2.1 Surge Protection

2.1 Surge Protection
2.1
Surge Protection
Surge Protection Devices and Lightning Arresters
Surge Protection Devices
2
Product Description
Application Description
Due to the evolution
of electronics and
microprocessors in the
home, there is a continuous
challenge to provide quality
(clean) power for electronic
loads such as appliances,
computers/home office and
entertainment systems.
Surges caused by lightning,
utility grid switching and
other sources travel on
current carrying conductors
throughout the home, which
can affect and destroy
sensitive electronic loads.
Two-Stage Protection
Eaton offers a comprehensive
family of surge products for
use at service entrances.
These products can help
protect sensitive electronics
against the damaging effects
of surges.
Service Entrance Surge
Protection
Eaton’s service entrance
surge protection units
provide premier surge
protection for AC power
at the service entrance.
These products provide
protection for residential
electrical equipment by
reducing power surges
to an acceptable level for
surge strips to handle at
the point of use.
UL 1449 3rd Edition Type 1 and
Type 2 Surge Protection
●
Type 1 Surge Protective
Device (SPD)—
Permanently connected
Type 1 SPDs are intended
for installation between the
secondary of the service
transformer and the line
side of the service
equipment overcurrent
device, as well as the load
side, including watt-hour
meter socket enclosures,
and are intended to be
V1-T2-2
installed without an
external overcurrent
protective device.
Type 1 devices are
dual-rated for Type 2
applications as well,
providing the highest
ratings available for
installation at the service
entrance
●
Eaton’s CHSPT1
products provide Type 1
surge protection in
accordance with UL®
1449 3rd Edition. These
units can be universally
mounted outside any
manufacturer’s primary
service equipment
Two stages of surge
suppression are
recommended to provide
the best protection for
electronic equipment.
Two-stage surge suppression
should be provided for all
cables entering a home,
including power, Internet,
coaxial and telephone.
●
Type 2 Surge Protective
Device—Permanently
connected Type 2 SPDs
are intended for installation
on the load side of the
service equipment
overcurrent device,
including SPDs located at
the branch panel
●
CHSPT2 products provide
Type 2 surge protection in
accordance with UL 1449
3rd Edition. These units
can be mounted outside
of any manufacturer’s
loadcenter or inside an
Eaton Surge/Surge Ready
loadcenter. Eaton also
offers accessories to the
CHSPT2 line for
telephone and cable
protection
Volume 1—Residential and Light Commercial CA08100002E—August 2015 www.eaton.com
●
Factory-Installed Surge
Protection—Eaton’s
loadcenters with factoryinstalled surge protection
include a CHSPT2ULTRA
and a two-pole 50 A circuit
breaker. These loadcenters
increase the effectiveness
of surge protection due
to reduced lead length.
A modified deadfront
allows for easy viewing
of indicating lights for
status indication
Surge Panel
●
Surge Ready
Loadcenter—The Surge
Ready loadcenter provides
a mounting provision for
the CHSPT2ULTRA. This
loadcenter has a modified
deadfront to allow for
viewing of indicating lights
Surge Protection
Surge Protection Devices and Lightning Arresters
2.1
Two-Stage Protection
●
1
2
CHSP installed at the service entrance panel.
SurgeTrap™ surge traps and strips located where sensitive electronics are plugged in.
Plug-On Surge Protection
●
Type CHSA—For use on
single-phase 120/240 Vac
systems. The CHSA easily
plugs into a single-phase
Type CH loadcenter and
occupies two 3/4-inch
(19.1 mm) pole spaces,
similar to a two-pole Type
CH breaker. When installed
properly, it provides surge
protection for the entire
loadcenter. If internal
components are damaged,
the CHSA LED visual
indicators will signal the
need for a replacement.
This device is suitable for
service entry locations
when installed in
accordance with NEC®
guidelines
●
Type BRSURGE—For
use on single-phase
120/240 Vac systems. This
easily plugs into a singlephase Type BR loadcenter
and occupies two 1-inch
(25.4 mm) pole spaces
similar to a two-pole Type
BR breaker. When installed
properly, it provides surge
protection for the entire
loadcenter. If internal
components are damaged,
the BRSURGE LED visual
indicators will signal the
need for replacement.
This device is suitable
for service entry locations
when installed in
accordance with NEC
guidelines. This unit is
also classified by UL for
use in select GE, ITE/
Siemens and Crouse-Hinds
Panels (refer to Pub No.
5655B65H01 for additional
details)
●
Type CHQSA—For use
on single-phase, 120/240 Vac
systems. This unit easily
plugs into a Square D
single-phase loadcenter
Type QO® and occupies
two 3/4-inch (19.1 mm)
pole spaces similar to a
two-pole Type QO breaker.
When installed properly, it
provides surge protection
for the entire loadcenter. If
internal components are
damaged, the CHQSA LED
visual indicators will signal
the need for a replacement.
This device is suitable for
service entrance locations
installed in accordance
with NEC guidelines. This
device is UL classified to
be used in place of Square D
Type QO surge arresters
(refer to Pub-23974)
Type BRSURGECSA—
For use on single-phase
120/240 Vac systems. This
easily plugs into a singlephase Type BR loadcenter
and occupies two 1-inch
(25.4 mm) pole spaces
similar to a two-pole Type
BR breaker. When installed
properly, it provides surge
protection for the entire
loadcenter. If internal
components are damaged,
the BRSURGECSA LED
visual indicators will signal
the need for replacement.
This device is suitable
for service entry locations
when installed in
accordance with Canadian
Electrical Code. This device
is CSA® listed to be used in
a Type BR loadcenter
Type 3 Point-of-Use Surge
Protection
Point-of-use surge protectors
such as surge receptacles
are installed within 30 ft of
conductor length from the
service panel and are
designed to offer premium
surge protection for specific
electronics while providing
innovative features to
enhance user convenience.
Standards and
Certifications
●
●
●
●
●
●
CHSPT1 Products: UL
1449 3rd Edition Type 1
CHSPT2 Products:
UL/cUL® 1449 3rd Edition
Type 2
CHSPTELE: UL 497A, cUL
CHSPCABLE: UL 6500, cUL
NEMA® 3R Enclosure for
CHSPTELE and
CHSPCABLE: UL 50
Enclosure
BRSURGE, CHSA,
BRSURGECSA, CHQSA:
UL 1449 3rd Edition plug-in
type; Type 2 SPD
Volume 1—Residential and Light Commercial CA08100002E—August 2015 www.eaton.com
V1-T2-3
2
2.1
Surge Protection
Surge Protection Devices and Lightning Arresters
Product Selection
2
SPD Type 1 CHSP Service Entrance Surge Protection—UL 1449 3rd Edition
Product Features
●
Commercial grade AC power protection
●
Type 1 surge device for installation before or after the main service disconnect
●
Convenient mounting options—universal fit to any manufacturer’s equipment
●
Clear, visible LED indication displaying status of the surge protector
Catalog
Number
Connection
Enclosure Voltage
Frequency
Phase (Hz)
MCOV 1
VPR
2
In
3
SCCR
4
Surge Current
Capacity, Per
Phase Rating 5
CHSPT1ULTRA
CHSPT1ULTRA
Permanently connected device
NEMA 4
installed before or after the service
disconnect overcurrent device.
100/200 Vac, Single
110/220 Vac,
120/240 Vac
50/60
300 V L–L, 1000 V L–L, 20 kA 200 kA
150 V L–N 600 V L–N
50 kA
CHSPT1MAX
CHSPT1MAX
Permanently connected device
NEMA 4
installed before or after the service
disconnect overcurrent device.
100/200 Vac, Single
110/220 Vac,
120/240 Vac
50/60
300 V L–L, 1000 V L–L, 20 kA 200 kA
150 V L–N 600 V L–N
45 kA
CHSPT1MICRO
CHSPT1MICRO Permanently connected device
NEMA 4
installed before or after the service
disconnect overcurrent device.
100/200 Vac, Single
110/220 Vac,
120/240 Vac
50/60
300 V L–L, 1000 V L–L, 20 kA 200 kA
150 V L–N 600 V L–N
36 kA
CHSPT1-208Y
CHSPT1-208Y
120/208 Vac Threephase
wye
50/60
300 V L–L, 1000 V L–L, 20 kA 200 kA
150 V L–N 600 V L–N
50 kA
Permanently connected device
NEMA 4
installed before or after the service
disconnect overcurrent device.
Accessory for Type 1 CHSP Service Entrance Surge Protection
SP1DINRAILKIT
Catalog
Number
Description
SP1DINRAILKIT
Mounting kit for wall or DIN rail installation.
Notes
1 MCOV: Maximum Continuous Operating Voltage that may be applied to the device per mode.
2 VPR: Voltage Protection Rating is the measured limiting voltage after a surge event.
3 I : Nominal Discharge Current is the current that the device can withstand for 15 impulses.
n
4 SCCR: The amount of current the product can withstand under short-circuit conditions.
5 Surge Current Capacity: The maximum one time surge current rating per phase.
For warranty details, go to www.eaton.com/surgetrap.
V1-T2-4
Volume 1—Residential and Light Commercial CA08100002E—August 2015 www.eaton.com
2.1
Surge Protection
Surge Protection Devices and Lightning Arresters
SPD Type 2 CHSP Service Entrance Surge Protection—UL 1449 3rd Edition; cUL
Product Features
●
AC power protection
●
Universally connects to any manufacturer’s loadcenter (breaker box)
●
Quick connect design—easy to mount telephone and cable protection modules
●
LED status indication
Catalog
Number
Connection
Enclosure Voltage
Frequency
Phase (Hz)
MCOV 1
VPR 2
2
In 3
CHSPT2ULTRA
CHSPT2ULTRA
Can be attached to the outside of NEMA 4
any manufacturer’s loadcenter
(breaker box). This product should
be connected on the load side of
the loadcenter main service
disconnect through a dedicated
circuit breaker (follow NEC
Guidelines).
Single
120/240
Vac rated
line voltage
60
150 V L–N, 600 V L–N, 20 kA
300 V L–L 1000 V L–L,
800 V N–G,
600 V L–G
CHSPT2MAX
CHSPT2MAX
Can be attached to the outside of NEMA 4
any manufacturer’s loadcenter
(breaker box). This product should
be connected on the load side of
the loadcenter main service
disconnect through a dedicated
circuit breaker (follow NEC
Guidelines).
120/240
Single
Vac rated
line voltage
60
CHSPT2MICRO
CHSPT2MICRO Can be attached to the outside of NEMA 4
any manufacturer’s loadcenter
(breaker box). This product should
be connected on the load side of
the loadcenter main service
disconnect through a dedicated
circuit breaker (follow NEC
Guidelines).
120/240
Single
Vac rated
line voltage
60
SCCR 4
6
Surge Current
Capacity, Per
Phase Rating 5
22 kA
108 kA
(L1–N 54 kA, L1–G
54 kA, L2-N 54 kA,
L2–G 54 kA)
150 V L–N, 600 V L–N, 10 kA
300 V L–L 1000 V L–L,
800 V N–G,
600 V L–G
22 kA
72 kA
(L1–N 36 kA, L1–G
36 kA, L2–N 36 kA,
L2–G 36 kA)
150 V L–N, 600 V L–N, 5 kA
300 V L–L 1000 V L–L,
800 V N–G,
600 V L–G
22 kA
36 kA
(L1–N 18 kA, L1–G
18 kA, L2–N 18 kA,
L2–G 18 kA)
Notes
1 MCOV: Maximum Continuous Operating Voltage that may be applied to the device per mode.
2 VPR: Voltage Protection Rating is the measured limiting voltage after a surge event.
3 I : Nominal Discharge Current is the current that the device can withstand for 15 impulses.
n
4 SCCR: The amount of current the product can withstand under short-circuit conditions.
5 Surge Current Capacity: The maximum one time surge current rating per phase.
6 When used with a 50 A two-pole circuit breaker, 10 kA when used with a 15 A two-pole circuit breaker.
For warranty details, go to www.eaton.com/surgetrap.
Volume 1—Residential and Light Commercial CA08100002E—August 2015 www.eaton.com
V1-T2-5
2.1
Surge Protection
Surge Protection Devices and Lightning Arresters
Accessories for CHSP Type 2 Service Entrance Protection
Catalog
Number
2
Description
Installation
Surge Current
Capacity
DC
Breakdown
Voltage
CHSPCABLE
CHSPCABLE
Quick Connect design—add additional
telephone and AC protection modules;
protects two quad shield cables;
bi-directional
Indoor installation; or rain-tight when
used with recommended enclosure
10 kA per line
145 V
CHSPTELE
CHSPTELE
Quick Connect design—add additional AC
and cable protection modules; protects four
telephone lines
Indoor installation; or rain-tight when
used with recommended enclosure
20 kA per line
230 V
CHSPT23PACK
CHSPT23PACK
3-Pack:
CHSPT2ULTRA+CHSPTELE+CHSPCABLE;
Surge protection for AC power,
telephone and cable—see individual product
features
CHSP3RTELCABLE
CHSP3RTELCABLE
Raintight enclosure for CHSPTELE and
CHSPCABLE; top or bottom feed; enclosure
only, surge not included; accommodates up to
two devices
CHSPFMKIT
CHSPFMKIT
Flushmount kit for: CHSPT2ULTRA,
CHSPT2MAX, CHSPT2MICRO, CHSPTELE,
CHSPCABLE
MSEGR2
MSEGR2
Outdoor communication grounding device;
meets 2008 NEC requirements for
intersystem bonding termination
Note
For warranty details, go to www.eaton.com/surgetrap.
V1-T2-6
Volume 1—Residential and Light Commercial CA08100002E—August 2015 www.eaton.com
See individual
product ratings
Voltage
Ring 90–120 Vac/
Tone 48–52 Vdc
2.1
Surge Protection
Surge Protection Devices and Lightning Arresters
Type BR and CH Surge Breakers
Product Description
The CH and BR surge
breaker is designed to
provide premier AC power
surge protection for sensitive
electronics and appliances
from the damaging effects of
electrical surges. In addition,
the surge breaker is a
functional two-pole thermal
magnetic breaker.
The combination of circuit
protection and surge
protection provides extra
flexibility and space saving in
the loadcenter.
Catalog
Number 1
Type CH Surge
Breakers
Product Features
Complete home surge
protection for all circuits
plus a functional two-pole
thermal magnetic breaker
●
LEDs provide protection
status
●
Plug-on connection to the
busbar provides superior
protection and easy
installation for new
construction or renovation
●
Eliminates the potential for
incorrect installation of
externally mounted surge
devices—(longer “lead”
lengths can reduce
protection levels)
Poles
Voltage
30
120/240 Vac Single
50/60
150 V L–N,
300 V L–L
600 V L–N,
1000 V L–L
10 kA
10 kA
36 kA (L1–N 36 kA,
L2–N 36 kA)
50
120/240 Vac Single
50/60
150 V L–N,
300 V L–L
600 V L–N,
1000 V L–L
10 kA
10 kA
36 kA (L1–N 36 kA,
L2–N 36 kA)
30
120/240 Vac Single
50/60
150 V L–N,
300 V L–L
600 V L–N,
1000 V L–L
10 kA
10 kA
36 kA (L1–N 36 kA,
L2–N 36 kA)
50
120/240 Vac Single
50/60
150 V L–N,
300 V L–L
600 V L–N,
1000 V L–L
10 kA
10 kA
36 kA (L1–N 36 kA,
L2–N 36 kA)
Phase
Frequency
(Hz)
Surge Current
Capacity, Per
Phase Rating 6
Ampere
Rating
MCOV
2
VPR
3
In
4
SCCR
5
Type CH Surge Breakers
CH230SUR
Two-pole
10 kAIC
CH250SUR
Type BR Surge
Breakers
2
●
Type BR Surge Breakers
BR230SUR
BR250SUR
Two-pole
10 kAIC
Notes
1 Clamshell packaging available with CS modification code on the end of catalog number.
2 MCOV: Maximum Continuous Operating Voltage that may be applied to the device per mode.
3 VPR: Voltage Protection Rating is the measured limiting voltage after a surge event.
4 I : Nominal Discharge Current is the current that the device can withstand for 15 impulses.
n
5 SCCR: The amount of current the product can withstand under short-circuit conditions.
6 Surge Current Capacity: The maximum one time surge current rating per phase.
Volume 1—Residential and Light Commercial CA08100002E—August 2015 www.eaton.com
V1-T2-7
2.1
Surge Protection
Surge Protection Devices and Lightning Arresters
Surge Protection Receptacles with LED Indicators and Audible Alarm
2
Product Description
●
Two-pole, three-wire
grounding
●
15 A, 125 Vac; 20 A,
125 Vac; NEMA 5-15R and
5-20R
ArrowLink option available.
Add “M” suffix to standard
catalog number (example
8300WS, 8300WSM).
Build-to-spec customizable
devices.
Catalog
Number
5362_S
Ampere
Rating
Color Suffix
Voltage
NEMA
Description
5-15R
Surge duplex receptacle
■
■
IG Surge duplex receptacle
■
■
Surge duplex receptacle
■
■
IG Surge duplex receptacle
■
■
Receptacles with Audible Alarm and LED Indicators, Back and Side Wire
5262__S
BL, GY, V, W
IG5262__S
BL, GY, RN, V, W
15
5362__S
BL, GY, V, W
IG5362__S
BL, GY, RN, V, W
125 Vac
20
125 Vac
5-20R
560 Joules, max. surge current—18 kA per mode
Receptacles with LED Indicators, Back and Side Wire
IG5350_S
5250__S
BL, GY, V, W
IG5250__S
BL, GY, RN, V, W
5350__S
BL, GY, V, W
IG5350__S
BL, GY, RN, V, W
15
125 Vac
5-15R
Surge duplex receptacle
■
■
IG Surge duplex receptacle
■
■
20
125 Vac
5-20R
Surge duplex receptacle
■
■
IG Surge duplex receptacle
■
■
Surge duplex receptacle
■
■
IG Surge duplex receptacle
■
■
Surge duplex receptacle
■
■
IG Surge duplex receptacle
■
■
840 Joules, max. surge current—18 kA per mode
Receptacles with Audible Alarm
IG1208
1208__
V, W
IG1208__
V, W
1210__
BL, V, W
IG1210__
V, W
15
125 Vac
20
125 vac
5-15R
5-20R
340 Joules, max. surge current—12 kA per mode
Catalog
Number
Color Suffix
Ampere
Rating
Voltage
Description
125
Multimedia wallplate with recessed duplex surge receptacle
Multimedia Wallplates with Surge Protectors
35M2S-__
W
15
cETLus listed to UL1863 & ANSI/UL 60950-1, CSA C22.2 no. 60950-1-03; complies with all TIA/EIA 568-A & 570-B requirements
1209
Catalog
Number
Color Suffix
Description
Replacement Surge Bloc Module
1209__
A, BL, GY, V, W
Replacement module
Catalog
Number
Color Suffix
Description
35M2S
Accessories for Surge Protection Receptacles
PJ26BL
BL
1-Gang mid-size decorator polycarbonate wallplate
PJ26W
W
1-Gang mid-size decorator polycarbonate wallplate
PJ26IG
RN
1-Gang mid-size decorator polycarbonate wallplate, pre-marked “ISOLATED GROUND”
Notes
For ordering devices, include catalog number followed by the color suffix: BL (Blue), GY (Gray), RD (Red), RN (Orange), V (Ivory), W (White)
BL
GY
RD
RN
V
(Blue)
(Gray)
(Red)
(Orange)
(Ivory)
Compliances, specifications and availability are subject to change without notice.
V1-T2-8
W
(White)
Volume 1—Residential and Light Commercial CA08100002E—August 2015 www.eaton.com
Surge Protection
Surge Protection Devices and Lightning Arresters
Factory-Installed Surge Protection
●
Includes a CHSPT2ULTRA
and a two-pole 50 A circuit
breaker
●
Increases the
effectiveness of surge
protection due to reduced
lead length
Surge Installed
●
2.1
A modified deadfront
allows for easy viewing
of indicating lights for
status indication
2
Surge Installed Loadcenters
Cover Catalog Number
Catalog Number
Description
Combination
Surface
CHSUR42N225L 1
42 ckt, 225 A, convertible
CHSUR8LF
CHSUR8LS
CHSUR42L225L2 1
42 ckt, 225 A, convertible 2
CHSUR8LF
CHSUR8LS
CHSUR42B200L2 1
42 ckt, 200 A, main breaker
CHSUR8LF
CHSUR8LS
CHSUR32N225K 1
32 ckt, 225 A, convertible
CHSUR8KF
CHSUR8KS
CHSUR32L225K 1
32 ckt, 225 A, convertible 2
CHSUR8KF
CHSUR8KS
CHSUR32B200K 1
32 ckt, 200 A, main breaker
CHSUR8KF
CHSUR8KS
CHSUR32B150K 1
32 ckt, 150 A, main breaker
CHSUR8KF
CHSUR8KS
CHSUR32B100K 1
32 ckt, 100 A, main breaker
CHSUR8KF
CHSUR8KS
2
CHSUR8EF
CHSUR8ES
CHSUR24B100E 1
24 ckt, 100 A, main breaker
CHSUR8EF
CHSUR8ES
Cover included
CHSUR24L125E
1
24 ckt, 125 A, convertible
BRSUR4040N200
40/40 ckt, 200 A, convertible
BRSUR4040L200
40/40 ckt, 200 A, main lug
Cover included
BRSUR4040B200
40/40 ckt, 200 A, main breaker
Cover included
Cover included
BRSUR3040N200
30/40 ckt, 200 A, convertible
BRSUR3040L200
30/40 ckt, 200 A, main lug
Cover included
BRSUR3040B200
30/40 ckt, 200 A, main breaker
Cover included
Surge Ready Loadcenters
●
Provides a mounting
provision for
CHSPT2ULTRA
●
A modified deadfront
allows for easy viewing of
indicating lights
Surge Ready
Surge Ready Loadcenters (Provision Only, CHSPT2ULTRA and Breaker Not Included)
Cover Catalog Number
Catalog Number
Description
Combination
Surface
CHEC42N225L 1
42 ckt, 225 A, convertible
CHSUR8LF
CHSUR8LS
2
CHSUR8LF
CHSUR8LS
CHEC42B200L 1
42 ckt, 200 A, main breaker
CHSUR8LF
CHSUR8LS
CHEC32L225K 1
32 ckt, 225 A, convertible 2
CHSUR8KF
CHSUR8KS
CHEC32N225K 1
32 ckt, 225 A, convertible
CHSUR8KF
CHSUR8KS
CHEC32B200K 1
32 ckt, 200 A, main breaker
CHSUR8KF
CHSUR8KS
CHEC32B150K 1
32 ckt, 150 A, main breaker
CHSUR8KF
CHSUR8KS
CHEC32B100K 1
32 ckt, 100 A, main breaker
CHSUR8KF
CHSUR8KS
CHEC24L125E 1
24 ckt, 125 A, convertible 2
CHSUR8EF
CHSUR8ES
1
24 ckt, 100 A, main breaker
CHSUR8EF
CHSUR8ES
CHEC42L225L
1
CHEC24B100E
42 ckt, 225 A, convertible
Notes
1 Order cover separately.
2 With main lugs installed.
Volume 1—Residential and Light Commercial CA08100002E—August 2015 www.eaton.com
V1-T2-9
2.1
Surge Protection
Surge Protection Devices and Lightning Arresters
SPD Type 2 Plug-On Surge Protection—UL 1449 3rd Edition
Product Features
●
Convenient surge protection for the loadcenter
2
Catalog
Number
Description
Connection
Frequency
Voltage Phase (Hz)
MCOV 1
VPR
2
In
3
SCCR
4
Surge Current
Capacity, Per
Phase Rating 5
BRSURGE
BRSURGE
UL for use in a single-phase Type BR
Plug on to the
120/240 Single 60
loadcenter. This unit is classified by UL loadcenter bus; Vac
for use in select GE, ITE/Siemens and see instructions.
Crouse-Hinds panels (refer to Pub. No.
5655B65H01 for additional details).
150 V L1–N, 600 V L1–N, 3 kA 10 kA
300 V L–L
1000 V L–L
18 kA
CHSA
CHSA
UL and CSA for use in a
Type CH loadcenter.
Plug on to the
120/240 Single 60
loadcenter bus; Vac
see instructions.
150 V L1–N, 600 V L1–N, 3 kA 10 kA
300 V L–L
1000 V L–L
18 kA
BRSURGECSA
BRSURGECSA CSA for use in an Eaton
Type BR loadcenter.
Plug on to the
120/240 Single 60
loadcenter bus; Vac
see instructions.
150 V L1–N, 600 V L1–N, 3 kA 10 kA
300 V L–L
1000 V L–L
18 kA
CHQSA
CHQSA
This device is UL classified to be used Plug on to the
120/240 Single 60
in place of Square D Type QO surge
loadcenter bus; Vac
arresters (refer to Pub-23974).
see instructions.
150 V L1–N, 600 V L1–N, 3 kA 10 kA
300 V L–L
1000 V L–L
18 kA
Notes
1 MCOV: Maximum Continuous Operating Voltage that may be applied to the device per mode.
2 VPR: Voltage Protection Rating is the measured limiting voltage after a surge event.
3 I : Nominal Discharge Current is the current that the device can withstand for 15 impulses.
n
4 SCCR: The amount of current the product can withstand under short-circuit conditions.
5 Surge Current Capacity: The maximum one-time surge current rating per phase.
For warranty details, go to www.eaton.com/surgetrap.
V1-T2-10