RISH FLEX 9024B

Add to my manuals
1 Pages

advertisement

RISH FLEX 9024B | Manualzz

RISH

FLEX 9024B

RoHS

Input Data

Nominal Input Voltage (2 x Vac)

Manual select Input from 230 to 400-500

Input Voltage range (Vac)

230 – 400 – 500 Vac

Inrush Current (Vn and In Load) I 2 t

Frequency

Input Current (230 – 400 – 500 Vac)

Internal Fuse

External Fuse (recommended)

Output Data

187 - 264 (230 )

330 – 550 (400 - 500 )

≤ 17 A ≤ 5 msec.

47 – 63 Hz ± 6%

1.0 - 0.5 – 0.4 A

T 4 A

10 A (MCB curve B)

Output Voltage (Vn) Factory Setting ± 3%

Adjustment range (Vadj)

Start up with Strong Load (capacitive load)

Turn-On delay after applying mains voltage

24 Vdc

22 – 27 Vdc

≤ 50.000

µ F

1 sec. (max)

Continuous Current at 24 V < 40°C (In)

Continuous Current at 24 V < 50°C (In)

Efficiency

Over temperature Protection

5 A (permanent)

4,5 A (permanent)

Continuous Current at 24 V < 60°C (In)

Max 2 sec.: Hiccup mode

Permanent : Continuous Mode

4 A (permanent)

Power Boost Current at 24 Vdc 60°C(In) In (60°C) x 1.5 ≥ 3 min.

Current max. Overload ≅ 4Vdc (permanent) Imax=In60°Cx(1.8 - 2.2)

Current Short Circuit Icc

12 A

Hold-up Time ( min. Vac) 24Vdc 5A

Residual Ripple

Typ. 20 msec

≤ 80 mV pp

≥ 91 %

Yes. Shut-down output

Short-circuit protection and automatic restart.

1° Manual Reset

2° Hiccup Mode

Dissipation power load max (W)

Over Load protection

Over Voltage Output protection

Parallel connection

Power Good Contact rating (EN60947.4.1):

Max. DC1: 30 Vdc 1 A; AC1: 60 Vac 1A

Min.1mA at 5 Vdc

Climatic Data

3° Continuous Out Mode

11

Yes

Yes (typ. 35 Vdc)

Yes

Resistive load

Min permissive load

Ambient Temperature operation -25 up to +70 °C

(>60°derating 2.5% °C)

-40 up to +85 °C

95 % to 25 °C

Ambient Temperature Storage

Humidity at 25 °C, no condensation

General Data

Isolation Voltage (In / Out)

Isolation Voltage (In / PE)

Isolation Voltage (Out / PE)

Protection Class (EN/IEC 60529)

Reliability: MTBF IEC 61709

Pollution Degree Environment

Connection Terminal Blocks Screw Type

Protection class

Dimension (w-h-d)

Weight

3000 Vac

1605 Vac

500 Vac

IP 20

> 500.000 h

2

2,5 mm (24 – 14 AWG)

I with PE connected

55x110x105 mm

0.50 kg approx.

R I S H A B H I N S T R U M E N T S

Input: 230 – 400 – 500 Vac

Output: 24 Vdc 60°C

Efficiency up to 91%

Strong overload without switch-off, up to 50%

Flexible Power continuity :from 96 to 120 W

“Power Good” Relay

Three mode of output protections:

1) Hiccup mode

2) Continuous Out Mode

3) Manual Reset

DIN Rail Mountable

Extremely small size

3 Year warranty

Norms and certifications

The CE mark in According to EMC 2004/108/EC and Low voltage directive 2006/95/EC.

Electrical Safety

In compliance to UL508.

According to IEC/EN 60950 (VDE 0805) e EN 50178 (VDE

0160) for assembling device. The unit must be installed according to IEC/EN 60950.Input / Output separation: SELV

EN60950-1 and PELV EN 60204-1. Double or reinforced insulation.

EMC Immunity

EN 61000-4-2, EN 61000-4-3, EN 61000-4-4, EN 61000-4-5,

EN 61000-4-6, EN61000-6-2

EMC Emission:

EN61000-6-4, EN61000-3-2

Standards Conformity

EN 60204-1 Safety of Electrical Equipment Machines

Output derating Curve

Continuous Load

%

160

140

120

100

80

60

40

20

0

-10 0 10 20 30 40 50 60 70 °C

All specifications are subject to change without notice