SAFETYLUX® Typ Ruby RU29
GB
B.E.G.
SAFETYLUX® Typ Ruby RU29
Operating and installation instructions - for aluminium profile light for four different types of installation
3. Wall mounting
Slide side part to one side (Fig. 1). The panel is now removed.
You can now drill the holes in the wall. Once the holes have
been drilled, the cable is inserted and the housing secured to
the wall. Connect power supply according to circuit diagram
(Fig. 7) and refit panel. Slide side part together and switch
on mains.
Accessories:
1 wall sheet
Fig. 4
Fig. 2
1. Operating mode
The SAFETYLUX® Type Ruby RU29 is an aluminium profile
light with a modern design. It can be used as emergency and
directional lighting. It can be seen up to a distance of 29 m
away. This emergency and directional lighting is either available with conventional function monitoring in the form of a
test button or with automatic function monitoring (data check
AF). Up to four different types of installation are possible.
Depending on the version, the emergency light can operate for
between 1 and 3 hours.
4. Ceiling mounting
5. Pendant mounting
Slide side part to one side. The panels are now removed.
Remove plug from upper part of housing. Screw a threaded
nut onto the threaded tube and slide the threaded tube from
above through the ceiling mounting box and secure with a
second threaded nut. Fit ceiling mounting box on ceiling. After
inserting the mains cable, secure housing to ceiling mounting
box with threaded nut.
Connect up mains according to circuit diagram and refit
panels. Slide side part together and switch on mains.
Slide side part to one side. The panels are now removed. Remove plug from upper part of housing. Secure the two square
threaded connectors with sockets to upper part of housing.
Screw pendant rods into sockets, slide baldachin over pendant
rod, screw pegs onto pendant rods and guide mains cable
through pendant rod into housing. Attach light. Connect mains
according to circuit diagram and refit panels. Slide side part
together and switch on mains.
2. Replacing the illuminant
Accessories:
Accessories:
The bulb is replaced without any tools. (Fig. 1)
2 pegs
2 baldachin
2 sockets M13
2 square threaded
connectors M13
2 pendant rods 0.5 mm
1 ceiling mounting box
2 threaded tubes 10 mm
6 threaded nuts 10 mm
• Slide mobile side part to
one side
• Remove panel
• Replace bulb
• Refit panel
• Slide side part together
again
Fig. 1
Fig. 5
Fig. 3
6. Wall bracket mounting
Guide cable through wall bracket and secure wall bracket to
wall. Slide side part of housing to one side. Now remove the
panels. Remove plug from upper part of housing. Use threaded
tubes and threaded nuts supplied to connect housing to wall
bracket. Insert mains cable and connect according to circuit
diagram. Slide in panels and snap side part back in. Switch
on mains.
Accessories: 1 wall bracket
2 threaded tubes 13 mm
6 threaded nuts 13 mm
• Ready light:
T erminal 2 and 3 (L1 und N) = 230 V
non-switched mains, charge battery
• Permanent light:
Terminal
1 and 3 (L2 und N) = switchable net, mains can be switched if light
is also to light up when the mains is
present
8. Regular maintenance work
• Weekly: emergency light function = press test
button on light or switch off mains
• Annually: perform endurance test = switch off
mains and measure period of light
• Bulb replacement: change illuminant every 10 - 12
months if maintained
9. Technical data
Fig. 6
7. Circuit diagram
AC/DC 230 V
1
EB
EVG
2
3
8 W T16
4
•Aluminium profile, white housing
•Display panels made from Perspex
Directional light
battery
Batterie
L
N
L’
PE
emergency
Notbetrieboperation
emergency
Notbetrieboperation
Emergency light
•Mains voltage: 230 VAC,
EB 230 VAC/DC ± 10 %
•Range:
ca. 29 m
•Emergency light:
NiCd batteries, maintenance-free,
operation 1 or 3 - hour period of light
•Illuminant:
LLp 8W T16
•Dimensions:
Wall mounting
L 370 x W 80 x H 185 mm
Wall bracket
L 370 x W 80 x H 188mm
Pendant mounting
L 370 x W 80 x H 685mm
Ceiling mounting
L 370 x W 80 x H 185mm
•Degree/class
of protection
IP20 / I /
≈
=
≈
8W
Fig. 7
10. Article / Part nr. / Accessories
Typ
Part nr.
RU29/8/EB-LLD/W
1400
RU29/8/1-LLD/W
1402
RU29/8/3-LLD/W
1403
RU29/8/EB-LLD/WB
1404
RU29/8/1-LLD/WB
1406
RU29/8/3-LLD/WB
1407
RU29/8/EB-LLD/P
1410
RU29/8/1-LLD/P
1412
RU29/8/3-LLD/P
1413
RU29/8/EB-LLD/D
1414
RU29/8/1-LLD/D
1416
RU29/8/3-LLD/D
1417
Accessories:
• Display, arrow to the left
• Display, arrow to the right
• Display, arrow down
30538
30539
30537
MAN 6280 – 041209-2
When working on the light, always switch
off the power supply!
Was this manual useful for you? yes no
Thank you for your participation!

* Your assessment is very important for improving the work of artificial intelligence, which forms the content of this project

Download PDF

advertising