Install-ULD+ULS - Lowell Manufacturing
INSTALLATION SHEET #IS-ULD
ULD Series 8" Speaker Assemblies
for Fire Protective Signaling
Installation - Series ULD (28LO) Fire Protective Signaling Speaker
SIGNALING
UL
FIRE ALARM
EQUIPMENT
28LO
R
LISTED
ULDWB82T572
ASSEMBLY
These speakers are intended to be employed in either of the following configurations:
A. For fire alarm signaling service in conjunction with a compatible Listed system control unit, the
combination of which is intended to be installed as a combination system control in accordance
with the applicable requirements of NFPA 72 and the local authorities having jurisdiction. The
amplifier, in conjunction with the tone generator located in the control unit, provides the power and
signal, either for the alarm evacuation and/or for voice communication.
B. For general (non-fire alarm) signaling service in conjunction with compatible Listed sound
recording and reproducing equipment, the combination of which is intended to be installed in
accordance with the applicable requirements of the National Electrical Code and the local
authorities having jurisdiction. The amplifier or other sound reproducing equipment provides the
power for voice communication or any other related function to the speakers.
Connection Notes: For the supervised fire system voice coil, parallel input leads are provided
on Series ULD speakers for proper utilization of the electrical supervision scheme. Connect one
pair (red and black) to the incoming line from the fire alert signal source or previous speaker.
Connect the other pair (red and black) to the outgoing line to the next speaker or end-of-line
termination device. A red jumper is connected to the 70.7V 0.5W tap when shipped from the
factory. If desired, move the red jumper to a different transformer power tap lug. See "Figure 1"
on this page for available transformer power taps.
ULDSG82T572
ASSEMBLY
Connection Notes: For the voice/music non-supervised voice coil, connect leads (white and
black) to the incoming line from the signal source or previous speaker. A red jumper is connected
to the 70.7V 0.5W tap when shipped from the factory. If desired, move the red jumper to a different
transformer power tap lug. See "Figure 1" this page for available transformer power taps.
ELECTRICAL SPECIFICATIONS
Frequency Response: 100Hz - 12kHz + 20dB
Intended Use: Indoor Dry Locations
2kHz Dispersion at -6dB down points: With SG8 Grille:100 Degrees With WB8 Grille:100 Degrees
Directional Characteristics Test With Full Power Pink Noise Input Measured at 3m:
On Axis = 91.1dBA, -3dBA at 25o off axis, -6dBA at 55o degrees off axis, 84.1dBA at 90o off axis
8C10DVC Driver Size: 8"
8C10DVC Impedance: 8 Ohms
8C10DVC Driver Power Rating: 15 watts RMS
8C10DVC Magnet: 10 oz. Ceramic
FIGURE 1
#13456
TRANSFORMER TAPS
8C10DVC Driver Construction: Dual Paper Cone, Dual 1" Voice Coils, 20 Ga.Stamped Steel Basket
Supervision Capacitor: 10uF 160V. Maximum Allowable Supervision Voltage: 100 VDC.
ULDWB82T572
ULDSG82T572
UL dBA RATING AT 10FT.
UL dBA RATING AT 10FT.
88.8
85.2
82.4
79.6
76.4
1.0 W.
0.5 W.
88.8
85.2
82.4
79.6
76.4
88.5
85.1
82.3
79.5
0.25 W.
76.2
76.2
ELECTRICAL AND AUDIBLE RATINGS
MAXIMUM
VOLTAGE
TLM572 (#13456)
TRANSFORMER TAP
5.0 W.
70.7 V
RMS
25 V
RMS
2.0 W.
1.0 W.
0.5 W.
0.25 W.
5.0 W.
2.0 W.
88.5
85.1
82.3
79.5
70V-5W
70V-2W
25V-0.25W
70V-1W
25V-5W
25V-2W
25V-1W
FRONT VIEW
25V-0.5W
70V-0.5W
70/25V COM
70V-0.25W
8 OHM
SPKR COM
REAR VIEW
Note: The UL dBA ratings given above are the low readings from 11 samples so they m ay not be as expected for one sample .
XCP84S ENCLOSURE
CP84 ENCLOSURE
Lowell Manufacturing Company
Call: 800-325-9660
Fax: 636-257-6606
ULP68X ENCLOSURE
CB84SG ENCLOSURE
100 Integram Drive
Pacific, Missouri 63069 U.S.A.
Printed in U.S.A. 1-27-15
Click: www.lowellmfg.com
Instruction Sheet:
IS-ULD & IS-ULS
P/N 15741
Page 1 of 2
INSTALLATION SHEET #IS-ULS
ULS Series 8" Speaker Assemblies
for Fire Protective Signaling
Installation - Series ULS (28LO) Fire Protective Signaling Speaker
SIGNALING
UL
FIRE ALARM
EQUIPMENT
28LO
R
LISTED
ULSWB8CT572
ASSEMBLY
These speakers are intended to be employed in either of the following configurations:
A. For fire alarm signaling service in conjunction with a compatible Listed system control unit, the
combination of which is intended to be installed as a combination system control in accordance
with the applicable requirements of NFPA 72 and the local authorities having jurisdiction. The
amplifier, in conjunction with the tone generator located in the control unit, provides the power and
signal, either for the alarm evacuation and/or for voice communication.
B. For general (non-fire alarm) signaling service in conjunction with compatible Listed sound
recording and reproducing equipment, the combination of which is intended to be installed in
accordance with the applicable requirements of the National Electrical Code and the local
authorities having jurisdiction. The amplifier or other sound reproducing equipment provides the
power for voice communication or any other related function to the speakers.
ULSSG8CT572
ASSEMBLY
Connection Notes: Parallel input leads are provided on Series ULS speakers for proper utilization
of the electrical supervision scheme. Connect one pair (red and black) to the incoming line from
the signal source or previous speaker. Connect the other pair (red and black) to the outgoing line
to the next speaker or end-of-line termination device. A red jumper is connected to the 70.7V 0.5W
tap when shipped from the factory. If desired, move the red jumper to a different transformer power
tap lug. See "FIGURE 1" on this page for available transformer power taps.
ELECTRICAL SPECIFICATIONS
Frequency Response: 60Hz - 12kHz + 9dB
Intended Use: Indoor Dry Locations
2kHz Dispersion at -6dB down points: With SG8 Grille:100 degrees With WB8 Grille:100 degrees
Directional Characteristics Test With Full Power Pink Noise Input Measured at 3m:
On Axis = 97.7dBA, -3dBA at 35o off axis, -6dBA at 65o degrees off axis, 89.3dBA at 90o off axis
810 Driver Size: 8"
810 Impedance: 8 Ohms
810 Driver Power Rating: 15 watts RMS
810 Magnet: 10 oz. Ceramic
FIGURE 1
#13456
TRANSFORMER TAPS
810 Driver Construction: Paper Cone, 1" Voice Coil, 20 Gauge Stamped Steel Basket
Supervision Capacitor: 10uF 160V. Maximum Allowable Supervision Voltage: 100 VDC.
ULSWB8CT572
ULSSG8CT572
TLM572 (#13456)
TRANSFORMER TAP
UL dBA RATING AT 10FT.
UL dBA RATING AT 10FT.
5.0 W.
2.0 W.
1.0 W.
90.4
86.6
83.6
90.4
0.5 W.
80.9
80.9
0.25 W.
77.1
77.1
ELECTRICAL AND AUDIBLE RATINGS
MAXIMUM
VOLTAGE
70.7 V
RMS
5.0 W.
25V-5W
25V-2W
25V-1W
FRONT VIEW
86.6
83.6
90.6
1.0 W.
0.5 W.
90.6
87.0
84.1
81.3
0.25 W.
78.0
78.0
2.0 W.
25 V
RMS
70V-5W
70V-2W
25V-0.25W
70V-1W
87.0
84.1
81.3
25V-0.5W
70V-0.5W
70/25V COM
8 OHM
SPKR COM
70V-0.25W
REAR VIEW
Note: The UL dBA ratings given above are the low readings from 11 samples so they m ay not be as expected for one sample .
XCP84S ENCLOSURE
CP84 ENCLOSURE
Lowell Manufacturing Company
Call: 800-325-9660
Fax: 636-257-6606
ULP68X ENCLOSURE
CB84SG ENCLOSURE
100 Integram Drive
Pacific, Missouri 63069 U.S.A.
Click: www.lowellmfg.com
Printed in U.S.A. 1-27-15
Instruction Sheet:
IS-ULD & IS-ULS
P/N 15741
Page 2 of 2