IBG LED HIGHBAY
INSTALLATION INSTRUCTIONS
WARNING: Please read all “important safety instructions” prior to installation of this product.
A) Identification of IBG Luminaire – Page 4
1) IBG 8000LM
2) IBG 12000LM, 15000LM
3) IBG 18000LM, 24000LM, 30000LM
4) IBGN 18000LM
5) IBGN 24000LM, 30000LM, 36000LM
6) IBG 36000LM, 48000LM, 60000LM
7) BPK Option
8) PS30250 Option
9) WGX Option
10) IBG V-HANGER Accessory
11) THUN (Surface Mount) Accessory
12) PMP (Pendant Mount) Option
B) Required Handling Locations – Page 5
C) Pre-installation for all mounting – Page 5
D) Installation – Suspended Fixture – Page 5
E) Installation – THUN (Surface) Mount – Page 6
F) Installation – PMP (Pendant) Mount – Page 6
G) Installation – External Occupancy Sensor – Page 7
H) Installation – NPP16D Controller – Page 7
I) Wiring – Emergency (BGTD, PSDC, PS1050, PS10250, PS30250) – Page 7
J) Wiring – IMP Connector – Page 8
K) Servicing – Page 8
U02301 Rev. B
Page 3 of 8
LED IMPORTANT SAFETY INSTRUCTIONS
SECTION A: Identification of IBG Luminaire
IBG 8000LM
IBG 12000LM, 15000LM
IBG 18000LM, 24000LM, 30000LM
2FT
IBGN 18000LM
IBGN 24000LM, 30000LM, 36000LM IBG 36000LM, 48000LM, 60000LM
4FT
BPK OPTION (Access Plate not removable)
HBBS V-HANGER ACCESSORY
U02301 Rev. B
PS30250 OPTION (Access Plate not removable)
THUN ACCESSORY
WGX OPTION
IBG PMP ACCESSORY
Page 4 of 8
LED IMPORTANT SAFETY INSTRUCTIONS
SECTION B: REQUIRED HANDLING LOCATIONS
BAD FOR HANDLING
GOOD FOR HANDLING
VENT HOLES, DO NOT PUT
SPLICE CONNECTIONS
ABOVE VENT HOLES
When handling the fixture during unpacking and installation do NOT use LED Modules for carrying/support. DO use the center
channel and end caps for carrying/support
Section C: PRE-INSTALLATION FOR ALL MOUNTING
1) Ensure power is OFF.
2) Inspect the mounting location for damage before installing new IBG Luminaire. Ensure mounting structure is properly sized to
support the weight of the fixture.
3) BPK and PS30250 are not available with THUN (Surface) or PMP (Pendant) mounting.
4) Remove luminaire from packing and inspect for any damages. If the fixture is damaged do not use; call your local representative
for assistance.
5) If a protective wrapping is included, do not remove until the final building/inspection stage. Do not use this luminaire as a work
light during construction. Do not touch the LEDs.
6) After installation ensure no wires are pinches or caught outside the electrical channel.
SECTION D: INSTALLATION - SUSPENDED FIXTURE
1) If using the V-hanger and chain, feed hanger through chain link.
2) If using the HBBS V-Hanger (supplied with HBBS36 and HBBSACVH), hook the hanger through holes in end cap shown below and
crimp closed. If using aircraft cable and hook, use the same holes to suspend the fixture. If using the HC V-Hanger (supplied with
HC36 and ZACVH), hook the hanger through holes in the electrical channel shown below. WARNING: For GYM applications additional
safety cables are needed.
Required Mounting Holes for
HBBS V-hanger, Hooks, Etc.
Access
Plate
Screw
U02301 Rev. B
Required Mounting Holes for
HC V-hanger (supplied with
HC36 and ZACVH)
Page 5 of 8
LED IMPORTANT SAFETY INSTRUCTIONS
3) Remove access plate screw as shown above. Input wires will be attached to the access plate. Remove the necessary knockout(s)
and connect input wires black to black, white to white and green to green. Use only UL listed connectors rated 90C or greater.
Purple and Gray wires are low voltage dimming leads.
4) Make any necessary electrical connections. Supply wire must meet applicable electrical codes and be rated for a minimum of
90⁰C. Purple and gray leads are 0-10V (low voltage) dimming leads.
5) Push wires inside center channel, ensure electrical connections are not located above vent holes as shown in the Section B image.
FAILURE TO DO SO WILL VOID CERTIFICATION AND WARRANTY.
SECTION E: INSTALLATION – THUN MOUNT
1) Follow Steps 3-5 from Section D
2) Attach THUN brackets to structure (not supplied). Two THUN brackets MUST be used on all configurations.
3) Support fixture while snapping fixture into THUN brackets. Ensure fixture is balanced.
4) Use supplied hardware to tighten THUN brackets around center channel as shown below. Tighten bolts to 13 in/lbs.
CARRIAGE BOLT
THUN BRACKETS
NUT
LOCK WASHER
SECTION F: INSTALLATION – PMP MOUNT
1) PMP Mounting is not available with BPK or PS30250
2) Attach PMP Hub to threaded pendant/conduit (not supplied) using 3/4"- 14 NPT THREAD HUB and Nut (supplied) as shown below.
3) If luminaire is 2FT install plastic bushing (supplied) in center hole.
4) Support fixture while snapping fixture into PMP Bracket. PMP bracket may need to be shifted off center in order for the fixture to
remain balanced. Ensure PMP Bracket Teeth fit inside center channel as shown below.
PMP Bracket Teeth
5) Use supplied carriage bolt, washer, and nut to tighten PMP Hub around center channel. Tighten to 13 in/lbs
6) Input wires will be pulled out of the center of the fixture. Make any necessary electrical connections. Supply wire must meet
applicable electrical codes and be rated for a minimum of 90⁰C. Purple and gray leads are 0-10V (low voltage) dimming leads.
7) Attach PMP Bracket sides with screws, one each as shown below. Ensure wires are not pinched.
8) DO NOT LEAN ON FIXTURE ONCE PMP IS ATTACHED.
U02301 Rev. B
Page 6 of 8
LED IMPORTANT SAFETY INSTRUCTIONS
Section G: Installation – External Occupancy Sensor
1) External Occupancy sensor will be pre-wired to the fixture.
2) Install external occupancy sensor to fixture by snapping into end cap as shown in the fixture below.
3) Rotate/Align the sensor head such that the sensor lens is parallel to the floor.
4) Install fixture based on specified mounting instructions.
Section H: Installation – NPP16D
1) NPP16D will be prewired to the fixture and attached to the access plate. The access plate will NOT be attached to the fixture.
2) Attach access plate to center channel using screw provided as shown below.
NPP16D and Access Plate
During Shipping
NPP16D and Access Plate
After Installation
Access Plate Screw
3) Install fixture based on specified mounting instructions.
Section I: Wiring – Emergency (BGTD, PSDC, PS1050, PS10250, PS30250)
1) Install fixture based on specified mounting instructions.
2) Input Wires will be located outside of the access plate. Access plate is not removeable. Connect unswitching power to fixture
wires labeled unswitched. Connect unswitched power to white, black, and green wires. Supply wire must meet applicable electrical
codes and be rated for a minimum of 90⁰C. Purple and gray leads are 0-10V (low voltage) dimming leads.
3) If using the PS1050 or PS10250, remove the top cover using the two quarter-turn fastners. Connector the white indictor light
connector to battery. If using the PS30250, two wires with connectors will be located outside of the access plate. Connect wires and
push back inside the luminaire as shown in the image below.
4) If using the PS1050 or PS10250, press the indicator light for testing. If using the PS30250, there will be a separate toggle switch
located on the outside of the fixture for testing.
Emergency Maximum Mounting Heights
Fixture Cat. No.
Max mounting height (ft)
IBG 8000LM SEF AFL WD PS1050
20
IBG 12000LM SEF AFL WD PS10250
15
IBG 12000LM SEF AFL WD PS30250
26
IBG 15000LM SEF AFL WD PS10250
15
IBG 15000LM SEF AFL WD PS30250
26
IBG 18000LM SEF AFL WD PS10250
18
IBG 18000LM SEF AFL WD PS30250
22
IBG 24000LM SEF AFL WD PS10250
18
IBG 24000LM SEF AFL WD PS30250
21
IBGN 30000LM SEF AFL WD PS10250
15
IBGN 30000LM SEF AFL WD PS30250
26
U02301 Rev. B
Top Cover
Wires with connectors will be
located outside of fixture
PS30250 Toggle Switch
Indicator Light
Page 7 of 8
LED IMPORTANT SAFETY INSTRUCTIONS
Section J: Wiring – IMP Connector
1) Install fixture based on specified mounting instructions.
2) A 5/8” knock out is located on the IMP access plate. If dimming is required remove access plate and knock out knockout. Pull
dimming wires through access plate and connect to dimming circuit. Reattached access plate to fixture.
3) Snap supply power with IMP male connector (not supplied) into luminaire female IMP connector.
SECTION K: SERVICING
1) Clean fixture as needed. Double check all mounting hardware.
2) After installation, wear protective gloves if the lenses need to be removed
3) The lens snaps around LED channel. To remove lens, carefully pull on outer leg to disengage from LED channel. Continue pulling
outer leg along the fixture length to disengage lens.
4) To replace the lens snap around LED Channel as shown in the image below.
LENS
LED CHANNEL
OUTER LEG TO BE
USED FOR REMOVAL
5) To access electrical components, loosen the two captive screws from central channel cover as shown below.
6) Driver Channel Cover will hang on central channel during servicing. Be cautious to avoid bumping fixture as the driver channel
cover can become disengaged.
DO NOT PLACE
ELECTRICAL
CONNECTIONS
BEHIND VENTS
DRIVER CHANNEL COVER DURING SERVICING
7) Make any necessary adjustments or driver changes. DO NOT PLACE ELECTRICAL CONNECTIONS ABOVE DRIVER CHANNEL COVER
VENTS
8) Close Driver channel cover and secure using two screws.
Warranty terms are located at the link below:
http://www.acuitybrands.com/resources/terms-and-conditions
U02301 Rev. B
Page 8 of 8