Ordering information
Supply voltage
I/O
Interfaces
230
-
230 (94…264) V AC
24
-
24 (19…30) V DC
1
-
8 DI, 6 DO
2
-
8 DI, 4 AI, 8 DO, 2 AO (4-20 mA)
4
-
8 DI, 4 AI, 8 DO, 2 AO (0-10 V)
0
-
none
1
-
RS485
2
-
2x RS485
Specifications
Table 1 General specification
PR200-230.2
PR200-24.2
PR200-24.1
PR200-230.4
PR200-24.4
Power supply
230 (94…264) V AC; 50 (47…63) Hz
24 (19…30) V DC
Power consumption, max
10 VA
17 VA
10 W
10 W
Galvanic isolation
2830 V
1780 V
Integrated voltage source
24±3 V DC, 100 mA
Galvanic isolation
1780 V
Inputs
Digital
8
Analog *
4
4
Outputs
Digital (relay)
6
8
6
8
Analog
2
2
IP Code
IP20
Dimensions
123 x 108 x 58 mm
Mounting
DIN rail (35 mm)
Weight
approx. 600 g
* Analog inputs AI1…AI4 can also be configured as digital inputs.
Device
PR200-230.1
Table 4 Analog inputs
Device
only PR200-230(24).2, PR200-230(24).4
Galvanic isolation
none
Mode
Analog
Input signal
0-10 V, 4-20 mA, 0-4 kohm
Input voltage *
-36…+36 V
Input resistance (0-10 V)
61 ohm
Input resistance (4-20 mA)
121 ohm
Mode
Digital
Logical 1 **
0…10 V, adjustable
Logical 0 **
0…10 V, adjustable
Current at input voltage 15…30 V, max
5 mA
* If the voltage at one input is below -0.5 V, the accuracy for all inputs cannot be guaranteed
** Parameter can be set in ALP Property Box using the option ‘Input mode’ = ‘digital’.
Table 5 Analog outputs
Device
Auxiliary voltage
Quantity
Output signal
Output load, max
Basic error, max
Temperature influence
Inductive load, max
Signal conversion time
DAC resolution
Galvanic isolation
PR200-230(24).2
PR200-230(24).4
12…30 V DC
2
4-20 mA
1 kohm
0-10 V
2 kohm
±0.5%
±0.05%/10 °C
50 µH
100 ms
10 bit
2830 V, individual
Table 2 Digital inputs
Device
PR200-230.2
PR200-230.4
PR200-230.1
Input voltage
Input voltage, max
Galvanic isolation
Test voltage between input groups
Test voltage against other circuits
230 V AC
264 V AC
a)
PR200-24.2
PR200-24.4
PR200-24.1
24 V DC
30 V DC
2830 V, in groups
Fig. 1 Dimensions
Fig. 2
b)
Fig. 3
Installation
in groups of 4 (1-4, 5-8)
1780 V
2830 V
1.
Align the upper slide of the DIN rail mounting groove with the DIN rail (arrow 1) and posh it onto the rail (arrow 2).
2.
Wire external connections in accordance with Fig. 5-9 and tables 6–7 using plug-in terminal blocks (included).
Table 3 Digital outputs
Device
PR200-230.1
Type
Galvanic isolation
Test voltage between output groups
Test voltage against other circuits
PR200-230.2
PR200-24.1
PR200-230.4
relay (NO)
in groups of 2 (1-2, 3-4, 5-6, 7-8)
1780 V
2830 V
PR200-24.2
PR200-24.4
►
NOTICE
When wiring the device the terminal blocks with the same number of contacts can be encoded using coding elements from the package to prevent
swapping. If the coding tab is inserted into the recess in the header (Fig. 3a), and the coding profile is inserted into the slot on the plug (Fig. 3b), it is
impossible to connect them.
WARNING
PR200_2016.08_0008_EN
© All rights reserved. Subject to technical changes and misprints.
The device should be configured via PC before mounting and wiring.
Switch on the power supply only after the wiring of the device has been completely performed.
akYtec GmbH · Vahrenwalder Str. 269 A · 30179 Hannover · Germany
Tel: +49 (0) 511 16 59 6720 · www.akytec.de
PR200
Programmable relay
Electrical connections
38
АО1+
39
АО2-
40
АО2+
Analog output AO2 (4-20 mA)
38
V+
Auxiliary voltage +24 VDC
39
АО1
Analog output AO1 (0-10 V)
40
АО2
Analog output AO2 (0-10 V)
b
a
Fig. 5 Connecting switch contacts to digital inputs: a) PR200-24, b) PR200-230
►
NOTICE
Fig. 6 Connecting 3-wire sensors with PNP transistor
outputs
Supply voltage for outputs may not exceed 30 V.
Fig. 4 Terminal blocks
Table 6 Terminal assignment
№
Designation
Function
№
Designation
Function
1
AC230V L /
DC24V -
Power supply AC / DC *
21
DO5
Digital output DO5
2
AC230V N /
DC24V +
Power supply AC / DC *
22
-
Common contact DO5...DO6
3
COM1
Common minus pole DI1...DI4
23
DO6
Digital output DO6
4
DI1
Digital input DI1
24
DO7
Digital output DO7
5
DI2
Digital input DI2
25
-
Common contact DO7...DO8
6
DI3
Digital input DI3
26
DO8
Digital output DO8
7
DI4
Digital input DI4
27
AI1
Analog input AI1
8
COM2
Common minus pole DI5...DI8
28
COM3
Common minus pole AI1...AI2
9
DI5
Digital input DI5
29
AI2
Analog input AI2
10
DI6
Digital input DI6
30
AI3
Analog input AI3
11
DI7
Digital input DI7
31
COM4
Common minus pole AI3...AI4
12
DI8
Digital input DI8
32
AI4
Analog input AI4
13
OUT 24V+
24 V DC integrated voltage source
33
RS-485 D-
RS485 Port1 D-
14
OUT 24V-
24 V DC integrated voltage source
34
RS-485 D+
RS485 Port1 D+
15
DO1
Digital output DO1
35
RS-485 D-
RS485 Port2 D-
16
-
Common contact DO1...DO2
36
RS-485 D+
RS485 Port2 D+
17
DO2
Digital output DO2
37
AO1- / V-
see Table 7
18
DO3
Digital output DO3
38
АО1+ / V+
see Table 7
19
-
Common contact DO3...DO4
39
АО2- / АО1
see Table 7
20
DO4
Digital output DO4
40
АО2+ / АО2
see Table 7
a
b
Fig. 7 Wiring of analog inputs: a) 4-20 mA, b) 0-10 V, c) resistors (up to 4000 ohm)
►
NOTICE
Wire the terminals only when the device is powered off.
a
Fig. 8 Relay outputs
b
Fig. 9 Wiring of analog outputs: a) 4-20 mA (PR200-X.2), b) 0-10 V (PR200-X.4)
Removal
1.
Take off the terminal blocks without disconnecting the
wires (Fig. 10)
* Depending on the device modification (PR200-230 or PR200-24)
2.
Insert a screwdriver into the eyelet of the slide interlock
(Fig. 11)
Table 7 Terminal assignment
only PR200-230(24).2.2
3.
Loosen the slide interlock pushing the screwdriver in the
direction of the arrow 1, and then remove the relay from the DIN
rail pulling the device in the direction of the arrow 2.
only PR200-230(24).4.2
№
Designation
Function
№
Designation
Function
37
АО1-
Analog output AO1 (4-20 mA)
37
V-
Auxiliary voltage -24 VDC
PR200_2016.08_0008_EN
© All rights reserved. Subject to technical changes and misprints.
c
Fig. 10 Disconnecting terminal blocks
Fig. 11 Removing PR200 from the
DIN rail
akYtec GmbH · Vahrenwalder Str. 269 A · 30179 Hannover · Germany
Tel: +49 (0) 511 16 59 6720 · www.akytec.de
Was this manual useful for you? yes no
Thank you for your participation!

* Your assessment is very important for improving the work of artificial intelligence, which forms the content of this project

Download PDF

advertising