Switched Rack PDU AP7968B
Switched Rack PDU AP7968B
Overview
The APC by Schneider Electric Switched Rack Power Distribution Unit (PDU) distributes power
to devices in the rack. It has a sensor that measures the current used by the PDU and its
attached devices. It can be monitored through Web, Telnet, SNMP, SSH, or StruxureWare Data
Center Expert® interfaces.
Outlets: The outlets connect the Rack PDU to equipment in your rack or enclosure. Each outlet
allows independent control of the connected equipment and the Rack PDU firmware also
provides Outlet User accounts. Twenty-one (21) IEC-320-C13 outlets (15A max) and three (3)
IEC-320-C19 outlets (16 A max). APC by Schneider Electric power cord AP9877 is available for
purchase for use with C19 outlets.
Digital display: A digital display shows aggregate current being used per bank.
Power cord: The 0.91-m (3-ft) cord terminates with a CS8365C plug.
Specifications
Electrical
Nominal input voltage
200– 240 VAC, 3-phase
Acceptable input voltage
+6% / -10% of nominal voltage
Maximum total current draw 35 A
Input frequency
50– 60 Hz
Cord length
0.91m (3 ft)
Input connector
CS8365C plug
Output connectors
(21) IEC-320-C13, (3) IEC-320-C19 outlets
Overload protection
Three (3) 2P 20 A circuit breakers
Output current
15A/C13, 16A/C19; 16A/ bank
Physical
Size (H × W × D)
Including breaker box
Shipping (H x W x D)
1778×56×45 mm (70.00×2.20×1.75 in)
1778×56×89 mm (70.00×2.20×3.50 in†)
2108 × 114 × 152 mm (83.00 × 4.50 × 6.00 in)
Weight
7.79 kg (17.78 lb)
Shipping weight
10.75 kg (24.28 lb)
Environmental
Elevation (above MSL)
Operating
Storage
0–15 000 ft (0–4500 m)
0–50 000 ft (0–15 000 m)
Temperature
Operating
Storage
–5 to 45° C (23 to 115° F)
–25 to 65° C (–13 to 149° F)
Humidity
Operating
Storage
5–95% RH, Non-condensing
5–95% RH, Non-condensing
Compliance
Safety
UL/cUL
EMC
FCC part 15 Class A, ICES-003 Class A
†
Depth of 89 mm (3.50 in) is for 191 mm (7.50 in) along the height of the Rack PDU.
Customer support and warranty information are available on the website, www.apc.com.