AC Normally Closed Solid State Relay Installation

AC Normally Closed Solid State Relay Installation
AC Normally Closed
Solid State Relay Installation
Quick Reference Guide
Required Tools and Equipment







Antistatic wrist strap
Small Phillips (#2) screwdriver
Wire stripper and wire cutter
Adjustable wrench
Voltmeter
Crimpers
Drill/drill bits
Installing the Equipment
80V AC Normally Closed
Solid State Relay
100V AC Normally Closed AC
Solid State Relay
WARNING: To prevent electrostatic discharge (ESD) damage when handling electronic equipment, always wear an
antistatic wrist strap attached to an unpainted, grounded metal object. Ensure the wrist strap has maximum contact
with bare skin. If wires are to be buried or covered, conduit must be used to protect the wires.
1
Power Off Rectifier & Install AC Normally
Closed Solid State Relay Inside Rectifier
1
Install AC Normally Closed Solid State
with the heat sink fins in a vertical
position to optimize air flow.
Relay
relay can be mounted on a panel or placed on the
rectifier floor, depending on available space.
If mounting the AC Normally Closed Solid
use one of the drill pattern
templates printed on the back of this Guide to drill
holes for either the 80A or 100A AC Normally
Closed Solid State Relay in a rectifier panel.
State Relay,
80V AC Normally
Closed Solid State
Relay
100V AC Normally
Closed Solid State
Relay
Connect Relay to Rectifier
1
2
3
3
Power off the rectifier.
NOTE: The AC Normally Closed Solid State
Relay must be installed inside the rectifier. The
2
2
3
Remove the tap change bar from the COARSE taps.
Route the black wires of the AC Normally Closed
toward the front of the rectifier to
the taps. See photo.
Solid State Relay
Connect black wires to the taps.
NOTE: Connect AC Normally Closed Solid State
Relay wires to the same taps that were connected by the
change bar.
Connect Relay to Remote Monitoring Unit
1
Connect red wires of the AC Normally
Closed Solid State Relay to the remote
monitoring unit. Route wires as necessary
through rectifier. Wrap and secure loose wires.
2
Power on the rectifier and other devices.
AC Normally Closed Solid State Relay
Connected to Rectifier Taps
IMPORTANT: After installing the AC solid state relay, you may see a decrease in rectifier output due to a slight voltage (up to 1.7V)
drop across the relay. The decrease will be based on the current across the relay.
NOTE: These procedures are general steps for a typical installation. If your installation requires additional technical assistance, please
call the Technical Services group at 1-800-229-3404.
March 28, 2013
1
1 of
of 2
1
Part No. 122191-000, Rev. 1
5.50
[139.7]
4.42
[112.3]
5.00
[127.0]
4.50
[114.3]
0.19
[4.8]
.21
[5.2]
100V AC Solid State Relay
80V AC Solid State Relay
Tolerances: ± 0.02 in / 0.5 mm. All dimensions are in inches [millimeters].
March 28, 2013
2 of 2
Part No. 122191-000, Rev. 1