Interface modules
Interface modules
Interface modules for intelligent fire detection and alarm systems
An analogue fire system is usually designed with a number of loops, each beginning and ending at the
fire panel. The integrity of loop wiring is vital for data transmission, where a short circuit between loop
wires would be very serious. Hence it is necessary to have isolating circuits positioned in the loop in
order to isolate any section containing a short circuit, until the fault is rectified.
The isolator detailed here is polarity sensitive and will normally switch out the negative arm of the loop, when a
short circuit is sensed.
Normally the isolator allows current flow in both directions. If the loop voltage falls beneath a preset threshold the
isolator will switch open to isolate the incoming and outgoing lines. The device will test the isolated section
regularly and will reconnect when the fault is cleared.
Isolating devices are provided either as standalone products or integral within many interfaces, detection or sounder
units. Interfaces with integral isolators and detectors fitted to isolating bases will stay operational when the adjacent
section of loop is isolated. The isolating unit, when isolating, will display a yellow fault indication LED.
It is good practice for devices wired between two isolators to be located in the same zone.
Zone monitor with isolator
FA95-ZMU
Powers a zone of up to 20 conventional detectors (Orbis or FAP6) from the
loop. The device sends a high analogue value to the panel, only when a
detector on the monitored circuit changes to an alarm state. Features:
●
Suitable for both Anatec FA95 and Discovery protocols
●
Surface mounting with entry points for cut out on sides and rear
●
Connections for loop in & out wiring and detector zone + & – inputs
SPECIFICATION
FA95-ZMU
Zone monitor unit [ZMU]
Loop in
Application:
A ZMU is used to connect a
system of conventional
devices to an analogue
addressable fire system.
PSU
o
17Vdc, 28Vdc
Indicators
Red LED for alarm, yellow LEDs for a short circuit loop-wiring fault
Output to panel
Signal on detector alarm
Isolation
Short circuit isolator fitted
Current consumption at 24V (max) 11mA in alarm
Loop out
Illustration
:
Zone monitor unit [FA95-ZMU]
Min/max loop operating voltage
Quiescent current
4mA
Construction
Polycarbonate box, indoor use
Dimensions hwd (mm)
150 x 90 x 48
Weight g
230
o
o
Conventional detectors
Emergi-Lite Orbis
FAP6
AL-1
o
AL-2
CIE
EOL
Office
o
Office
o
Office
o
Canteen
o
H
Reception
o
o
o
o
o
Key:
ZMU
SCC
Manual call point
o
28
o
Separate building - annex
PSU
Analogue detector
Conventional detector
o
o
o
o
A building previously protected by a conventional fire system:-
Conventional sounder
Interface modules | Zone monitor
The conventional panel is replaced by a zone monitor unit [ZMU] and a sounder circuit controller
[SCC]. This system can now be connected to the main analogue panel in another building (the
conventional devices and wiring remain unaltered).
www.emergi-lite.co.uk
Interface modules
Switch monitor with isolator
FA95-SMU
Monitors one or more volt-free contacts connected on a single pair of
wires. Open or short circuit faults are reported. Features:
●
Suitable for both Anatec FA95 and Discovery protocols
●
Surface mounting with entry points for cut out on sides and rear
●
Connections for loop in & out wiring and external monitor
SPECIFICATION
Min/max loop operating voltage
17Vdc, 28Vdc
Indicators
Red LED for alarm, 2 yellow LEDs for wiring faults
Output to panel
Normal, fault, pre-alarm, alarm
Isolation
Short circuit isolator fitted
Current consumption at 24V (max)
3.6mA
Quiescent current
1.25mA
Max. switching current
3A
Construction
ABS plastic box, indoor use
IP rating
IP54
Dimensions hwd (mm)
150 x 90 x 48
Weight g
240
FA95-SMU
AL-1
Beam
reflector
CIE
AL- 2
Office
Office
o
o
Office
Canteen
o
Switch monitor unit [SMU]
H
o
Loop out
Loop in
Reception
Device to be
monitored
o
o
o
o
o
Warehouse
Key: analogue devices
Manual call point
SMU
o
Beam
detector
A switch monitor unit [FA95-SMU]
is used to input a ‘fire’ signal down
the loop within 10 seconds from
the activation of devices such as:
• Sprinkler switch activated
• Beam detector activated
• Plant alarm
Detector
Sounder
Mini switch monitor
FA95-SMUM
Monitors one or more volt-free contacts connected on a single pair of
wires. Small unit, ideal for fitting into equipment with limited space.
Features:
●
Suitable for both Anatec FA95 and Discovery protocols
●
Locate with double sided tape in seat area
●
Connect flying leads to user provided connector block. Red & black for
loop, yellow & green to remote LED, violet & white to monitored circuit
SPECIFICATION
Min/max loop operating voltage
17Vdc, 28Vdc
Indicators
Red LED for alarm with connection for a remote LED (triggered
simultaneously)
Output to panel
Normal, fault, pre-alarm, alarm
Current consumption at 24V (max)
3.5mA on alarm
Quiescent current
1mA
Construction
Polycarbonate moulding with six flying leads
Dimensions hwd (mm)
76 x 47 x 14
Weight g
46
www.emergi-lite.co.uk
FA95-SMUM
29
Switch monitors | Interface modules
Interface modules
Switch monitor PLUS with isolator
FA95-SMUPLUS
Monitors one or more volt-free contacts connected on a single pair of
wires. An opto coupled output is fitted for resetting a remote detector and
a selectable delay. Applicable for flow switch monitoring. Features:
●
Suitable for both Anatec FA95 and Discovery protocols
●
Surface mounting with entry points for cut out on sides and rear
●
Connections for loop in & out wiring and external monitor
SPECIFICATION
FA95-SMUPLUS
Min/max loop operating voltage
17Vdc, 28Vdc
Indicators
Red LED for alarm, 2 yellow LEDs for wiring faults
Output to panel
Normal, fault, pre-alarm, alarm
Isolation
Short circuit isolator fitted
Current consumption at 24V (max)
3.6mA
Quiescent current
1.25mA
Max. switching current
3A
Construction
ABS plastic box, indoor use
IP rating
IP54
Dimensions hwd (mm)
150 x 90 x 48
Weight g
240
Mini switch monitor with interrupt
FA95-SMUM-INT
Monitors one or more open switches connected on a single pair of wires
and gives a priority response in the event of a fire. For example: to signal
when a conventional manual call point (singly or in a zone) is activated.
Features:
FA95-SMUM-INT
●
Suitable for both Anatec FA95 and Discovery protocols
●
Locate with double sided tape in seat area
●
Connect flying leads to user provided connector block. Red & black for
loop, yellow & green to remote LED, violet & white to monitored circuit
Switch monitor interrupt unit [SMUM-INT]
SPECIFICATION
Loop in
Loop out
MCP
Min/max loop operating voltage
17Vdc, 28Vdc
Indicators
Red LED for alarm with connection for a remote LED (triggered
simultaneously)
Output to panel
Normal, fault, alarm
Current consumption at 24V (max)
4mA
Quiescent current
870µA
Construction
Polycarbonate moulding with six flying leads
Dimensions hwd (mm)
76 x 47 x 14
Weight g
46
EOL
A switch monitor interrupt unit [FA95-SMUM-INT]
signals back to the CIE within 3 seconds of
activation, so that it can be used for priority devices
such as:o Supervisory call points
o Secure area key operated call points
AL-1
CIE
Key:
Office
AL-2
Office
Office
Canteen
SMUM-INT
o
o
o
o
H
Manual call point
Reception
o
30
o
Analogue detector
Conventional detector
o
o
o
o
o
Conventional sounder
Interface modules | Switch monitor
www.emergi-lite.co.uk
Interface modules
Sounder circuit controller
FA95-SCC
Operates and controls a zone of externally powered sounders. Status report
signals are sent to the panel. Sounders are able to work continuously or
pulsed, individually or in groups (sounders can be synchronised in pulsed
operation.) External power supply is monitored. Features:
●
Suitable for both Anatec FA95 and Discovery protocols
●
Surface mount unit with entry points for cut out on sides and rear
●
Connections for loop in & out wiring, sounder circuit, fault inputs &
local power supply
FA95-SCC
SPECIFICATION
Min/max loop operating voltage
SCC is loop powered:17Vdc, 28Vdc.
An external supply is required for the alarm load
Indicators
Red LED for alarm, yellow LED for a short circuit loop
wiring fault & another yellow LED for fault detection
Output to panel
Signal on short or open circuit fault, or external
power supply fault
Isolation
Short circuit isolator fitted
Current consumption, loop, at 24V (max)
3.6mA
Quiescent current
1.95mA
Current consumption, external supply (max)
47mA at 32Vdc plus sounder load
Maximum sounder circuit current
1A at 30Vdc
Construction
ABS plastic box, indoor use
Dimensions hwd (mm)
150 x 90 x 48
Weight g
240
AL-1
CIE
SCC
Office
AL-2
o
Office
o
Canteen
Office
o
Loop in
Loop out
H
o
PSU
Reception
o
o
o
o
o
EOL
SCC
Sounder circuit controller, FA95-SCC
controlling conventional 24 volt
sounders, when a signal is received
from the loop.
PSU
Application examples:
• When loop sounders do not provide
a high enough sound output
required for the premises
• When more than 2 conventional
alarm outputs are required on the
system
Warehouse – noisy environment
Key:
Manual call point
o
o
Analogue detector
Conventional detector
Conventional sounder
www.emergi-lite.co.uk
Sounder circuit controller | Interface modules
31
Interface modules
Input/Output unit with isolator
FA95-1CI/O
A two channel I/O interface device for interfacing external equipment and
the fire detection system together. Two outputs, with volt-free contacts, are
provided from a loop powered relay which is activated by a control signal
from the panel. Two inputs (one monitored and one opto-coupled
unmonitored) enable open or closed switch positions to be reported along
with fault. Features:
FA95-1CI/O
●
Suitable for both Anatec FA95 and Discovery protocols
●
Surface mount unit with entry points for cut out on sides and rear
●
Connections for loop in & out wiring, relay contacts and external
monitoring
SPECIFICATION
Input/output unit
[I/O]
NO
C
NC
NO
C
Loop out
17Vdc, 28Vdc
Indicators
2 red LEDs for relay and switch position, 2 yellow LEDs for
wiring faults
Isolation
Short circuit isolator fitted
Current consumption at 24V (max)
3.5mA
Quiescent current
1.25mA
Max switching current
3A
Construction
ABS plastic box, indoor use
IP rating
IP54
Dimensions hwd (mm)
150 x 90 x 48
Weight g
240
NC
HVac
FA95-ICI/O Input/output interface unit
Two single pole volt free relay outputs for
controlling various pieces of equipment in the
event of a fire, for example:
• Plant shutdown
• Fire dampers
• Door magnets
• Security doors
• Moving a lift to ground floor
GS
I/O
GAS
BOILER
Loop in
Min/max loop operating voltage
CIE
o
An HVac (heating, ventilation or air-conditioning)
control is illustrated
o
o
I/O
o
PSU
Door retainer
o
Fire door
o
Door retainer
o
GS - gas solenoid
o
o
Fire door
o
o
Key:
Manual call point
o
32
o
Analogue detector
Conventional detector
Conventional sounder
Interface modules | Input/output units
www.emergi-lite.co.uk
Interface modules
Output unit with isolator
FA95-1CO
A two channel output device for interfacing external equipment and the
fire detection system together. Two outputs, with volt-free contacts, are
provided from a loop powered relay which is activated by a control signal
from the panel. Features:
●
Suitable for both Anatec FA95 and Discovery protocols
●
Surface mount unit with entry points for cut out on sides and rear
●
Connections for loop in & out wiring and relay contacts
SPECIFICATION
FA95-1CO
Min/max loop operating voltage
17Vdc, 28Vdc
Indicators
1 red LED for relay and switch position, 1 yellow LED for wiring
faults
Isolation
Short circuit isolator fitted
Current consumption at 24V (max)
3mA
Quiescent current
400µA
Max switching current
3A
Construction
ABS plastic box, indoor use
IP rating
IP54
Dimensions hwd (mm)
150 x 90 x 48
Weight g
240
Mains switching input/output unit
FA95-1CO-240
Designed to switch equipment operating at 230V/50Hz, such as mains
powered magnetic door holders or other mains powered machinery.
Features:
●
Suitable for both Anatec FA95 and Discovery protocols
●
Volt-free single pole changeover relay output
●
Monitored switch input
●
Surface mount unit with entry points for cut out on sides and rear
●
Connections for loop in & out wiring, mains and relay
FA95-1CO-240
SPECIFICATION
Min/max loop operating voltage
17Vdc, 28Vdc
Indicators
1 red LED for relay set, 1 red LED for switch input closed,
1 yellow LED for wiring faults
Isolation
Short circuit isolator fitted
Current consumption at 24V (max)
3.5mA
Quiescent current
1.25mA
Max switching capacity
1.25kVA
Construction
ABS plastic box, indoor use
IP rating
IP54
Dimensions hwd (mm)
150 x 90 x 48
Weight g
240
33
www.emergi-lite.co.uk