE ALARM CONTROL UNIT
MR-2608
TECHNICAL DATA
120VAC, 60Hz or 220VAC, 50Hz
INPUT POWER
INPUT CIRCUITS (8)
Voltage
Supervisory current
Contact devices
Smoke detectors
Alarm current
Contact devices
Smoke detectors
Max. no. of devices
Compatible devices
End-of-line device
Contact circuit
Smoke detectors
Total line resistance
Total line capacitance
Maximum line length
20-28VDC
BATTERY
10mA
10mA
ANNUNCIATOR
10mA
80mA
30 (smoke detectors)
MR series
BELL 1
BELL 2
470 Ω resistor
3.9kΩ resistor
60Ω
100µf
3,050m (10,000ft) (18AWG)
NOTIFICATION APPLIANCE (BELL) CIRCUITS (2)
Supervisory current
Alarm current
Voltage
End-of-line device
1.0mA
2.0A, 3.0A total for unit
24VDC (unfiltered)
10kΩ resistor
SYSTEM RELAYS (2)
Alarm, trouble
0.5A @ 120VAC
GENERAL PURPOSE RELAY (1)
0.6A @ 120VAC
BATTERY CAPACITY
4.0Ah
+
+
TXD
RXD
+
+
-
ORDERING INFORMATION
Model
Description
BASIC CONTROL UNIT PACKAGE
MR-2608
Conventional control unit,
8 circuit
ACCESSORIES
COM
AUX. RELAY N.O.
N.C.
MR-220-4VAC
MR-2614
MR-2614S
COM
N.O.
N.C.
CHASSIS GND
COM
TROUBLE N.C.
N.O.
+
ZONE 1
+
ZONE 2
+
ZONE 3
+
ZONE 4
+
ZONE 5
+
ZONE 6
+
ZONE 7
+
ZONE 8
ALARM
MR-2613
MRD-MP300
MRD-EOL-470
MRD-EOL-3k9
MRD-EOL-10k
MR-2995
MR-2608FT
Terminal Strip
220VAC, 50Hz option
Remote annunciator board
Remote annunciator
c/w board
Remote trouble buzzer
Plate for end-of-line resistor
for contact circuits and
notification appliance
(bell) circuits
470Ω end-of-line resistor for
contact circuits
3.9kΩ end-of-line resistor for
smoke detector circuits
10kΩ end-of-line resistor for
notification appliance (bell)
circuits
4Ah battery pack
Flush trim
DIMENSIONS
Back box :
Outer door :
30.48W x 26.67H x 9.84Dcm
(12 x 10.5 x 3.875in)
32.70W x 27.31H x 1.27Dcm
(12.875 x 10.75 x 0.5in)
Distributor:
Secutron Inc.
Electronic Protection Systems
70 Esna Park Drive, Unit 14
Markham, Ontario, Canada
L3R 6E7
MODUL-R
Tel: (905) 470-4070
Fax: (905) 470-2880
Toll Free: 1-800-387-8058
E-mail: inquiry@secutron.ca
www.secutron.ca
MR-2608
One River Place
1225 East River Drive, Suite 210
Davenport, IA 52803
Phone: 1-888-673-2900
Fax: (319) 322-0497
Fire Alarm
MODUL-R™ is a
trademark of Secutron Inc.
®
A DSC Company
Control
Document #10-204
Unit
Release 2.0 - 07/99
©1999 Printed in Canada