- Industrial & lab equipment
- Electrical equipment & supplies
- Power conditioning
- Electrical relays
- User manual
advertisement
RISH
FLEX 9024B
RoHS
Input Data
Nominal Input Voltage (2 x Vac)
Manual select Input from 230 to 400-500
Input Voltage range (Vac)
230 – 400 – 500 Vac
Inrush Current (Vn and In Load) I 2 t
Frequency
Input Current (230 – 400 – 500 Vac)
Internal Fuse
External Fuse (recommended)
Output Data
187 - 264 (230 )
330 – 550 (400 - 500 )
≤ 17 A ≤ 5 msec.
47 – 63 Hz ± 6%
1.0 - 0.5 – 0.4 A
T 4 A
10 A (MCB curve B)
Output Voltage (Vn) Factory Setting ± 3%
Adjustment range (Vadj)
Start up with Strong Load (capacitive load)
Turn-On delay after applying mains voltage
24 Vdc
22 – 27 Vdc
≤ 50.000
µ F
1 sec. (max)
Continuous Current at 24 V < 40°C (In)
Continuous Current at 24 V < 50°C (In)
Efficiency
Over temperature Protection
5 A (permanent)
4,5 A (permanent)
Continuous Current at 24 V < 60°C (In)
Max 2 sec.: Hiccup mode
Permanent : Continuous Mode
4 A (permanent)
Power Boost Current at 24 Vdc 60°C(In) In (60°C) x 1.5 ≥ 3 min.
Current max. Overload ≅ 4Vdc (permanent) Imax=In60°Cx(1.8 - 2.2)
Current Short Circuit Icc
12 A
Hold-up Time ( min. Vac) 24Vdc 5A
Residual Ripple
Typ. 20 msec
≤ 80 mV pp
≥ 91 %
Yes. Shut-down output
Short-circuit protection and automatic restart.
1° Manual Reset
2° Hiccup Mode
Dissipation power load max (W)
Over Load protection
Over Voltage Output protection
Parallel connection
Power Good Contact rating (EN60947.4.1):
Max. DC1: 30 Vdc 1 A; AC1: 60 Vac 1A
Min.1mA at 5 Vdc
Climatic Data
3° Continuous Out Mode
11
Yes
Yes (typ. 35 Vdc)
Yes
Resistive load
Min permissive load
Ambient Temperature operation -25 up to +70 °C
(>60°derating 2.5% °C)
-40 up to +85 °C
95 % to 25 °C
Ambient Temperature Storage
Humidity at 25 °C, no condensation
General Data
Isolation Voltage (In / Out)
Isolation Voltage (In / PE)
Isolation Voltage (Out / PE)
Protection Class (EN/IEC 60529)
Reliability: MTBF IEC 61709
Pollution Degree Environment
Connection Terminal Blocks Screw Type
Protection class
Dimension (w-h-d)
Weight
3000 Vac
1605 Vac
500 Vac
IP 20
> 500.000 h
2
2,5 mm (24 – 14 AWG)
I with PE connected
55x110x105 mm
0.50 kg approx.
R I S H A B H I N S T R U M E N T S
Input: 230 – 400 – 500 Vac
Output: 24 Vdc 60°C
Efficiency up to 91%
Strong overload without switch-off, up to 50%
Flexible Power continuity :from 96 to 120 W
“Power Good” Relay
Three mode of output protections:
1) Hiccup mode
2) Continuous Out Mode
3) Manual Reset
DIN Rail Mountable
Extremely small size
3 Year warranty
Norms and certifications
The CE mark in According to EMC 2004/108/EC and Low voltage directive 2006/95/EC.
Electrical Safety
In compliance to UL508.
According to IEC/EN 60950 (VDE 0805) e EN 50178 (VDE
0160) for assembling device. The unit must be installed according to IEC/EN 60950.Input / Output separation: SELV
EN60950-1 and PELV EN 60204-1. Double or reinforced insulation.
EMC Immunity
EN 61000-4-2, EN 61000-4-3, EN 61000-4-4, EN 61000-4-5,
EN 61000-4-6, EN61000-6-2
EMC Emission:
EN61000-6-4, EN61000-3-2
Standards Conformity
EN 60204-1 Safety of Electrical Equipment Machines
Output derating Curve
Continuous Load
%
160
140
120
100
80
60
40
20
0
-10 0 10 20 30 40 50 60 70 °C
All specifications are subject to change without notice
advertisement